Application Note Interfacing AC Drives with Safety Relays

Similar documents
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Safeguarding Applications and Wiring Diagrams

Safe Torque Off Option (Series B) for PowerFlex 40P and PowerFlex 70 Enhanced Control AC Drives

Application Technique. Safety Function: Magnetic Door Switch Monitoring

Next Generation Guardmaster Safety Relay (GSR)

Programming A PLC. Standard Instructions

Safety Function: Door Monitoring

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Electrical Symbols and Line Diagrams

EXPERIMENT 2 TRAFFIC LIGHT CONTROL SYSTEM FOR AN INTERSECTION USING S7-300 PLC

Application Technique. Safety Function: Door Monitoring

Multizone Application >3. MSR300 System. No Software configurable? GuardPLC. Enet RECOMMENDED PRODUCTS. Time Delay MSR138

3BASIC RELAY INSTRUCTIONS

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

How to read this guide

Bul. 440R Guardmaster Safety Relays (DI, DIS, SI, CI, GLP, EM, and EMD) Selection Guide

*.ppt 11/2/ :48 PM 1

Safety Requirements Specification Guideline

Safety Relays ESM/ESM-F

Cam switches. Page. Overview 4-2. ON-OFF switches, main switches, maintenance switches 4-3. Changeover switches, reversing switches 4-5

GPD 506/P5 Start-up Procedure and Checklist

DC Motor control Reversing

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Creating Relay Logic Diagrams

EET272 Worksheet Week 8

Safety automation solutions

General 1-2-Opto-electronics Safety Switches 4-Emergency

mecotron Safety relay ESTOP-2 For emergency stop monitoring

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. MOVIDRIVE MDX60B/61B Functional Safety

Fig 3. PLC Relay Output

CONFIGURABLE SAFETY RELAYS

Mini Breakout-Board. CNC Interface for LPT Port. Installation Manual Version 4

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3

Programming Timers CHAPTER 4-1 GOALS AND OBJECTIVES 4-2 MECHANICAL TIMING RELAYS

SECTION VARIABLE FREQUENCY DRIVES

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

PLC SW and Programming. Nagy István, BMF BGK MEI

GLOLAB Two Wire Stepper Motor Positioner

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Study Guide for the Electronics Technician Pre-Employment Examination

ETZGAR CONVEYOR COMPANY Controls Section v12.05

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

What Is Regeneration?

ABB industrial drives. Application guide ACS800-01/U1/04/04LC/04M/U4/11/U11/14/31/U31/104/104LC Safe torque off function (+Q967)

CONFIGURABLE SAFETY RELAYS

KCIEN KCIENSBP. Heavy Duty Stainless Steel Illuminated Keypads INSTALLATION MANUAL. Range: DIGICODE (Stand-Alone Keypad)

2011, The McGraw-Hill Companies, Inc. Chapter 5

Configuring Alarms & Relays in the Enhanced Transformer Advantage

Implementation of a New Substation Restoration System Using Protective Relays and a Logic Processor

Programming Logic controllers

PUSH BUTTON START INSTALLATION MANUAL

IO-RM3 3-Stage Relay Module

3FBD DC Motor Drive User Manual

Circuit Breakers. NRC Series. NRC Series

GSM AUTO DIALER. Remote Monitoring & Control using your mobile phone.

X8Pro Remote Control

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

PROGRAMMABLE LOGIC CONTROLLERS Unit code: A/601/1625 QCF level: 4 Credit value: 15 OUTCOME 3 PART 1

BLOCK OCCUPANCY DETECTOR WITH SEMAPHORE OPERATION BOD1/DAP4-BR

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

Data Sheet. Electro-mechanical counters Hengstler 800 series

Emergency Stop Push Buttons

Operational Overview and Controls Guide

Speed Control Relays SX2

TRILOGI 5.3 PLC Ladder Diagram Programmer and Simulator. A tutorial prepared for IE 575 by Dr. T.C. Chang. Use On-Line Help

Wiring diagrams. Compact NSX. Contents

Operating Instructions. UL325 Compliant Non-monitored

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

FIREDEX Conventional Fire Panels

Conventional Fire Detection and Extinguishant Control System Specification

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

Configure Inverter output for two utility settings, (1)120V/60Hz, (2)220V/50Hz

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Products and solutions for lifting systems

Understanding Emergency Power Off (EPO)

AC motor control circuits

INSTALLATION/PROGRAMMING INSTRUCTIONS 928 ENTRYCHECK

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February FA-300 SERIES Fire Alarm Control Panel

INSTALLATION & SERVICE MANUAL. Display Panel

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.

11. FLOWCHART BASED DESIGN

NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD

Sentron Series Circuit Breakers

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

WITURA CORPORATION SDN BHD

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings

Machine Safety Switches

CPW Current Programmed Winder. Application Handbook. Copyright 2002 by Eurotherm Drives, Inc.

DIL R Industrial Control Relays Basic Relay, Modules

The Interaction of Contactors with PLCs

MANUAL FOR MODEL MP300 to MP700 ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS

Transcription:

Purpose The intent of this document is to provide typical examples of how to interface AC Drives with safety relays. This document will not describe machine guarding safety or risk assessment, which are covered in our safety business documentation. References NFPA79, Electrical Standards for Industrial Machinery EN954-1, Safety of Machinery safety related parts of a control system Part 1. General Principles for Design Stop Categories Stop Category 0 Coast. Immediate removal of power to the motor. With immediate removal of power to the motor, the motor will coast to stop. The time required to stop motion is dependent on the load inertia and speed as well as the friction in the mechanical power transmission equipment used in the system. Stop Category 1 Controlled. Controlled Stop then removal of power to the motor. A ramp to stop will be used to control the mechanical power transmission to rest then power is removed from the motor. The time required to bring the mechanical system to rest is dependent upon load inertia and speed as well as the regenerative dissipation capacity of the drive. Component Descriptions Gate Interlock - The Trojan gate interlock uses direct opening contacts. When the gate is opened, the contacts in the interlock are forced open by non-resilient components (e.g., not by springs). A redundant (two) set of double break contacts are designed to ensure that at least one signal is sent to the safety relay, when the gate is opened. E-Stop - When the E-Stop button is pressed the safety function is activated (Drive goes to safe state). When a contactor is used it is opened by the E-Stop circuit. The E-stop button must utilize direct-opening contacts. The button must latch to an open state when the contacts open (i.e., you must not be able to tickle the contacts without latching the button). The button must be a red with a yellow background. Contactor - Provides electromechanical disconnection of the motor from the drive. Its normallyclosed mechanically linked contacts are monitored by the safety relay to help ensure that the contactor has dropped out before the next resetting of the safety relay. Start / Stop Pushbuttons - The Start and Stop pushbuttons are used to turn the drive on and off. They are also symbolic of the non-safety related parts of the machine control system. These buttons can be replaced by a programmable control system. Generic Drive Describes a drive that does not contain a Safe-off option The PowerFlex Safe-Off Option Board: o Is designed to safely remove power from the gate firing circuits of the Drives output power devices (IGBT s). This prevents then from switching in the pattern necessary to generate AC power to the motor. o Can be used in combination with other safety devices to meet the Stop and protection against restart requirements of EN954-1. IMPORTANT: The option is suitable for performing mechanical work on the drive system or affected area of a machine only. It does not provide electrical safety. Safety Relay Reset The examples in this document use an automatic reset scheme for the safety relay. The use of a manual or automatic reset should be dictated by the application. Related Publications DriveGuard TM User Manual for the Safe-Off Option Rev04.doc 1

Stop Type: Category 0, Coast Safety Level: EN954-1, Category 3 Drive Type: Drive without Safe-off option Other: Output contactor for NFPA79 Emergency Stop operation Overview: This example shows how to provide Stop and protection against restart (Category 3 per EN954-1) on a drive without a safe-off feature. The contactors can also satisfy the NFPA79 Emergency Stop requirements. Circuit Operation: The gate will trigger the safety function. When triggered the safety relay outputs (Terminals 13 to 14 and 23 to 24) open. This immediately removes +24vdc from the drive Enable, the drive Start/Stop inputs and both contactor coils K1 & K2. The result is the drive is disabled, a stop signal is asserted the contactors open, and the motor will coast to stop. The N.O. auxiliary contact of K1 and K2 open to prevent a drive Start before the contactors close. The N.C. auxiliary contacts are monitored by the safety relay at terminals X1 & X2. When the gate is restored and satisfies the safety relay inputs, the safety relay is reset. The safety relay outputs are energized restoring +24vdc to the drive Enable input, the coils of the contactors and the Drive Not Stop. A start command must be issued to the drive to restart. When the E-Stop is activated, the safety function is triggered and performs the same as the gate triggered function. Restoration of the E-Stop also recovers in the same manner as the gate restoration. Rev04.doc 2

If the contactors N.C. auxiliary contacts are in an abnormal state, as monitored by the safety relay (X1 & X2) the safety relay will prevent operation at the next cycling of the safety circuit. Other Considerations: The safe-off jumper in the drive must be installed when the Safe-Off Option is not present. Drives with hardware enable feature Use of hardware enable is not required for this example but in general is recommended when the drive is interfaced with a safety relay. Rev04.doc 3

Stop Type: Category 1, Controlled Safety Level: EN954-1, Category 3 Drive Type: Drive without Safe-off option Other: Output contactor for NFPA79 Emergency Stop operation Overview: This example shows how to provide Controlled Stop and protection against restart (Category 3 per EN954-1) on a drive without a safe-off feature. The contactors can also satisfy the NFPA79 Emergency Stop requirements. Circuit Operation: The gate will trigger the safety function. When triggered the safety relay outputs (Terminals 13 to 14 and 23 to 24) open. This immediately removes +24vdc from the drive Start/Stop input. The result is the drive stop signal is asserted and a ramp to stop is issued. Once the time delay in the safety relay expires, the safety relay time delay contacts (Terminals 47 to 48 & 57 to 58) open. The +24vdc is then removed from the drive enable as well as both contactor coils K1 & K2. The N.O. auxiliary contact of K1 and K2 open to prevent a drive Start before the contactors close. The N.C. auxiliary contacts are monitored by the safety relay at terminals Y1 & Y2. Note: The time delay of the safety relay must be greater than the deceleration ramp time of the drive otherwise a coast stop will occur when the timer expires. Rev04.doc 4

When the gate is restored and satisfies the safety relay inputs, the safety relay is reset (terminals 39 & 40 are N.C.). The safety relay outputs are energized restoring +24vdc to the drive Enable input, the coils of the contactors and the Drive Start/Stop. A start command must be issued to the drive to restart. Other Considerations: The safe-off jumper in the drive must be installed when the Safe-Off Option is not present. Drives with hardware enable feature Use of hardware enable is not required for this example but in general is recommended when the drive is interfaced with a safety relay. Rev04.doc 5

Stop Type: Category 0, Coast Safety Level: EN954-1, Category 3 Drive Type: Drive with Safe-Off Option Other: Overview: This example shows how to provide Stop and protection against restart (Category 3 per EN954-1) on a drive with a safe-off feature. Circuit Operation: The gate will trigger the safety function. When triggered the safety relay outputs (Terminals 13 to 14 and 23 to 24) open. This immediately removes +24vdc from the drive Enable, the Safe-Off Option relay and the drive Start/Stop input. The result is the drive is disabled, a stop signal is asserted, the Safe-Off Option goes to a safe state (off), and the motor will coast to stop. When the gate is restored and satisfies the safety relay inputs, the safety relay is reset. The safety relay outputs are energized restoring +24vdc to the drive Enable input, the Safe-Off Option relay and the Drive Start/Stop. A start command must be issued to the drive to restart. If the Safe-off monitor contact is in an abnormal state, as monitored by the safety relay (X1 & X2) the safety relay will prevent operation at the next cycling of the safety circuit. Other Considerations: Note: The hardware enable jumper in the drive must be removed if the Safe-Off Option is installed. If not, the drive will fault (F111) when a start command is issued. Rev04.doc 6

Stop Type: Category 0, Coast Safety Level: EN954-1, Category 3 Drive Type: Drive with Safe-Off Option Other: Output contactor for NFPA79 Emergency Stop operation Overview: This example shows how to provide Stop and protection against restart (Category 3 per EN954-1) on a drive with a safe-off feature. The contactors can also satisfy the NFPA79 Emergency Stop requirements. Circuit Operation: The gate will trigger the safety function. When triggered the safety relay outputs (Terminals 13 to 14 and 23 to 24) open. This immediately removes +24vdc from the drive Enable, the Safe-Off Option relay and the drive Start/Stop input. The result is the drive is disabled, a stop signal is asserted, the Safe-Off Option goes to a safe state (off), and the motor will coast to stop. The contactor K1 stays energized. When the gate is restored and satisfies the safety relay inputs, the safety relay is reset. The safety relay outputs are energized restoring +24vdc to the drive Enable input, the Safe-Off Option relay and the Drive Not Stop. A start command must be issued to the drive to restart. When the E-Stop is activated, the safety function is triggered and performs the same as the gate. The E- Stop also removes power from the contactor coil which opens the contactor and disconnects the motor from the drive. The auxiliary contacts open the circuit to the drive Start/Stop to prevent a drive Start before the contactor closes. Upon restoring the E-Stop (and gate is in normal condition) the safety relay resets and the contactor is energized closing the main poles and auxiliary contacts. A start command will now restart the drive. Rev04.doc 7

If the Safe-off monitor contact is in an abnormal state, as monitored by the safety relay (X1 & X2) the safety relay will prevent operation at the next cycling of the safety circuit. Other Considerations: Note: The hardware enable jumper in the drive must be removed if the Safe-Off Option is installed. If not, the drive will fault (F111) when a start command is issued. Rev04.doc 8

Stop Type: Category 1, Controlled Safety Level: EN954-1, Category 3 Drive Type: Drive with Safe-Off Option Other: Overview: This example shows how to provide Controlled Stop and protection against restart (Category 3 per EN954-1) on a drive with a safe-off feature. Circuit Operation: The gate will trigger the safety function. When triggered the safety relay outputs (Terminals 13 to 14 and 23 to 24) open. This immediately removes +24vdc from the drive Start/Stop input. The result is the drive stop signal is asserted and a ramp to stop is issued. Once the time delay in the safety relay expires, the safety relay time delayed contacts (Terminals 37 to 38, 47 to 48 & 57 to 58) open. The +24vdc is then removed from the drive Enable input as well as the Safe- Off Option. The Safe-Off Option goes to a safe state (off). Note: The time delay of the safety relay must be greater than the deceleration ramp time of the drive otherwise a coast stop will occur when the timer expires. When the gate is restored and satisfies the safety relay inputs, the safety relay is reset (terminals 39 & 40 are N.C.). The safety relay outputs are energized restoring +24vdc to the drive Enable input, the Safe-Off Option and the Drive Start/Stop. A start command must be issued to the drive to restart. If the Safe-off monitor contact is in an abnormal state, as monitored by the safety relay (X1 & X2) the safety relay will prevent operation at the next cycling of the safety circuit. Rev04.doc 9

Other Considerations: Note: The hardware enable jumper in the drive must be removed if the Safe-Off Option is installed. If not, the drive will fault (F111) when a start command is issued. Rev04.doc 10

Stop Type: Category 1, Controlled Safety Level: EN954-1, Category 3 Drive Type: Drive with Safe-Off Option Other: Output contactor for NFPA79 Emergency Stop operation Overview: This example shows how to provide Controlled Stop and protection against restart (Category 3 per EN954-1) on a drive with a safe-off feature. The contactors can also satisfy the NFPA79 Emergency Stop requirements. Gate GuardMaster Trojan Gate Example Stop Type: Category 1, Controlled Safety Level: EN954-1, Cat. 3 Drive Type: Drive with Safe-Off Option Other: Output contactor for NFPA79 Emergency Stop +24V DC +24VDC PowerFlex 70 AC Drive AC Line Input Power Stop Stop Start Start Gate Control Power Supply +24V DC A1 S21 S11 S52 S12 S22 37 47 57 Minotaur MSR138DP 13 23 S33 S34 K1 K1 1 2 Safe Off Option A2 X1 X2 X3 X4 39 40 38 48 58 14 24 Y2 Y1 3 4 24V DC Com K1 DigIn Com Com Gate Control Circuit Enable Gate triggers safety function Contactor, Drive Enable, and Safe Off open after time delay Automatic reset when gate closes Monitored output Drive requires new start command after safety relay reset Contactor shown for NFPA79 purposes, not required for Category 3 certification M K1 Circuit Operation: The gate will trigger the safety function. When triggered the safety relay outputs (Terminals 13 to 14 and 23 to 24) open. This immediately removes +24vdc from the drive Start/Stop input. The result is the drive stop signal is asserted and a ramp to stop is issued. Once the time delay in the safety relay expires, the safety relay time delayed contacts (Terminals 37 to 38, 47 to 48 & 57 to 58) open. The +24vdc is then removed from the contactor K1 coil, the drive Enable input as well as the Safe-Off Option. The N.O. auxiliary contact of K1 open to prevent a drive Start before the contactor closes. The N.C. auxiliary contacts of K1 and the Safe-Off Option are monitored by the safety relay at terminals Y1 & Y2. Note: The time delay of the safety relay must be greater than the deceleration ramp time of the drive otherwise a coast stop will occur when the timer expires. Rev04.doc 11

When the gate is restored and satisfies the safety relay inputs, the safety relay is reset (terminals 39 & 40 are N.C.). The safety relay outputs are energized restoring +24vdc to the drive Enable input, the coil of the contactor K1 and the Drive Start/Stop. A start command must be issued to the drive to restart. If the Safe-off monitor contact is in an abnormal state, as monitored by the safety relay (X1 & X2) the safety relay will prevent operation at the next cycling of the safety circuit. Other Considerations: Note: The hardware enable jumper in the drive must be removed if the Safe-Off Option is installed. If not, the drive will fault (F111) when a start command is issued. Rev04.doc 12