UK Trade Association for PIR Core Sandwich Panels. EPIC

Similar documents
Colorcoat Technical Paper Fire performance of pre-finished steel cladding systems

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Composite Panel Firewall Systems

Loss Prevention Standard

Fire safety in timber buildings

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market

Fire testing for BCA compliance

Insulated Roof & Wall Panels. Product Data Sheet. Trapezoidal Insulated Roof Panels KS1000 RW

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

ModuSec. Secure and efficient IT room solutions Composite Panel Systems Compared. Panel Systems are not all the same!

Guidance on loft conversions in two-storey houses

Introduction. Facade Fire Test on PUR External Thermal Insulation Composite System (ETICS)

The FIRE BOOK. Passive fire protection solutions

Fire safety in buildings and implementation of European fire test standards

Warehouse Checklist. Warehouse Construction

Decree of the Ministry of the Environment on fire safety of ventilation systems

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS

Watermist fire suppression systems for commercial low hazard occupancies

Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration

Loss Prevention Standard

ASFP Ireland - Fire Safety Certification. Colin Keeley Senior Site Inspector & Training Officer 22 nd September 2011

FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England

Excerpts from the Canadian National Building Code (NBC)

CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES

Decree of the Ministry of the Environment. on fire safety of garages

SUPERIOR FIRE RESISTANCE

Annex of the certificate (Page 1/6) Accreditation Scope

CLASSIFICATION OF REACTION TO FIRE IN ACCORDANCE WITH EN :2007

The Kingspan Insulation Price List 1 st January 2013

Wood use in Type I and II (noncombustible) construction

Fire Barriers & Fire Stopping

Examples of construction classifications used in the insurance industry

Preventing arson in buildings

Fire-Rated Glass and Glazing START

Building Code Clarifications - 7. Fire Resistance

IFE Level 4 Certificate in Fire Science and Fire Safety (HL)

FIREWALLS FIREWALLS. Technical specifications

STEEL BUILDINGS IN EUROPE. Single-Storey Steel Buildings Part 8: Building Envelope

Tremco Fire Protection Systems Group Technical Bulletin

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

Services Enclosures and Protected Shafts - Maintaining Compartmentation

Fire and Security Products and Services

Analysis II Façade Redesign: Architectural Precast Panels

Code of Practice for fire resisting metal doorsets

If you are a web registered user of ArlingontPermits.com you may also request an inspection at:

Decree of the Ministry of the Environment on fire safety of buildings

ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape

Energy Company Obligation (ECO): Technical Monitoring Questions

Approval Standard for Class 1 Fire Rating of Building Panels or Interior Finish Materials

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01

Gordon Cooke BSc PhD CEng MICE MIMechE FIFireE

Installation Instructions

Safety Storage Cabinets

Building Condition Assessment: North Howard Street Baltimore, Maryland

Association of British nsurers LPC. A Code of Practice for the Protection of Business

fire separating walls #2

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications

Fire Safety Requirements for Child Care Centre

Fiberglas, Exterior Wall Thermal Insulation

INTERNATIONAL FIRE PROTECTION

Fire and Concrete Structures

Fire Risk Assessment For Simple Premises

ISO Types 1-6: Construction Code Descriptions

- 5 - Table1. Maximum Compartment Volumes

Advantages and Disadvantages of Timber Frame Construction

SANDWICH PANEL FILLING MATERIALS

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

A new approach to the Danish guidelines for fire protection of combustible insulation

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012

FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES

The risk assessment of fire damper installations

Sandwich panels for external cladding fire safety issues and implications for the risk assessment process.

FLAMMABLE AND COMBUSTIBLE LIQUIDS

Meeting the Fire Code with Continuous Foam Plastic Insulation

M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003

Facility Assessment for East Main Street, Huntley, IL

18 June 2001 GUIDELINES ON FIRE TEST PROCEDURES FOR ACCEPTANCE OF FIRE-RETARDANT MATERIALS FOR THE CONSTRUCTION OF LIFEBOATS

Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5

Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces

1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety.

Structural fire design Eurocode Timber structures

Rockwool Flexi Insulation Application Guide

Fire Security Systems

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

St. John s University

Certification: Building Plans Examiner. Exam ID: B3

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N

Structural Insulated Panels: Design and Application

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

Terms and Definitions In Canada

Guide to the safe installation of downlighters in dwellings

Transcription:

Sandwich Panels: fire testing, insurance industry demands and case studies from real fires in the UK. Mark Harris Divisional Building Technology Director. EPIC UK Trade Association for PIR Core Sandwich Panels.

Fire Performance of Sandwich Panels General Introduction UK Insurance Industry Attitudes & Design Guidance. Fire testing EN13501 (Euroclassification) Loss Prevention Certification Board FM Global UK Fire Fighter Attitudes Real Fire Case Studies Summary What is a sandwich panel? Also called composite or insulated panels Insulation core with metal facings Interlocking joint detail Typically 1 metre wide and up to 30 metres long Insulation types include PIR, mineral fibre, polyurethane and EPS. European Standard EN14509.

What are insulated panels used for? External fabric - core now PIR or mineral fibre in UK. Historically was generally polyurethane. Internal boxes within buildings e.g. cold stores, food processing areas core now PIR or mineral fibre in Ireland & UK. Historically was generally EPS. Building types and applications Industrial Industrial Commercial Distribution Retail

Building types and applications Manufacturing Hospitals Health Pharmaceutical Building types and applications Education Leisure Motor Public

Internal applications UK Building Regulation Reaction to Fire Tests Key objective is specifically life safety rather than property conservation. UK National tests are generally small scale and do not differentiate well between different levels of performance. New European system EN 13501. All combustible core panels achieve Euroclass B Some achieve S1 or S2 smoke classification Some achieve D0 burning droplets classification.

Euroclassification - EN13501 PIR Core PIR Core B, S2, D0 B, S1, D0 UK Insurance Industry Reaction

Key issue UK experience The fundamental problem is that from the mid 1980s serious fires involving certain types of sandwich panels have created Insurer concerns about the fire performance of all sandwich panel systems How did insurers react? Commercial Property Insurance Where does the underwriter turn to for help?

Commercial Property Insurance Snapshot of UK food sector losses... Egg packers Lincoln 2005 Bakery Carlisle 2005 Pasta/pizza Humberside 2005 Tea blenders Knowsley 2005 Distribution Manchester 2006 Bakery Sheffield 2006 Chicken processors Co. Down 2006 Biscuits Bloxwich 2006 Distribution Chester-le-Street 2006 Bakery Bathgate 2006 Bakery Harrogate 2007 Seafood processor Annan 2007

Key challenges for insurers Promoting testing and certification schemes for the fire performance of panels Identification of panel type and aiding holistic fire risk assessment of existing buildings Establishing real reasons for large losses Developing good design advice with dissemination to architects, developers etc. Loss Prevention Certification Board Completely independent Part of Building Research Establishment in UK LPCB provide research, testing and fire test approvals. LPCB still has very close connections to ABI, FPA and Lloyds. LPS 1181 is a wall and ceiling lining test to evaluate insulated panels.

Loss Prevention Certification Board LPS 1181 - EXT Loss Prevention Certification Board LPS 1181

Comparative - Fire Performance Data EPIC - ARUP Warrington - LPCB- LPS 1181 Fire Tests KINGSPAN LPCB SYSTEM Thick char protects core foam from fire attack. FM Global Major insurer with own test facilities and standards for building cladding systems. FMRC 4880 approval requirements for class 1 fire classification with no height restriction. Approved suppliers are subject to detailed quality surveillance. FM APPROVED

FM Grades FMRC 4880 Class 1 - Walls & Ceilings No height restriction Max 50ft height Max 30ft height FM Global 50ft Wall Test On Kingspan Panels A pass can result in unlimited height approval

Association of British Insurers Technical bulletin on the fire performance of sandwich panels partially revised August 2008. ABI Statement - For insurance underwriting purposes, Insurers use the Design Guide for the Fire Protection of Buildings as a basis for providing guidance on what they require for property protection purposes, subject to a broad based risk assessment. In respect of external composite (Sandwich) panels, these must be suitable for the intended end use application and should either have non-combustible cores or be LPCB approved to the appropriate requirements of LPS 1181(see paragraph 3.11) and fully satisfy insurers fire resistance requirements (insulation and integrity) through appropriate testing.

Insurer approach to building design Holistic fire safety engineering Combining personnel protection with property conservation The 4 key fire safety design priorities for new build Fire protection solutions for: 1. Maintaining the structural integrity of the building framework passive fire protection 2. Protection of contents - sprinklers 3. External roofs and walls of the building approved panels 4. Internal compartment walls and enclosures approved panels Fire Safety Management policies and operational procedures

FM 50 ft Fire Test Using Cardboard Cartons Demonstrates speed of fire development in high bay racking situation. UK Fire Protection Association guidance Original LPC Design Guide - 1999. New Core Documents Essential Principles Protected Zones

UK Fire Protection Association guidance Food Factories Risk assessment based Points based system Only acceptable panel systems are those approved by LPCB (essentially PIR & mineral fibre) Fire Protection Association guidance Stand Alone Cold Stores Risk assessment based Points based system Recognises that stand alone stores generally present less risk but Recommends panel cores approved by LPCB. (essentially PIR & mineral fibre)

Fire-Fighter Attitudes Wiltshire, Suffolk, Greater Manchester Hereford & Worcester West Midlands Cheshire Conclusions No brigade visited has a no-entry policy. Brigades recognise dangers of internal panel systems. Large uncompartmented buildings and lack of fire sprinklers of more concern. Real Fire Case Studies

Case Studies Panasonic Wales - Steel frame and site assembled mineral fibre roof and wall system - Contents - Electrical consumer goods Italy - Concrete frame - roof structure and metal clad wall - Contents Electrical consumer goods and scooters Boots (UK) England - Polyurethane insulated roof Nottingham and wall system - Contents - Aerosol canisters and cosmetic products Case Studies on LPCB / FM Approved panels. We have comprehensive case study information on major fires in the following buildings Hospital Warehouse School Food retail Factories All case studies are independently investigated and have all been published where we have permission. We have never had situation where PIR core LPCB/FM approved panels have caused fire propagation.

Clifton Comprehensive, Rotherham LPCB Approved PIR core roof panels. Serious fire in roof void. Independent investigation by Tenos. Clifton Comprehensive, Rotherham View outside elevated walkway.

Clifton Comprehensive, Rotherham Damage in elevated walkway. Clifton Comprehensive, Rotherham Damage to ridge in elevated walkway.

Clifton Comprehensive, Rotherham No fire spread through panels & minimal smoke seepage into school. Clifton Comprehensive, Rotherham The PIR core insulated roofing sheets did not contribute to the fire The LPCB approved panels helped prevent fire spread above the internal compartment wall.

Wharfdale Hospital LPCB Approved PIR panels Very high Fire load (intumescent coated beams distorted and compartment floor cracked). Independent investigation completed by Tenos. Wharfdale Hospital 10 metre high flames impinged directly onto panels.

Wharfdale Hospital Panel cut away to expose steel columns for inspection. Core unaffected Wharfdale Hospital PIR core is virtually unaffected when steel is pulled away.

Wharfdale Hospital Tenos Conclusion -the cores of the panels did not ignite, did not promote fire spread within the core or to the eaves and did not significantly contribute to the products of combustion. External Arson in Co. Wicklow.

External Arson in Co. Wicklow. Arson in Co. Wicklow

Arson in Co. Wicklow Arson in Co. Wicklow Fire developed very quickly Burned for 25 minutes before fire fighting commenced Direct flame impingement on panels High levels of radiated heat on panels Core remained in place No fire spread via the PIR core PIR did not contribute to heat damage

R A Wood Adhesives - Cannock R A Wood Adhesives - Cannock

R A Wood Adhesives - Cannock R A Wood Adhesives - Cannock

R A Wood Adhesives - Cannock R A Wood Tenos Conclusions. The block work fire wall was exposed to fire equivalent to at least 60 minutes in a standard fire resistance test. The charring exhibited by the PIR provided an effective fire stop between the steel skins of the cladding at the head of the compartment wall

Conclusions LPCB & FM tests provide realistic full scale tests only PIR core or mineral fibre core panels can meet certification requirements. Real fire case studies indicate that PIR core panels perform well. The design process must be based on holistic fire risk assessment building fabric is a key part of the solution. Future building regulation, sustainability and environmental performance requirements make sandwich panels the optimum choice. Any Questions?

Wall penetrations.