Electronic timer CT-APS.22 OFF-delayed with 2 c/o (SPDT) contacts

Similar documents
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Three-phase monitoring relay CM-PFE

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.43

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

Analog signal converters CC-E I/I Current / current isolators

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF19 and EF45

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

38 Series - Relay interface modules A

RM4TG20 three-phase network control relay RM4-T - range V

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

38 Series - Relay interface modules A

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

Thermistor motor protection

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Pluggable interface relays CR-P Pcb relays

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

80 Series - Modular timers 16 A. Features

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

Manual motor starter MS116

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

48 SERIES Relay interface modules 10 A

MasterINTERFACE 39 Series - Relay interface modules

Three-phase monitoring relays Product group picture

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

MasterINTERFACE 39 Series - Relay interface modules

Type: DILM32 10(24V50HZ) Article No.:

Catalog. Modular DIN rail components Installation contactors

Type: DILM50(230V50HZ,240V60HZ) Article No.:

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Grid feeding monitoring according to VDE-AR-N 4105 and BDEW CM-UFD.M31

49 Series - Relay interface modules A. Features

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

Relés e Contatores de Estado Sólido SIRIUS

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

Type: DILM9 10(24VDC) Article No.:

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2CDG1101xxR0011

EMR measuring and monitoring relays

80 Series - Modular timers 16 A. Features

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Safety technique. Emergency stop module BO 5988 safemaster

15 Series - Electronic step relay and dimmer. Features SERIE

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

PHOENIX CONTACT Features

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Technical catalogue. Modular DIN rail components Installation contactors

93.68/ Time scale: from 0.1s to 6h Multi-function For use with (EMR) and (SSR) relays. Screw terminal and push-in terminal

System pro M compact Miniature Circuit Breaker S 200/S 200 M

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Digital input modules

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

Bimetallic Overload Relay Specifications

Signal converters Index

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

Redundancy Module QUINT-DIODE/40

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/2

ABB i-bus KNX SA/S Switch Actuators Product Manual

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

ZS25 Screw Clamp Terminal Blocks Feed-through

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/2x15DC/1

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Power Supplies 3. SDN-P DIN Rail Series

40 Series - Miniature PCB/Plug-in relays A. Features

R.C.C.B. s two-pole LEXIC

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Technicaldata General

Waveguide Access Point WGA631. Product Guide

PHOENIX CONTACT - 01/2007

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Fixed - Over/Under voltage limits, ( ) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

mecotron Safety relay ESTOP-2 For emergency stop monitoring

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

E-STOP relays, safety gate monitors

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

STRATO LED Drivers 70W, Single output

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA

Easy Multifunctional Safe

Signal converters Index

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

Contact expansion modules

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Manual Motor Starter MS 116 up to 16 A Technical Data

Transcription:

Data sheet Electronic timer CT-APS.22 OFF-delayed with 2 c/o (SPDT) contacts The CT-APS.22 is an electronic timer from the CT-S range with OFF-delay and 10 time ranges. All electronic timers from the CT-S range are available with two different terminal versions. You can choose between the proven screw connection technology (double-chamber cage connection terminals) and the completely tool-free Easy Connect Technology (push-in terminals). 2CDC 251 038 V0011 Characteristics Rated control supply voltage 24 48 V DC, 24 240 V AC OFF-delay (with auxiliary voltage) 10 time ranges (0.05 s 300 h) Control input with voltage related triggering to start timing Precise adjustment by front-face operating controls Screw connection technology or Easy Connect Technology available Housing material for highest fire protection classification UL 94 V-0 Tool-free mounting on DIN rail as well as demounting 2 c/o (SPDT) contacts Width of 22.5 mm 2 LEDs for the indication of operational states Approvals A UL 508, CAN/CSA C22.2 No.14 C GL R EAC E CCC L RMRS Marks a CE b RCM Order data Electronic timers Type Rated control supply voltage Connection technology Time ranges Order code CT-APS.22P 24 48 V DC, 24 240 V AC Push-in terminals 0.05 s 300 h 1SVR 740 180 R3300 CT-APS.22S 24 48 V DC, 24 240 V AC Screw type terminals 0.05 s 300 h 1SVR 730 180 R3300 Accessories Type Description Order code ADP.01 Adapter for screw mounting 1SVR 430 029 R0100 MAR.01 Marker label for devices without DIP switches 1SVR 366 017 R0100 COV.11 Sealable transparent cover 1SVR 730 005 R0100

Connection technology Maintenance free Easy Connect Technology with push-in terminals Type designation CT-xxS.yyP Approved screw connection technology with double-chamber cage connection terminals Type designation CT-xxS.yyS 2CDC 253 026 F0011 2CDC 253 025 F0011 Push-in terminals Tool-free connection of rigid and flexible wires with wire end ferrule Easy connection of flexible wires without wire end ferrule by opening the terminals No retightening necessary One operation lever for opening both connection terminals For triggering the lever and disconnecting of wires you can use the same tool (Screwdriver according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in)) Constant spring force on terminal point independent of the applied wire type, wire size or ambient conditions (e. g. vibrations or temperature changes) Opening for testing the electrical contacting Gas-tight Double-chamber cage connection terminals Terminal spaces for different wire sizes One screw for opening and closing of both cages Pozidrive screws for pan- or crosshead screwdrivers according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in) Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage connection terminals have the same connection geometry as well as terminal position. 2 - Electronic timer CT-APS.22 Data sheet

Functions Operating controls 1 Rotary switch for the preselection of the time range 2 Fine adjustment of the time delay 3 Indication of operational states U/T: green LED - control supply voltage / timing R: yellow LED - status of output relays 1 4 Marker label 2CDC 251 038 V0011 3 2 4 Application The CT S range timers are designed for use in industrial applications. They operate over an universal range of supply voltages and a large time delay range, within compact dimensions. The easy to set front face potentiometers, with direct reading scales, provide accurate time delay adjustment. Operating mode The CT APS.22 with 2 c/o (SPDT) contacts offers 10 time ranges, from 0.05 s to 300 h, for the adjustment of the time delay. The time delay range is rotary switch selectable. The fine adjustment of the time delay is made via an internal potentiometer, with a direct reading scale, on the front of the unit. Timing is displayed by a flashing green LED labelled U/T. Function diagram B OFF delay with auxiliary voltage This function requires continuous control supply voltage for timing. If control input A1 Y1/B1 is closed, the output relays energize immediately. If control input A1 Y1/B1 is opened, the time delay starts. The green LED flashes during timing. When the selected time delay is complete, the output relays de energize and the flashing green LED turns steady. If control input A1 Y1/B1 recloses before the time delay is complete, the time delay is reset and the output relays do not change state. Timing starts again when control input A1 Y1/B1 re opens. If control supply voltage is interrupted, the output relays de energize and the time delay is reset. A1-A2 A1-Y1/B1 15-18, 25-28 15-16, 25-26 green LED t = adjusted time delay t < t 2CDC 252 015 F0207 Data sheet Electronic timer CT-APS.22-3

Electrical connection A1 Y1/B1 15 25 Y1/ B1 A1 15 25 15 16/18 1st c/o (SPDT) contact 25 26/28 2nd c/o (SPDT) contact A1 A2 Rated control supply voltage U S 24 48 V DC or 24 240 V AC A1 Y1/B1 Control input A2 16 18 26 28 28 26 18 16 A2 2CDC 252 011 F0b06 Connection diagram Wiring instructions Control input (voltage related triggering) The control input Y1/B1 is triggered with electric potential against A2. It is possible to use the control supply voltage from terminal A1 or any other voltage within the rated control supply voltage range. L(+) L(+) L(+) A1 Y1/B1 A1 Y1/B1 N(-) A2 2CDC 252 102 F0b06 N(-) A2 L(-) 2CDC 252 103 F0b06 4 - Electronic timer CT-APS.22 Data sheet

Technical data Data at T a = 25 C and rated values, unless otherwise indicated Input circuits Supply circuit Rated control supply voltage U S A1 A2 Rated control supply voltage U S tolerance 24 48 V DC 15...+10 % 24 240 V AC 15...+10 % Rated frequency DC n/a AC 24 48 V DC, 24 240 V AC 50/60 Hz Frequency range AC 47 63 Hz Typical current / power consumption 24 V DC 230 V AC 115 V AC 24 48 V DC 16 ma / 0.4 W 24 240 V AC / 60 ma / 14 VA Power failure buffering time 24 V DC min. 15 ms Release voltage Control circuit 230 V AC min. 20 ms Control input, control function A1 Y1/B1 start timing external Kind of triggering Restistance to reverse polarity Polarized Capable of switching a parallel load Maximum cable length to the control inputs Minimum control pulse length Control voltage potential / / 36 ma / 4.5 VA > 10 % of the min. rated control supply voltage U s voltage related triggering yes no yes 50 m 100 pf/m 20 ms Current consumption of the control input 24 V DC 1.2 ma Timing circuit 230 V AC 8 ma see rated control supply voltage U S Kind of timer Single function timer OFF delay with auxiliary voltage Time ranges 0.05 s 300 h 0.05 1 s, 0.15 3 s, 0.5 10 s, 1.5 30 s, 5 100 s, Recovery time 15 300 s, 1.5 30 min, 15 300 min, 1.5 30 h, 15 300 h < 80 ms Repeat accuracy (constant parameters) Δt <± 0.2 % Accuracy within the rated control supply voltage tolerance Accuracy within the temperature range Setting accuracy of time delay Δt < 0.004 %/V Δt < 0.03 %/ C ± 6 % of full-scale value User interface Indication of operational states Control supply voltage / timing U/T: green LED V: control supply voltage applied U/T: green LED W: timing Relay status R: yellow LED V: output relays energized Data sheet Electronic timer CT-APS.22-5

Output circuits Kind of output 15 16/18 relay, 1st c/o (SPDT) contact 25 26/28 relay, 2nd c/o (SPDT) contact Contact material Cd free Rated operational voltage U e 250 V Minimum switching voltage / Minimum switching current 12 V / 10 ma Maximum switching voltage / Maximum switching current see Load limit curves on page 8 Rated operational current I e AC-12 (resistive) at 230 V 4 A AC-15 (inductive) at 230 V 3 A DC-12 (resistive) at 24 V 4 A DC-13 (inductive) at 24 V 2 A AC rating (UL 508) utilization category (Control B 300 Circuit Rating Code) max. rated operational voltage 300 V AC max. continuous thermal 5 A current at B 300 max. making / breaking 3600/360 VA apparent power at B 300 Mechanical lifetime 30 x 10 6 switching cycles Electrical lifetime AC-12, 230 V, 4 A 0.1 x 10 6 switching cycles Frequency of operation, with/without load 360/72000 h -1 Maximum fuse rating to achieve short-circuit n/c contact 6 A fast acting protection n/o contact 10 A fast acting General data MTBF on request Duty time 100 % Dimensions (W x H x D) product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in) Weight packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in) Screw connection technology Easy Connect Technology (push-in) net weight 0.138 kg (0.304 lb) 0.127 kg (0.280 lb) gross weight 0.160 kg (0.353 lb) 0.149 kg (0.328 lb) Mounting DIN rail (IEC/EN 60715), Mounting position Minimum distance to other units vertical not necessary horizontal snap on mounting without any tool any not necessary Material of housing UL 94 V-0 Degree of protection housing IP50 terminals IP20 Electrical connection Screw connection technology Easy Connect Technology (push-in) Connecting capacity fine strand with(out) wire end ferrule 1 x 0.5-2.5 mm² (1 x 18-14 AWG) 2 x 0.5-1.5 mm² (2 x 18-16 AWG) 2 x 0.5-1.5 mm² (2 x 18-16 AWG) rigid 1 x 0.5-4 mm² (1 x 20-12 AWG) 2 x 0.5-2.5 mm² (2 x 20-14 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) Stripping length 8 mm (0.32 in) Tightening torque 0.6-0.8 Nm (7.08 lb.in) - 6 - Electronic timer CT-APS.22 Data sheet

Environmental data Ambient temperature ranges operation 25...+60 C storage 40...+85 C Relative humidity range 25 % to 85 % Vibration, sinusoidal (IEC/EN 60068 2 6) functioning 40 m/s 2, 10-58/60-150 Hz resistance 60 m/s 2, 10-58/60-150 Hz, 20 cycles Vibration, seismic (IEC/EN 60068 3 3) functioning 20 m/s² Shock, half sine (IEC/EN 60068 2 27) functioning 150 m/s 2, 11 ms, 3 shocks/direction resistance 300 m/s 2, 11 ms, 3 shocks/direction Isolation data Rated insulation voltage U i input circuit / output circuit 500 V output circuit 1 / output circuit 2 300 V Rated impulse withstand voltage U imp between all isolated circuits 4 kv; 1.2/50 µs Power frequency withstand voltage between all isolated circuits (test voltage) 2.0 kv; 50 Hz, 1 min Basic insulation (IEC/EN 61140) input circuit / output circuit 500 V Protective separation (IEC/EN 61140; EN 50178) input circuit / output circuit 250 V Pollution degree 3 Overvoltage category III Standards / Directives Standards IEC/EN 61812 1 Low Voltage Directive 2014/35/EU EMC Directive 2014/30/EU RoHS Directive 2011/65/EU Electromagnetic compatibility Interference immunity to IEC/EN 61000 6 2 electrostatic discharge IEC/EN 61000 4 2 Level 3, 6 kv / 8 kv radiated, radio-frequency, electromagnetic field IEC/EN 61000 4 3 Level 3, 10 V/m (1 GHz) / 3 V/m (2 GHz) / 1 V/m (2.7 GHz) electrical fast transient / burst IEC/EN 61000 4 4 Level 3, 2 kv / 5 khz surge IEC/EN 61000 4 5 Level 4, 2 kv A1 A2 conducted disturbances, induced by radio-frequency fields IEC/EN 61000 4 6 Level 3, 10 V harmonics and interharmonics IEC/EN 61000 4 13 Class 3 Interference emission IEC/EN 61000 6 3 high-frequency radiated IEC/CISPR 22, EN 55022 Class B high-frequency conducted IEC/CISPR 22, EN 55022 Class B Data sheet Electronic timer CT-APS.22-7

Technical diagrams Load limit curves AC voltage [V] resistive load DC voltage [V] resistive load 2CDC 252 150 F0206 AC current [A] 2CDC 252 149 F0206 DC current [A] 2CDC 252 150 F0206 AC load (resistive) DC load (resistive) Derating factor F 1.0 0.9 0.8 0.7 Switching cycles 250 V resistive load 2CDC 252 148 F0206 0.6 0.5 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ 2CDC 252 124 F0206 Switching current [A] 2CDC 252 148 F0206 Derating factor F for inductive AC load Contact lifetime 8 - Electronic timer CT-APS.22 Data sheet

Dimensions in mm and inches 113.4 4.47 105.9 4.17 22.5 0.89 85.6 3.37 103.7 4.08 2CDC 252 009 F0011 Accessories in mm and inches 22.5 0.89 8 0.32 4.8 0.19 6.5 0.256 62.5 2.461 60 2.362 70 2.756 10 11.5 0.394 0.453 20 0.787 2CDC 252 008 F0010 3A11 20.787 8.315 CDC 252 186 F0005 2CDC 252 186 F0005 68 2.68 front to back 110.5 4.31 2CDC 252 010 F0011 ADP.01 Adapter for screw mounting MAR.01 Marker label COV.11 Sealable transparent cover Further documentation Document title Document type Document number Electronic Products and Relays Technical catalogue 2CDC 110 004 C02xx CT-APS, CT-ERS, CT-MVS, CT-SDS Instruction manual 1SVC 730 020 M0000 You can find the documentation on the internet at www.abb.com/lowvoltage -> Automation, control and protection -> Electronic relays and controls -> Electronic timers. CAD system files You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com -> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls. Data sheet Electronic timer CT-APS.22-9

Contact us ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organization on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Document number 2CDC 111 117 D0201 (09.2016) Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2016 ABB All rights reserved