An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Similar documents
Research on the Air Conditioning Water Heater System

UNIT 2 REFRIGERATION CYCLE

New Trends in the Field of Automobile Air Conditioning

Characteristics of Evaporators

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Waste Heat Recovery through Air Conditioning System

Chapter 3.4: HVAC & Refrigeration System

Glossary of Heating, Ventilation and Air Conditioning Terms

Testing methods applicable to refrigeration components and systems

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

Creating Efficient HVAC Systems

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES

How To Calculate The Performance Of A Refrigerator And Heat Pump

HVAC Systems: Overview

Mohan Chandrasekharan #1

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Low GWP Replacements for R404A in Commercial Refrigeration Applications

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Evaporative Cooling for Residential and Light-Commercial

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Analysis of Ammonia Water (NH3-H2O) Vapor Absorption Refrigeration System based on First Law of Thermodynamics

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process.

Heat Recovery In Retail Refrigeration

Refrigeration Basics 101. By: Eric Nelson

The Development of a Frost-Less Heat Pump

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Automobile Air Conditioning Primer

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

HVAC Efficiency Definitions

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

AIR CONDITIONING - ENERGY CONSUMPTION AND ENVIRONMENTAL QUALITY

Performance Test of Solar Assisted Solid Desiccant Dryer

6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

Analytical Study of Vapour Compression Refrigeration System Using Diffuser and Subcooling

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

How does solar air conditioning work?

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE. ACHP 104 Refrigeration & Air Conditioning Service II

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

Refrigeration & HVAC

How To Understand Evaporator

Thermodynamics - Example Problems Problems and Solutions

FEASIBILITY OF A BRAYTON CYCLE AUTOMOTIVE AIR CONDITIONING SYSTEM

LG Electronics AE Company, Commercial Air Conditioning

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

DRAFT. Appendix C.2 - Air Conditioning Thermodynamics 1

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?

The Second Law of Thermodynamics

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

Why and How we Use Capacity Control

جامعة البلقاء التطبيقية

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

The Different Types of Air Conditioning Equipment for IT Environments

Silicagel-water adsorption cooling prototype system for mobile air conditioning

How do I measure the amount of water vapor in the air?

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Energy savings in commercial refrigeration. Low pressure control

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Lesson 36 Selection Of Air Conditioning Systems

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION

AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

How Ground/Water Source Heat Pumps Work

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Condensers & Evaporator Chapter 5

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Heat. Investigating the function of the expansion valve of the heat pump. LD Physics Leaflets P Thermodynamic cycle Heat pump

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

HVAC Basic Science - System Capacity

AIR REVERSING R744 AIR CONDITIONING SYSTEM

SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS

HP switch LP switch Discharge thermo Comp. Surface thermo

Contents and Nomenclature

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

Environmental Data Center Management and Monitoring

Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov to Mar. 15, 2004.

Air-Conditioning Buying Guide

The Second Law of Thermodynamics

Energy and Buildings

saving energy in comfort Factsheet Recair Enthalpy

GEOTHERMAL HEATING AND COOLING INTRODUCTION

ENERGY SAVING WORT BOILING SISTEM IN BREWING FACTORY

SOLAR COOLING WITH ICE STORAGE

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

Dehumidification Frequently Asked Questions

Drying Parawood with Superheated Steam

Residential HVAC System Sizing

Transcription:

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner P. Suntivarakorn, S. Satmarong, C. Benjapiyaporn, and S. Theerakulpisut Abstract This paper was to study the clothes dryer using waste heat from a split type air conditioner with a capacity of 12,648 btu/h. The drying chamber had a minimum cross section area with the size of 0.5 x 1.0 m 2. The chamber was constructed by sailcloth and was inside folded with aluminium foil. Then, it was connected to the condensing unit of an air conditioner. The experiment was carried out in two aspects which were the clothes drying with and without auxiliary fan unit. The results showed that the drying rate of clothes in the chamber installed with and without auxiliary fan unit were 2.26 and 1.1 kg/h, respectively. In case of the chamber installed with a auxiliary fan unit, the additional power of 0.011 kwh was consumed and the drying rate was higher than that of clothes drying without auxiliary fan unit. Without auxiliary fan unit installation, no energy was required but there was a portion of hot air leaks away through the punctured holes at the wall of the drying chamber, hence the drying rate was dropped below. The drying rate of clothes drying using waste heat was higher than natural indoor drying and commercial dryer which their drying rate were 0.17 and 1.9 kg/h, respectively. It was noted that the COP of the air conditioner did not change during the operating of clothes drying. Keywords Drying Rate, Clothes Dryer, COP, Air Conditioner. I. INTRODUCTION ORMERLY, drying clothes usually use natural way by F using the energy from the sunlight and the wind, but nowadays the technology is plentifully developed upward and the clothes dryers that use the electric energy or other energy come to use extensively, especially in the urban area where people live in the tall buildings. Then, people who live in the building have the limitation in the area in drying clothes from the sunlight. However, they can dry their clothes in the balcony. In order to maintain an acceptable appearance of building façade, clothes drying using natural means by Prapat Suntivarakorn is an assistance professor of the Mechanical Engineering Department, Faculty of Engineering, Khon Kaen University, Khon Kaen, 40002, Thailand (phone: +66-81-989-1983; fax: +66-43-347-879; e-mail: sprapat@ kku.ac.th). Somchai Satmarong is a graduate student of the Mechanical Engineering Department, Faculty of Engineering, Khon Kaen University, Khon Kaen, 40002, Thailand (e-mail: somch_s@hotmail.com). Chatchai Benjapiyaporn is an assistance professor of the Mechanical Engineering Department, Faculty of Engineering, Khon Kaen University, Khon Kaen, 40002, Thailand (e-mail: chaben@ kku.ac.th). Somnuk Theerakulpisut is an associate professor of the Mechanical Engineering Department, Faculty of Engineering, Khon Kaen University, Khon Kaen, 40002, Thailand (e-mail: somthe@ kku.ac.th). hanging clothes in the balcony may not be allowed. Increasingly, clothes drying has become confined to indoors which take time for drying clothes, especially drying clothes in the period that the air humidity is high such as in the raining season. Clothes drying indoors by natural ventilation can take a long time and still yield unsatisfactory results. In addition, drying clothes indoors by natural ventilation impacts indoor thermal environment, as the moisture contained in wet clothes is transferred to indoor air during drying, by evaporation and diffusion. This additional indoor moisture load must be dealt with either mechanical or natural ventilation means. If clothes drying as achieved by either electricity or gas-powered dryer, the drying process may be completed within hours with the expense of additional energy use and pollution. On the other hand, for residential buildings in subtropical regions, because of its subtropical climates, annually, air conditioning is normally necessary for 7-8 months when it is either hot or humid, or both. From a survey of user behavior in the residential buildings, it was indicated that most people use split-type air conditioner. For split-type air conditioner, air is used to carry away heat rejected from its air-cooled condenser and is therefore heated so that its temperature may increase by up to 10 o C [1]. This presents an opportunity to reuse the heated air exiting from an air-cooled split-type air conditioner for clothes drying in residential building located in regions where air-conditioning is required for a long period, thus improving energy use efficiency for residential clothes drying and reducing heat pollution to the environment. Thus, many researchers utilized the waste heat from air conditioner for clothes drying. The clothes drying chamber was designed and installed to the condensing unit of air conditioner and its experiment was examined. It was proved that using waste heat from air conditioner was functional and realistic for clothes drying [2-5]. However, installation the clothes drying chamber in the condensing unit may effect to the performance of air conditioner due to the decreasing of air flow from the exit of condenser. To protect the reduction of the air conditioner efficiency, an auxiliary fan unit was installed at the exit of clothes drying chamber. However, it was found that the previous design of clothes drying chamber had a limitation for utilizing due to its big structure and unsuitable installation area, including there was a few of the study about re-using waste heat from split type air conditioner. Therefore, to collect more data about clothes drying using waste heat from 483

air conditioner, a study on clothes drying was studied in this work. An experiment for reduction the energy of fan unit installed at the end of clothes drying chamber was also carried out to find a suitable way to utilize the waste heat from air conditioner for clothes drying. II. PRINCIPLE OF SPLIT-TYPE AIR CONDITIONER Split type air conditioner works by vapor compression refrigeration cycle as showed in Fig. 1. It consists of four major processes namely: (1) Isentropic compression in a compressor, (2) Constant-pressure heat rejection in a condenser, (3) Throttling in an expansion device and (4) Constant-pressure heat absorption in an evaporator. In vapor compression refrigeration cycle, the refrigerant enters the compressor at state 1 as saturated vapor and is compressed isentropically to the condenser pressure. The temperature of the refrigerant increases well above the temperature of the surrounding medium during this compression process. The refrigerant then enters the condenser as superheated vapor at state 2 and leaves as saturated liquid at state 3 as a result of heat rejection to the surroundings. The temperature of the refrigerant at this state is still above the temperature of the surroundings. The saturated liquid refrigerant at state 3 is throttled to the evaporator pressure by passing it through an expansion valve or capillary tube. The temperature of the refrigerant drops below the temperature of the refrigerated space during this process. The refrigerant enters the evaporator at state 4 as a low quality saturated mixture, and it completely evaporates by absorbing heat from the refrigerated space. The refrigerant leaves the evaporator as saturated vapor and reenters the compressor, completing the cycle. The performance of this refrigeration cycle is expressed in terms of the coefficient of performance (COP), which was defined as [6] Q COP = (1) W where Q represents the heat transferred to evaporator and W represents the work supplied to the system. In this paper, the heat transferred to the evaporator was defined as Q = m (h a1 h a2 ) (2) where m represents the mass flow rate of air that flows into the evaporator and h a1 and h a2 represent respectively the enthalpy of air at the inlet and outlet of evaporator. h a2 h a1 Fig. 1 Vapor compression refrigeration cycle III. DRYING THEORETICAL CONSIDERATION When the material, which has moisture inside, is contacted to the hot air, the heat transfer will occur at the surface of the material. The temperature of the material will be increased and the moisture inside the material will evaporate to the surrounding. The process of drying is related to the mass transfer from moisture inside the material to the surrounding. Reduction of moisture in the material will be divided in 3 periods as shown as a typical drying curve in Fig. 2. A typical drying curve, where the drying rate (kg/s) is plotted against moisture content, has an initial heating stage (A-B), unhindered or constant drying rate period (B-C) and hinder drying or falling rate drying period (C-D-E). At point C, the drying rate starts to decrease and this point is called the critical humidity point. The drying rate continuously decreases and stops at point E when the moisture in material is in the equilibrium state with surrounding. One of the important criteria with respect to the performance of dryer is drying rate in kg/h. The drying rate ( m d ) is defined as: W W f m d = 0 (3) t where W 0 and W f represent the weight of material before and after drying, respectively, and t represents the time for drying. Fig. 2 Typical drying rate curve [2] IV. EXPERIMENTATION Spilt type air conditioner with capacity of 12,648 btu/h was used to examine the clothes drying using heat rejected from condensing unit. Clothes drying chamber was designed with the capacity of 0.5x0.5x1.0 m 3. The chamber consists of 3 parts namely; (1) the expansion area, (2) the constant area and (3) the contraction area as shown in Fig. 3. The chamber was constructed by sailcloth with an aluminum steel structure and aluminum foil was folded inside the chamber in order to protect heat loss. The drying chamber with 180 watts of auxiliary fan unit was installed to the condenser. The clothes used in the experiment were 100% of cotton and were one meter high. Before installation the drying chamber to the condenser, the velocity, temperature and humidity of air at the entrance and exit of condenser were measured for calculating the COP. The room temperature, while the experiment was conducted, was set at 25 o C. After that, the drying chamber was installed to 484

the exit of condenser. The experiment was started with weight measurement of the clothes, then hanging the clothes in parallel with the flow direction of hot air from condenser. During the examination, the weight of clothes, humidity and the temperature of hot air were collected every two minutes. The COP of the air conditioner was again calculated from the experimental data. The experiment will be finished when the clothes were dried after the weight of clothes was not changed. In this study, clothes drying with and without the auxiliary fan unit were conducted to compare the drying rate and the suitable way to utilize the waste heat from air conditioner. The comparison of the drying rate between drying with waste heat from air conditioner, commercial dryer and natural drying indoors were also conducted. COP 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 Experimental data y=6.19317-0.09121x 0.0 31 32 33 34 35 36 37 38 39 40 41 Outdoor air temperature ( 0 C) Fig. 4 The relation between the COP and the outdoor temperature Fig. 3 Clothes drying chamber installed to the condensing unit V. RESULTS AND DISCUSSION A. Coefficient of Performance of the Experimental Air Conditioner The COP of the air conditioner was varied to the temperature outside the room. Therefore, the data for calculation the COP were collected in two weeks. From the calculation, the results were shown that the COP was decreased with the increasing of the temperature outside the room as shown in Fig. 4. The value of COP was varied between 2.5 to 3.5 while the outdoor temperature was varied between 32 to 40 o C. The relation between the COP and the temperature was expressed as ( ) COP = 6.19317 0. 09121 (4) T outdoor where T outdoor represents the temperature outside the room. Moreover, it was found the temperature at the exit of condenser was increased by up to 10 o C. This is because that the air is used to carry away heat rejected from its air-cooled condenser. From Fig. 5, it was shown that the air temperature at the exit of condenser was increased with the increasing of the temperature outside the room, and its relation can be expressed as: T indoor = 10.41752 + 1. 58185 ( T outdoor ) (5) where T indoor represents the temperature at the exit of the condenser or the temperature inside the drying chamber. Outlet air temp ( 0 C) 50 45 40 35 30 25 20 15 10 5 Experimental data y=-10.41752+1.58185x 0 31 32 33 34 35 36 37 38 39 40 41 Inlet air temperature 0 C Fig. 5 The relation between the temperature at the entrance and exit of condenser Number of clothes TABLE I DRYING RATE OF THE CLOTHES IN CASE OF 4-10 PIECES Temperature ( o C) Humidity (%) Distance between 2 pieces of clothes (m) Drying rate from experiment (kg/h) Drying rate from theoretical calculation (kg/h) 4 42.6 45 0.0840 1.44 0.72 6 41.5 46 0.0543 1.77 1.42 8 41.9 45 0.0378 2.26 2.38 10 42.2 44 0.0273 1.58 3.65 B. Clothes Drying with Auxiliary Fan Unit During the operation of the air conditioner, if there was an obstruction in front of the condensing unit, the COP will be decreased due to the inadequate heat transfer. Consequently, the auxiliary fan unit was installed at the exit of drying chamber for solving that problem. The 120 watts of fan unit with vary speed control was used in the experiment. By adjusting the speed of fan, the air flow rate at the exit of drying chamber was controlled to be equal to flow rate of the hot air from the exit of the condenser. The experiment was 485

begun from drying four pieces of clothes, and then adding the number of clothes to be 6, 8, and 10 respectively. From collecting the experimental data, the drying rate from the experiment was examined and compared with that of the theoretical calculation as shown in Table I and Fig. 6. DryingRate(kg/h) 3.5 3.0 2.5 2.0 1.5 1.0 0.5 Experimental Theory 4 5 6 7 8 9 10 Number of Clothes Fig. 6 The drying rate from the experiment compared with that of the theoretical calculation From Table I and Fig. 6, the drying rate of 8 pieces of clothes had maximum drying rate of 2.26 kg/h, which was close to that of theoretical (2.38 kg/h). In case of theoretical calculation, the drying rate was increased when the number of clothes was increased. This was contrasted with the experimental results. Due to the limitation of the size of the drying chamber, which its wideness was only 0.5 meter, the drying rate was decreased in case of drying 10 pieces of clothes. The distance between 2 pieces of clothes was only 0.0273 meter and was very close to each other, then the hot air can not flow through the clothes in the chamber and the heat exchanging was not occurred. This caused the hot air changing its direction to the top and bottom in the chamber as shown in Fig. 7. The results were shown that the suitable number of clothes in this chamber was eight pieces. Fig. 8 Hanging 8 pieces of clothes in the chamber TABLE II AIR FLOW RATE AND THE COP RECEIVED FROM THE EXPERIMENT IN CASE OF CLOTHES DRYING WITHOUT FAN UNIT AND PUNCTURING THE HOLES AT THE WALL OF THE CHAMBER Number of holes Air flow rate at the exit of the chamber (m 3 /h) COP in case with clothes drying COP in case without drying chamber The difference of percentage 3 0.208 2.66 3.24 17.82 6 0.212 2.48 3.21 22.41 9 0.217 2.49 3.33 25.21 12 0.221 3.24 3.34 3.02 15 0.222 3.36 3.46 2.94 18 0.226 3.38 3.41 0.42 21 0.230 3.45 3.45 0.00 Fig. 9 The drying chamber without auxiliary fan unit Fig. 7 The direction of hot air to the top and bottom of the chamber C. Clothes Drying without Auxiliary Fan Unit The disadvantage of clothes drying with auxiliary fan unit was the electrical energy consumption. Therefore, the experiment on clothes drying without auxiliary fan unit was examined in order to reduce the energy consumption. The auxiliary fan was removed. The experiment was set up to dry 486

8 pieces of clothes in the chamber. It was found that the flow rate at the exit of the chamber was 0.203 m 3 /h which was less than the flow rate of 0.23 m 3 /h from the exit of the condenser. This indicated that the COP of the air conditioner was decreased. Hence, the difference of the flow rate, which was 0.03 m 3 /h, was used to calculate the area for puncture at the wall of the drying chamber in order to balance the flow rate of the hot air. From the calculation, the suitable area of 0.0363 m 2 was obtained. Three holes with the size of 0.11x0.11 m 2 were punctured at the bottom and the sides of the chamber in order to allow the ventilation of hot air over the drying chamber. The experiment of clothes drying without auxiliary fan unit and puncturing three holes at the wall, the COP was examined and compared with that of the case without the drying chamber. The results were revealed that the COP in case of clothes drying without fan unit was 17.82 % less than that of the case without drying chamber. It means that the hot air from condenser was accumulated within the chamber and the ventilation of hot air was still inadequate. Then, the addition of holes was done by gradually puncturing every three holes. The experimental data was still continuously collected and finished until the wall was punctured up to 21 holes (See Fig. 9). The COP and air flow rate for each step were shown in Table II. From Table II, the results showed that the air flow rate was increased with the addition of the holes. In case those 21 holes were punctured at the wall of the chamber, the air flow was 0.23 m 3 /h and equal to the flow rate in case without drying chamber. This means that the clothes drying were conducted without any effect to the COP of the air conditioner. The drying rate in case of clothes drying without auxiliary fan unit was 1.1 kg/h and less than the drying rate in case of clothes drying with auxiliary fan unit. Volume flowrate (m 3 /s) 0.24 Standard volume flowrate = 0.23 m 3 /s 0.22 0.20 0.18 0.16 0.14 0.12 0.10 0.08 0.06 0.04 0.02 Volume flowrate at side wall (m 3 /s) Volume flowrate at exit dryer (m 3 /s) Total volume flowrate (m 3 /s) 0.00 0 2 4 6 8 10 12 14 16 18 20 22 No. of hole Fig. 10 The air flow rate at the exit and the side wall of the chamber D. Comparison of the Drying Rate in Various Type of Clothes Drying Besides, clothes drying using waste heat from split type air conditioner were carried out, clothes drying by using commercial clothes dryer (2,000 watts heater) and natural clothes drying indoors were also examined. The comparison of the drying rate in each type of clothes drying was shown in Table 3. It was found that the maximum drying rate was 2.26 kg/h in case that the clothes drying chamber with auxiliary fan unit was conducted by using waste heat from air conditioner. This drying rate was higher than that of clothes drying using commercial dryer and clothes drying indoor which their drying rate were 1.9 kg/h and 0.17 kg/h, respectively. For the clothes drying chamber without auxiliary fan unit, the drying rate was 1.1 kg/h and less than that of clothes drying with commercial dryer and clothes drying chamber with auxiliary fan unit, but more than that of indoor drying. However, when consider the energy consumption, it was indicated that the energy was not consumed in case of using clothes drying without auxiliary fan unit, while clothes drying with auxiliary fan unit consumed 0.011 kwh of electrical energy or 1.5% of the energy consumption in commercial dryer. TABLE III COMPARISON OF THE DRYING RATE IN VARIOUS TYPES OF CLOTHES DRYING Type of clothes drying Clothes drying with fan unit Clothes drying without fan unit Clothes Drying indoor Commercial clothes dryer Time (h) Initial weight (kg) Final weight (kg) Energy consumption (kwh) Drying rate (kg/h) 0.3 2.09 1.41 0.011 2.26 0.6 2.1 1.41-1.1 4 2.09 1.4-0.17 0.33 2.05 1.42 0.66 1.9 VI. CONCLUSION An experiment study on the effectiveness of clothes drying using waste heat from condensing unit has been carried out and reported. Results from the study indicated that clothes drying using waste heat from condensing unit in residential building can be effective, for its reasonably short drying duration and high energy efficiency during air conditioning seasons. The suitable size of clothes drying chamber is 0.5x0.5x1.0 m 3 and is suitable for 8 pieces of clothes drying. The drying rate of clothes drying using waste heat from air conditioner is between 1.1-2.26 kg/h. This is better than that of clothes drying with commercial dryer and natural indoor drying which their drying rate are 1.9 and 0.17 kh/h, respectively. Moreover, the result is also revealed that the drying chamber without auxiliary fan unit is workable and can help achieve energy saving, even its drying rate is lower than that of clothes drying chamber with fan unit. ACKNOWLEDGMENT The authors acknowledge the grant from Energy Management and Conservation Office, Faculty of Engineering, Khon Kaen University to financially support the project reported in this paper. 487

REFERENCES [1] S. Deng and H. Han, An experimental study on clothes drying using rejected heat (CDURH) with split-type residential air conditioners Applied Thermal Engineering vol. 24, 2004, pp. 2789-2800. [2] A. Ameen and S. Bari, Investigation into the effectiveness of heat pump assisted clothes dryer for humid tropics Energy Conversion and Management vol. 45, 2004, pp. 1397-1405. [3] A. B. Ng and S. Deng, A new termination control method for a clothes drying process in a clothes dryer Applied Energy vol. 85, 2008, pp. 818-829. [4] V. Yadav and C. G. Moon, Modelling and experimentation for the fabric-drying process in domestic dryers Applied Energy vol. 85, 2008, pp. 80-95. [5] J. Deans, The modeling of a domestic tumbler dryer Applied Thermal Engineering vol. 21, 2001, pp. 977-900. [6] Y. A. Cengel and M. A. Boles, Thermodynamics: An engineering approach, 4 th edition, McGraw-Hill, New York, 2002, 930 pages. P. Suntivarakorn was born in Loei, Thailand in 1973 and is a lecture from Department of Mechanical Engineering. He received his Bachelor degree in Mechanical Engineering from Khon Kaen University, Thailand. In 2000 and 2003, he has got Master of Engineering (M.E) and Doctor of Philosophy (Ph.D) in Mechanical Engineering, respectively. His main field is Alternative Energy and Energy Conservation. 488