utopia DC Inverter 7kW-14kW G8 5kW-25kW Split Systems
Contents Company profile 4 Product range overview 6 Features and benefits 8 DC Inverter 12 Utopia G8 24 Utopia centrifugal 40 Total heat exchanger 42 Control systems 44 Set-up and operation 46 Lon interface 48 Optional parts 50 3
Air Conditioning from HITACHI can justifiably be described as the art of exploiting the latest ideas and developments in technology to create a range of innovative products which provide a more comfortable and more productive environment in which people can happily live and work. It is also an art executed with a responsible concern for protecting the environment. Ecological thinking begins at the very first stages of new product design and continues throughout production, installation procedures, equipment and operation. Specifiers and users alike can always be assured that performance and costs are not the only parameters by which HITACHI products can be judged. To achieve success with such objectives on a global scale requires not only enormous resources but also a commitment to the future. As one of the largest companies in the world, with over 321,517 employees, HITACHI is well positioned to undertake this commitment with confidence that comes from successfully responding to the changing needs of people for over 90 years. worldwide. In 1993 HITACHI invested in a new purpose built, state of the art factory (HAPE) in Barcelona, Spain. The site of the factory was carefully chosen to accommodate further building on its 40,000 square meter site. The creation of a European manufacturing facility and customer training centre helps reduce production costs, speed up delivery times and enables full support to be given to all customers. HITACHI s advanced air conditioning products are specified all over the world, wherever there is a requirement for ultimate performance and cost effective, long term reliability. A wide range of units coupled with a choice of advanced control systems mean HITACHI can provide solutions to meet every possible air conditioning application or specification. Authorised Distributors all over the world contribute their own specialised technical support and practical assistance to provide individual system designs, commissioning and after sales service. HITACHI Authorised Distributors are committed to providing an unrivalled support from a combination of experienced engineers, local product and spare parts stock, Hitachi Air Conditioning Products Europe HAPE works, Spain Hitachi Air Conditioning Products Europe (HAPE works, Spain) has acquired International Standard Quality Management System ISO9001 & ISO 14001 authorisation. HAPE performs thorough product quality control using various environmental tests. Hitachi Set Free Series Indoor units and panels are manufactured according to this ISO certification system. Hitachi Air Conditioning Systems Co., Ltd. (Shimizu works, Japan) has acquired International Standard Quality Management System ISO9001 and ISO14001 authorisation. Shimizu works perform thorough product quality control using various environmental tests, severe heating testing for compressors, and many others. Hitachi Set Free Series Outdoor units are manufactured according to this ISO certification system. Hitachi Air Conditioning Products (M) Sdn.Bhd (HAPM works, Malaysia) has acquired International Standard Quality Management System ISO9001 and ISO14001 authorisation. HAPM perform thorough product quality control using various environmental tests. Hitachi Set Free Series RPK Indoor units are manufactured according to this ISO certification system. Company profile Hitachi Air Conditioning Systems Co., Ltd. Shimizu works, Japan Quality control HITACHI in Japanese the name means sunrise is at the forefront of research and development turning new ideas and innovations into new products. Of its $81.4 billion sales worldwide in 2003, close to 5.2% was invested in research and development programs. This vast amount of money has given HITACHI the opportunity to conceive many world firsts examples of which include the technologically advanced and acclaimed scroll and semi-hermetic Screw compressors. These have been incorporated in HITACHI s air conditioning systems and water chillers which have revolutionised air conditioning supported in turn by on-going technical support from HITACHI. From the initial product concept at HITACHI s research and development facility in Japan, product development is dedicated to providing the products the customer requires. Product design and development is continuous with priority being given to the use of ecologically friendly refrigerants. To satisfy your cooling and heating requirements and to ensure the optimum indoor environment, consider HITACHI the first and last word in air conditioning. Hitachi Air Conditioning Products (M) HAPM works, Malaysia 5
Indoor Units Utopia Split Systems In-the-Ceiling Capacity Range [HP] 1.5 2.0 2.5 3.0 3.5 4.0 5.0 6.0 8.0 10.0 4-Way Cassette 2-Way Cassette Mini Wall Wall Ceiling Floor-Standing Floor-Concealed DC Inverter Utopia Outdoor Units Capacity Range [HP] Adjustable by dip switch setting - + 3.0 4.0 5.0 6.0 RAS-HVRNE Series Utopia G8 Outdoor Units Capacity Range [HP] Hitachi s new range of Utopia Split Systems has developed significantly in recent years following a great deal of investment in research and development and testing facilities at various Hitachi factories and laboratories, around the world. Hitachi has continuously developed sophisticated energy saving air conditioning systems that reduce CO 2 emissions and help to protect the global environment. The latest addition to the Utopia range of air conditioning systems is the new G8 series outdoor unit with its combination of SYSTEM FREE indoor units. This combination allows the interconnection of the same indoor units in all the systems. The system provides effortless selection, easy control, logical zooming, and trouble-free installation. Through its modularity the system delivers maximum flexibility and consequently offers increased benefits for both installers and end users. The Hitachi range of Utopia Split Systems benefit from a vast array of significant features all designed with the user in mind! Remarkably low sound levels Improved efficiency due to DC Fan Motor Simple and Flexible Installation Highest Air Quality Space Saving Designs Easy Servicing and Commissioning RAS-AG8E RAS-HG8E RASC-HG8E Econofresh 2.0 2.5 3.0 3.5 4.0 5.0 6.0 8.0 Capacity Range [HP] 5.0 10.0 EF-5GE 7
High Efficiency Scroll Compressor EER (Cooling) COP (Heating) Performance is greatly improved by the high-efficiency, high pressure, inverter driven scroll compressor. Reliability greatly improved by optimised bearing Intake loss and leakage loss largely reduced by asymmetric scroll lap Heat loss largely reduced by oil return structure Accurate oiling to the compressor by improved oiling system Rotor shape optimized Peculiar electromagnetic noise to DC compressor cut Compressor rotor Neodymium magnet used Efficiency increased across entire range of rpm used High-efficiency motor [ C] 95 70 2,000 DC motor AC motor rpm 4,000 6,000 4.00 3.50 3.00 2.50 2.00 3HP 4HP 5HP R407C Fix speed HVRN (R410A Inverter) 4.50 4.00 3.50 3.00 2.50 2.00 3HP 4HP 5HP G8 (R407C Fix speed) HVRN (R410A Inverter) Supercooling circuit Performance improved by high-efficiency plate type of heat exchanger Effect of subcooler DC Compressor By using DC, the performance is improved at around 30-40Hz where the operation time of the inverter compressor is longest. Also, to suppress electromagnetic noise interference and achieve low noise, the rotor has been divided into two and the electric pole displaced. Standard R407C Fix Speed and Hitachi R410A Inverter Refrigerating ability increased by supercooling circuit Features and benefits DC Inverter System Free Indoor Units The complete Utopia outdoor unit range can be connected to any of the Hitachi range of indoor units. Compact and Light design Extremely compact design enabling easy installation and effective use of plant space. Hitachi has created one of the lightest and most compact systems on the market. Flexible Installation Piping connectors pivot four ways (front, rear, lateral and down) to allow easier positioning of units. This greatly enhanced flexibility reduces problems during installation and encourages the alignment of multiple outdoor units in small areas. New R410A Refrigerant 800 1240 Using new R410A refrigerant adds the following benefits: 850 315 Reduced power consumption 950 315 Increased system performance Higher heat exchange coefficient Reduction in component size. Low sound Levels Super high stream fan, delta shaped edges reduces fan size and noise levels. Bell Mouth, the new bellmouth minimises friction, resulting in smooth flow and sound. 9
Twin with UTOPIA G8 series outdoor unit TOPIA G8 series outdoor unit Combination Flexibility The systems are offered in the following combinations: Quad with UTOPIA Big Non visible installation With its modular design the new Utopia G8 series outdoor unit provides a totally flexible air conditioning solution. This offers not only standard cooling functions but, in addition, heating (for heat pump models), dry and fan operation for all environments. Single, Twin or Triple with the Utopia range of outdoor units Single, Twin, Triple and Quad with the Utopia Big outdoor unit Single with Centrifugal Utopia unit The Utopia Centrifugal unit can be installed indoors or outdoors making it the ideal choice for places where it is is forbidden or impossible to place an outdoor unit outside the building. Avoids legislation and local regulations regarding outdoor unit installation. Twin with Utopia G8 series Outdoor unit Quad with UTOPIA Big TOPIA G8 series outdoor unit Single with Centrifugal Utopia Unit Single with UTOPIA G8 series outdoor unit Twin with UTOPIA G8 series outdoor unit Twin with UTOPIA Big Single with Centrifugal UTOPIA Unit Single with Centrifugal Utopia Unit Features and benefits Utopia G8 ad with UTOPIA Big Space Saving Design A sensibly located front access panel allows installation in a space saving in line configuration with as little as 50mm separation between each unit. This is an advantage over conventional side access units that must be positioned several feet apart. Flexible Installation Piping connectors pivot four ways (front, rear, lateral and down) to allow easier positioning of units. This greatly enhanced flexibility reduces problems during installation and encourages the alignment of multiple outdoor units in small areas. H-Link Control System The system requires only two transmission wires for connecting each outdoor unit to its indoor units (to control up to 16 refrigerant cycles). Both outdoor units and indoor units require connecting wires in series. The advantages of using this system are: Outdoor Unit Transmission Wires Refrigerant Piping Trouble-free and adaptable installation No polarity requirements CS Net connection via indoor or outdoor unit Up to 128 indoor units Indoor Unit Indoor Units System Free Indoor Units ith Centrifugal Up to Utopia cable run Unit length: 1000m CS-NET The complete Utopia outdoor unit range can be connected to any of the Hitachi range of indoor units. 11
DC Inverter RPI Technical Description Slim, space saving design Adjustable fan speed Adjustable static pressure Drain Pump as standard Air Filter as standard Broader range of external static pressure up to 150 Pa. Flexibly supports a wide range of installation conditions at site, e.g. longer ducts. Increased flexibility and extended ducting now available, provides full temperature control even to remote areas. Adjustable air flow and fan speed control. Wide selection Full line-up from model 0.8HP to 6.0HP. Econofresh Kit As part of the Set Free range the Econofresh can provide up to 100% fresh air and has the ability to provide free cooling via dampers when the outdoor ambient temperature is below the temperature required indoors. Available for 5.0HP unit. In the ceiling In the ceiling ducted systems Slimmest design in the industry Less than 197mm in height, this unit can be fitted practically any existing false ceiling or formerly ducted space, without substantial modification. 120mm 197mm Minimum 5mm False Ceiling (0.8 ~ 1.5HP) Drain-up mechanism Drain-up mechanism is built in the units as standard. An electronic sensor monitors the water level and automatically activates the pump when draining becomes necessary. Return Air (2.0-6.0HP) Available as bottom or rear entry. Suction filter equipped as standard New RPI unit is equipped with a filter as standard. Model Combined Indoor Unit Model Outer Dimensions EF-5GE RPI-5FSN(E) Height mm 254 Width mm 1350 + 59 Depth mm 270 Net Weight Kg 12.5 Damper Motor Quality 1 Approx. Packing Measurement m 3 0.13 Standard Accessories Fresh Outdoor Air Inlet Thermistor Model RPI 1.5FSNE RPI 2.0FSNE RPI 2.5FSNE RPI 3.0FSNE RPI 4.0FSNE RPI 5.0FSNE RPI 6.0FSNE Indoor Unit Configuration Twin Twin Triple Twin Single Twin Single Single Single Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.1(3.9~8.0) 10(4.9~11.2) 14(TBC) 12.5 (6.7~14) 7.1 (3.9~10.0) 14(TBC) 10 (4.9~11.2) 12.5 (6.7~14) 14 Nominal Heating Capacity kw 8(4~10.0) 11.2(5.7~14.0) 16(TBC) 14(7~18) 8.0 (4.0~10.0) 16 (TBC) 11.2 (5.7~14) 14.0(7~18) 16(TBC) Sound Pressure Levels db(a) 38/37/35 39/37/34 40/38/35 40/38/35 42/41/37 45/44/43 46/45/44 Static Pressure (Hi/Me/Lo) mmaq 5/5/5 8/6/5 8/6/5 8/6/5 8/7/6 8/7/6 8/7/6 Dimensions (HxWxD) mm 197/1020/574 274/1074/643 274/1074/643 274/1074/643 274/1464/643 274/1464/643 274/1464/643 Net Weight Indoor unit kg 33.5 43 45 45 51 52 52 Air Flow Rate (Hi/Me/Lo) m 3 /min 10/9/7 16/14/12 19/17/15 22/20/17 30/29/26 35/32/29 36/33/31 Approx packing measurement Unit m 3 0.16 0.36 0.36 0.36 0.48 0.48 0.48 Combined Outdoor Unit Heat Pump RAS 3.0HVRNE RAS 4.0HVRNE RAS 6.0HRNE RAS 5.0HVRNE RAS 3.0HVRNE RAS 6.0HRNE RAS 4.0HVRNE RAS 5.0HVRNE RAS 6.0HRNE Total Input power cooling kw 1.86 2.49 4.39 3.44 1.86 4.39 2.49 3.44 4.39 Total Input power heating kw 1.84 2.44 4.23 3.26 1.84 4.23 2.44 3.26 4.23 Energy Efficiency Class Cooling/Heating A/A A/A A/A A/A A/A A/A Sound Pressure Levels db(a) 43(39) 45(41) 48(44) 47(43) 43(39) 48(44) 45(41) 47(43) 48(44) Air Flow Rate (Hi/Me/Lo) m 3 /min 45 80 100 90 45 100 80 90 100 Dimensions (HxWxD) mm 800/850/315 1240/950/315 1240/950/315 1240/950/315 800/850/315 1240/950/315 1240/950/315 1240/950/315 1240/950/315 Net Weight kg 60 95 97 97 60 97 97 97 Refrigerant type R410A R410A Refrigerant charge kg 2.4 3.6 3.6 3.6 2.4 3.6 3.6 3.6 3.6 Precharged Length m 30 30 Liquid line inches Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Gas line inches Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3Ø 220/240V 1Ø 380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Approximate packing measurement m 3 0.34 0.55 0.55 0.55 0.34 0.55 0.55 0.55 0.55 13
DC Inverter RCI Technical Description High Efficiency Inside of ceiling NOTES For setting 3 and 2 directions, the separately sold 3-way outlet parts set is necessary. Speed up (1) and Speed-up (2) can be selected through RCS by using C5 option. Silent Operation Slim Air Panel Drain Pump as standard New design air panel DC Motor Efficiency increased by 40% (motor input halved) AC Motor The air panel was revised to give a fresh and simple design. Prevention of smudging and short-circuiting is also taken into account. Motor Efficiency (%) Revolutions per Min. (rpm) 298mm False ceiling Indoor unit body 3HP Air panel High ceiling adaptability satisfies a wide variety of requirements This model is adaptable to a high ceiling with a height of 4.2m by using speed-up taps. These features allow comfortable air conditioning in high street stores. Wireless controller (option) See page 47. Fresh air intake Connection of fresh air intake can be taken in by connecting the duct beside the indoor unit. The control duct fan will operate only when unit is operating giving good air recirculation and comfort. Branch duct Available across the range for added flexibility 4-way cassette 4 way cassette systems Extremely Quite Operation Uses a blade design resulting in an exceptionally quiet fan. HI-stream fan achieves the lowest level of noise, 28 db (A) (RCI-1.0FSN1E). Compact, low height units The height of the units is just 298mm so they can easily be installed in a small space. The units require limited ceiling space which enables improved work efficiency in installation behind the ceiling. High Ceiling 1.0/1.5/2.0/2.5 HP 3.0/3.5/4.0/5.0/6.0 HP (m) 4-way 3-way 2-way 4-way 3-way 2-way Standard 2.7 3.0 3.3 3.2 3.6 4.0 Speed-up (1) 3.0 3.3 3.5 3.6 4.0 4.2 Speed-up (2) 3.5 3.6-4.2 4.3 - DC Fan Motor with Outstanding Efficiency The DC fan motor greatly improves efficiency compared with conventional products having an AC motor. Also, air blasts are reduced by controlling the rotation speed of the fan. Drain-up mechanism is equipped as standard. Anti-mould filter is equipped as standard. Model RCI 1.5FSN1E RCI 2.0FSN1E RCI 2.5FSN1E RCI 3.0FSN1E RCI 4.0FSN1E RCI 5.0FSN1E RCI 6.0FSN1E Indoor Unit Configuration Twin Twin Triple Twin Single Twin Single Single Single Compatible Panel PG23WA2 PG23WA2 Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.1(3.9~8.0) 10(4.9~11.2) 14(TBC) 12.5 (6.7~14) 7.1 (3.9~10.0) 14(TBC) 10 (4.9~11.2) 12.5 (6.7~14) 14(TBC) Nominal Heating Capacity kw 8(4~10.0) 11.2(5.7~14.0) 16(TBC) 14(7~18) 8.0 (4.0~10.0) 16 (TBC) 11.2 (5.7~14) 14.0(7~18) 16(TBC) Sound Pressure Levels db(a) 32/30/28 32/30/28 32/30/28 34/32/30 38/35/33 39/37/35 42/40/36 Dimensions (HxWxD) mm 248/840/840 248/840/840 248/840/840 298/840/840 298/840/840 298/840/840 298/840/840 Net Weight Indoor unit kg 23 24 24 26 29 29 29 Air Flow Rate (Hi/Me/Lo) m 3 /min 15/14/12 16/14/12 20/17/15 26/23/20 32/28/24 34/29/25 37/32/27 Approx packing measurement Unit m 3 0.22 0.22 0.22 0.26 0.26 0.26 0.26 Combined Outdoor Unit Heat Pump RAS 3.0HVRNE RAS 4.0HVRNE RAS 6.0HRNE RAS 5.0HVRNE RAS 3.0HVRNE RAS 6.0HRNE RAS 4.0HVRNE RAS 5.0HVRNE RAS 6.0HRNE Total Input power cooling kw 1.86 2.49 4.39 3.44 1.86 4.39 2.49 3.44 4.39 Total Input power heating kw 1.84 2.44 4.23 3.26 1.84 4.23 2.44 3.26 4.23 Energy Efficiency Class Cooling/Heating A/A A/A A/A A/A A/A A/A Sound Pressure Levels db(a) 43/(39) 45(41) 48(44) 47(43) 43(39) 48(44) 45(41) 47(43) 48(44) Air Flow Rate (Hi/Me/Lo) m 3 /min 45 80 100 90 45 100 80 90 100 Dimensions (HxWxD) mm 800/850/315 1240/950/315 1240/950/315 1240/950/315 800/850/315 1240/950/315 1240/950/315 1240/950/315 1240/950/315 Net Weight kg 60 95 97 97 60 97 95 97 97 Refrigerant type R410A R410A Refrigerant charge kg 2.4 3.6 3.6 3.6 2.4 3.6 3.6 3.6 3.6 Precharged Length (m) m 30 30 Liquid line inches Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Gas line inches Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3 Ø 220/240V 1Ø 380/415 3 Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Approximate packing measurement m 3 0.34 0.55 0.55 0.55 0.34 0.55 0.55 0.55 0.55 15
DC Inverter RCD Technical Description Quiet Operation Slim line design New Air panel, perfect fit for any ceiling Quiet operation and low height design for any ceiling. Reduced weight and size simplify handling for easier renewal. The length of the 3HP type is reduced from 1,320mm to 860mm, the height is also reduced and the volume is decreased by about 50%. The reduced weight of 30kg also makes handling much easier. Inside of Ceiling Ceiling Compact Turbo Fan 298mm 2-way cassette 2 way cassette systems 398mm 298mm 860mm 1,320mm New Model (50%) Current Model (100%) Low-profile design allows installation in a small space inside of ceiling. A compact turbo fan simplifies the structure and reduces the height to 298mm, for easy installation. Top-class noise control due to compact turbo fan. The three-dimensional twisted wings of the compact turbo fan greatly reduce noise and electromagnetic disturbance is minimised by PWM (Pulse Width Modulation) control. Simple Maintenance Auto-louvers are not flocked, therefore the unit does not accumulate dirt and is easy to clean. Speed-up tap ensures comfortable air conditioning even when installed in high ceiling areas. Even rooms with a high ceiling can be comfortably air-conditioned by setting the speed-up tap with the remote control switch. Model RCD 1.5FSN RCD 2.0FSN RCD 2.5FSN RCD 3.0FSN RCD 4.0FSN RCD 5.0FSN Indoor Unit Configuration Twin Twin Triple Twin Single Twin Single Single Compatible Panel PG23DWA1 PG46DWA1 Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.1(3.9~8.0) 10(4.9~11.2) 14(TBC) 12.5 (6.7~14) 7.1 (3.9~10.0) 14(TBC) 10 (4.9~11.2) 12.5 (6.7~14) Nominal Heating Capacity kw 8(4~10.0) 11.2(5.7~14.0) 16(TBC) 14(7~18) 8.0 (4.0~10.0) 16 (TBC) 11.2 (5.7~14) 14.0(7~18) Sound Pressure Levels db(a) 35/32/30 35/32/30 38/34/31 40/36/33 40/36/33 43/40/36 Dimensions (HxWxD) mm 298/860/620 298/860/620 298/860/620 298/860/620 298/1420/620 298/1420/620 Net Weight Indoor unit kg 27 27 30 30 48 48 Air Flow Rate (Hi/Me/Lo) m 3 /min 12/10/8.5 15/13/11 18/15.5/13.5 22/19/16 30/26/23 32/29/25 Approx packing measurement Unit m 3 0.10 0.10 0.10 0.10 0.15 0.15 Combined Outdoor Unit Heat Pump RAS 3.0HVRNE RAS 4.0HVRNE RAS 6.0HRNE RAS 5.0HVRNE RAS 3.0HVRNE RAS 6.0HRNE RAS 4.0HVRNE RAS 5.0HVRNE Total Input power cooling kw 1.86 2.49 4.39 3.44 1.86 4.39 2.49 3.44 Total Input power heating kw 1.84 2.44 4.23 3.26 1.84 4.23 2.44 3.26 Energy Efficiency Class Cooling/Heating A/A A/A A/A A/A A/A A/A Sound Pressure Levels db(a) 43/(39) 45(41) 48(44) 47(43) 43/(39) 48(44) 45(41) 47(43) Air Flow Rate (Hi/Me/Lo) m 3 /min 45 80 100 90 45 100 80 90 Dimensions (HxWxD) mm 800/850/315 1240/950/315 1240/950/315 1240/950/315 800/850/315 1240/950/315 1240/950/315 1240/950/315 Net Weight kg 60 95 97 97 60 97 95 97 Refrigerant type R410A R410A Refrigerant charge kg 2.4 3.6 3.6 3.6 2.4 3.6 3.6 3.6 Precharged Length m 30 30 Liquid line inches Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Gas line inches Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3 Ø 220/240V 1Ø 380/415 3 Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Approximate packing measurement m 3 0.34 0.55 0.55 0.55 0.34 0.55 0.55 0.55 17
FSNM Wall mounted DC Inverter RPK Technical Description Extended Line-up NEW 0.8 4.0 Quiet operation More compact than previous models FSN1M Mini Wall mounted New design Ideal for the home Compact and stylish Wall mounted Wall mounted systems Wall Mounted Compact, allowing easy installation Designed with ease of installation in mind this new space saving model uses a high proportion of light weight parts reducing the unit weight to 12kg. Expanded product line up 2.5/3.0/4.0HP models available Compact design It s compact size allows easy installation and the weight has been reduced by 15%. Quiet Operation Trapezoidal blades cut the air diagonally to reduce air flow resistance. The conical blade fan ensures a high air flow and low noise with slow rotation. This model creates a pleasant, quiet and comfortable environment. Swing Louver The Swing Louver with 3 flaps at both sides has been adopted, in order to provide comfortable air to the entire room. Wireless or Wired Control The indoor unit is equipped with a wireless receiver kit inside as an standard accessory. The wired remote control switch, PC-P1HE is also applicable. Mini Wall Mounted Compact and Stylish Design This model has been designed with a flat panel and the width has been reduced by 250mm to 780mm. The weight has also been condensed by approximately 17%. Ideal for the Home This model creates a pleasant, quiet and comfortable environment, making it the ideal choice for the home. Wireless or Wired Control The indoor unit is equipped with a wireless receiver kit (PC-LH3A) inside as a standard accessory. The wired remote control switch, PC-P1HE is also applicable. Easy Maintenance Alarm indication when using PC-LH3A has been improved (LED of the unit shows alarm code). Quiet Operation Trapezoidal blades cut the air diagonally reducing air flow resistance. Conical blade fans with their slow rotation ensure a high air flow and low noise levels. Model RPK 1.5FSNM RPK 1.5FSN1M RPK 2.0FSNM RPK 2.5FSNM RPK 3.0FSNM RPK 4.0FSNM Indoor Unit Configuration Twin Quad Twin Quad Twin Triple Twin Single Twin Single Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.1(3.9~8) 14.0 9.0 18.0 10.0(4.9~11.2) 14(TBC) 12.5 (6.7~14.0) 7.1(3.9~8) 14(TBC) 10.0(4.9~11.2) Nominal Heating Capacity kw 8.0(4.0~10.0) 16.0 10.0 20.0 11.2(5.7~14.0) 16(TBC) 14(7~18) 8.0(4.0~10.0) 16(TBC) 11.2(5.7~14.0) Sound Pressure Levels db(a) 39/37/34 40/38/36 40/38/36 43/40/37 43/40/37 49/46/43 Dimensions (HxWxD) mm 295/1030/183 280/780/210 295/1030/183 360/1390/225 360/1390/225 360/1390/225 Net Weight kg 12 10 12 21 21 22 Air Flow Rate (Hi/Me/Lo) m 3 /min 13/11/9 11/10/9 14/12/10 22/18/15 22/18/15 26/22/19 Approx packing measurement Unit m 3 0.11 0.07 0.11 0.20 0.20 0.20 Combined Outdoor Unit Heat Pump RAS 3.0HVRNE RAS 6.0HRNE RAS 3.0HVRNE RAS 6.0HRNE RAS 4.0HVRNE RAS 6.0HRNE RAS 5.0HVRNE RAS 3.0HVRNE RAS 6.0HRNE RAS 4.0HVRNE Total Input power cooling kw 1.86 4.39 1.86 4.39 2.49 4.39 3.44 1.86 4.39 2.49 Total Input power heating kw 1.84 4.23 1.84 4.23 2.44 4.23 3.26 1.84 4.23 2.44 Energy Efficiency Class Cooling/Heating A/A A/A A/A A/A A/A A/A Sound Pressure Levels db(a) 43/(39) 48(44) 43/(39) 48(44) 45(41) 48(44) 47(43) 43(39) 48(44) 45(41) Air Flow Rate (Hi/Me/Lo) m 3 /min 45 100 45 100 80 100 90 45 100 80 Dimensions (HxWxD) mm 800/850/315 1240/950/315 800/850/315 1240/950/315 1240/950/315 1240/950/315 1240/950/315 800/850/315 1240/950/315 1240/950/315 Net Weight kg 60 97 60 97 95 97 97 60 97 95 Refrigerant type R410A R410A Refrigerant charge kg 2.4 3.6 2.4 3.6 3.6 3.6 3.6 2.4 3.6 3.6 Precharged Length m 30 30 Liquid line inches Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Gas line inches Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3Ø 220/240V 1Ø 380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Approximate packing measurement m 3 0.34 0.34 0.55 0.55 0.55 0.55 0.34 0.55 0.55 19
DC Inverter RPC Technical Description Stylish design Space saving design Easy installation Quiet Operation Quiet operation, easy installation and space saving design Versatile mounting To expand installation and positioning options, HITACHI has added a second drain pipe connector, one more than conventional units. Refrigeration pipes have also been improved and can now be connected at the left, right or rear of the unit. Rear Side Quiet Operation The ceiling unit is equipped with a highly efficient, multi-blade centrifugal fan that generates a powerful yet gentle airflow throughout the room. A redesigned aerodynamically tested air panel minimises operational sound even at high fan speeds. Easier installation By enabling refrigeration piping to be tucked-in close to each indoor unit, piping layout and installation have been made much easier. Anti-mildew filter Anti-mildew filter is equipped as a standard accessory. Ceiling suspended Ceiling suspended systems Open Space 163mm Concealed 150mm (2,0, 2,5 and 3,0 HP) Drain piping Space saving design Hitachi s unique feature An innovative fan and heat exchanger design led to the creation of today s ultra-slim ceiling unit. Fully adjustable mounting brackets permit close fitting to the ceiling to make installation possible in even the smallest area. Less than 163mm of vertical space are required for installation. Model RPC 2.0FSNE RPC 2.5FSNE RPC 3.0FSNE RPC 4.0FSNE RPC 5.0FSNE RPC 6.0FSNE Indoor Unit Configuration Twin Triple Twin Single Twin Single Single Single Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 10.0 (4.9~11.2) 14(TBC) 12.5 (6.7~14.0) 7.1(3.9~8) 14(TBC) 10.0(4.9~11.2) 12.5 (6.7~14.0) 14 (TBC) Nominal Heating Capacity kw 11.2 (5.7~14.0) 16(TBC) 14(7~18) 8.0(4.0~10.0) 16(TBC) 11.2(5.7~14.0) 11.2 (7~18) 16 (TBC) Sound Pressure Levels db(a) 44/42/38 46/43/41 48/45/42 49/45/39 49/46/41 50/48/44 Dimensions (HxWxD) mm 163/1094/625 163/1314/625 163/1314/625 225/1314/625 225/1574/625 225/1574/625 Net Weight Indoor unit kg 28 31 31 35 41 41 Air Flow Rate (Hi/Me/Lo) m 3 /min 15/13/10 18/16/12 21/17/15 30/24/19 35/28/21 37/32/27 Approx packing measurement Unit m 3 0.24 0.29 0.29 0.36 0.43 0.43 Combined Outdoor Unit Heat Pump RAS 4.0HVRNE RAS 6.0HRNE RAS 5.0HVRNE RAS 3.0HVRNE RAS 6.0HRNE RAS 4.0HVRNE RAS 5.0HVRNE RAS 6.0HRNE Total Input power cooling kw 2.49 4.39 3.44 1.86 4.39 2.49 3.44 4.39 Total Input power heating kw 2.44 4.23 3.26 1.84 4.23 2.44 3.26 4.23 Energy Effciency Class Cooling/Heating A/A A/A A/A A/A A/A Sound Pressure Levels db(a) 45(41) 48(44) 47(43) 43(39) 48(44) 45(41) 47(43) 48(44) Air Flow Rate (Hi/Me/Lo) m 3 /min 80 100 90 45 100 80 90 100 Dimensions (HxWxD) mm 1240/950/315 1240/950/315 1240/950/315 800/850/315 1240/950/315 1240/950/315 1240/950/315 1240/950/315 Net Weight kg 95 97 97 60 97 95 97 97 Refrigerant type R410A R410A Refrigerant charge kg 3.6 3.6 3.6 2.4 3.6 3.6 3.6 3.6 Precharged Length m 30 30 Liquid line inches Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Gas line inches Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3 Ø 220/240V 1Ø 380/415 3 Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Approximate packing measurement m 3 0.55 0.55 0.55 0.34 0.55 0.55 0.55 0.55 21
DC Inverter RPF/RPFI Technical Description Floor mounted indoor units RPF Floor Type Slim design, only 200mm deep Low height, only 630mm Light unit Low sound level Floor concealed indoor units RPFI Compact design 620mm in height 220mm in depth Space-saving slim unit, only 220mm in depth Slim line design only 220mm in depth allowing the unit to be installed without spoiling the style or beauty of the room. Effective use of space by window With a height of 630mm, may be installed by a window leaving plenty of window space. Best installed in a perimeter zone. Low height Only 630mm. Concealed Floor Mounted Compact design for limited space inside of perimeter wall. So compact that it fits into even the smallest space. Special emphasis placed on interior design compatibility as well as space saving design, allowing it to fit perfectly into the space below a bay window. Optional location for remote control switch Install the PC-P1HE under the plastic cover Floor Mounted Floor mounted systems uncased Model RPFI 1.5FSNE RPFI 2.0FSNE RPFI 2.5FSNE Indoor Unit Configuration Twin Twin Triple Twin Power Supply V/Ph/Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.1(3.9~8.0) 10.0 (4.9~11.2) 14(TBC) 12.5 (6.7~14.0) Nominal Heating Capacity kw 8.0(4.0~10.0) 11.2 (5.7~14.0) 16(TBC) 14(7~18) Sound Pressure Levels db(a) 38/35/31 39/36/32 42/38/34 Dimensions (HxWxD) mm 620/988/220 620/1238/220 620/1238/220 Net Weight Indoor unit kg 23 27 28 Air Flow Rate (Hi/Me/Lo) m 3 /min 12/10/9 16/14/11 16/14/11 Approx packing measurement Unit m 3 0.23 0.25 0.25 Floor mounted systems cased Model RPF 1.5FSNE RPF 2.0FSNE RPF 2.5FSNE Indoor Unit Configuration Twin Twin Triple Twin Power Supply V/Ph/Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.1(3.9~8.0) 10.0 (4.9~11.2) 14(TBC) 12.5 (6.7~14.0) Nominal Heating Capacity kw 8.0(4.0~10.0) 11.2 (5.7~14.0) 16(TBC) 14(7~18) Sound Pressure Levels db(a) 38/35/31 39/36/32 42/38/34 Dimensions (HxWxD) mm 630/1170/220 630/1420/220 630/1420/220 Net Weight Indoor unit kg 23 33 34 Air Flow Rate (Hi/Me/Lo) m 3 /min 12/10/9 16/14/11 16/14/11 Approximate packing measurement m 3 0.24 0.29 0.29 Combined Outdoor Unit RAS 3.0HVRNE RAS 4.0HVRNE RAS 6.0HRNE RAS 5.0HVRNE Total Input power cooling kw 1.86 2.49 4.39 3.44 Total Input power heating kw 1.84 2.44 4.23 3.26 Energy Efficiency Class Cooling/Heating A/A A/A A/A Sound Pressure Levels db(a) 43/(39) 45(41) 48(44) 47(43) Air Flow Rate (Hi/Me/Lo) m 3 /min 45 80 100 90 Dimensions (HxWxD) mm 800/850/315 1240/950/315 1240/950/315 1240/950/315 Net Weight kg 60 95 97 97 Refrigerant type R410A Refrigerant charge kg 2.4 3.6 3.6 3.6 Precharged Length m 30 Liquid line inches Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Gas line inches Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3 Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Approximate packing measurement m 3 0.34 0.55 0.55 0.55 Combined Outdoor Unit RAS 3.0HVRNE RAS 4.0HVRNE RAS 6.0HRNE RAS 5.0HVRNE Total Input power cooling kw 1.86 2.49 4.39 3.44 Total Input power heating kw 1.84 2.44 4.23 3.26 Energy Efficiency Class Cooling/Heating A/A A/A A/A Sound Pressure Levels db(a) 43/(39) 45(41) 48(44) 47(43) Air Flow Rate (Hi/Me/Lo) m 3 /min 45 80 100 90 Dimensions (HxWxD) mm 800/850/315 1240/950/315 1240/950/315 1240/950/315 Net Weight kg 60 95 97 97 Refrigerant type R410A Refrigerant charge kg 2.4 3.6 3.6 3.6 Precharged Length m 30 Liquid line inches Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Ø9.53(3/8) Gas line inches Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Approximate packing measurement m 3 0.34 0.55 0.55 0.55 23
Utopia G8 RPI Technical Description Slim, space saving design Adjustable fan speed Adjustable static pressure Drain Pump as standard Air Filter as standard Slimmest design in the industry Less than 197mm in height, this unit can be fitted practically any existing false ceiling or formerly ducted space, without substantial modification. Minimum 5mm Broader range of external static pressure up to 150 Pa. Flexibly supports a wide range of installation conditions at site, e.g. longer ducts. Increased flexibility and extended ducting now available, provides full temperature control even to remote areas. Adjustable air flow and fan speed control. Wide selection Full line-up from model 0.8HP to 6.0HP. Drain-up mechanism 197mm Drain-up mechanism is built in the units as standard. An electronic sensor monitors the water level and automatically activates the pump when draining becomes necessary. In the ceiling 120mm False Ceiling (0.8 ~ 1.5HP) Return Air (2.0-6.0HP) Available as bottom or rear entry. Suction filter equipped as standard New RPI unit is equipped with a filter as standard. In the ceiling ducted systems Model RPI 1.5FSNE RPI 2.0FSNE RPI 2.5FSNE RPI 2.5FSNE RPI 3.0FSNE RPI 3.5FSNE RPI 4.0FSNE Indoor Unit Configuration Twin Quad Single Twin Triple Quad Single Twin Single Twin Single Single Twin Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.10 14.00 5.00 10.00 14 20 6.30 12.50 7.10 14.00 8.00 10.00 20.00 Nominal Heating Capacity kw 8.00 16.00 5.60 11.20 16 22.4 7.00 14.00 8.00 16.00 9.00 11.20 22.40 Sound Pressure Levels check LSP db(a) 38/37/35 39/37/34 40/38/35 40/38/35 40/38/35 40/38/35 42/41/37 Static Pressure (Hi/Me/Lo) mmaq 5/5/5 8/6/5 8/6/5 8/6/5 8/6/5 8/6/5 8/7/6 Dimensions (HxWxD) mm 197/1020/574 274/1074/643 274/1074/643 274/1074/643 274/1074/643 274/1074/643 274/1464/643 Net Weight Indoor unit kg 33.5 43 45 45 45 45 51 Air Flow Rate (Hi/Me/Lo) m 3 /min 10/9/7 16/14/12 19/17/15 19/17/15 22/20/17 22/20/17 30/29/26 Approx. Packing Measurement m 3 0.16 0.36 0.36 0.36 0.36 0.36 0.48 Cooling Only RAS 3.0AG(V)8E RAS 6.0AG8E RAS 2.0AGV8E RAS 4.0AG(V)8E RAS 6.0AG8E RAS 8.0AG8E RAS 2.5AG(V)8E RAS 5.0AG8E RAS 3.0AG(V)8E RAS 6.0AG8E RAS 3.5AG(V)8E RAS 4.0AG(V)8E RAS 8.0AG8E Combined Outdoor Unit Heat Pump RAS 3.0HG8E RAS 6.0HG8E RAS 2.0HGV8E RAS 4.0HG8E RAS 6.0HG8E RAS 8.0HG8E RAS 2.5HG8E RAS 5.0HG8E RAS 3.0HG8E RAS 6.0HG8E RAS 3.5HG8E RAS 4.0HG8E RAS 8.0HG8E Total Input Power Cooling kw 3.2 6.45 2.8 4.6 6.45 9.4 2.7 5.6 3.2 6.45 3.33 4.6 9.4 Total Input Power Heating kw 3.20 6.2 2.4 4.34 6.2 9.6 2.7 5.8 3.2 6.2 3.5 4.3 9.3 Sound Pressure Levels db(a) 53 56 49 55 56 61 51 56 53 56 55 55 61 Air Flow Rate m 3 /min 46 110 36 70 110 135 40 103 46 110 Dimensions (HxWxD) mm 800/850/350 1240/850/350 800/850/350 1240/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 800/850/350 1240/850/350 1240/850/350 1240/850/350 1562/1000/875 Net Weight kg 72 106 70 104 106 230 71 105 72 106 91 104 230 Refrigerant type R407C R407C Refrigerant charge kg 2.8 4.7 2.5 4.00 4.7? 2.8 4.5 2.8 4.7 3.5 4.00? Precharged Length m 10 metres 10 metres Liquid line inches 9.53(3/8) 9.53(3/8) 6.35(1/4) 9.53(3/8) 9.53(3/8) Ø12.7(1/2) 9.53(3/8) 9.53(3/8) 9.53(3/8) 9.53(3/8) 9.53(3/8) 9.53(3/8) Ø12.7(1/2) Gas line inches 15.88(5/8) 19.05(3/4) 15.88(5/8) 19.05(3/4) 19.05(3/4) Ø28.6(1 1/8) 15.88(5/8) 19.05(3/4) 15.88(5/8) 19.05(3/4) 15.88(5/8) 19.05(3/4) Ø28.6(1 1/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3Ø 220/240V 1Ø 380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Approx. packing measurement m 3 0.36 0.53 0.36 0.53 0.53 1.62 0.36 0.53 0.36 0.53 0.53 0.53 1.62 25
Utopia G8 RPI Technical Description Econofresh Kit As part of the Set Free range the Econofresh can provide up to 100% fresh air and has the ability to provide free cooling via dampers when the outdoor ambient temperature is below the temperature required indoors. Available for 5.0HP unit. In the ceiling Model EF-5GE Combined Indoor Unit Model RPI-5FSN(E) Outer Dimensions Height mm 254 Width mm 1350 + 59 Depth mm 270 Net Weight Kg 12.5 Damper Motor Quality 1 Approx. Packing Measurement m 3 0.13 Standard Accessories Fresh Outdoor Air Inlet Thermistor In the ceiling ducted systems Model RPI 5.0FSNE RPI 6.0FSNE RPI 8FSNE RPI 10FSNE Indoor Unit Configuration Single Twin Single Single Single Power Supply V/Ph/Hz 220-240V/50Hz Nominal Cooling Capacity kw 12.5 25 14.00 20 25 Nominal Heating Capacity kw 14.00 28 16.00 22.4 28 Sound Pressure Levels check LSP db(a) 45/44/43 46/45/44 54/54/51 55/55/52 Static Pressure (Hi/Me/Lo) mmaq 8/7/6 8/7/6 18/18/14 18/18/14 Dimensions (HxWxD) mm 274/1464/643 274/1464/643 475/1580/600 475/1580/600 Net Weight Indoor unit kg 52 52 85 87 Air Flow Rate (Hi/Me/Lo) m 3 /min 35/32/29 36/33/31 66/66/57 75/75/66 Approx. Packing Measurement m 3 0.48 0.48 0.5 0.5 Cooling Only RAS 5.0AG8E RAS 10AG8E RAS 6.0AG8E RAS8.0AG8E RAS10AG8E Combined Outdoor Unit Heat Pump RAS 5.0HG8E RAS 10HG8E RAS 6.0HG8E RAS8.0HG8E RAS10HG8E Total Input Power Cooling kw 5.6 11.6 6.5 9.4 11.6 Total Input Power Heating kw 5.8 11.3 6.2 9.6 11.3 Sound Pressure Levels db(a) 56 62 56 61 62 Air Flow Rate m 3 /min 135 Dimensions (HxWxD) mm 1240/850/350 1562/1000/875 1240/850/350 1562/1000/875 1562/1000/875 Net Weight kg 105 240 106 230 240 Refrigerant type Refrigerant charge kg 4.5? 4.7?? Precharged Length m Liquid line inches 9.53(3/8) Ø15.88(5/8) 9.53(3/8) Ø12.7(1/2) Ø15.88(5/8) Gas line inches 19.05(3/4) Ø28.6(1 1/8) 19.05(3/4) Ø28.6(1 1/8) Ø28.6(1 1/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Approx. packing measurement m 3 0.53 1.62 0.53 1.62 1.62 27
Utopia G8 RCI Technical Description Silent Operation Inside of ceiling NOTES For setting 3 and 2 directions, the separately sold 3-way outlet parts set is necessary. Speed up (1) and Speed-up (2) can be selected through RCS by using C5 option. Slim Air Panel Drain Pump as standard New design air panel DC Motor Efficiency increased by 40% (motor input halved) AC Motor The air panel was revised to give a fresh and simple design. Prevention of smudging and short-circuiting is also taken into account. Motor Efficiency (%) Revolutions per Min. (rpm) 298mm False ceiling Indoor unit body 3HP Air panel High ceiling adaptability satisfies a wide variety of requirements This model is adaptable to a high ceiling with a height of 4.2m by using speed-up taps. These features allow comfortable air conditioning in high street stores. Wireless controller (option) See page 47. Fresh air intake Connection of fresh air intake can be taken in by connecting the duct beside indoor unit. The control duct fan will operate only when unit is operating giving good air recirculation and comfort. Branch duct Available across the range for added flexibility 4-way cassette 4 way cassette systems Extremely Quite Operation Uses a blade design resulting in an exceptionally quiet fan. HI-stream fan achieves the lowest level of noise, 28 db (A) (RCI-1.0FSN1E). Compact, low height units The height of the units is just 298mm so they can easily be installed in a small space. The units require limited ceiling space which enables improved work efficiency in installation behind the ceiling. High Ceiling 1.0/1.5/2.0/2.5 HP 3.0/3.5/4.0/5.0/6.0 HP (m) 4-way 3-way 2-way 4-way 3-way 2-way Standard 2.7 3.0 3.3 3.2 3.6 4.0 Speed-up (1) 3.0 3.3 3.5 3.6 4.0 4.2 Speed-up (2) 3.5 3.6-4.2 4.3 - DC Fan Motor with Outstanding Efficiency The DC fan motor greatly improves efficiency compared with conventional products having an AC motor. Also, air blasts are reduced by controlling the rotation speed of the fan. Drain-up mechanism is equipped as standard. Anti-mould filter is equipped as standard. Model RCI 1.5FSN1E RCI 2.0FSN1E RCI 2.5FSN1E RCI 3.0FSN1E RCI 3.5FSN1E RCI 4.0FSN1E RCI 5.0FSN1E RCI 6.0FSN1E Indoor Unit Configuration Twin Quad Single Twin Triple Quad Single Twin Quad Single Twin Single Single Twin Single Twin Single Compatible Panel P-G23WA2 P-G23WA2 Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.10 14.00 6.30 10.00 14.00 20.00 6.30 12.50 25.00 7.10 14.00 8.00 10.00 20.00 12.50 25.00 14.00 Nominal Heating Capacity kw 8.00 16.00 6.00 11.20 16.00 22.40 7.00 14.00 28.00 8.00 16.00 9.00 11.20 22.40 14.00 28.00 16.00 Sound Pressure Levels db(a) 32/30/28 32/30/28 32/30/28 34/32/30 34/32/30 38/35/33 39/37/35 42/40/36 Dimensions (HxWxD) mm 248/840/840 248/840/840 248/840/840 298/840/840 298/840/840 298/840/840 298/840/840 298/840/840 Net Weight Indoor unit kg 23 24 24 26 26 29 29 29 Air Flow Rate (Hi/Me/Lo) m 3 /min 15/14/12 16/14/12 20/17/15 26/23/20 26/23/20 32/28/24 34/29/25 37/32/27 Approx. packing measurement m 3 0.22 0.22 0.22 0.26 0.26 0.26 0.26 0.26 Cooling Only RAS 3.0AG(V)8E RAS 6.0AG8E RAS 2.0AGV8E RAS 4.0AG(V)8E RAS 6.0AG8E RAS 8.0AG8E RAS 2.5AG(V)8E RAS 5.0AG8E RAS 10AG8E RAS 3.0AG(V)8E RAS 6.0AG8E RAS 3.5AG(V)8E RAS 4.0AG(V)8E RAS 8.0AG8E RAS 5.0AG8E RAS 10AG8E RAS 6.0AG8E Combined Outdoor Unit Heat Pump RAS 3.0HG8E RAS 6.0HG8E RAS 2.0HGV8E RAS 4.0HG8E RAS 6.0HG8E RAS 8.0HG8E RAS 2.5HG8E RAS 5.0HG8E RAS 10HG8E RAS 3.0HG8E RAS 6.0HG8E RAS 3.5HG8E RAS 4.0HG8E RAS 8.0HG8E RAS 5.0HG8E RAS 10HG8E RAS 6.0HG8E Total Input power cooling kw 3.2 6.5 2.8 4.6 6.5 9.4 2.74 5.6 11.6 3.2 6.5 3.3 4.6 9.4 5.6 11.6 6.5 Total Input power heating kw 3.2 6.2 2.4 4.3 6.2 9.6 2.7 5.8 11.3 3.2 6.6 3.5 4.3 9.6 5.8 11.3 6.2 Sound Pressure Levels db(a) 53 56 49 55 56 61 51 56 62 53 56 55 55 61 56 62 56 Air Flow Rate m 3 /min 46 110 36 70 110 135 40 103 135 46 110 52 70 135 103 135 110 Dimensions (HxWxD) mm 800/850/350 1240/850/350 800/850/350 1240/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1240/850/350 1240/850/350 1562/1000/875 1240/850/350 1562/1000/875 1240/850/350 Net Weight kg 72 106 70 104 106 230 71 105 240 72 106 91 104 230 105 240 106 Refrigerant type kg R407C R407C Refrigerant charge 2.8 4.7 2.5 4 4.7 7.2 2.8 4.5 9.0 2.8 4.7 3.5 4 7.2 4.5 9.0 4.7 Precharged Length m 10m 10m Liquid line inches 9.53(3/8) 9.53 6.35(1/4) 9.53 9.53 Ø12.7(1/2) 9.53 9.53 Ø15.88(5/8) 9.53 9.53 9.53 9.53 Ø12.7(1/2) 9.53 Ø15.88(5/8) 9.53 Gas line inches 15.88 19.05 15.88 19.05 19.05 28.6 15.88 19.05 28.6 15.88 19.05 15.88 19.05 28.6 19.05 26.6 19.05 Power supply V/Ph/Hz 220/240V 1Ø 380/415 3Ø 220/240V 1Ø 380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Approx. packing measurement m 3 0.36 0.53 0.36 0.53 0.53 0.36 0.53 1.62 0.36 0.53 0.53 0.53 1.62 0.53 1.62 0.53 29
Utopia G8 RCD Technical Description Quiet Operation Slim line design New Air panel, perfect fit for any ceiling Quiet operation and low height design for any ceiling. Reduced weight and size simplify handling for easier renewal. The length of the 3HP type is reduced from 1,320mm to 860mm, the height is also reduced and the volume is decreased by about 50%. The reduced weight of 30kg also makes handling much easier. Inside of Ceiling Ceiling Compact Turbo Fan 298mm 2-way cassette 2 way cassette systems 398mm 298mm 860mm 1,320mm New Model (50%) Current Model (100%) Low-profile design allows installation in a small space inside of ceiling. A compact turbo fan simplifies the structure and reduces the height to 298mm, for easy installation. Top-class noise control due to compact turbo fan. The three-dimensional twisted wings of the compact turbo fan greatly reduce noise and electromagnetic disturbance is minimised by PWM (Pulse Width Modulation) control. Simple Maintenance Auto-louvers are not flocked, therefore the unit does not accumulate dirt and is easy to clean. Speed-up tap ensures comfortable air conditioning even when installed in high ceiling areas. Even rooms with a high ceiling can be comfortably air-conditioned by setting the speed-up tap with the remote control switch. Model RCD 1.5FSN RCD 2.0FSN RCD 2.5FSN RCD 3.0FSN RCD 4.0FSN RCD 5.0FSN Indoor Unit Configuration Twin Quad Single Twin Triple Quad Single Twin Quad Single Twin Single Twin Single Twin Compatible Panel P-G23DWA1 PG46DWA1 Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.1 14 5.00 10.00 14.00 20.00 6.30 12.50 25.00 7.10 14.00 10.00 20.00 12.50 25.00 Nominal Heating Capacity kw 8 16 5.60 11.20 16.00 22.40 7.00 14.00 28.00 8.00 16.00 11.20 22.40 14.00 28.00 Sound Pressure Levels db(a) 35/32/30 35/32/30 38/34/31 40/36/33 40/36/33 43/40/36 Dimensions (HxWxD) mm 298/860/620 298/860/620 298/860/620 298/860/620 298/1420/620 298/1420/620 Net Weight Indoor unit kg 27 27 30 30 48 48 Air Flow Rate (Hi/Me/Lo) m 3 /min 12/10/8.5 15/13/11 18/15.5/13.5 22/19/16 30/26/23 32/29/25 Approx. packing measurement m 3 0.10 0.10 0.10 0.10 0.15 0.15 Cooling Only RAS 3.0AG(V)8E RAS 6.0AG8E RAS 2.0AGV8E RAS 4.0AG(V)8E RAS 6.0AG8E RAS 8.0AG8E RAS 2.5AG(V)8E RAS 5.0AG8E RAS 10AG8E RAS 3.0AG(V)8E RAS 6.0AG8E RAS 4.0AG(V)8E RAS 8.0AG8E RAS 5.0AG8E RAS 10AG8E Combined Outdoor Unit Heat Pump RAS 3.0HG8E RAS 6.0HG8E RAS 2.0HGV8E RAS 4.0HG8E RAS 6.0HG8E RAS 8.0HG8E RAS 2.5HG8E RAS 5.0HG8E RAS 10HG8E RAS 3.0HG8E RAS 6.0HG8E RAS 4.0HG8E RAS 8.0HG8E RAS 5.0HG8E RAS 10HG8E Total Input power cooling kw 3.2 6.5 2.8 4.6 6.5 9.4 2.7 5.6 11.6 3.2 6.5 4.6 9.4 5.6 11.6 Total Input power heating kw 3.2 6.2 2.4 4.3 6.2 9.3 2.7 5.8 11.3 3.2 6.2 4.3 9.3 5.8 11.3 Sound Pressure Levels db(a) 53 56 49 55 56 61 51 56 62 53 56 55 61 56 62 Air Flow Rate m 3 /min 46 110 36 70 110 135 40 103 135 46 110 70 135 103 135 Dimensions (HxWxD) mm 800/850/350 1240/850/350 800/850/350 1240/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1240/850/350 1562/1000/875 1240/850/350 1562/1000/875 Net Weight kg 72 106 70 104 106 230 71 105 240 72 106 104 230 105 240 Refrigerant type R407C R407C Refrigerant charge kg 2.8 4.7 2.5 4 4.7 7.2 2.8 4.5 9.0 2.8 4.7 4 7.2 4.5 9.0 Precharged Length m 10m 10m Liquid line inches 9.53 (3/8) 9.53(3/8) 6.35(1/4) 9.53(3/8) 9.53(3/8) Ø12.7(1/2) 9.53(3/8) 9.53(3/8) Ø15.88(5/8) 9.53(3/8) 9.53(3/8) 9.53(3/8) Ø12.7(1/2) 9.53(3/8) Ø15.88(5/8) Gas line inches 15.88(5/8) 19.05(3/4) 15.88(5/8) 19.05(3/4) 19.05(3/4) Ø28.6(1 1/8) 15.88(5/8) 19.05(3/4) Ø28.6(1 1/8) 15.88(5/8) 19.05(3/4) 19.05(3/4) Ø28.6(1 1/8) 19.05(3/4) Ø28.6(1 1/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3Ø 220/240V 1Ø 380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Approx. packing measurement m 3 0.36 0.53 0.36 0.53 0.53 1.62 0.53 1.62 0.36 0.53 0.53 1.62 0.53 1.62 31
FSNM Wall mounted Utopia G8 RPK Technical Description Extended Line-up NEW 0.8 4.0 Quiet operation More compact than previous models FSN1M Mini Wall mounted New design Ideal for the home Compact and stylish Wall mounted Wall mounted systems Wall Mounted Compact, allowing easy installation Designed with ease of installation in mind this new space saving model uses a high proportion of light weight parts reducing the unit weight to 12kg. Expanded product line up 2.5/3.0/4.0HP models available Compact design It s compact size allows easy installation and the weight has been reduced by 15%. Quiet Operation Trapezoidal blades cut the air diagonally to reduce air flow resistance. The conical blade fan ensures a high air flow and low noise with slow rotation. This model creates a pleasant, quiet and comfortable environment. Swing Louver The Swing Louver with 3 flaps at both sides has been adopted, in order to provide comfortable air to the entire room. Wireless or Wired Control The indoor unit is equipped with a wireless receiver kit inside as an standard accessory. The wired remote control switch, PC-P1HE is also applicable. Mini Wall Mounted Compact and Stylish Design This model has been designed with a flat panel and the width has been reduced by 250mm to 780mm. The weight has also been condensed by approximately 17%. Ideal for the Home This model creates a pleasant, quiet and comfortable environment, making it the ideal choice for the home. Wireless or Wired Control The indoor unit is equipped with a wireless receiver kit (PC-LH3A) inside as a standard accessory. The wired remote control switch, PC-P1HE is also applicable. Easy Maintenance Alarm indication when using PC-LH3A has been improved (LED of the unit shows alarm code). Quiet Operation Trapezoidal blades cut the air diagonally reducing air flow resistance. Conical blade fans with their slow rotation ensure a high air flow and low noise levels. Model RPK 1.5 FSNM RPK 1.5FSN1M RPK 2.0FSNM RPK 2.0FSNM RPK 2.5FSNM RPK 3.0FSNM RPK 3.5FSNM RPK 4.0FSNM Indoor Unit Configuration Twin Quad Twin Quad Single Twin Triple Quad Single Twin Quad Single Twin Single Twin Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.1 14.0 9.0 18.0 5.00 10.00 14 20 6.30 12.50 25.00 7.10 14 8.00 20.00 Nominal Heating Capacity kw 8.0 16.0 10.0 20.0 5.60 11.20 16 22.4 7.00 14.00 28.00 8.00 16 9.00 22.40 Sound Pressure Levels db(a) 39/37/34 40/38/36 40/38/36 40/38/36 43/40/37 43/40/37 49/46/43 49/46/43 Dimensions (HxWxD) mm 295/1030/183 280/780/210 295/1030/183 295/1030/183 360/1390/225 360/1390/225 360/1390/225 360/1390/225 Net Weight Indoor unit kg 12 10 12 12 21 21 22 22 Air Flow Rate (Hi/Me/Lo) m 3 /min 13/11/9 11/10/9 14/12/10 14/12/10 22/18/15 22/18/15 26/24/20 26/22/19 Approximate packing measurement m 3 0.11 0.07 0.11 0.11 0.20 0.20 0.20 0.20 Cooling Only RAS 3.0AG(V)8E RAS 6.0AG8E RAS 3.0AG(V)8E RAS 6.0AG8E RAS 2.0AGV8E RAS 4.0AG(V)8E RAS 6.0AG8E RAS 8.0AG8E RAS 2.5AG(V)8E RAS 5.0AG8E RAS 10AG8E RAS 3.0AG(V)8E RAS 6.0AG8E RAS 3.5AG(V)8E RAS 8.0AG8E Combined Outdoor Unit Heat Pump RAS 3.0HG8E RAS 6.0HG8E RAS 3.0HG8E RAS 6.0HG8E RAS 2.0HGV8E RAS 4.0HG8E RAS 6.0HG8E RAS 8.0HG8E RAS 2.5HG8E RAS 5.0HG8E RAS 10HG8E RAS 3.0HG8E RAS 6.0HG8E RAS 3.5HG8E RAS 8.0HG8E Total Input power cooling kw 3.2 6.5 3.2 6.5 2.8 4.6 6.5 9.4 2.7 5.6 11.6 3.2 6.5 3.3 9.4 Total Input power heating kw 3.2 6.2 3.2 6.2 2.4 4.3 6.2 9.3 2.7 5.8 11.3 3.2 6.2 3.5 9.3 Sound Pressure Levels db(a) 53 56 53 56 49 55 56 61 51 56 62 53 56 55 61 Air Flow Rate (Hi/Me/Lo) m 3 /min 46 110 46 110 36 70 110 135 40 103 135 46 110 52 Dimensions (HxWxD) mm 800/850/350 1240/850/350 800/850/350 1240/850/350 800/850/350 1240/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1240/850/350 1562/1000/875 Net Weight kg 72 106 72 106 70 104 106 230 71 105 240 72 106 91 230 Refrigerant type R407C R407C Refrigerant charge kg 2.8 4.7 2.8 4.7 2.5 4 4.7 7.2 2.8 4.5 3.5 2.8 4.7 3.5 7.2 Precharged Length m 10m 10m Liquid line inches 9.53 (3/8) 9.53(3/8) 9.53 (3/8) 9.53(3/8) 6.35(1/4) 9.53 (3/8) 9.53 (3/8) Ø12.7(1/2) 9.53 (3/8) 9.53 (3/8) Ø15.88(5/8) 9.53 (3/8) 9.53 (3/8) 9.53 (3/8) Ø12.7(1/2) Gas line inches 15.88(5/8) 19.05(3/4) 15.88(5/8) 19.05(3/4) 15.88(5/8) 19.05(3/4) 19.05(3/4) Ø28.6(1 1/8) 15.88(5/8) 19.05(3/4) Ø28.6(1 1/8) 15.88(5/8) 19.05(3/4) 15.88(5/8) 19.05(3/4) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3Ø 220/240V 1Ø 380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Approximate packing measurement m 3 0.36 0.53 0.36 0.53 0.36 0.53 0.53 1.62 0.36 0.53 1.62 0.36 0.53 0.53 1.62 33
Utopia G8 RPC Technical Description Stylish design Space saving design Easy installation Quiet Operation Quiet operation, easy installation and space saving design Versatile mounting To expand installation and positioning options, HITACHI has added a second drain pipe connector, one more than conventional units. Refrigeration pipes have also been improved and can now be connected at the left, right or rear of the unit. Rear Side Quiet Operation The ceiling unit is equipped with a highly efficient, multi-blade centrifugal fan that generates a powerful yet gentle airflow throughout the room. A redesigned aerodynamically tested air panel minimises operational sound even at high fan speeds. Easier installation By enabling refrigeration piping to be tucked-in close to each indoor unit, piping layout and installation have been made much easier. Anti-mildew filter Anti-mildew filter is equipped as a standard accessory. Ceiling suspended Ceiling suspended systems Open Space 163mm Concealed 150mm (2,0, 2,5 and 3,0 HP) Drain piping Space saving design Hitachi s unique feature An innovative fan and heat exchanger design led to the creation of today s ultra-slim ceiling unit. Fully adjustable mounting brackets permit close fitting to the ceiling to make installation possible in even the smallest area. Less than 163mm of vertical space are required for installation. Model RPC 2.0FSNE RPC 2.5FSNE RPC 3.0FSNE RPC 3.5FSNE RPC 4.0FSNE RPC 5.0FSNE RPC 6.0FSNE Indoor Unit Configuration Single Twin Triple Quad Single Twin Quad Single Single Single Twin Single Twin Single Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 5.00 10.00 14.00 20.00 6.30 12.50 25.00 7.10 8.00 10.00 20 12.50 25.00 14.00 Nominal Heating Capacity kw 5.60 11.20 16.00 22.40 7.00 14.00 28.00 8.00 9.00 11.20 22.4 14.00 28.00 16.00 Sound Pressure Levels db(a) 44/42/38 46/43/41 48/45/42 48/45/42 49/45/39 49/46/41 50/48/44 Dimensions (HxWxD) mm 163/1094/625 163/1314/625 163/1314/625 163/1314/625 225/1314/625 225/1574/625 225/1574/625 Net Weight Indoor unit kg 28 31 31 31 35 41 41 Air Flow Rate (Hi/Me/Lo) m 3 /min 15/13/10 18/16/12 21/17/15 21/17/15 30/24/19 35/28/21 37/32/27 Approx. packing measurement m 3 0.24 0.29 0.29 0.29 0.36 0.43 0.43 Cooling Only RAS 2.0AGV8E RAS 4.0AG(V)8E RAS 6.0AG8E RAS 8.0AG8E RAS 2.5AG(V)8E RAS 5.0AG8E RAS 10AG8E RAS 3.0AG(V)8E RAS 3.5AG(V)8E RAS 4.0AG(V)8E RAS 8.0AG8E RAS 5.0AG8E RAS 10AG8E RAS 6.0AG8E Combined Outdoor Unit Heat Pump RAS 2.0HGV8E RAS 4.0HG8E RAS 6.0HG8E RAS 8.0HG8E RAS 2.5HG8E RAS 5.0HG8E RAS 10HG8E RAS 3.0HG8E RAS 3.5HG8E RAS 4.0HG8E RAS 8.0HG8E RAS 5.0HG8E RAS 10HG8E RAS 6.0HG8E Total Input power cooling kw 2.8 4.6 6.5 9.4 2.7 5.6 11.6 3.2 3.3 4.6 9.4 5.6 11.6 6.5 Total Input power heating kw 2.4 4.3 6.2 9.3 2.7 5.8 11.3 3.2 3.5 4.3 9.3 5.8 11.3 6.2 Sound Pressure Levels db(a) 49 55 56 61 51 56 62 53 55 55 61 56 62 56 Air Flow Rate (Hi/Me/Lo) m 3 /min 36 70 110 135 40 103 135 46 70 70 135 103 135 110 Dimensions (HxWxD) mm 800/850/350 1240/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1240/850/350 1562/1000/875 1240/850/350 1562/1000/875 1240/850/350 Net Weight kg 70 104 106 230 71 105 240 72 91 104 230 105 240 106 Refrigerant type R407C R407C Refrigerant charge kg 2.5 4 4.7? 2.8 4.5 7.2 2.8 3.5 4 7.2 4.5 9.0 4.7 Precharged Length m 10 10 Liquid line inches 6.35(1/4) 9.53 (3/8) 9.53 (3/8) Ø12.7(1/2) 9.53 (3/8) 9.53 (3/8) Ø15.88(5/8) 9.53 (3/8) 9.53 (3/8) 9.53 (3/8) Ø12.7(1/2) 9.53 (3/8) Ø15.88(5/8) 9.53 (3/8) Gas line inches 15.88(5/8) 19.05(3/4) 19.05(3/4) Ø28.6(1 1/8) 15.88(5/8) 19.05(3/4) Ø28.6(1 1/8) 15.88(5/8) 15.88(5/8) 19.05(3/4) Ø28.6(1 1/8) 19.05(3/4) Ø28.6(1 1/8) 19.05(3/4) Power supply V/Ph/Hz 220/240V 1Ø380/415 3Ø 220/240V 1Ø380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/15.5 c WB Approx. packing measurement m 3 0.36 0.53 0.53 1.62 0.36 0.53 1.62 0.36 0.53 1.62 0.53 1.62 0.53 35
Utopia G8 RPFI Technical Description Floor concealed indoor units RPFI Compact design 620mm in height 220mm in depth Space-saving slim unit, only 220mm in depth Slim line design only 220mm in depth allowing the unit to be installed without spoiling the style or beauty of the room. Effective use of space by window With a height of 630mm, may be installed by a window leaving plenty of window space. Best installed in a perimeter zone. Low height Only 630mm. Concealed Floor Mounted Compact design for limited space inside of perimeter wall. So compact that it fits into even the smallest space. Special emphasis placed on interior design compatibility as well as space saving design, allowing it to fit perfectly into the space below a bay window. Optional location for remote control switch Install the PC-P1HE under the plastic cover Floor Mounted Floor mounted systems uncased Model RPFI 1.5FSNE RPFI 2.0FSNE RPFI 2.0FSNE RPFI 2.5FSNE Indoor Unit Configuration Twin Quad Single Twin Triple Quad Single Twin Quad Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.10 14.00 5.00 10.00 14.00 20.00 6.30 12.50 25.00 Nominal Heating Capacity kw 8.00 16.00 5.60 11.20 16.00 22.40 7.00 14.00 28.00 Sound Pressure Levels db(a) 38/35/31 39/36/32 39/36/32 42/38/34 Dimensions (HxWxD) mm 620/988/220 620/1238/220 620/1238/220 620/1238/220 Net Weight Indoor unit kg 23 27 27 28 Air Flow Rate (Hi/Me/Lo) m 3 /min 12/10/9 16/14/11 16/14/11 16/14/11 Approx. packing measurement m 3 0.23 0.25 0.25 0.25 Cooling Only RAS 3.0AG(V)8E RAS 6.0AG8E RAS 2.0AGV8E RAS 4.0AG(V)8E RAS 6.0AG8E RAS 8.0AG8E RAS 2.5AG(V)8E RAS 5.0AG8E RAS 10AG8E Combined Outdoor Unit Heat Pump RAS 3.0HG8E RAS 6.0HG8E RAS 2.0HGV8E RAS 4.0HG8E RAS 6.0HG8E RAS 8.0HG8E RAS 2.5HG8E RAS 5.0HG8E RAS 10HG8E Total Input power cooling kw 3.2 6.5 2.8 4.6 6.5 9.4 2.7 5.6 11.6 Total Input power heating kw 3.2 6.2 2.4 4.3 6.2 9.3 2.7 5.8 11.3 Sound Pressure Levels db(a) 53 56 49 55 56 61 51 56 62 Air Flow Rate (Hi/Me/Lo) m 3 /min 46 110 36 70 110 135 40 103 135 Dimensions (HxWxD) mm 800/850/350 1240/850/350 800/850/350 1240/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1562/1000/875 Net Weight kg 72 106 70 104 106 230 71 105 240 Refrigerant type R407C R407C Refrigerant charge kg 2.8 4.7 2.5 4 4.7 7.2 2.8 4.5 9.0 Precharged Length m 10 10 Liquid line inches 9.53 (3/8) 9.53 (3/8) 6.35(1/4) 9.53 (3/8) 9.53 (3/8) Ø12.7(1/2) 9.53 (3/8) 9.53 (3/8) Ø15.88(5/8) Gas line inches 15.88(5/8) 19.05(3/4) 15.88(5/8) 19.05(3/4) 19.05(3/4) Ø28.6(1 1/8) 15.88(5/8) 19.05(3/4) Ø28.6(1 1/8) Power supply V/Ph/Hz 220/240V 1Ø380/415 3Ø 220/240V 1Ø380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Approx. packing measurement m 3 0.36 0.53 0.36 0.53 0.53 1.62 0.36 0.53 1.62 37
Utopia G8 RPF Technical Description Floor mounted indoor units RPF Floor Type Slim design, only 200mm deep Low height, only 630mm Light unit Low sound level Space-saving slim unit, only 220mm in depth Slim line design only 220mm in depth allowing the unit to be installed without spoiling the style or beauty of the room. Effective use of space by window With a height of 630mm, may be installed by a window leaving plenty of window space. Best installed in a perimeter zone. Low height Only 630mm. Concealed Floor Mounted Compact design for limited space inside of perimeter wall. So compact that it fits into even the smallest space. Special emphasis placed on interior design compatibility as well as space saving design, allowing it to fit perfectly into the space below a bay window. Optional location for remote control switch Install the PC-P1HE under the plastic cover Floor Mounted Floor mounted systems cased Model RPF 1.5FSNE RPF 2.0FSNE RPF 2.0FSNE RPF 2.5FSNE Indoor Unit Configuration Twin Quad Single Twin Triple Quad Single Twin Quad Power Supply V/Ph/Hz 220-240V/50Hz 220-240V/50Hz Nominal Cooling Capacity kw 7.10 14.00 5.00 10.00 14.00 20.00 6.30 12.50 25.00 Nominal Heating Capacity kw 8.00 16.00 5.60 11.20 16.00 22.40 7.00 14.00 28.00 Sound Pressure Levels db(a) 38/35/31 39/36/32 39/36/32 42/38/34 Dimensions (HxWxD) mm 630/1170/220 630/1420/220 630/1420/220 630/1420/220 Net Weight Indoor kg 23 33 33 34 Air Flow Rate (Hi/Me/Lo) m 3 /min 12/10/9 16/14/11 16/14/11 16/14/11 Approx. packing measurement m 3 0.24 0.29 0.29 0.29 Cooling Only RAS 3.0AG(V)8E RAS 6.0AG8E RAS 2.0AGV8E RAS 4.0AG(V)8E RAS 6.0AG8E RAS 8.0AG8E RAS 2.5AG(V)8E RAS 5.0AG8E RAS 10AG8E Combined Outdoor Unit Heat Pump RAS 3.0HG8E RAS 6.0HG8E RAS 2.0HGV8E RAS 4.0HG8E RAS 6.0HG8E RAS 8.0HG8E RAS 2.5HG8E RAS 5.0HG8E RAS 10HG8E Total Input power cooling kw 3.2 6.5 2.8 4.6 6.5 9.4 2.7 5.6 11.6 Total Input power heating kw 3.2 6.2 2.4 4.3 6.2 9.3 2.7 5.8 11.3 Sound Pressure Levels db(a) 53 56 49 55 56 61 51 56 62 Air Flow Rate (Hi/Me/Lo) m 3 /min 46 110 36 70 110 135 40 103 135 Dimensions (HxWxD) mm 800/850/350 1240/850/350 800/850/350 1240/850/350 1240/850/350 1562/1000/875 800/850/350 1240/850/350 1562/1000/875 Net Weight kg 72 106 70 104 106 230 71 105 240 Refrigerant type R407C R407C Refrigerant charge kg 2.8 4.7 2.5 4 4.7 7.2 2.8 4.5 9.0 Precharged Length m 10 10 Liquid line inches 9.53 (3/8) 9.53 (3/8) 6.35(1/4) 9.53 (3/8) 9.53 (3/8) Ø12.7(1/2) 9.53 (3/8) 9.53 (3/8) Ø15.88(5/8) Gas line inches 15.88(5/8) 19.05(3/4) 15.88(5/8) 19.05(3/4) 19.05(3/4) Ø28.6(1 1/8) 15.88(5/8) 19.05(3/4) Ø28.6(1 1/8) Power supply V/Ph/Hz 220/240V 1Ø 380/415 3Ø 220/240V 1Ø 380/415 3Ø Working Range C Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Cooling Operation: -5 c/43 c DB Heating Operation: -8 c/ 15.5 c WB Approx. packing measurement m 3 0.36 0.53 0.36 0.53 0.53 1.62 0.36 0.53 1.62 39
Utopia G8 Centrifugal 5HP Outdoor Units Ducted Condensing Unit Non visible installation: Suitable application in business and housing where it s forbidden or impossible to place outdoor unit outside the building. Avoid legislation and local regulations regarding outdoor units installation. Hitachi high reliable Scroll Compressor, and Utopia series control. Utopia centrifugal New structure and dimensioning according to use of centrifugal fan. Space saving due to use of centrifugal fan. Installation of ducts could be performed. The new unit can be installed in indoor or outdoor locations. Four different configurations for air inlet and outlet (changeable in the field). Compatible with all indoor units. Centrifugal systems Model RASC-5HG8E RASC-10HG8E Nominal Cooling Capacity kw 12.5 25.0 Nominal Heating Capacity kw 14.0 28.0 Cabinet Colour (RAL 9002) Soft Grey Soft Grey (RAL 9002) Sound Pressure Level (1*) db(a) 53 75 Outer Dimensions (HxWxD) mm 555/1312/835 640/2050/930 Net Weight kg 175 310 Refrigerant Charge kg 4.5 4.5 Refrigerant R407C (Factory charged for 10 meters) (2*) R407C (Factory charged for 10 meters) (2*) Compressor Type Hermetic (Scroll) Hermetic (Scroll) Model G500DH G1000EL Quantity un. 1 1 Fan Motor Type Centrifugal Fan Centrifugal Fan Output kw 550 1.10 Quantity un. 1 1 Nominal Static Pressure Pa 50 50 Maximum Static Pressure Pa 130 130 Connections Service Valves with Flare Nut connection S-Valves with Flare Nut/Flange connection Refrigerant Piping Liquid Line mm (in) 9.53 (3/8) 15.88 (5/8) Gas Line mm (in) 19.05 (3/4) 28.6 (1 1/8) Drain Piping (exterior diameter) mm 22 22 Packing Measurements m 3 0.88 0.88 Note: (1*). The sound pressure level is based on the following conditions: - 3 m. from the unit front surface. The above data was measured in anechoic chamber so that reflected sound should be taken into consideration in the field. In case of night Shift setting, the noise level decrease about 2 db(a). (2*). The outdoor unit is charged with refrigerant before shipment. The charged volume is suitable for a maximum refrigerant piping of 10m., when combining to a Hitachi standard indoor unit. 41
Utopia G8 KPI Technical Description Various Control Examples of Total Heat Exchanger Standard Connection Central Station (PSC-5S) Structure Outdoor air Air supply fan Outdoors Electrical components box Air discharge Fixed Type Heat Exchanging Element Air supply Air filter (for discharge) Indoors Indoor air The newly developed fixed type heat exchanging element with high temperature exchange efficiency equivalent to the rotor type element, has been adopted for the new total heat exchangers (Temp Exchange Efficiency: 77% <in case of 500m 3 /h type unit>). In addition, reliability is increased due to reduction of moving parts. Low weight with simple unit structure: 33kg (in case of 500m 3 /h type unit). Provides a comfortable environment by control interlocking with air conditioning units. Controllable using the remote control switch for the air conditioning unit. Can be controlled in various ways using the remote control switch for the air conditioning unit (PC-P1H). Functions Simultaneous RUN/STOP switch both for air conditioning units and heat exchanging unit Individual operation of heat exchanging unit Fan speed control (high/medium/low) Ventilation mode selection (automatic/heat exchange/bypass) *1 Pre-cool/pre-heat control (interlocking start with delay in 30 or 60 minutes)*1 ON/OFF timer (every half hour, maximum 24 hours) Increased air supply operation Specific alarm display *1 Required option to be selected at remote control switch. Automatic selection of most suitable ventilation mode Depending on temperature conditions both outdoors and indoors, the most suitable ventilation mode is automatically selected, designed for energy efficiency. Example of System Outlook of System Component of System Example of System Outlook of System Component of System PC-P1H SET-FREE PC-P1HE UTOPIA Able to control up to 16 Indoor Units and Total Heat Exchanger Units PC-P1H Remote Control Switch (PC-P1H) CS-NET 1 PC-P1H Hitachi Computer Control Network System CS-NET (version 7) PC-P1H 2 T.H.E+PC-P1H Able to control with PC-P1H directry CS-NET PC-P1H PSC-5S Able to control up to 128 Indoor Units consist of 16 refrigeration series Central Station (PSC-5S) Remote Control Switch (PC-P1H) 4 H-LINK Able to control up to 128 Indoor Units consist of 16 refrigeration series CS-NET Remote Control Switch (PC-P1H) 3 H-LINK PC-P1H ~ 1 5 :INDOOR UNIT :TOTAL HEAT EXCHANGER ( T.H.E ) :NEW AVAILABLE SYSTEM Model KPI-2521 KPI-5021 KPI-8021 KPI-10021 CS-NET 5 H-LINK Total heat exchanger Other Characteristics Quiet operation with low noise level of 32.5-33.5 db (A) (at Hi Tap of KPI 5021 Type) has been realised by improving the flow path configuration. Operation not only with SET-FREE Series Indoor Unit, but also with UTOPIA Series Indoor Unit. Connectable to H-LINK System with Central Station or with CS-NET in Operation with Indoor Unit. Flexible Duct Installation: The connecting direction of duct at outdoor side (OA,EA) can be changed according to the condition of the installation site (2 directions). Reduced packing material for environment protection. The wood for the packing use has been reduced for environment protection. Can also be installed upside down. Power Supply AC 1 -,220-240V / 50Hz, 60Hz*1 Air Flow Rate (m 3 /h) Hi 250/250 500/500 800/800 1,000/1,000 Me 250/250 500/500 800/800 1,000/1,000 Lo 165/150 350/300 670/660 870/720 Temperature Exchange Efficiency (%) 83 82 81 81 Enthalpy Exchange Efficiency Heating/Cooling 74/68 73/68 73/68 73/67 Sound Pressure Level Hi 26.5-27.5/28.5 32.5-33.5/32.5 33.3-34.5/35 36-37/36 (Overall A Scale) at 1.5m Me 25-26/25.5 30-31/28.5 32-33/31 34-35/34 from the unit (under)*3 *4 Lo 21-22/21 23.5-24.5/23 30-31/29 31.5-32.5/30 External Pressure (PA) Hi 65/100 150/200 140/230 160/200 *2 Me 40/50 60/60 100/120 100/110 Lo 20/20 30/20 70/80 80/60 Outer Dimensions Height 275 317 398 398 Width 735 1016 1004 1231 Depth 780 888 1164 1164 Net Weight Kg 21 33 61 72 Approx Packing Measurement m 3 0.26 0.46 0.70 0.84 NOTES: *1 KPI-10021 has different units according to the applied power supply, 220-240v, 50Hz and 200V/60Hz *2 Use it under the following conditions. KPI-8021: 29Pa or more, KPI-10021: 49Pa or more *3 The sound pressure level is based on the following conditions; 1.5 meter beneath the unit and this data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. *4 The sound pressure is based on the total heat exchange mode. In case of the bypass ventilation mode, the sound pressure level increased by approximately 1dB(A). 43
System Example 1 : Outdoor Units 16 PC USB Connection (Field supply) H-LINK Max. 16* 1 Outdoor Units HARC 40 Max. 16* 3 Indoor System Example 1 : Outdoor Units 16 (Option) Units per cycle PCB for 10HP and 128 USB Connection units per Harc-box (Field supply) PC in CS-NET system H-LINK Max. 16* 1 Outdoor Units PCB Control systems System Example 2 : 16<Outdoor in CS-NET system Units 128 PC USB Connection (Field supply) H-LINK System Example 2 : 16<Outdoor Units 128 PC USB Hub (Field supply) HARC 40 (Option) HARC 40 ID=0(Option) USB USB Hub Connection (Field (Field supply) H-LINK HARC 40 ID=0(Option) HARC 40 ID=7(Option) PCB H-LINK HARC 40 ID=7(Option) H-LINK PCB PCB PCB Max. 16* 3 Indoor Units per cycle for 10HP and 128 units per Harc-box Max. 16* 1 Outdoor Units Max. 16* 1 Outdoor Units Max. 16* 1 Outdoor Units Max. 16* 3 Indoor Units per cycle PCB for 10HP and 128 units per Harc-box Max. 16* 1 Outdoor in CS-NET Units system Max. 16* 3 Indoor Units per cycle for 10HP and 128 units per Harc-box in CS-NET system PCB PCB PCB PCB PCB CS-NET Features * 1: If the number of indoor units per a refrigeran cycle is 17 or greater, count one outdoor unit as two units. *2: Max. total length of transmission wire is 1,000 meters. * 3: Max. 8 units for 5HP *1: If the number of indoor units per a refrigerant cycle is 17 or greater, Max. 13 count units one for outdoor 8HP unit as two units. Max. 16 units for 16 and 20HP Max. 27 units for 24HP *2: Max. total length of transmission wire is 1,000 meters. Max. 32 units for 30HP *3: Max. 8 units for 5HP Max. 13 units for 8HP Max. 16 units for 16 and 20HP Max. 27 units for 24HP Max. 32 units for 30HP H-Link Transmission System This system connects the control wires for the outdoor and indoor units across two or more refrigerant systems. Regardless of the order or number of units to be connected, all the units can be controlled once they have been connected. By this method, design flexibility is very high, installation is easy and total costs are reduced. Furthermore, central control is possible by connecting CS-NET to H-LINK wiring located in the room next to the room where CS-NET is installed. Computer Controlled Network System Control Function On/Off control Operation mode setting Temperature setting [setting range: Cooling 19 C 30 C, Heating 19 C 30 C] Air direction setting Remote control fully allowed/prohibited Remote control partially allowed/prohibited Fan speed setting Air direction setting (cannot be set by wireless remote control) Filter sign resetting Annual timer Monitoring Function On/Off Control Operation mode Set fan speed Set air direction Set temperature Remote control prohibition setting Filter sign Alarm Alarm code Air inlet temperature Floor layout plan (BMS style) Web server functionality (internet/intranet connection) CS-NET HARC-40 45
Easy Set Up Floor Layout Plan Web Connection after Easy Set Up CS-NET set up and operation Module configuration box Click on the Module Configuration Icon of the first Unit to open the Module Configuration Box. The Icon for the open Module will have a yellow surround to indicate the Module that is open. Operation When the Set Up and Auto Configuration have been completed, the Unit information must be entered in each Individual Module. It is important for future service to enter the Serial Numbers and Models in their respective fields, as this will avoid time consuming searching in the event of warranty claims or spare parts identification. Graphic Representation When the systems are running, the operating conditions for each unit are shown in a graphical layout which can be operated through FAULT and then SYSTEM STATUS. By clicking on DISPLAY the operating conditions will be shown in a tabular form. This graphical layout is not available for UTOPIA or UTOPIA BIG units. 47
PC-P1HE Remote Control Switch Specifications of HARC-BX Features a wide range of functions, including a large liquid crystal display screen, self-diagnostic capabilities, and a timer which can be set in 0.5 hour intervals. A convenient remote control which is supplied as standard with all units. Type Standard Option A Option B Connectable Q ty 64 64 32 Control Monitor Control Monitor Control Monitor Run/Stop & Alarm* Operation Mode Set Temp Fan Speed Louver Position RC. Sw.Permission/Prohibition Alarm Code IU Inlet Air Temp IU Outlet Air Temp Outdoor Air Temp Thermo-ON/OFF Remark Use PC-P1H or PC-2H2 Maximum Wiring Length 1000m (Bus Total length) *Alarm for monitor only PC-LH3A Wireless Remote Control Switch No wiring work required. Two or more units can be operated simultaneously by remote control. The receiver kit is integral in wall mounted units. Receiver kit PC-RLH11 is required for all other models. PC-P5H Simplified remote control switch The main function of this easy-to-use remote control is temperature setting. Suitable for a variety of applications such as hotels, restaurants and offices. 2 remote controls or group control (for 16 controls max) can be used, similar to the standard remote control. If a problem occurs, an alarm code immediately shows the details of the problem. *When the half-size remote control is used, cooling/heating is automatic. Lon Works Gateway Interface to LON WORKS BMS Systems Using HARC-BX allows control of up to 5 setting points and remote monitoring of up to 9 valves. By connecting HARC-BX to H-LINK, a group of up to 16 remote controls can be used and up to 64 indoor units can be controlled. interface PSC-5S Centralised Remote Control Switch Remote controllers This Central Station enables centralised control of up to 16 groups of indoor units (at maximum 256 indoor units). Features a wide range of functions, including a large liquid crystal display screen and alarm code. User friendly Central Station. Remote start/stop and common fault signal available. PSC-5T 7-Day Timer The 7-Day Timer allows long-term unattended control. By plugging this time to the optional remote control switch or Central Station, daily ON/OFF operation control throughout the week is available. ON/OFF setting is available three times a day by two different patterns. HARC-BX 49
Indoor Units 4-Way Cassette Type Item Receiver Kit for Wireless Control RCI 1.0-6.0FSN1E PC-RLH8 (on the panel) 2-Way Cassette Type Item Receiver Kit for Wireless Control RCD 1.0-5.0FSN PC-RLH9 (on the panel) Mini Wall Mounted Type Item Wireless Receiver Kit RPK 0.8-4.0FSNM As standard In-the-Ceiling, Wall, Floor and Ceiling Type Item RPI (0.8-5.0HP), RPK (0.8-4.0HP), RPC (2.0-5.0HP), RPF (1.0-2.5HP), RPFI (1.0-2.5HP) Receiver Kit for Wireless Control (with 5m cable) PC-RLH11 (wall mounted) Optional parts Control System Compatibility Item RPI-FSN RCI-FSN RCD-FSN RPK-FSN RPC-FSN RPF(1)-FSN KPI Remote Control Switch* 1 PC-P1H (without cable) Wireless Remote Control Switch* 2 PC-LH3A (new) Half-size Remote Control Switch PC-P5H 7-Day Timer PSC-5T Centralised Remote Control Switch* 3 PSC-5S Remote Control Cable PRC-10E1, 15E1, 20E1, 30E1 for PC-P1H 3P Connector Cable PCC-1A Remote Sensor THM-R2A Computer Controlled Network System CS-NET *1 As the PC-P1H does not include a remote control cable, prepare one in the field, or use PRC-10E1, 15E1, 20E1, 30E1. *2 PC-LH3 can be used instead of PC-LH3A. *3 Supply 220V or 240V 51
Specifications in this catalogue are subject to change without notice in order that HITACHI may bring the latest innovations to their customers. Omitting typing errors. Hitachi Europe Ltd Whitebrook Park Lower Cookham Road Maidenhead Berkshire SL6 8YA United Kingdom Distributed by: email: aircon.enquiries@hitachi-eu.com www.hitachiaircon.com HELGB-SF-002