TECUMSEH PRODUCTS COMPANY GUIDELINES FOR UTILIZATION OF



Similar documents
R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight Temperature glide o C Boiling point (1 atm)

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

RS-24 (R426A): Q & A

TECHNICAL INFORMATION

Refrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Recommended Compressor Installation Practices

RS-44 (R424A) : Q & A

SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)

COMPRESSOR REPLACEMENT PROCEDURE

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois Information compiled by Frank Prah, CMS

REFRIGERANT REFERENCE GUIDE

UNDERSTANDING REFRIGERANT TABLES

Flushing and Cleaning the A/C System

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

Subject: 2005 Air Conditioning Service Guidelines

Vacuum. How It Relates to Refrigeration And Air Conditioning Service

Recharge Procedure for Telemark TVP-2000 and TVP-3500

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

THE REPLACEMENT OF R-22

Patech. Our Conviction. Quality Service Innovation PATECH FINE CHEMICALS CO., LTD

Evaluation of HFO-1234yf as a Potential Replacement for R-134a in Refrigeration Applications

A/C refrigerant system, overview

COMPRESSOR REPLACEMENT PROCEDURE

Rusty Walker, Corporate Trainer Hill PHOENIX

Automobile Air Conditioning Primer

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

SEALED SYSTEM DIAGNOSIS

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Training Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. Page

refrigerants DuPont Suva 134a (HFC-134a) for Mobile Air Conditioning Technical Information Introduction Transition to HFC-134a

TECHNICAL BULLETIN hydrocarbons

Federal Clean Air Act Section 609 Training Manual & Exam

Engineering Recommendation on: Accumulators Revised Issued January 10, 1979 Page 1 of 7

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON

This chapter is devided into two sections:

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity

How To Clean Water From An Ammonia Refrigeration System

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

MACS Recommended Service Procedures

Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR İ-COLD Rev. 00

HVAC-02, Air Conditioning Troubleshooting and Repair

Engineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume Refrigerant History

Refrigeration Basics 101. By: Eric Nelson

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Product overview Air conditioning service units

DESIGN STANDARDS SECTION

Heating and Air Conditioning

Elements Elements describe the essential outcomes.

Commercial CO 2 Refrigeration Systems

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment

System Diagnosis. Proper vehicle diagnosis requires a plan before you start

Production of R-134a

Danfoss compressors - Repair of hermetic refrigeration systems

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Part A: Fluid properties

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30,

HVAC Made Easy - Selection Tips for Chiller Compressors

Why and How we Use Capacity Control

Information on New Refrigerant (R-1234yf) for A/C Service

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

Filter and sight glass REFRIGERATION AND AIR CONDITIONING. Fitters notes

REPAIR OF HERMETIC REFRIGERATION SYSTEMS

Aluminium as Construction Material in Ammonia Refrigeration Cycles

R134a in Small Commercial Refrigeration System: Some Practical Aspects

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

Refrigeration & Air Conditioning System Protectors. Catalog RAC-1 USA October 2000

Introduction; Kit Contents: Page 1

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Estimation Method For Thermal Stability Of Refrigeration Oil And Automatic Sealed Glass Tube Processing Device

CHEM 2423 Recrystallization of Benzoic Acid EXPERIMENT 4 - Purification - Recrystallization of Benzoic acid

AIR CONDITIONING TECHNOLOGY

CHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS

Refrigeration System Installation & Operation Manual

Chemistry 13: States of Matter

Planning for the ban on R22 in building air conditioning

Making Biodiesel from Virgin Vegetable Oil: Teacher Manual

AUTOMOTIVE AIR CONDITIONING

How To Understand Evaporator

SYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING. Effective From :- UNDER DEVELOPMENT.

Refrigerant handling code of practice 2007

Air Conditioning 101. STN Presentation AC101

This equipment has been certified by ITS/ETL to meet or excees SAE J1990 and J1991 for AR512 series and SAE J2099 and J2210 for AR500 series

experiment5 Understanding and applying the concept of limiting reagents. Learning how to perform a vacuum filtration.

MIDLAND COLLEGE SYLLABUS DEMR 1323 AUTOMOTIVE HEATING AND AIR CONDITIONING 2-4

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

Certification in the safe and efficient use of alternative refrigerants

Transcription:

TECUMSEH PRODUCTS COMPANY GUIDELINES FOR UTILIZATION OF

GUIDELINES FOR UTILIZATION OF R134a After many years of investigation and testing, HFC134a has emerged as the industry's choice as an alternative refrigerant for CFC12. R134a has an ozone depletion potential (ODP) factor of zero (0.0) and a direct global warming potential (GWP) factor of 0.26. It is not flammable and has acceptable toxicity levels. Unfortunately, R134a is not a "drop-in" replacement for R12. There are significant differences between R12 and R134a, which must be considered when handling, processing, applying or retrofitting with R134a. The following is offered to help understand these differences. I REFRIGERANT PROPERTIES ---------------------------------------------------------------------------------------- A. Pressure/temperature plot of R134a vs. R12 is shown in figure 1. The crossover point is approximately at 64 F. Above this temperature, the saturation pressure of R134a is higher than that of R12; below, it is lower. B. A capacity curve is shown in figure 2 for relative capacity of R134a vs. R12 for evaporating temperatures from 0 F to 50 F. This curve is based on 120 F condensing temperature. The crossover point will move depending on the condensing temperature. The higher the condensing temperature, the higher the crossover point. Figure 1. Pressure vs. Temperature Figure 2. Relative Capacity vs. Evaporator Temperature

C. Figure 3 shows the comparison of some properties of R12, R134a and R22. The data is taken at the standard refrigerant conditions of 5 F evaporating or 86 F condensing. D. For the same amount of subcooling, R134a produces the greater refrigerating effect. E. Water Solubility: Liquid R134a, like R22, can absorb much more water than R12 therefore it would be less likely for a low temperature system to exhibit capillary tube blockage due to ice buildup. However, this does not reduce the need for a dry system. See Section II. B. F. Extensive investigation and testing have been conducted to determine that R134a is compatible with all materials used in Tecumseh Products' hermetic compressors and condensing units. Figure 3 DATA R12 R134a R22 Chemical Formula CCL 2 F 2 CH 2 FCF 3 CHCLF 2 Evaporating Pressure (PSIG) 11.8 9.1 28.2 Condensing Pressure (PSIG) 93.3 97 158.2 Sat. Vapor Density @ 5 F (Lbs./cu. ft.) Sat. Liquid Density @ 86 F (Lbs./cu. ft.) Latent Heat of Vaporization @ 5 F (BTU/Lb.).6859.5128.8042 80.7 74.3 73.3 68.2 89.3 93.2 II LUBRICANTS - POLYOL ESTERS (POE's) -------------------------------------------------------------------------- A. Miscibility 1. Miscibility is the ability of the lubricant and the refrigerant to mix. This miscibility is a very important factor in the returning of the lubricant to the compressor in a refrigeration system over its range of operating temperatures. 2. R134a and mineral oils are not miscible. 3. Polyol ester oils and R134a are miscible. The miscibility of polyol ester (POE) oils and R134a is similar to that of current refrigerant oils and R22. Some types of POE's are fully miscible with R134a (as are synthetic alkylate and R22), while some POE's are partially miscible with R134a (as are mineral oils and R22). B. Moisture 1. Polyol ester oils, while not as hygroscopic (ability to absorb moisture) as earlier considered PAG's (poly alkylene glycols), are 100 times more hygroscopic than mineral oils. This moisture is difficult to remove even with heat and vacuum. 2. Utmost care must be taken to prevent moisture from getting into the refrigeration system. Do not leave the compressor or system open to the atmosphere for longer than 15 minutes maximum. The preferred method of assembly would be to remove system component plugs and caps just prior to brazing. The maximum system moisture content after completing system processing should be 80 PPM. After running the system with the appropriate drier installed, the system moisture level should be 10 PPM or less. 3. Always use an appropriate drier in the system when using R134a. (See section on DRIERS.) C. Compatibility 1. Extensive investigation and testing have been conducted by Tecumseh Products Company to determine that the polyol ester lubricants approved by Tecumseh are compatible with all materials used in Tecumseh hermetic compressors. Contact your Tecumseh sales representative for the latest list of approved oils. (Policy Bulletin No. 105.) 2. All polyol ester oils approved by Tecumseh Products are compatible with each other. 3. While polyol ester oils are compatible with mineral oils, they should not be indiscriminately mixed with mineral oils in R134a refrigerant systems. This practice could result in the inability of the oil to return to the compressor and/or reduce heat transfer performance in the evaporator. However, small amounts, up to 1% of mineral oil are acceptable in field retrofit situations.

III SYSTEM DESIGN ----------------------------------------------------------------------------------------------------------- A. Compressor selection: Tecumseh is continuing to design R134a compressors with the compatibility of oil, refrigerant and materials in mind. These compressors will have the letter "Y" as the refrigerant designator, e.g. AE3440Y. These compressors are designed to closely match the capacity of their corresponding R12 compressors at their individual rating point. In many cases, the same displacement is used, especially in HBP compressors, while in some cases it is necessary to use the next larger displacement. It will be necessary to test each compressor selection in the applications to determine its suitability, since system operating conditions vary greatly from one application to another. B. Capillary tube selection: In general, R134a has a greater refrigerating effect than R12, thus reducing the required mass flow for a given capacity. Consequently, a non-heat exchange capillary tube may require a change, either more restrictive or less restrictive, depending on the actual application. A heat exchange capillary tube may not require any change. As with any capillary tube selection, system testing is necessary. C. Expansion valve selection: The expansion valve manufacturers have designed product specifically for use with R134a. Consult them for their recommendations. D. Driers: Tecumseh requires that an appropriate drier be used on every R134a system. See section on DRIERS. E. Return gas/discharge temperatures: The theoretical discharge temperature for R134a is slightly lower than that of R12 at similar conditions. Therefore existing compressor guidelines regarding return gas and discharge temperatures for R12 should apply to R134a compressors as well. In general, keeping the return gas cool without flooding is beneficial in limiting compressor discharge and motor temperatures to acceptable levels. F. Refrigerant quantity: The refrigerant quantity will depend on the system components. In general, based on limited application data, 5% to 30% less R134a will be needed compared to R12. IV DRIERS ------------------------------------------------------------------------------------------------------------------------ A. The polyol ester oils, which are used with R134a, are prone to hydrolyze with moisture, resulting in the formation of acids. Therefore, Tecumseh requires that an appropriate drier be used in every R134a application. B. The types of driers, which should be used, are the molecular sieve type, which are presently compatible with R22. The XH-6 (bonded core), XH-7 and XH-9 types are recommended. The XH- 6 (loose fill) type is not recommended due to its high attrition rates. C. Solid core driers if made with bauxite would have the tendency to absorb both polyol ester oil and moisture. The ester could hydrolyze and form acidic materials. If the drier were to be overloaded due to excessive moisture in the system, it could release the acidic materials back into the system. Clearly this would not be healthy for the compressor. For this reason, Tecumseh does not recommend the use of solid core driers made with bauxite for systems containing polyol ester oils. D. For specific drier selection, contact your drier supplier. V SYSTEM PROCESSING --------------------------------------------------------------------------------------------------- A. Compatibility 1. R12 has more tolerance to system processing materials, such as drawing compounds, rust inhibitors and cleaning compounds, than R134a. Such materials as these are not soluble in R134a. If they were to be washed from the system surfaces by the polyol ester oils, they could be free to accumulate at the capillary tube or expansion valve and plug it. Care must be taken to remove such processing materials from all the system components. 2. The earlier investigated PAG oils were totally incompatible with chlorinated materials. The current polyol ester oils, however, do not behave the same way. Similar to R12 systems, residual chlorinated materials must be considered as system contamination and eliminated from all internal surfaces of the refrigeration system.

B. Evacuation 1. The evacuation levels for R134a systems should be the same as for R12 systems (minimum of 200 microns at the system and pulled from both the low and high pressure sides of the system). If care is not taken to prevent moisture from entering the system components prior to assembly, evacuation could be expected to take longer to achieve acceptable limits of system moisture and noncondensibles. Tecumseh recommends a maximum of 2% non-condensibles and 80 PPM moisture. The completed system should have a moisture level of 10 PPM or less after running with an appropriate drier installed. 2. Polyol ester oils vaporize much less than mineral oils for the same level of heat and vacuum. Therefore, if oil vaporization was not a problem with the R12 system processing, it should not be a problem with the R134a system processing. 3. Consult your vacuum pump manufacturer to learn if your existing equipment may need to be converted for use on R134a/polyol ester systems. C. Leak Testing 1. Use equipment that is designed for R134a detection or approved for R134a use by its manufacturer. Many leak detector manufacturers have R134a detectors on the market, and more are in development. Consult these manufacturers for their recommendations. 2. CAUTION. DuPont warns not to attempt to use R134a as a mixture with air to pressure test for leaks. Contact DuPont for more information. D. Refrigerant Charging 1. In general, refrigerant charging equipment such as charging boards, valves, and hoses, which are compatible with R22 (considered more aggressive with gaskets and plastics than R12), should be compatible with R134a. This equipment would need to be recalibrated for use with R134a. Once designated for R134a use, it should be used specifically for R134a only. Converted R12 equipment should be clean of all residual R12. Pulling a deep vacuum (25 to 50 microns) and repeated flushing with R134a should be sufficient. Consult your equipment and component manufacturer for specific recommendations for converting R12 equipment for use with R134a. 2. R134a can be charged in either the liquid or vapor state. If refrigerant charging is done in the liquid state, it should be done into the liquid line. Vapor charging can be done into the suction line while the compressor is running. CAUTION: Always break the vacuum with refrigerant vapor before applying power to the compressor. VI RETROFITTING ------------------------------------------------------------------------------------------------------------- The ideal situation regarding the use of R134a 1. Recover the R12 refrigerant and any residual would be that it be limited to new equipment only. mineral oil left in the system using proper In this way, the system components would all be recovery equipment. selected and tested by a system designer with the necessary concerns regarding R134a and polyol 2. Refit the system with the proper capillary ester oils in mind. However, in the real world of tube or expansion valve. today with millions of existing R12 systems in the 3. Install a drier suitable for R134a use and of field, and the supply of R12 rapidly declining as the suitable size for the system being retrofitted. CFC phaseout date approaches, this would not be possible. Therefore we offer some general guidelines to those who must retrofit existing R12 units in the field with R134a. Specific procedures can only be determined after an in-depth evaluation of the existing equipment. Contact the equipment OEM for specific details. A. Replacing an R12 compressor with an R134a ("Y") compressor: Use generally accepted system change out procedures, taking special effort not to leave the system or the R134a compressor open to the atmosphere for more than a few minutes (15 minutes maximum). 4. Install the proper Tecumseh R134a ("Y") compressor containing polyol ester oil. This compressor displays a blue label stating that it uses R134a refrigerant and polyol ester oil. (See Figure 4.) Be sure to use the correct electrical components; they could differ from those used with the R12 compressor. 5. Evacuate the system thoroughly. (Ref. VB.1.) 6. Break the system vacuum with R134a vapor. 7. Charge the system using industry acceptable charging methods with the proper amount of R134a. Generally, the system will use less than that used with R12. 8. Check the system for proper operation.

B. Replacing the R12 in an existing system with R134a: 1. Recover the R12 using proper recovery equipment and procedure. 2. Remove the compressor from the system and drain the original oil from the compressor. 3. Recharge the compressor with the proper amount of a Tecumseh approved polyol ester oil. Consult your authorized Tecumseh Wholesaler or Tecumseh literature for the correct oil charge. (Compare the correct oil charge with the amount drained from compressor to determine if a substantial quantity of oil has been left in the system.) 4. Reinstall the compressor and evacuate the system. 5. Charge the system with R12 using industry acceptable charging methods. 6. Run the system long enough to allow the remaining original oil to mix with the polyol ester oil. 7. Repeat this process (steps B.1 through B.6) of draining and recharging with new polyol ester oil until the amount of original oil remaining in the polyol ester oil is approximately 1% or less. (Typically three change outs will be sufficient.) 8. Recover the R12 from the system using proper recovery equipment and procedures. 9. Remove the compressor from the system and drain the used oil. Recharge with the proper amount of new, dry Tecumseh approved polyol ester oil. 10. Refit the system with the proper capillary tube or expansion valve. 11. Install a drier suitable for R134a use and of suitable size for the system being retrofitted. 12. Evacuate the system thoroughly. (Ref. V.B.1.) 13. Break the vacuum with R134a vapor. 14. Charge the system using industry acceptable charging methods with the proper amount of R134a. Generally the system will use less than that used with R12. 15. Check the system for proper operation. After retrofitting an R12 system with R134a, always identify the system as being charged with R134a and containing a polyol ester oil. Indicate on the unit the amount of R134a used. Figure 4 THIS COMPRESSOR CHARGED WITH POLYOLESTER OIL TECUMSEH PRODUCTS CO. NO. 41440 The transition from the familiar R12 refrigerant to the new unfamiliar R134a refrigerant will present many challenges to our industry. Tecumseh Products Company is working diligently to meet these challenges. For information regarding the new Tecumseh R134a "Y" compressors, contact your Tecumseh sales representative.

Tecumseh Products Company Tecumseh, Michigan 49286