Temperature Transmitter TTX300



Similar documents
Data Sheet 10/ EN. Contrac power electronics Customer specific settings

Degree programme in Automation Engineering

Alert/Alarm Configuration in FG-110 for Emerson s AMS Suite: Intelligent Device Manager

TwinCAT NC Configuration

Technical Information POWER PLANT CONTROLLER

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

6ES7313-5BF03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A

Instruction Manual Service Program ULTRA-PROG-IR

Process Control Primer

Device Management Jonas Berge Emerson Process Management

PREMIUM CLEAN ROOM MONITOR MODELS 8630-CRM-S 8630-CRM-P

FIELDBUS DIAGNOSTICS: LATEST ADVANCEMENTS OPTIMIZE PLANT ASSET MANAGEMENT

CPW Current Programmed Winder. Application Handbook. Copyright 2002 by Eurotherm Drives, Inc.

Terminology and Symbols in Control Engineering

Controller Automation, Model II+

Unidirectional Transmitter/ Receiver Units Introduction

Control of an industrial process using PID control blocks in automation controller

TTH300 Head-mount temperature transmitter

PRODUCT PROFILE FEATURES

Section 3. Sensor to ADC Design Example

Measurement Products. FieldKey Wireless Adapter Unlock the process and maintenance information stranded in your field instruments

Automation System TROVIS 5100 Ventilation Controller TROVIS 5177

Transmitter Interface Program

EBS852 (Contrac) Power Electronic Unit

Automation and Systems Technology. LABCONTROL TFM/TPM User Manual TroxMConnect Operating Software. 1. Introduction Software Installation 2

PC BASED PID TEMPERATURE CONTROLLER

T7560A,B,C Digital Wall Module

JUMPFLEX 857 Series ma V ma. Transducers / Relay and Optocoupler Modules

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

DeviceNet Bus Software Help for Programming an Allen Bradley Control System

A Design of a PID Self-Tuning Controller Using LabVIEW

Belimo Gateway MP to Modbus RTU - UK24MOD

SuperIOr Controller. Digital Dynamics, Inc., 2014 All Rights Reserved. Patent Pending. Rev:

S4000TH HART. HART Communication Manual

NortechCommander Software Operating Manual MAN R6

Electromagnetic Flowmeter ProcessMaster, HygienicMaster FEX300, FEX500

SIMATIC. WinCC V7.0. Getting started. Getting started. Welcome 2. Icons 3. Creating a project 4. Configure communication 5

SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.

Temp. & humidity Transmitter Instructions

NX Series Inverters. HVAC Pocket Programming Guide

SIMATIC. SM 335 High-Speed Analog Input/Output Module for the SIMATIC S7-300

FieldIT Head mounted Temperature Transmitter TF02/TF02-Ex

ROC Protocol Specifications Manual

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE

NEW. EVEN MORE data acquisition and test stand automation

Option field bus: without bus with profibus DP. Design-Index (Subject to change)

Proportional relief valves type AGMZO-TERS, AERS two stage, with integral or remote pressure transducer, ISO 6264 size 10, 20 and 32

DS1621 Digital Thermometer and Thermostat

Industrial IT System 800xA Satt Products and Systems

InTouch Example Description

WEB log. Device connection plans

ValveLink Mobile Software

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Reference Manual. Pressure/Temperature Compensated Flow (P_PTComp) Version 3.1

Low Cost, Precision IC Temperature Transducer AD592*

Microcontroller-based experiments for a control systems course in electrical engineering technology

How To Build A Rockwell Library Of Process Objects

AC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134

StackFlowMaster FPD580 TORBAR probe Stack gas metering systems. Measurement made easy. Introduction. For more information

Industrial Steam System Process Control Schemes

Designing Event-Controlled Continuous Processing Systems Class 325

LM118/LM218/LM318 Operational Amplifiers

SenseLink TM. End-Point Controller. Addendum

# 2. Selecting and Using Thermistors for Temperature Control

Cover. SEB SIMOTION Easy Basics. Collection of standardized SIMOTION basic functions. FAQ April Service & Support. Answers for industry.

SPW3 Speed Programmed Winder. Application Handbook. Copyright 2000 by SSD Drives, Inc. Printed in the United States of America HA Issue 3

EDK 350 (868 MHz) EDK 350U (902 MHz) EnOcean Developer Kit

APPLICATION NOTE. Measuring Current Output Transducers with Campbell Scientific Dataloggers. App. Note Code: 2MI-B Revision: 1

Measuring Temperature withthermistors a Tutorial David Potter

EDI Distributor Control Interface Wiring and Setup Instructions

Safety Requirements Specification Guideline

Process controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line

Certificate: / 20 August 2013

Basic RTD Measurements. Basics of Resistance Temperature Detectors

Electronic Control Devices The European Product Catalogue 2007

Device configurator DRC200

LLRF. Digital RF Stabilization System

FOUNDATION Fieldbus High Speed Ethernet Control System

Flue gas measurement and control Partial-insertion pitot tubes in CEMS applications

ACS800. Master/Follower Application Guide Supplement to Firmware Manual for ACS800 Standard Application Program

T0118 T2118 T3118. Instruction Manual

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Chapter 10. Control Design: Intuition or Analysis?

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode:

I.S. 1 remote I/O system Redundant coupling via PROFIBUS DP

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015

J TB/TW Temperature limiter, temperature monitor

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on analog output

Allen-Bradley/Rockwell

DS1621 Digital Thermometer and Thermostat

Certificate: _01 / 29 April 2014

DAQ in MATLAB HANS-PETTER HALVORSEN,

Computer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC

Wahl C50 Calibrator FEATURES

O C M III. Open Channel Flow Monitor

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

DS1307ZN. 64 x 8 Serial Real-Time Clock

Transcription:

coo Interface Description COM/TTX300/FF-EN Temperature Transmitter TTX300 FOUNDATION Fieldbus

Contents Blinder Text Temperature Transmitter TTX300 Interface Description COM/TTX300/FF-EN 01.2010 Manufacturer: ABB Automation Products GmbH Borsigstraße 2 63755 Alzenau Germany Tel.: +49 551 905-534 Fax: +49 551 905-555 CCC-support.deapr@de.abb.com Customer service center Phone: +49 180 5 222 580 Fax: +49 621 381 931-29031 automation.service@de.abb.com Copyright 2010 by ABB Automation Products GmbH Subject to changes without notice This document is protected by copyright. It assists the user in safe and efficient operation of the device. The contents of this document, whether whole or in part, may not be copied or reproduced without prior approval by the copyright holder. 2 TTX300 COM/TTX300/FF-EN

Contents 1 Introduction...4 2 Block overview...5 2.1 Resource block...6 2.2 Analog input block...6 2.3 PID block...6 2.3.1 PID block diagram...7 2.3.2 Examples of PID block applications...9 2.4 Discrete input block...11 2.5 Analog output block...11 2.6 Transducer temperature...11 2.7 Transducer HMI...14 2.8 Transducer extended diagnostics...14 3 Possible commissioning errors...16 3.1 AI block cannot be switched to "AUTO" mode...16 3.2 PID block cannot be switched to "AUTO" mode...16 COM/TTX300/FF-EN TTX300 3

Introduction 1 Introduction This manual describes the communication-specific properties of the TTX300-FF transmitter. General information on operation, sensor configuration, connection, or explosion protection can be found in the operating instructions and commissioning instructions. The TTX300 transmitter conforms to FF specification FF007-2008.3 and is certified in accordance with ITK 5.10. A device driver in the form of an EDD (Electronic Device Description) is required for commissioning purposes. The EDD can be downloaded from the Fieldbus Foundation website and from www.abb.com. The functional scope of the EDD has been expanded to support additional languages. This means that if it is used in conjunction with older host applications, in particular, you may encounter compatibility problems. For this reason, there is currently a version that conforms to the old standard and one that conforms to the new standard. You can find out whether the host application supports the new EDD standard by referring to the documentation for the system in question. It is recommended that you only use certified host systems such as ABB's Industrial IT System 800xA, as these (like the field device being described here) have been tested against the FF standard by an independent body. The parameters described in this documentation are available via the EDD in FF-compliant host applications. The way in which the individual parameters are displayed and arranged, as well as their names, may vary from host application to host application. 4 TTX300 COM/TTX300/FF-EN

Block overview 2 Block overview The transmitter contains the following FF blocks: Number Block 1 Resource block 4 AI (analog input) block 1 epid block (PID controller with expanded features) 2 DI (discrete input) block 1 AO (analog output) block 1 Temperature transducer block 1 Extended diagnostics transducer block 1 HMI transducer block (LCD) Sensor 1 Sensor 2 Transducer Temperature Calculated value Sensor 1 Sensor 2 AI 1 AI 2 AI 3 Electrical temp. AI 4 Transducer HMI Transducer ExtDiag Display value Diagnostics Diagnostics AO DI DI PID optional Resource Block A00251 Fig. 1 AI, DI, and AO are standard FF blocks. "Resource Block", "Transducer Temperature", and "epid" are extended standard FF blocks. "Transducer HMI" and "Transducer ExtDiag" are device/manufacturer-specific blocks. COM/TTX300/FF-EN TTX300 5

Block overview 2.1 Resource block The "Resource Block" contains general information about the fieldbus device, such as the manufacturer, device type, version number, and so on. Parameter Serial Number Assembly Date Bus Voltage Software Version Hardware Version Running Hours Running Hours at Device Temperature Device Temperature Min / Max Device Temperature Description Serial number of field device Assembly date of field device Fieldbus power supply in volts Firmware version of field device Hardware version of field device Running hours counter Running hours at certain electronics temperature classes Actual temperature of electronic unit Absolute minimum and maximum electronics temperature 2.2 Analog input block An AI block performs various tasks, such as rescaling, alarm handling, simulation, and so on. This is described in detail in FF document FF891. To make it easier to configure the transmitter, the channel parameter (CHANNEL) is already preset to the relevant channel for the "Transducer Temperature" block: AI 1: PRIMARY_VALUE_3 = Value calculated from sensor 1 and sensor 2 (differential, average, etc.) AI 2: PRIMARY_VALUE_1 = Measured value for sensor 1 AI 3: PRIMARY_VALUE_2 = Measured value for sensor 2 AI 4: SECONDARY_VALUE = Temperature of the reference junction or device temperature with internal reference junction 2.3 PID block The PID function block contains a proportional-integral-differential controller, as well as all the components required for scaling, limiting, alarm handling, disturbance variable feedforward control, cascading, and so on. For details, please refer to FF specification FF-891. 6 TTX300 COM/TTX300/FF-EN

Block overview 2.3.1 PID block diagram The block is structured as shown below: FF_VAL Disturbance variable calculation FF_SCALE FF_GAIN BKCAL_ BKCAL_IN Bypass TRK_IN_D Mode Setpoint limits BYPASS R_IN RCAS_IN CAS_IN SP SP_RATE_DN SP_RATE_UP SP_HI_LIM SP_LO_LIM RCAS_ PID algorithm GAIN RESET BAL_TIME RATE Output value scaling and limits _HI_LIM _LO_LIM _SCALE IN TRK_VAL Scaling and filtering PV_SCALE PV_FTIME Scaling TRK_SCALE PV Alarm HI_HI_LIM HI_LIM LO_LIM LO_LO_LIM DV_HI_LIM DV_LO_LIM R_ A00252 Fig. 2 COM/TTX300/FF-EN TTX300 7

Block overview The controlled variable (actual value) is sent to the IN input. It is scaled using the PV_SCALE parameter and is routed via a filter with the time constant PV_FTIME. The value processed in this way is called the PV (primary analog value). The mode determines the way in which the setpoint is specified. In automatic mode (AUTO), the setpoint is specified by the SP parameter. In "Cascade" mode (CAS), the setpoint is specified by the CAS_IN input of a different function block. In "Remote Cascade" mode (RCAS), the setpoint is specified by a control system in the RCAS_IN parameter. The setpoint range is limited by parameters SP_HI_LIM and SP_LO_LIM, while the maximum rate of change (only applies to AUTO mode) is limited by parameters SP_RATE_DN and SP_RATE_UP. The setpoint limited in this way is called RCAS_ and is available for use as a feedback value by control systems (this is necessary for "Remote Cascade" mode). The PID algorithm is composed of the following: Proportional component: Integral component: Differential component: The output value (manipulated variable) is proportional to the control deviation (= difference between setpoint and actual value). The proportionality factor is the "Gain" parameter. The drawback of using a purely P controller is its persistent control deviation. An I component can compensate for this, however. The control deviation is integrated in this. The time constant used here is the "Rest" parameter. The manipulated variable is the value of the integral. In this case, the control deviation changes are taken as the manipulated variable. The time constant is called the "rate". The manipulated variable for the PID algorithm is the total of the manipulated variables from all three components. A bypass is available at the same point as the PID algorithm: This allows the PID algorithm to be bypassed. In this case, the setpoint is immediately taken as the manipulated variable. A known disturbance variable can be fed forward to input FF_VAL; it is scaled using FF_SCALE and FF_GAIN. The disturbance variable scaled in this way is added to the PID algorithm's manipulated variable. The manipulated variable is scaled using _SCALE, limited by _LO_LIM and _HI_LIM, and output via. In AUTO, CAS, and RCAS modes, the value from the PID algorithm (or bypass) is taken as the output value. In R (Remote Out) mode, however, the R_IN value specified by a control system is taken. Tracking is active in LO (Local Overwrite) mode, which means that the tracking value is taken as the output value. The user can set the output value in MAN or OOS mode. The value for a tracking procedure is specified via the TRK_VAL input and scaled using TRK_SCALE. In order to use the tracking function, "Track enable" or "Track in Manual" must be activated in parameter CONTROL_OPTS. Tracking can then be activated using TRK_IN_D. The mode will change to LO (Local Overwrite) when you do this. 8 TTX300 COM/TTX300/FF-EN

2.3.2 Examples of PID block applications 2.3.2.1 Straightforward control loop, constant setpoint Block overview The flow in a pipeline is to be controlled by a butterfly valve. A permanent setpoint has been specified. Flowmeter Butterfly valve AI PID AO A00247 Fig. 3 The actual value is measured by the flowmeter and made available as an AI block. The setpoint is set in parameter SP in the PID block. The manipulated variable is sent to the AO block of the butterfly valve. It is absolutely essential for a feedback value to be sent from the AO block to the PID block so that the system can switch between modes smoothly. The PID block is in AUTO mode. BKCAL_IN BKCAL_ IN SP PID AUTO CAS_IN AO AI A00248 Fig. 4 COM/TTX300/FF-EN TTX300 9

Block overview 2.3.2.2 Straightforward control loop, external setpoint specification An external setpoint from a different function block (here, AI 1) is sent to the CAS_IN input of the PID block. To enable it to be used, the PID block enters CAS mode. AI 1 BKCAL_IN BKCAL_ AI 2 CAS_IN IN PID CAS CAS_IN AO A00249 Fig. 5 2.3.2.3 Cascaded control loops PID controllers can be cascaded. This example involves an internal control loop consisting of controller PID2, whose actual value (IN) comes from AI 3, and setpoint CAS_IN, which comes from an external controller (PID1). The external control loop (with controller PID1) receives its setpoint (CAS_IN) from AI 1 and its actual value (IN) from AI 2. The external PID controller also receives feedback values - from BKCAL_ of PID2 in this case - to make it possible to switch between modes smoothly. BKCAL_IN BKCAL_ BKCAL_IN BKCAL_ CAS_IN IN PID 1 CAS_IN IN PID 2 CAS_IN AO AI 1 AI 2 AI 3 A00250 Fig. 6 10 TTX300 COM/TTX300/FF-EN

2.4 Discrete input block Block overview The discrete input block conforms to FF standard FF891 and is used by the TTX300 for cyclic reading out of extended diagnostics information. Both DI blocks are used in conjunction with the "Transducer ExtDiag" block. See the section titled "Transducer extended diagnostics". 2.5 Analog output block The analog output block conforms to FF standard FF891 and can be used as an option for outputting any cyclic analog value from the network. The value may come from a different field device or even from the host (i.e., from the control system). The TTX300 can be used as a display device for this purpose. 2.6 Transducer temperature The transducer block contains all the parameters and functions required for measuring and calculating temperature. The values that are measured and calculated are available as transducer block output values, and are called by the function blocks as "channels". It is only possible to read out measured values cyclically from function blocks. Process Transducer Block RJ_TEMP R.J. 0 1 2 EXT_RJ_VALUE Transducer Block AI FB( s) RJ_TYPE SECONDARY_ VALUE T1 T2 Input Input 1 Input 2 SENSOR_RANGE SENSOR_CONNECTION COMP_WIRE R.J. Comp. + LIN Linearization LIN Arithmetic + LIN + SENSOR_TYPE BIAS_1 BIAS_2 + PV3_MEASURE_ TYPE PRIMARY_ VALUE_1 PRIMARY_ VALUE_3 PRIMARY_ VALUE_2 A00253 Fig. 7 COM/TTX300/FF-EN TTX300 11

Block overview Parameter Description PV1 / 2 Type Identifies measurement type of sensor 1 / 2: Process temperature Non-process temperature Differential temperature PV1 / 2 Range Physical measurement range of sensor 1 / 2, depending on sensor type selected Sensor 1 / 2 Sensor type setting for sensor 1 / 2. All types specified in the datasheet or manual are supported. Sensor Range 1 / 2 Physical measurement range of sensor. Depends on sensor type selected. Serial Number Sensor Optional field for sensor serial number 1 / 2 Cal Method Optional field for selecting calibration method 1 / 2 Cal Location 1 / 2 Optional field for specifying location of calibration Cal Date Optional field for specifying calibration date 1 / 2 Cal Person 1 / 2 Optional field for entering name of person who calibrated the sensor Connection Sensor Sensor connection type for RTD (2-, 3-, 4-wire) 1 / 2 SV (Device Displays the device temperature (secondary value) Temperature) SV Unit SV unit (device temperature), always C PV3 Displays the calculated value (PV3) (calc. value) PV3 Unit Determines the PV3 unit. Selection depends on selected sensor types 1 and 2. PV3 Measure Type PV3 measurement type. Selection depends on selected sensor types 1 and 2: PV1 (sensor 1) PV2 (sensor 2) PV1 (sensor 1) - PV2 (sensor 2) difference PV2 (sensor 2) - PV1 (sensor 1) difference Average Redundancy Bias (Offset) 1 / 2 Offset to PV1 / 2 (sensor 1 / 2) Max. Value Drag indicator: Maximum value, sensor 1 / 2 Sensor 1 / 2 Min. Value Drag indicator: Minimum value, sensor 1 / 2 Sensor 1 / 2 Device Temperature Temperature of reference junction (Reference junction Temperature internal) 12 TTX300 COM/TTX300/FF-EN

Block overview Parameter Cold Junction Compensation 1 / 2 Temperature fixed CJ 1 / 2 Description Reference junction type: Not used Internal External Sensor 1 No compensation Measured internally (inside transmitter) Externally stabilized via thermostat Measured via resistance thermometer at channel 1 (can only be set at channel 2) If an externally stabilized reference junction is being used, its temperature is entered here in C. Line Resistance 1 / 2 Line resistance for sensor 1 / 2 if an RTD or linear resistor has been selected as a sensor and a two-wire circuit connection has been selected CvD Dataset 1 / 2 Callendar-Van Dusen dataset 1 / 2. Coefficients R0, A, B, C FixPoint User-specific characteristic with 32 pairs of reference points each 1 / 2 (X1..32, Y1..32), strictly monotonically increasing or decreasing Drift Limit Detection level for drift monitoring between sensor 1 / 2 Drift Time Detection time for drift monitoring between sensor 1 / 2 Drift Detection active Switch sensor drift monitoring on / off Noise Suppression The transmitter has a characteristic representing noise / interference suppression for the sensor measuring signals. This characteristic can be changed during runtime. The "slow" setting improves the quality of the measurement for noisy measuring signals. The "fast" setting reduces the response time of the transmitter, but requires higherquality measuring signals. The quality of the measuring signals can be improved by using shielded measuring lines that are as short as possible. COM/TTX300/FF-EN TTX300 13

Block overview 2.7 Transducer HMI The "Transducer HMI" block contains all the parameters and functions that are required for configuring the local LCD display. As an option, the display value can be specified using an AO block, via the fieldbus network. Parameter Language Contrast Local Operation View 1 View 2 line 1 View 2 line 2 Autoscroll Description Language used for HMI (LCD display). Language of device driver in host system / configuration tool is not influenced by this setting. Contrast adjustment Option of blocking local operation Selects signal to show in 1-line view Selects signal to show at line 1 in 2-line view Selects signal to show at line 2 in 2-line view Activates or deactivates automatic changeover between view 1 (1-line) and 2 (2-line) 2.8 Transducer extended diagnostics FF devices supply diagnostic information via their "Resource Block". This information can be read out by the device driver (EDD). Normally, it is not possible to access this data in the host from its application, meaning that there is also no way of responding to individual diagnostics events in an application-controlled manner. For example, a particular function could be started in the control system if a display indicating that maintenance is required appears as a result of redundancy switching in the sensor. The transmitter offers two DI (discrete input) blocks for this purpose. Physical Block Diagnosis Information Mask Output 1 AND Diag. Output 1 DI 1 Mask Output 2 AND Diag. Output 2 DI 2 A00254 Fig. 8 14 TTX300 COM/TTX300/FF-EN

Block overview The behavior of the binary signals can be parameterized in the "Transducer ExtDiag" block using parameters "Mask Output 1" and "Mask Output 2". ANDing is performed bit by bit. The result is TRUE (not equal to 0) if at least one bit operation produces 1 logically; otherwise, it is FALSE (equal to 0). The result is sent on to the connected DI block. Both masks can be set independently of one another. The operation with the second mask provides the value for DI block 2. Activating a checkbox sets a 1 in the mask. Parameter Description Output 1 / 2 Displays output channel 1/2 (communicated via DI 1 / 2) Mask Output 1 / 2 Masking of diagnostic conditions that will lead to a logic 1 signal at the block's output. The output is 1 (true) if at least one of the masked conditions is true. The setting does not influence diagnostics processing itself. COM/TTX300/FF-EN TTX300 15

Possible commissioning errors 3 Possible commissioning errors 3.1 AI block cannot be switched to "AUTO" mode The following conditions must be fulfilled in order for an AI block to enter "AUTO" mode: - The resource block must be in "AUTO" mode. There are no other preconditions for this. - A valid "Channel" (1 to 8) must be entered in the AI block. - L_Type must be set to "Direct" or "Indirect" (indirect square root is also possible). - The XD_Scale unit must be the same as the "Channel Unit". - If L_Type is set to "Direct", the XD_Scale and _Scale structure must have exactly the same settings throughout. If these conditions have been fulfilled and the "Target Mode" of the AI block is switched to "AUTO", the "Actual Mode" and, therefore, the block itself are also switched to "AUTO". You can see whether these conditions have been fulfilled in the BLOCK_ERR parameter (in the NI Configurator in the AI window, under the "Diagnostics" tab). If "Block Configuration Error" is signaled here, one of the conditions has not been fulfilled. If the PD_Tag of the device or the block tag was adjusted after a "Schedule" was loaded into the device, it may no longer be possible for blocks to be switched to "AUTO" even if the conditions listed above have been fulfilled. In this case, a new "Schedule" containing the "new" blocks (= new tags = new name) must be created and loaded into the device. 3.2 PID block cannot be switched to "AUTO" mode The following conditions must be fulfilled in order for the PID block to enter "AUTO" mode: - The resource block must be in "AUTO" mode. There are no other preconditions for this. - Bypass must have the correct setting (must not be set to the default value "uninitialized") - Shed_Opt must have the correct setting (must not be set to the default value "uninitialized") - Gain and SP must be set The actual mode of the PID remains set to "IMan": Check the downstream function block from which the BKCAL_IN parameter comes. 16 TTX300 COM/TTX300/FF-EN

ABB has Sales & Customer Support expertise in over 100 countries worldwide. www.abb.com/temperature The Company s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. Printed in the Fed. Rep. of Germany (01.2010) ABB 2010 3KXT200001R4001 COM/TTX300/FF-EN ABB Limited Salterbeck Trading Estate Workington, Cumbria CA14 5DS UK Tel: +44 (0)1946 830 611 Fax: +44 (0)1946 832 661 ABB Inc. 125 E. County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183 ABB Automation Products GmbH Borsigstr. 2 63755 Alzenau Germany Tel: +49 551 905-534 Fax: +49 551 905-555 CCC-support.deapr@de.abb.com