PRODUCT / APPLICATION INFORMATION



Similar documents
BSX TM. Self-Regulating Heating Cable. Product Specifications

Sizing Circuit Breakers for Self-Regulating Heat Tracers

Self-Regulating Low Temperature Heating Cable

Pictorial Index... A-14 Introduction to Heat Trace Cable Systems Installation Examples Engineering Guide Heat Loss Tables...

Nelson MI Cable is a high performance, industrial grade heat tracing cable used for applications requiring:

Heating Cable. Construction

Cable Size Selection for Energy Efficiency

Insulation Resistance Testing of Low Voltage Cables in the Field

NEMA Magnet Wire Thermal Class Ratings

Electric Heat Tracing INSTALLATION PROCEDURES

Complex Piping Design Guide for Self-Regulating Heating Cables

Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation

UNITHERM UNITHERM 2256/2266 SELF-REGULATING ELECTRIC TRACE TUBING

Heat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation.

Appendix J: Engineering Specification for Electrical Heat-Tracing Systems

CABLE 101. The Basics of Wire & Cable. Copyright 2007, Belden Inc.

Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE

FLEXTREME AND FLEXTREME IF

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET

Effect of Temperature on Wireline Cables Technical Bulletin Ten

WHITE PAPER Fire & safety performance standards

Chromalox PRECISION HEAT AND CONTROL. Electrical Heat Tracing Systems Design Guide

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems

SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES

New Cable Tie Type Classifications

Thermocouple Wire & Cable

Protection Systems. A UTC Fire & Security Company F Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

Pipe Freeze Protection Design/Install Guide

The soot and scale problems

ALARMLINE ANALOGUE Linear Heat Detection System

HEAT TRACING PRODUCTS

CATHODIC PROTECTION SYSTEM DESIGN

Uniprise Solutions COAX 101. White Paper.

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering

Stephen G. Whitley, Senior Vice President & Chief Operating Officer

This chapter is devided into two sections:

POWER AND VOLTAGE RATING

Mineral Insulated Cable A cable for today and tomorrow!

Avoiding Burning Through: Control the Inside Surface Temperature, Not the Pressure

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

Fire Performance Standard

Avoiding AC Capacitor Failures in Large UPS Systems

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.

Wire and Cable Product Guide

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

Chapter 9. Bonding and Grounding

UGVCL/SP/591/11KV HT AB CABLE

Top Drive Service Loops. Conventional, Enhanced and Superior Solutions for Drilling Applications

Cable Limiters. Increase System Reliability Decrease Downtime PRODUCT GUIDE

This paper describes Digital Equipment Corporation Semiconductor Division s

Flexible cables for submersible products

ICM Project Underground Infrastructure and Cable

SELF-REGULATING PIPE TRACING HEATER CABLE

KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES

HVAC Super Pro FAQ. Can HVAC SUPER PRO be used on both hard and soft copper and aluminum tubing?

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

Installation Instructions. Industrial Heating Cable Products

Electric heat tracing

Carbon Cable. Sergio Rubio Carles Paul Albert Monte

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

Oscar E. Morel UtilX Corporation

Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5

Electric Heat Tracing INSTALLATION PROCEDURES

ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

GroundRod AC Substation Earthing Tutorial

PTC-Resistor Temperature-Sensors MINIKA to DIN and DIN

NELSON HEAT TRACING SYSTEMS

WIRE AND CABLE ENGINEERING GUIDE

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

Application Note. Soldering Methods and Procedures for 1st and 2nd Generation Power Modules. Overview. Analysis of a Good Solder Joint

Fault location on power cables. Fault location on power cables

COLD LEAD OPTIONS FOR XMI MINERAL INSULATED (MI) HEATING CABLES

A quick product finder for commercial applications JUDD WIRE INC. A member of the Sumitomo Electric Industries group of companies

The Electrical Properties of Materials: Resistivity

13 common causes of motor failure

Polyolefin Heat Shrink Tubing for Tight-Tolerance Medical Applications

Heat Pipe Selection Revision 12/04/2001

Shelf Life Prediction Of Medical Gloves

Basic RTD Measurements. Basics of Resistance Temperature Detectors

INTERNATIONAL STANDARD

Heat Tracing Sales Mt. Airy, Maryland Installation Instructions

Stephanie Watson. Service Life of Electrical Cable and Condition Monitoring Methods

G670 Intermittent Pilot Ignition Controls

Self-Regulating Pipe Tracing Heating Cable Specification/Application Guide. Polyolefin. Performance and Rating Data

Power Supply Cables and Connectors

RE-ENTERABLE SPLICE CLOSURE KITS. (For Air Core None Pressurized Cable)

RayClic Connection System Installation Instructions

Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc.

Contact Information: Electrical Connection Kit for CL Series Constant Wattage Temptrace for Low Temperature Maintenance.

INTERNATIONAL TELECOMMUNICATION UNION #/.3425#4)/. ).34!,,!4)/.!.$ 02/4%#4)/. /& #!",%3!.$ /4(%2 %,%-%.43 /& /543)$% 0,!.43

International Electrotechnical Commission Standards

Transcription:

Abstract This paper will discuss performance life testing and stability testing used for self-regulating heating cables. It will show how the techniques were developed and evolved from the 970 s to the present How these techniques re used to establish ratings on the latest high temperature heating cables will also be discussed. INTRODUCTION Self-regulating conductive polymer heating cables are widely used for freeze protection and process temperature maintenance in industrial applications. In these applications the cost of downtime is significant. Therefore, it is critical that heat tracing provide the required heat to maintain operating conditions over the expected life of the process unit. The question arises, How does one establish or project long term performance and stability of a self-regulating heating cable?. The typical expectation for industrial applications is that the cable will function for 5 to 20 years. Basic Constructions First it is important to understand the basic constructions of self-regulating heating cables. The heating element of a self-regulating heating cable is a conductive polymer that exhibits a PTC effect. As the temperature of the heating element increases, its electrical resistivity increases. Thus, the conductive polymer has a positive temperature coefficient for resistance (PTC). The power output or thermal output decreases with increasing temperature. A typical construction for a self-regulating heating cable is shown in Figure. Figure Bus Conductors Heating Element Primary Dielectric Metallic Braid Outer Jacket This shows a monolithic construction with the heating element or core between two conductors. This forms a parallel circuit so the heating cable can be cut to length without changing its lineal power output. The heating element consists of carbon black mixed into a semicrystalline polymer. The melting point of the polymer dictates the self-regulating temperature or shut-off temperature. Polyethylene based heating cores are primarily used for low temperature, freeze protection applications, while fluoropolymer based heating cores are used for process temperature maintenance and higher temperature exposure applications. The primary jacket provides the dielectric insulation. Metallic braid, usually tinned copper surrounds the primary jacket and serves as a ground path. For additional mechanical protection and corrosion resistance there is an outer polymer jacket over the braid. Another self-regulating cable construction is shown in Figure 2. Figure 2 Bus Conductors Spacer Heating Element (Fiber) Primary Jacket Metallic Braid Outer Jacket Here instead of a monolithic core or heating element, the heating element is a fiber that is spirally wrapped around two bus conductors with a non-conducting polymer spacer separating the bus conductors. This heating element fiber is a conductive polymer. Contact between the bus conductor and fiber heating element is enhanced with an electrically conductive paste. A primary dielectric jacket surrounds the fiber heating elements. Like the previous monolithic construction, a metal braid and outer jacket are included with the fiber construction self-regulating heating cable. Form PAF0054-00 Thermon Manufacturing Co. Subject to change without prior notice.

Factors for Long-Term Performance and Stability With conductive polymer heating elements, the aging mechanism is primarily oxidation with temperature and time. In most cases the resistance of the conductive polymer increases with temperature and time. Thus, the self-regulating heating cable is fail-safe from a burnout standpoint and excessive sheath temperatures in hazardous areas. However, it is important that the cable provide the rated power for maintaining the specified temperatures. Service life of a self-regulating heating cable is not only dependent on the polymer used for the heating element using long term performance and stability but, also is dependent on the processing. There are three key factors in manufacturing a self-regulating heating cable for long-term performance and stability: heating core homogeneity, contact resistance between heating element and bus conductor, and a closely conforming primary dielectric jacket. Heating core homogeneity - The mixing of carbon black with the polymer base is critical. Mixing is done in a compounding process. If the core does not have good homogeneity, hot spots can occur across the heating element due to localized variations in resistance. With time this results in localized thermal run away and a non-functioning heating cable. Contact between the bus conductor and the heating element - Reliable self-regulating heating cables have low contact resistance between the bus conductor and the heating element. Poor contact is somewhat like a cold joint where there is excessive heat build up. In time the localized resistance increases to the point where the heating cable is not producing its rated power. Loose primary jacket - If there are air gaps between the heating element and the primary jacket, heat transfer from the heating cable will be impeded. This results in potentially higher than normal heating core temperatures. In turn this results in faster oxidation and reduction in heating cable output. While there are other factors affecting life and stability, these three are the major factors. Temperature Ratings Due to the temperature dependence of polymers on retained properties, the temperature rating of a selfregulating heating cable is the key factor affecting performance life and stability. However, one will find not a single temperature rating, but a number of temperature rating terms for self-regulating heating cables. These terms are described as follows: Maximum maintain temperature The highest temperature of the pipe or vessel that the heating cable is capable of maintaining continuously in an energized condition. The service life expectation is 5 to 20 years. Maximum intermittent temperature - The highest temperature that the heat tracing cable may be exposed for a period of time as declared by the manufacturer. This last definition may need more explanation. Since polymer properties are time/temperature dependent, higher ratings to accommodate exposures such as steam clean or purge could be established which are higher than the continuous temperature exposure ratings. The intermittent rating is typically 000 hours of cumulative exposure. This addresses steam clean exposure over the expected system life (5-20 years) in industrial applications. Another factor in intermittent exposure is whether or not the heating cable is energized during the exposure. The power condition (energized or de-energized) is declared by the manufacturer. Performance Life and Stability Testing Since the introduction of self-regulating heating cables in the early 970 s, numerous methods have been used to establish performance life and stability. This section will describe test methods used as they evolved from the 970 s to the present.

Accelerated Aging Testing One of the first approaches used to project life of a conductive polymer heating cable was based on the Arrhenius equation. The test technique is described in UL 746B. In the 970 s many temperature ratings for polymer dielectric insulations on wire were based on UL 746B accelerated aging techniques. The material properties such as tensile and elongation of the polymer insulation changed with time and temperature according to the Arrhenius reaction rate equation: K = A exp (-E/RT) Where: K = specific reaction rate A = constant E = activation energy of the reaction R = gas constant T = temperature By taking the natural log (Loge) of both sides, the equation becomes, Loge (time) = constant + [(/2.303) (E/RT)] Or Loge (time) = a + b / T Loge(time) becomes a linear relationship with temperature. This lends itself to obtaining experimental results over short periods and being able to a project temperature at a longer time. For wire insulation an end point was typically defined such as 50% retained elongation or tensile strength. Then specimens of the polymer material were exposed to a range of elevated temperatures.tensile and elongation measurements are made on a schedule. When the end point is attained for a given specimen, the exposure time and temperature were recorded. Figure 3 shows typical data for 50% retained elongation. Elongation, % Retained 00 50 0 Figure 3 Tensile Elongation vs. Time & Temp T T2 Time T3 Failure T is the highest temperature exposure and T5 is the lowest. As the Arrhenius equation would predict, as temperature decreases, it takes longer to reach the end point. By taking this data and plotting it with Loge (time) on the y-axis and the reciprocal of absolute temperature on the x-axis a straight line is formed. Time/temperature data taken for 6 months to 24 months that will provide adequate data for a straight-line correlation that can be extrapolated to longer times (years) to find the intersection of /T. The resulting temperature becomes the rated temperature for that time period or life definition. Refer to Figure 4. Loge Time o Failure Figure 4 Projected Life, Tensile Elongation Projected Life at T X T T 2 T 3 T oven T 4 T X T4 Failure Defined as 50% Decrease in Elongation

For conductive polymer heating cables the same concepts can be applied except with a different end point criterion. As stated earlier, conductive polymer heating cables increase in resistance with time and temperature. Therefore, retained power % or percentage resistance increase is the most indicative end point for long-term performance projections. In this case the time and temperature data is recorded for the 25% resistance increase end point. Refer to Figures 5. Resistance time Resistance initial.25.00 0 Figure 5 Retained Resistance vs. Time and Temp. T T 2 T3 Time Failure Similar to the wire insulation case, data can be acquired over a period of 6 months to 24 months, and then an extrapolation can be made for establishing the temperature rating for 20 years or more for the heating cable. Refer to Figure 6. Loge Time to Failure Figure 6 Projected Life S/R Heating Cable Projected Life at T X T T 2 T 3 T oven T 4 T x T 4 Failure Defined as 25% Increase in Resistance UL 746B provides a basis for accelerated aging and life projections of materials. In the case of wire insulating material the test specimens are strips of the polymer to be evaluated. In the case of conductive polymer heating cables, sections or short lengths of heating cable are used. Strictly adhering to UL 746B, the specimens are placed in the various temperature controlled ovens in a passive or de-energized state. However, the heating cable is an active element and the test can be constructed to develop the correlation with the heating cable specimen active or in an energized condition. To do this the cable temperature in the oven must be measured and this temperature used for the time/ temperature end point. However, while accelerated aging testing provided a basis to project life of a self-regulating heating cable at a temperature, other forms of testing are necessary. A heating cable can have a 20-year life expectancy based on passive accelerated aging testing and yet degrade to an unacceptable level of performance in weeks under active conditions of voltage and temperature cycling. This can be due to the previously mentioned processing conditions that result in poor heating core homogeneity, high contact resistance between heating element and bus conductor, and a loose primary dielectric jacket. For example, a heating cable with poor contact between the bus conductor and heating core would not exhibit any abnormal degradation in performance with passive (non-energized) accelerated aging testing, but would increase rapidly in resistance with active (energized cyclic testing. As a result, various forms of short term active cyclic testing were developed to assure stability.

IEEE 55 Benchmark Test - 997 In the early 990s self-regulating heating cables were the most common approach to electrical heat tracing. Users relied on manufacturer s ratings for long-term performance. IEEE Standard 55 had been in use since 983 yet did not have any testing requirements addressing longer-term performance and stability. The IEEE 55 Working Group established for the second 5-year review cycle decided to address this issue. The matter was compounded in complexity because no longer was maximum maintain temperature the only temperature rating; maximum intermittent temperature was frequently used. Key elements for test conditions were identified: High temperature exposure Power/voltage cycling (active testing) Heating cable specimens based on the entire resistance range The resulting test conditions incorporating these elements in the IEEE 55 Std 997 are: Test specimens are selected to represent the maximum and minimum resistance Exposure at the maximum declared maintain temperature Heating cable is continuously cycled - 2 minutes energized at rated voltage and 3 minutes de-energized Duration of the test is 32 weeks (5376 hours) If intermittent temperature rating is used - Heating cable is exposed to declared maximum intermittent temperature for a time period of 8 hours per week - Power ON or OFF condition during this exposure is based on the manufacturer s rating At the completion of the test after 32 weeks the acceptance criterion is based on power output change. The window is, 0.75 < Pfinal / Pinitial <.20 This requires the heating cable to retain 75% of its initial power output and to not increase in power by more than 20%. The IEEE 55 997 Service Life Performance Benchmark test provided a means of establishing long term performance and stability based on the stated temperature ratings of the cable. Since the heating cable is energized for the maximum maintain temperature exposure, and if specified for maximum intermittent exposure, actual worst-case conditions are tested. In North America approval agencies have adopted this test as a requirement.

IEEE 55 Benchmark Test 2004 In the 990s higher temperature cable options were being developed. Polymers such as perfluoroalkoxy fluorocarbon resin (PFA) were being used for the heating element. At the time PFA was introduced, accelerated aging testing per IEEE- and UL 746B found no correlation to enable projection of a temperature rating for 0 or 20 years. For wire and cable applications long-term performance was established by measuring retained properties over 20,000 hours at 285 C which is just below the melt temperature of PFA. Therefore, use of UL 746 B for projecting life and establishing temperature ratings was not possible with these higher temperature conductive polymer self-regulating heating cables. The IEEE 55-997 Service Life Performance Benchmark test required 32 weeks. Since this test had become part of the approval process, the time required for the test became a factor in product development time and market introduction. The CSA 30.3 Working Group in Canada as well as the IEEE 55 Working Group in the USA (established for the third 5-year review cycle) decided to address this issue. The goal was to develop an equally stringent test which would provide an indication of long-term performance but which could be accomplished in a shorter period of time. The key factor is doing this was introducing thermal stress. The new shorter duration test incorporated the following: Test specimens are selected to represent the maximum and minimum resistance The heating cable is thermally cycled - Between the manufacturer s declared maximum maintain temperature and 23 C - Minimum time dwell at each extreme temperature is 5 minutes. - Total duration is 500 cycles Following the 500 cycles is the test for maximum intermittent temperature rating - The cable is exposed at the maximum rated temperature for 250 hours. - Power ON of OFF condition during this exposure is based on the manufacturer s rating After these exposures the same acceptance criterion as used in the IEEE 55 997 Benchmark test which is based on power output is applied. 0.75 < Pfinal / Pinitial <.20 To further validate this test, self-regulating cables with a known long-term stable performance were tested along with cables that had shown deterioration in performance with time. The results confirmed the 55-2004 Benchmark test is a reliable screen or indicator of long-term life and stability of self-regulating heating cables. NEW HIGH TEMPERATURE HEATING SOLUTONS In the past twenty years compounding equipment and extrusion techniques have advanced. This has provided the capability to manufacture self-regulating heating cables with high performance high temperature polymers such as PFA. A recently introduced self-regulating cable based on a PFA polymer heating element was developed with goal of () high heating core homogeneity, (2) no contact resistance between bus conductors, and (3) tight primary jacket over heating core. For this new heating cable a high degree of homogeneity is achieved through use of state-of the-art compounding equipment and techniques. The contact between the bus conductors and polymer is optimized with a monolithic type heating element construction. The primary dielectric jacket is integral to the core, which maximizes heat transfer from the heating element. The combination of the monolithic construction and integral jacket results in uniform power flux and the lowest core temperature for the lineal heating provided. This new high temperature heating cable is capable of lineal power output of 64 W/m @ 0 C with an operating voltage of 230 Vac. Based on the IEEE 55-2004 Benchmark test, the temperature ratings achieved are: Maximum maintain temperature - 2 C Maximum intermittent temperature Energized - 25 C De-energized - 250 C

Test results for the energized exposure are shown in Figure 7. After 500 cycles from 23 C to 2 C and a 250 hour exposure to 25 C, the change in power output were an increase of 4% for the higher wattage cable and a 8% decrease for the lower wattage cable. These changes are well within the requirements of IEEE 55 and indicate stability Per Centage Power Retention or Gain 20.00 00.00 80.00 60.00 40.00 20.00 0.00 Figure 7 Performance After Thermal Ageing Benchmark Maintain Temp 2 o C Maximum Intermittent Exposure Temp Maximum Minimum Power On 25 o C. 0 200 400 600 800 000 200 400 600 Thermal Cycles Low Resistance High Resistance SUMMARY With the advent of self-regulating conductive polymer heating cables in the early 970 s, a method to establish product life and stability was needed. Accelerated aging testing based on the Arrhenius equation was used along with short term cyclic testing. Heating cable life could be projected as a function of rated operating temperature. However, manufacturing faults were not always detected with accelerated aging tests based on UL 746B and IEEE. Active testing (heating cable energized) was employed in the 980 s to detect improper processing faults that can lead to deterioration in power output with time. These active testing methods were refined and became part of the IEEE 55-997 heat tracing standard as the Benchmark Service Life Test for heating cables. This test provided basis for intermittent temperature exposure ratings of S/R heating cables. It also provides the ability to establish temperature ratings for S/R cables using high temperature polymers such as PFA which do not follow Arrhenius techniques for projecting life at a rated temperature In the latest version of CSA 30.3 published in 2003 and IEEE 55 published in 2004, the severity of the exposure is increased by changing from voltage cycling to thermal cycling. This allowed a reduction is in test duration from 32 weeks to 2 weeks. The major North American approval agencies, UL and FM use the IEEE 55-2004 Benchmark test and CSA uses the virtually identical Performance After Thermal Ageing Test in CSA 30.3 as a requirement in approvals for self-regulating heating cables. With advances in processing equipment and techniques that address some of the processing challenges of the past, self-regulating heating cables are available with high lineal power outputs and high temperature exposure ratings. Their temperature ratings for long -term life and stability are established with service life tests such in IEEE 55-2004 and CSA 30.3. REFERENCES [] IEEE -2000 Recommended Practice: General Principles for Temperature Limits in the Rating of Electric Equipment and for the Evaluation of Electrical Insulation. Reaffirmed September 22, 2005. [2] IEEE Standard 55-2004 IEEE Standard for the Testing, Design, Installation, and Maintenance of Electrical Resistance Heat Tracing for Industrial Applications. Revision of IEEE Std 55-997 [3] UL 746B Standard for Polymeric Materials; Long Term Property Evaluations. August 28, 996. VITAE Richard H. Hulett received a BSME, in 964 and an MSME in 965 from Stanford University. He is the Senior Vice President of Electrical Products for Thermon Manufacturing Company, where he has been employed for 0 years. He was previously employed by Raychem for 20 years. He has been a member of the IEEE and the IEEE/IAS/PCIC for the past 25 years. He is currently a member of the IEEE Standards Board. As a member of PCIC, he has been on the Standards Subcommittee, where he has served as chair, from 993-present. He has been a member of the IEEE 55 Working Group since 979, where he has served as Chair, since 985. He is also a member of the Codes and Regulations Working Group and the Chemical Subcommittee. Mr. Hulett is a member of the American Society of Mechanical Engineers, since 964. He has received the David C. Azbill Award and the IEEE Standards Medallion.