Basics of Electricity

Similar documents
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Basics of Electricity

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

Chapter 11. Inductors ISU EE. C.Y. Lee

Chapter 24. Three-Phase Voltage Generation

How To Understand And Understand The Theory Of Electricity

AC Generators. Basic Generator

Three phase circuits

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 3 of 4

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

Lecture Notes ELE A6

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Electronics. Basic Concepts. Yrd. Doç. Dr. Aytaç GÖREN Yrd. Doç. Dr. Levent ÇETİN

Diodes have an arrow showing the direction of the flow.

ε: Voltage output of Signal Generator (also called the Source voltage or Applied

Aircraft Electrical System

Chapter 35 Alternating Current Circuits

Trigonometry for AC circuits

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Z +

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Introduction to Electricity & Magnetism. Dr Lisa Jardine-Wright Cavendish Laboratory

Current and Temperature Ratings

Inductors & Inductance. Electronic Components

First Year (Electrical & Electronics Engineering)

(3 )Three Phase Alternating Voltage and Current

Common Mode and Differential Mode Noise Filtering

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Inductors in AC Circuits

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture phase System 4

Critical thin-film processes such as deposition and etching take place in a vacuum

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

Line Reactors and AC Drives

EEL303: Power Engineering I - Tutorial 4

AC Power. by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department

Science and Reactor Fundamentals Electrical CNSC Technical Training Group. Table of Contents

Application Guide. Power Factor Correction (PFC) Basics

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

VOLTAGE REGULATOR AND PARALLEL OPERATION

Module Title: Electrotechnology for Mech L7

7. Reactive energy compensation

W03 Analysis of DC Circuits. Yrd. Doç. Dr. Aytaç Gören

Voltage Stability Improvement using Static Var Compensator in Power Systems

RLC Resonant Circuits

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

Motor Efficiency and Power Factor ME 416/516

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

Lecture - 4 Diode Rectifier Circuits

S-Parameters and Related Quantities Sam Wetterlin 10/20/09

THREE-PHASE POWER SYSTEMS ECE 454/554: Power Systems Laboratory

Effect of Frequency on Inductive Reactance

Chapter 10. RC Circuits ISU EE. C.Y. Lee

Transformer circuit calculations

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

Application Note. So You Need to Measure Some Inductors?

104 Practice Exam 2-3/21/02

Static Analysis of Power Systems. Lennart Söder and Mehrdad Ghandhari

ECE 431. Experiment #1. Three-Phase ac Measurements. PERFORMED: 26 January 2005 WRITTEN: 28 January Jason Wells

Modeling of Transmission Lines

Alternating Current and Direct Current

13.10: How Series and Parallel Circuits Differ pg. 571

GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software

Induced voltages and Inductance Faraday s Law

Slide 1 / 26. Inductance by Bryan Pflueger

Power Quality Paper #3

DRAFT. University of Pennsylvania Moore School of Electrical Engineering ESE319 Electronic Circuits - Modeling and Measurement Techniques

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

PHY114 S11 Term Exam 3

Power Factor Correction - The Easiest, Biggest, Green Initiative

6 ELECTRICAL PARAMETERS

GenTech Practice Questions

Eðlisfræði 2, vor 2007

Balanced vs. Unbalanced Audio Interconnections

Coupled Inductors. Introducing Coupled Inductors

ACCURACY OF POTENTIALTRANSFORMERS

SYNCHRONOUS MACHINES

DC-DC Converter Basics

Impedance Matching. Using transformers Using matching networks

= (0.400 A) (4.80 V) = 1.92 W = (0.400 A) (7.20 V) = 2.88 W

Students Manual for the Exam. General Engineering and Electrical Civil Engineering Discipline

EE301 Lesson 14 Reading: , , and

45. The peak value of an alternating current in a 1500-W device is 5.4 A. What is the rms voltage across?

Guideline for Energy Efficient Electrical systems for building. Presentation by TERI

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

Power Factor The Basics

Chapter 25 Alternating Currents

Joslyn Clark Controls, Inc.

Distributed Generation and Power Quality Case Study

The Critical Length of a Transmission Line

Transcription:

Basics of Electricity Power Flow on AC Transmission Lines PJM State & Member Training Dept.

Objectives Describe the basic make-up and theory of an AC transmission line Given the formula for real power and information, calculate real power flow on an AC transmission facility Given the formula for reactive power and information, calculate reactive power flow on an AC transmission facility Given voltage magnitudes and phase angle information between 2 busses, determine how real and reactive power will flow

Introduction Transmission lines are used to connect electric power sources to electric power loads. In general, transmission lines connect the system s generators to it s distribution substations. Transmission lines are also used to interconnect neighboring power systems. Since transmission power losses are proportional to the square of the load current, high voltages, from 115kV to 765kV, are used to minimize losses

AC Power Flow Overview

AC Power Flow Overview R X L V S V R 1/2X C 1/2X C Different lines have different values for R, X L, and X C, depending on: Length Conductor spacing Conductor cross-sectional area X C is equally distributed along the line

Resistance in AC Circuits Resistance (R) is the property of a material that opposes current flow causing real power or watt losses due to I 2 R heating Line resistance is dependent on: Conductor material Conductor cross-sectional area Conductor length In a purely resistive circuit, current and voltage are in phase; instantaneous power equaling the product of the two

Power in Out-of-Phase AC Circuits Reactance is the opposition to current caused by capacitors and inductors Reactance causes current to be out-of-phase with voltage Inductive reactance (X L ) causes current to lag the voltage Capacitive reactance (X C ) causes current to lead the voltage Loads containing pure capacitance or pure inductance cause the current to be exactly 90 o out of phase with the voltage

Power in Out-of-Phase AC Circuits Inductance and capacitance depend on: Conductor cross-sectional area Conductor length Distance between phase conductors Inductive reactance decreases as the cross-sectional area of the conductor increases, and increases as the conductor spacing increases Capacitive reactance increases as the cross-sectional area of the conductor increases, and decreases as the conductor spacing increases

Power in Out-of-Phase AC Circuits For transmission lines less than 50 miles in length, capacitance is small and negligible Capacitance is always greater for underground cables where conductors and ground are very close AC voltage causes the charge on the conductors to increase and decrease as the voltage increases and decreases Charging Current is current that flows due to the alternate charge and discharge of the line due to alternating voltage regardless of whether the circuit is closed or open-ended

Review Total impedance (Z) is made up of resistance, inductance, and capacitance The reactive component (X) of impedance is made up of inductance and capacitance and is greater than the resistive (R) component of a line Reactive components of impedance are greater for higher voltage lines than for lower voltage lines

Flow of Real Power

Power Flow MW flow on a transmission facility is the result of the resistive component (R) Real power is measured in watts (W) and is in-phase with the load VAR flow on a transmission facility is the result of the reactive component (X) VARs supply magnetizing current for inductive loads and charging current for capacitive loads

Real Power Flow Real Power (P R ) flow between two buses is obtained by: Where, P = Real power in MW V S = Sending-end voltage V R = Receiving-end voltage X = Line impedance between buses = Angle delta between bus voltages

Real Power Flow Angle theta, is the symbol for the angle difference between current and voltage Used in determining power factor indicating the portion of total current and voltage that is producing real power Angle delta, is the symbol for phase angle difference between the sending and receiving voltages Negative MW s indicate flow into the sending bus Positive MW s indicate flow out of the sending bus

Real Power Flow Angle Angular difference between buses V B Angle V A I A

Question #1 The voltage at Bus A (reference) is 522 kv at an angle of -15 degrees. The voltage at Bus B is 518 kv at an angle of -18 degrees. Total impedance of the transmission path between the buses is 50 ohms. What is (a) the real power flow, and (b) what is its direction? (a) P R = {(V A ) (V B ) / X } sinᵟ = {(522)(518)/50} sin (-15 -(-18 )) = (270,396/50)(sin 3) = (5408)(0.0523) = 283 MW (b) Direction of flow is from bus A to bus B

Question #2 Calculate the a) real power, and b) it s direction of flow using the following information: Bus A voltage is 235 kv at an angle of -23 degrees with a power factor of 0.79 Bus B voltage is 237 kv at an angle of -21 degrees with a power factor of 0.85 Total impedance of the transmission path between the buses is 45 ohms (a) P R = {(V A ) (V B ) / X } sinᵟ = {(235)(237)/45} sin (-23 -(-21 )} = (55,695/45)(sin -2) = (1,237.6)(-0.0349) = -43.2 MW (b) Direction of flow is from Bus B to Bus A

Real Power Flow In order to transfer real power across a transmission line, there must be an angle (delta) between the voltages at each end of the line Greater phase angle difference; more real power transferred Maximum power transfer theoretically occurs at 90 o Real Power flows downhill to a more lagging angle

Flow of Real Power Summary Increasing impedance results in a decrease in real power transfer Increasing the phase angle difference increases real power transfer Neither increasing or decreasing voltage magnitudes has a significant effect on the flow of real power If impedances of parallel lines are equal, power flow is equally distributed If impedances of parallel lines are different, real power flow is inversely proportional to line impedance

Flow of Reactive Power

Flow of Reactive Power Reactive Power (P Q ) flow on a transmission line is a result of the inductive reactance of the load requirement and is obtained by: Where, Q = Reactive Power in MVAR V S = Sending-end voltage ΔV = Difference between bus voltages V S and V R X = Line Impedance between buses = Phase angle between VS and VR

Flow of Reactive Power VARS flow only if there is a difference in bus voltage potential VAR s flow downhill from a higher per unit value to a lower per unit value of voltage Reactive power flow is similar to real power flow: Negative VAR value indicates flow into the reference bus Positive VAR value indicates flow out of the reference bus

Question #3 Bus A has a voltage of 234 kv at an angle of -18 degrees, and Bus B voltage is 239 kv at an angle of -25 degrees. If the impedance of the transmission path is 45 ohms, what is (a) the reactive power flow between the buses, and (b) in what direction is the reactive power flowing? (a) P Q = {(V A ) (ΔV) / X } cosᵟ = {(239)(239-234)/45} cos {-25 -(-18 )} = {(239)(5)/45} cos {-7} = (26.55)(0.9925) = 26.4 MVAR (b) Flow is from Bus B to Bus A

Question #4 Calculate the a) reactive power between Bus A and Bus B, and b) it s direction of flow using the following information: Bus A voltage is 547 kv at an angle of -15 degrees with a power factor of 0.78 Bus B voltage is 544 kv at an angle of -18 degrees with a power factor of 0.81 Total impedance of the transmission path is 86 ohms (a) P Q = {(V A ) (ΔV) / X } cosᵟ = {(547)(547-544)/86} cos {-15 -(-18 )} = {(547)(3)/86} cos 3 = (19.1)(0.998) = 19.07 MVAR (b) Flow is from Bus A to Bus B

Flow of Reactive Power Summary Increasing the voltage magnitude at the sending end increases the reactive power flow toward the receiving end Increasing the voltage magnitude at the receiving end decreases the reactive power flow toward the receiving end Increasing the path impedance between the two buses decreases the reactive power flow towards the receiving end

Integrating Real & Reactive Power Flows

Scenario 1 Voltages are in-phase; Bus A voltage > Bus B voltage E B E A Bus A Bus B MW MVAR No MW flow; no phase angle difference VAR s flow from Bus A to Bus B

Scenario 2 Voltages are in-phase; Bus A voltage < Bus B voltage E A E B Bus A MW MVAR Bus B No MW flow; no phase angle difference VAR s flow from Bus B to Bus A

Scenario 3 Voltages are not in-phase; Bus A voltage > Bus B voltage E A E B Bus A MW MVAR Bus B MW flow; Bus B voltage is lagging Bus A voltage VAR s flow from Bus A to Bus B

Scenario 4 Voltages are not in-phase; Bus A voltage > Bus B voltage E B E A Bus A MW MVAR Bus B MW flow; Bus A voltage is lagging Bus B voltage VAR s flow from Bus A to Bus B

Scenario 5 Voltages are not in-phase; Bus A voltage < Bus B voltage E A E B Bus A MW MVAR Bus B MW flow; Bus B voltage is lagging Bus A voltage VAR s flow from Bus B to Bus A

Scenario 6 Voltages are not in-phase; Bus A voltage < Bus B voltage E B E A Bus A MW MVAR Bus B MW flow; Bus A voltage is lagging Bus B voltage VAR s flow from Bus B to Bus A

Scenario 7 Voltages are not in-phase; Bus A voltage = Bus B voltage MW flow E A E B E A Bus A MW MVAR Bus A voltage lags Bus B voltage, MW flow into Bus A Bus B voltage lags Bus A voltage, MW flow out of Bus A VAR s flow from Bus B and from Bus A into the line Bus B

Question #5 Bus A, the reference bus, has a voltage of 527 kv at an angle of -16 degrees. Bus B voltage is equal to 542 kv at an angle of -19 degrees. Load 1 has a power factor of 0.93, while load 2 has a power factor of 0.82. If the total impedance of the transmission path is 75 ohms, find (a) the real power flow, (b) the direction of real power flow, (c) the reactive power flow, and (d) the direction of reactive power flow?

Question #5 P R = (V S ) (V R ) / Z * sin ᵟ = (527 kv) (542 kv) / 75 Ω * sin (-16 (-19)) = 3808.4 * 0.052 = 199.3 MW Real Power will flow from Bus A to Bus B P Q = (V S ) (V S - V R ) / Z * cos ᵟ = (542 kv) (542 kv -527 kv) / 75 Ω * cos (-19 (-16)) = 108.4 * 0.998 = 108.2 MVAR Reactive Power will flow from Bus B to Bus A

Summary Reviewed the three basic components that make up a transmission line: resistance, inductance, and capacitance Applied the formula for calculating real power flow on an AC transmission line Applied the formula for calculating reactive power flow on an AC transmission line Given voltage and phase angle information, interpreted how real and reactive power will flow on a transmission facility

Questions?

Disclaimer: PJM has made all efforts possible to accurately document all information in this presentation. The information seen here does not supersede the PJM Operating Agreement or the PJM Tariff both of which can be found by accessing: http://www.pjm.com/documents/agreements/pjmagreements.aspx For additional detailed information on any of the topics discussed, please refer to the appropriate PJM manual which can be found by accessing: http://www.pjm.com/documents/manuals.aspx

Resources and References Rustebakke, Homer M. (1983). Electric Utility Systems and Practices. New York: John Wiley and Sons Miller, Robert H., & Malinowski, James H. (1993). Power System Operation. New York: McGraw-Hill Inc.