TECHNICAL BULLETIN hydrocarbons
|
|
- Oswald Ford
- 7 years ago
- Views:
Transcription
1 TECHNICAL BULLETIN hydrocarbons
2
3 SUMMARY Introduction: Hydrocarbons 4 I. Properties 4 II. Lubricants 9 III. System Design 10 IV. Safety Aspects 14 V. Retrofitting 17 VI. FAQs (Frequently Asked Questions) 17 VII. References 18 VIII. Glossary 19
4 INTRODUCTION: HYDROCARBONS The use of hydrocarbon (HC) refrigerants R600a (isobutane) and R290 (propane) as substitutes of HCFC s (hydrochlorofluorocarbons) and HFC s (hydrofluorocarbons) continues around the globe. R600a and R290 have ozone depletion potential (ODP) factors of zero (0.0) and a fraction of the global warming potential of those refrigerants they are intended to replace. The process of replacement for CFC (chlorofluorocarbon) in all products worldwide started in 1996 with the Montreal Protocol, initially in developed countries and then extended to other nations. The fluorocarbons like R12 (used as refrigerant) and R11 (used as blowing agent in the foam insulation) have been phased out in most of uses, considering that feasible alternatives like R134a and hydrocarbons are widely available. In 2007 Meeting of Parties (signer countries of the protocol), the Montreal Protocol was updated to adopt control measures also for the HCFC s, establishing reduction targets in quantities for consumption and production until the complete elimination of these refrigerants. This process has already started in several countries, having a successful example in Europe R600a is in use with safety for years in domestic appliances. Hydrocarbons have acceptable toxicity levels; however, they are flammable. Neither of these refrigerants are drop-in replacements for HCFC s or HFC s. There are significant differences between R600a and R290, and the non-hc refrigerants that must be considered in handling, processing and application. Tecumseh cannot control the final use and application of the compressors it sells, nor can Tecumseh guarantee that compliance with agency standards will eliminate all risk of fire. However, we do urge all OEM s to use care in the selection and use of such compressors and to obtain appropriate certifications from recognized testing agencies concerning compliance with all standards. I. PROPERTIES Formula and Composition Refrigerant Formula Chemistry Name Critical Temperature C ( F) Molecular Weight (kg/kmol) Boiling Point C ( F) R12 CCl 2 F 2 Dichlorodifluoromethane 112 (233.6) (-21.6) R134a CF 3 CH 2 F 1,1,1,2-Tetrafluoroethane 101 (213.8) (-15.5) R600a CH(CH 3 ) 3 Isobutane 135 (275) (11.1) R22 CHF 2 CI Chlorodifluoromethane 96 (204.8) (-41.4) R290 CH 3 CH 2 CH 3 Propane 96.8 (206.2) (-43.8) Source: ANSI ASHRAE Standart 34, TECHNICAL BULLETIN - HYDROCABONS
5 With the above characteristics, R290 works as a substitute for R22. As it has a boiling point very close to R22, the propane allows that the evaporator project be similar to the original. Pressure temperature table Temperature Pressure PSIA (kpa Abs.) C ( F) R600a R134a R (-40) 4.1 (28.3) 7.4 (51.2) 16.1 (111.0) (-30) 5.4 (37.4) 9.9 (68.0) 20.3 (140.3) (-20) 7.0 (48.6) 12.9 (88.9) 25.4 (175.1) (-10) 9.0 (62.3) 16.6 (114.7) 31.4 (216.3) (0) 11.5 (79.0) 21.2 (146.0) 38.4 (264.5) (10) 14.3 (98.9) 26.6 (183.6) 46.5 (320.4) -6.7 (20) 17.8 (122.5) 33.1 (228.4) 55.8 (384.8) -1.1 (30) 21.8 (150.3) 40.8 (281.2) 66.5 (458.4) 4.4 (40) 26.5 (182.7) 49.7 (343.0) 78.6 (542.0) 10.0 (50) 31.9 (220.1) 60.1 (414.6) 92.3 (636.4) 15.6 (60) 38.2 (263.1) 72.1 (497.1) (742.5) 21.1 (70) 45.3 (312.1) 85.8 (591.6) (861.0) 26.7 (80) 53.3 (367.6) (699.0) (992.8) 32.2 (90) 62.4 (430.3) (820.6) (1139) 37.8 (100) 72.6 (500.5) (957.3) (1300) 43.3 (110) 83.9 (578.8) 161.1(1111) (1477) 48.9 (120) 96.6 (665.8) (1281) (1672) 54.4 (130) (762.1) (1471) (1884) 60.0 (140) (868.3) (1682) (2116) 65.6 (150) (984.9) (1914) (2369) Source: Data Refprop 6.01 Environment characteristics The ozone layer The ozone layer is located in the stratosphere, with 13 to 20 kilometers of altitude and contains approximately 90% of atmospheric ozone. It is one of the main barriers that protect us from the ultraviolet (UV) radiation, however it is vulnerable from chemical products known as organohalogen compounds that contain fluorine, chlorine and bromine in their composition. 5
6 The chlorofluorocarbons (CFC s) contain the element chlorine, which is the main responsible for depletion of the ozone layer. These highly stable compounds are capable of surviving around 150 years and migrate to the stratosphere completely unmodified, where the ultraviolet rays reach them with great intensity, releasing the chlorine that, consequently, catalyze a chain reaction capable of breaking down the ozone molecules: CFCl 3 + uv CFCl 2 + Cl Cl + O 3 ClO + O 2 ClO + O Cl + O 2 The greenhouse effect and the global warming The presence of gases in the atmosphere (water vapor, CO2, methane, etc) maintains the energy from the sun and keeps the temperature on Earth positive. The greenhouse effect occurs when additional gases (CFCs, HFCs, HCs) besides the existing ones in the atmosphere cause an increase in average global temperature. The scheme of this process is given below: A B D C A: Absorption of radiation emitted by the sun in the atmospheric layers B: Reflection of solar radiation (approximately 30% of absorbed radiation) C: Retention of solar radiation reflected by the gases that cause greenhouse gases (CFC, HFC) D: Solar radiation released to space The cycle formed by the arrows B and C is responsible for raising the temperature in the layers nearer the surface. Two indicators of how the refrigerants behave in relation to aggression to the environment are the ODP (Ozone depleting Potential) and GWP (Global Warming Potential). 6 TECHNICAL BULLETIN - HYDROCABONS
7 As shown in the table below, both the R600a and R290 do not affect the ozone layer (ODP = 0) and, moreover, their GWP values are much lower than R12, R134a and R22. Refrigerant ODP GWP (100 years TH*) R R134a R600a R R *Time Horizon Source: IPCC Comparative between evaporating temperatures (-41.4) (-44.0) (-21.6) (-15.5) (-11.1) R12 R134a R600a R22 R290 REFRIGERANT TEMPERATURE o C ( o F) Toxicity The refrigerants mentioned in this bulletin have similar values of TLV (Threshold Limit Values), which is a value that defines the maximum concentration of toxic gases in the workplace, without affecting those exposed to this environment. This way, the same care that should be taken when handling other fluids must also be taken when handling the R290 or R600a, such as: Work in ventilated rooms; Avoid direct inhalation; Avoid contact with skin; Avoid contact with fire. Flammability The flammability of a fluid is defined by lower and upper explosion limits, LEL (Low Level Explosion) and UEL (Upper Explosion Level) respectively. LEL and UEL represent the minimum and maximum fluid concentration in the air, where it could cause the spread of flame in the presence of an ignition source. Refrigerant LEL (% Volume) UEL (% Volume) Ignition Temperature C ( F) R12, R134a, R22 Non-flammable Non-flammable - R600a (860) R (878) Source: ACRIB 7
8 Due to the fact that the hydrocarbons have low toxicity and are flammable, they are classified as A3 according to ASHRAE Standard 34: INCREASING TOXICITY SAFETY GROUP Higher Flammability A3 B3 Lower Flammability A2 B2 No Flame Propagation A1 B1 Lower Toxicity Higher Toxicity INCREASING TOXICITY Refrigerant Safety Group (ASHRAE) R12 A1 R134a A1 R600a A3 R290 A3 Source: ANSI ASHRAE Standart 34, 2007 The aspects shown above imply the adoption of certain precautions and procedures in the operation and maintenance of products designed for hydrocarbons, which will be shown in following chapters. Compatibility with materials According to the chemical characteristics of each refrigerant, its compatibility with lubricating oils and other components of the refrigeration system, like the filter dryer, must be considered. The hydrocarbons are compatible with all common elastomers and plastic refrigeration materials used as valve seats, seals and gaskets. Materials such as natural rubber, silicone, PP, PVC, PVDF, EPDM and CSM are not suitable for use with the hydrocarbons: Compatible Neoprene (polychloroprene) Viton (fluoropolymer) Nitrile rubber HNBR PTFE (Teflon - Polytetrafluoroethylene) Nylon Incompatible EPDM (Etilenopropilenodieno) Natural rubber Silicone Rubbers Source: ACRIB Tecumseh always recommends consulting the manufacturer or distributor, due to the variety of available components. 8 TECHNICAL BULLETIN - HYDROCABONS
9 Purity The refrigerants must contain a low level of contamination. The presence of impurities can cause: Moisture: acids / saturation filter / capillary blockage; Reduction of cooling capacity; Increasing on energy consumption; Increasing on work pressures (overheating). For hydrocarbons, the specifications of purity are determined according to international standards. Considering the DIN 8960 standard: Criteria Specification Moisture Purity 99,5 % mass Non-condensable gases 1,5 % (vapor phase vol.) Humidity 25 (mg/kg) Remark: The refrigerants R600a (isobutane) and R290 (propane) must be specific for use in refrigerating systems, due to the levels of purity and moisture listed in the table above. II. LUBRICANTS The using of the proper type of lubricant oil in the compressor contributes greatly to its good performance and longer lifetime. The lubricating oil has the following functions: In order to be used in refrigeration compressors, a lubricant must have the following characteristics: Reduce friction in the bearings; Seal the refrigerant in the cylinder during the suction and compression cycles; Cool the motor and pump (transport of heat). Miscibility with the refrigerant; No chemical reaction with the refrigerant; Fluidity at low temperatures; Thermal and electrical stability; Thermal conductor; Electrical insulation. 9
10 The following table shows the compatibility of lubricating oils with refrigerants: Refrigerant Mineral Oil Alkylate Oil Polyol Ester R12 Compatible Compatible Incompatible R134a Incompatible Incompatible Compatible R600a Compatible Compatible Compatible R22 Compatible Compatible Compatible R290 Compatible Compatible Compatible Lubricants containing silicone or silicate are not compatible with hydrocarbons and should not be used. III. SYSTEM DESIGN Compressors designed for application of hydrocarbon refrigerants have some peculiarities that differ from those used with other refrigerants. The characteristics of Tecumseh compressors for these refrigerants are presented below. Displacement COOLING CAPACITY (Btu/h) Min. Displacement R290 Max. Displacement R134a R600a R DISPLACEMENT (cm 3 /s) Test made at LBP ASHRAE 32 The graph beside, built for LBP application, presents the relation between compressor displacement and cooling capacity for different refrigerants. The dashed lines establish the displacement range of the compressors produced by Tecumseh for this application. Considering the same displacement, the R290 performs a cooling capacity approximately 70% higher than the obtained with R134a. On the other hand the R600a demands a displacement approximately 55% higher than R134a, to perform the same cooling capacity. Thus, the choice of R290 and R600a determines a new project with a new compressor displacement and does not allow the activity of retrofitting with R134a compressors 10
11 originally installed on the application. This can be seen in the example below: Characteristic / Refrigerant R134a R600a R290 Model TP1390YS TPJ1350MJS TPA2414UKS Cooling Capacity at 50 Hz Displacement (cc/rev) 7,28 7,28 7,28 Lubricant POE Mineral POE Comparing the R290 with a R22 compressor in the same displacement, we have: Characteristic / Refrigerant R22 R290 Model AE9415ES AE9415US Cooling Capacity at 50 Hz Displacement (cc/rev) 5,67 5,67 Lubricant AB1 Mineral Lubricants Electrical components Hydrocarbons are compatible with both mineral oils used in refrigeration systems for R12 and R22 and with the polyol ester oil used in R134a systems, as mentioned in Chapter II. As mentioned in chapter I of this bulletin, the hydrocarbon is a flammable refrigerant, thus, Tecumseh compressors for R290 and R600a are designed with electrical components that ensure its safe operation and maintenance, since they are free of electric event. Compressor designator Tecumseh offers selected compressors for use with R600a and R290. These compressors have the letter M as the designator for R600a and the letter U as the designator for R290, e.g., TSA1370MGS and THA2395UDS. It will be necessary to test each compressor selection in the applications to determine its suitability, since system operating conditions vary greatly from one application to another. 11
12 Besides the previous label, all Tecumseh compressors for R290 and R600a are identified according to their flammability, as shown at picture 4 below: When modifying or designing a product for the use of hydrocarbons, certain aspects should be carefully studied to obtain a good system performance and maximum reliability. In a product design, the best practice is to follow the specifications of the system manufacturer when modifying one of its components. In the following there are some recommendations for the refrigeration system with hydrocarbons. Evaporators and condensers There is no need to modify the evaporator or condenser when converting a system for the use of hydrocarbons, thus, it is possible to use the same components designed for R12, R22 and R134a that operate at similar pressures, without efficiency loss. Filter-driers Hydrocarbons allow the use of different types of filters when compared with R12, R22 or R134a. The Molecular Sieve desiccant type used with R600a (XH5, XH7, XH9 and MS594) may be fully applied to systems with R290. The table below shows the compatibility of filter driers in refrigeration systems loaded with the following refrigerants. Refrigerants Screen Silica XH5 XH6 XH7 XH9 Universal (MS 594) R22 R134a R600a R290 12
13 Capillary tubes In general, capillary tubes selected for R22 applications should be suitable for systems with the R290, and, likely, capillary tubes selected for R134a applications should be adequate as a preliminary selection for R600a. The use of mineral oil in systems for R600a implies in a lower risk of capillary blockage, when compared to R134a and POE oil. Thus, Tecumseh recommends using capillary tubes similar to those designed for R12, which have similar values of volume flows as to R600a. It is important to emphasize the need to conduct system tests to determine the final selection in a proper way. Refrigerant charge It is possible to establish a correlation of the refrigerant charge between hydrocarbons and CFC s and HCFC s through an analysis between their densities, as shown at picture 5 below. However, Tecumseh recommends performing an empirical analysis when modifying a system originally designed for a specific refrigerant. Reduction R22 R134a 40% R290 Reduction R12 60% R600a Reduction R134a 45% R600a 13
14 Working temperatures and pressures The recommended working temperatures and pressures for systems with hydrocarbons are shown below: Working Temperatures Condensing temperature Suction temperature Compressor discharge temperature Compressor dome temperature Compressor winding temperature C (50-55 F) over the environment temperature 3-5 C (37-41 F) below the environment temperature Lower than or equal to 120 C (248 F) Lower than or equal to 110 C (230 F) Lower than 130 C (266 F) Working Pressures (Application: LBP) Maximum pressures (psig) R134a R22* R600a R290 Equilizing pressure 85 / / /58 128/128 Peak pressure (discharge) Stabilized discharge pressure *Application: HBP Evacuation The evacuation levels for R600a or R290 systems should be the same as for HCFC systems (minimum of 200 microns at the system and pulled from both low and high pressure sides of the system). If care is not taken to prevent moisture from entering the system components prior to assembly, evacuation could be expected to take longer to achieve acceptable limits of system moisture and non-condensables. IV. SAFETY ASPECTS General aspects The main disadvantage in the use of hydrocarbons (R290 and R600a) is the flammability. Due to this characteristic, some safety measures are necessary, both in the refrigerator, as well as the environment of the factory that produces it. Thus, it is important to have knowledge of 14
15 the conditions for the occurrence of an accident, which are: Flammable mixture between air and flammable refrigerant; Source of heat that causes the ignition. The occurrence of the two conditions above must be prevented, so that no accidents occur. According to the TS standard for household refrigerators, all elements of the refrigerator that can emit or generate electric events are considered sources of heat or ignition, since there is no guarantee that the environment around the compressor or the refrigeration system is kept below the lower limit of explosion. Safety aspects of the product System components that are considered sources of leakage: evaporators, condensers, connectors, and the compressor. Products with flammable refrigerants shall be identified with the symbol below. All Tecumseh compressors have a label with this identification: The risk of explosion of a system equipped a flammable refrigerant depends on certain factors that should be analyzed according to the situation and location. Inside a cabinet, the risk depends on the evaporator and is much higher, because it is where the confinement of the refrigerant occurs. Outside the cabinet, the risk is lower because the combined conditions do not imply a saturation of the refrigerant in the environment. All electric switches installed in the product must be insulated. Thermostat, door contacts, internal lights contacts, defrost relay contacts, and others must be considered. Certain methods can be applied to assure the safety of the electrical components: Insulate terminals Locate within IP65 enclosure Replace with solid state type component Replace with Ex type component Locate externally Fans that can be installed inside or outside the refrigerator also must be included in the complement of these safety guidelines. They should not produce arcs, even when short circuit or blocked. Tecumseh compressors are equipped with sealed starting relays and thermal overload protectors, preventing the production of electric events that can cause the ignition of the flammable mixture. 15
16 The dimensional design of the product must take into consideration the separation of the environment of a possible ignition source (switches) and where the refrigerant leakage may occur. For instance, the evaporator must not be placed in the same environment that a electric event may occur. The replacement of any such equipment must be done by others with the same characteristics, assuring the safety and preventing the risk of explosion. Any device with flammable gases must be tested and approved in accordance with the procedures of the TS / IEC / EN by an independent body. Consult standards for details. Safety aspects in the manufacturing process In the manufacturing process, a safety system regarding the storage and handling of flammable refrigerants, containing authorities approval and compliance with legislation, must be adopted. This system must include: Adequate and secure facilities for storage of cylinders; Special fans (no arcs in the engines) to prevent the storage of gases; Control of areas with risk of leakages in pipes through detectors or sensors; Chargers designed for flammable refrigerants. Suppliers of chargers, detectors and the refrigerant itself can offer security systems projects In addition, controls and procedures must be followed as below: Leakage testing with equipment able to detect refrigerants R290 and/or R600a. If not available, Helium or Nitrogen can be used; Proper sealing of the system by cold welding or ultrasound, which does not require brazing with torch; Electronic leakage detectors must be calibrated (greater sensitivity = less than 0.5 g / year) for use with flammable gases and certificates; Trained team to handle the flammable gases. Maximum refrigerant charge According to international safety standards, the maximum refrigerant charge must be less than or equal to 150 g. This can be complied by keeping a maximum of 25% of the minimum explosion (LEL), which is approximately 8 g/m³ for the dimensions of a standard kitchen. To ensure the maximum efficiency in the leakage controls, it is recommended to use a detector specifically designed for use with the R290, or alternatively, a detector designed for use with Helium. 16
17 Accident situations Eye injuries At burns use cold water immediately. At frostbite use warm water. Lift the eyelid careful and rinse for at least 20 min. with copious amounts of water. Do not rub the eyes. Remove contact lenses, if present. Loose fitting, amicrobic dressing. Then take the injured person immediately to an eye specialist or accident hospital. Skin contact At frostbite warm up person by body heat. Do not rub. Do not open blisters from burns. Cover wounds aseptic. Take the injured person to a doctor or accident hospital as quickly as possible. Injuries from swallowing liquid refrigerant Give the injured person, as long as he or she is conscious, as much water or other warm drink as possible. V. RETROFITTING Since special safety considerations must be applied in the design of equipment using hydrocarbon refrigerants, such as R600a and R290, Tecumseh does not approve of, endorse, nor recommend retrofitting existing systems with R600a and R290. VI. FAQs (FREQUENTLY ASKED QUESTIONS) Can R134a systems be adapted to hydrocarbons such as R600a and R290 without any modification? No, Tecumseh does not recommend this practice. What should I do to detect leakages in the system? Tecumseh recommends the use of appropriate equipment able to detect refrigerants R290 and/or R600a or electronic leakage detectors. Are hydrocarbons flammable? Yes, hydrocarbons are flammable refrigerants. Can I use the torch to make repairs on the system that uses hydrocarbon refrigerant? Yes, repairs can be performed like for any conventional cooling system, but it is needed to ensure that the vacuum system is free of refrigerant. 17
18 If a leakage occurs inside a residence, is there a risk of explosion? The risk is almost zero due to the small quantity of hydrocarbon refrigerant used in domestic refrigerators (40 to 120g). How do I perform a refrigerant charge? After performing the evacuation in the system, charge the refrigerator according to the specified by the manufacturer, respecting the safety procedures. Tecumseh recommends the use of a precise balance to perform the charging, since small variations in the quantity can affect the performance of the system. Can I charge any quantity of hydrocarbons in the system? No, the maximum refrigerant charge for hydrocarbons is 150g. VII. REFERENCES ACRIB -. Guidelines for the use of Hydrocarbon Refrigerants in Static Refrigeration and Air Conditioning Systems Air Conditioning and Refrigeration Industry Board First Published February ANSI/ASHRAE Standard Designation and Safety Classification of Refrigerants - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. BS EN :2001. Title Identifier Specification for safety of household and similar electrical appliances. Particular requirements for refrigerating appliances, ice-cream appliances and ice-makers. DIN 8960:1998: Requirements and coding system for refrigerants. Little Inc., A.D. Global comparative analysis of HFC and alternative technologies for refrigeration, air conditioning, foam, solvent, aerosol propellant, and fire protection applications, report for The Alliance for Responsible Atmospheric Policy, Cambridge, MA, Reference 75966, Handbook for the Montreal Protocol on Substances that Depletethe Ozone Layer - Eighth edition (2009). Ozone Secretariat United Nations Environment Programme (UNEP). IEC/TRF ( ), Ed. 2.0, English. This Test Report Form applies to IEC :2002 (Sixth edition) used in conjunction with IEC :2001 (Fourth edition). IPCC Fourth Assessment Report: Climate Change 2007 (AR4). Working Group I Report. The Physical Science Basis, chapter II. Jazwin, Richard. Alternative refrigerants, Business News Publishing Company, USA, Wikipedia the free encyclopedia. 18
19 VIII. GLOSSARY Boiling Point: the temperature and pressure at which a liquid changes states to a gas. CFC: chlorofluorocarbon. Condenser: the component in the refrigeration system where the refrigerant releases heat and changes from vapor to a liquid. Critical Temperature: The highest temperature a gas can reach and still be able to be condensed by applying pressure. Evaporator: The component in the refrigeration system that absorbs heat, thereby allowing liquid refrigerant to change to vapor. Flammability: defined as how easily something will burn or ignite, causing fire or combustion. The degree of difficulty required to cause the combustion of a substance is quantified through fire testing. Global Warming Potential (GWP): measure of how much a given mass of greenhouse gas is estimated to contribute to global warming. HC: hydrocarbon; a compound containing only the elements hydrogen and carbon. HCFC: hydrochlorofluorocarbons. HFC: hydrofluorocarbons. Lower flammability limit (LFL): the minimum concentration of a substance, a refrigerant in this standard, that is capable of propagating a flame through a homogeneous mixture of the substance and air under specified test conditions. Montreal Protocol: an international treaty designed to protect the ozone layer by phasing out the production of a number of substances believed to be responsible for ozone depletion. Ozone depletion potential (ODP): the relative amount of degradation to the ozone layer a chemical compound can cause, with trichlorofluoromethane (R-11 or CFC-11) being fixed at an ODP of 1.0. Chlorodifluoromethane (R-22), for example, has an ODP of CFC or R11 has the maximum potential amongst chlorocarbons because of the presence of three chlorine atoms in the molecule. Refrigerant: the fluid used for heat transfer in a refrigerating system; the refrigerant absorbs heat and transfers it at a higher temperature and a higher pressure, usually with a phase change. Retrofitting: procedure of converting a system originally design and built to operate with a certain refrigerant to operate with another refrigerant.
20 Informações sujeitas a alterações sem prévio aviso. Nos reservamos el derecho de introducir cambio en las informaciones sin-aviso previo. All information is subject to change without previous notice. Consulte para atualizações on-line. / Consulte para actualizaciones on-line. / Visit for online updates. TECUMSEH DO BRASIL LTDA. Rua Ray Wesley Herrick 700 Jd. Jockey Club São Carlos - SP, Brasil PHONE: FAX: marketing@tecumseh.com.br BIT /10
R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C
GUIDELINES FOR UTILIZATION OF R407C 2009 Tecumseh Products Company. All rights reserved. Page 1 of 6 After many years of testing and investigation, R407C is recognized as a suitable alternative refrigerant
More informationSERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as
More informationRS-24 (R426A): Q & A
RS-24 (R426A): Q & A 1 Q: What is RS-24? A: RS-24 is a non ozone depleting Drop-in replacement for R12 in all applications including mobile air conditioning. 2 Q: Yes, but what does RS-24 contain? A: RS-24
More informationRS-44 (R424A) : Q & A
RS-44 (R424A) : Q & A 1 Q: What is RS-44? A: RS-44 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-44 contain? A: RS-44 is a blend of HFC134a, HFC125,
More informationPart A: Fluid properties
UNEP Ozone Secretariat UNEP Ozone Secretariat Background Workshop Material on HFC for management: HFC Workshop, technical 2015 issues Bangkok, 20 and 21 April 2015 FACT SHEET 15 Glossary of terms and technical
More informationRS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm)
RS-52 (R428A) COMPOSITION % HFC 125 77.5 HFC 143a 20.0 R600a 1.9 R290 0.6 HCFC replacement Temperature glide R22, 502 & interim blends Approximately 0.8 o C Drop-in or long term Both Lubricant MO/AB/POE
More informationTECHNICAL INFORMATION
1- INTRODUCTION The destruction of the ozone layer by the chlorofluorcarbons (CFC s), among which are CFC 11, CFC 12, and CFC 13 and its vital effect on the earth's ecosystem, were the principal reasons
More informationREFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016. Information compiled by Frank Prah, CMS
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 REFRIGERANT 410A Information compiled by Frank Prah, CMS INTRODUCTION Recently a new refrigerant, R-410A, has been formulated
More informationRefrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
More informationHFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY
HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY The impact of refrigeration
More informationEnvironmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT
More informationTHE REPLACEMENT OF R-22
ENGLISH TRANSLATION OF ARTICLE IN FRIO-CALOR AIRE ACONDICIONDAO BY GAS-SERVEI, S.A JUNE 2010 THE REPLACEMENT OF R-22 Courtesy of D. Lluis Giralt Lopez (Chemical Engineering Industrial) Gas Technical Department
More informationRefrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
More informationMohan Chandrasekharan #1
International Journal of Students Research in Technology & Management Exergy Analysis of Vapor Compression Refrigeration System Using R12 and R134a as Refrigerants Mohan Chandrasekharan #1 # Department
More informationProduction of R-134a
Production of R-134a Background In the 1930 s, chlorofluorocarbons (CFC s) were developed as a supposedly safe alternative to ammonia and sulfur dioxide refrigerants. While sulfur dioxide is toxic and
More informationCOMPRESSOR REPLACEMENT PROCEDURE
R-22 and R-410A COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003F Supersedes 2100-003E File: Volume I,
More informationR-32. The next generation refrigerant for air conditioners and heat pumps
R-32 The next generation refrigerant for air conditioners and heat pumps Daikin is the first company in the world to launch heat pumps and air conditioners charged with R-32. This refrigerant has several
More informationPerformance of R-438A in R-22 Refrigeration and Air Conditioning Systems
Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems Dr. Charles C. Allgood 1, C. Curtis Lawson 2 1 DuPont Fluorochemicals, Wilmington, DE, USA E-mail: Charles.C.Allgood-1@usa.dupont.com
More informationEvaluation of HFO-1234yf as a Potential Replacement for R-134a in Refrigeration Applications
Evaluation of HFO-1234yf as a Potential Replacement for R-134a in Refrigeration Applications Thomas J. Leck DuPont Fluorochemicals Wilmington, Delaware 3rd IIR Conference on Thermophysical Properties and
More informationPractical Application of Refrigerant R600a Isobutane in Domestic Refrigerator Systems
COMPRESSORS Technical information Practical Application of Refrigerant R600a Isobutane in Domestic Refrigerator Systems REFRIGERATION AND AIR CONDITIONING Refrigerant R 600a, or isobutane, is a possible
More informationRecommended Compressor Installation Practices
ASPEN COMPRESSOR, LLC Phone: 508.481.5058 Fax: 508.480.0328 Email:info@aspencompressor.com Website: www.aspencompressor.com Recommended Compressor Installation Practices 1. COMPRESSOR SELECTION AND USE
More informationEngineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume 40 2. Refrigerant History
providing insights for today s hvac system designer Engineers Newsletter volume 40 2 HVAC Refrigerants: A Balanced Approach One of the constant themes throughout the history of the HVAC industry is the
More informationRefrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507 Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale changeover of HCFCs
More informationHistory of Chlorofluorocarbons
History of Chlorofluorocarbons 1928 : Chlorofluorocarbons () were invented. were developed as ideal gases used as refrigerants for refrigerators. Because of their special characteristics, inflammability
More informationCommercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:
PART 1: CO 2 Commercial refrigeration has been in the environmental spotlight for more than a decade, especially as leakage studies have revealed the true effects of hydrofluorocarbon (HFC) emissions.
More informationAutomobile Air Conditioning Primer
Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the
More informationThe phase out of R22. Phase out of HCFCs
The phase out of R22 The Montreal Protocol on Substances that Deplete the Ozone Layer is widely regarded as the world s most successful environment protection agreement. It is the only treaty with universal
More informationTechnical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity
Technical Note: Comparing R407C and R410A as Alternatives for R22 A Technical Note from the Experts in Business-Critical Continuity Purpose The purpose of this document is to provide a brief overview of
More informationTHE POSSIBILITY OF USING LIQUIFIED PETROLEUM GAS IN DOMESTIC REFRIGERATION SYSTEMS
www.arpapress.com/volumes/vol9issue3/ijrras_9_3_02.pdf THE POSSIBILITY OF USING LIQUIFIED PETROLEUM GAS IN DOMESTIC REFRIGERATION SYSTEMS Zainal Zakaria 1 & Zulaikha Shahrum 2 Department of Gas Engineering,
More informationRepair, Retrofit, or Replace Choices for Servicing R-22 Equipment
Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment Brett Van Horn Market Manager HVAC Arkema Inc. 900 First Ave King of Prussia, PA 19406 Topics Covered Today R-22 Phase-out EPA Allowances
More informationTHEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A
THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A Jignesh K. Vaghela Assistant Professor, Mechanical Engineering Department, SVMIT, Bharuch-392001, (India) ABSTRACT
More informationRusty Walker, Corporate Trainer Hill PHOENIX
Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat
More informationRefrigerants for Residential and Commercial Air Conditioning Applications
Refrigerants for Residential and Commercial Air Conditioning Applications October 2008 Table of contents Executive summary 2 Introduction and background 3 Environmental drivers 4 Regulatory update 8 Criteria
More informationElements Elements describe the essential outcomes.
AURETU005 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. Retrofit and modify air conditioning and HVAC systems This unit describes the performance outcomes
More informationRefrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-502 to R-402A/R-408A Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale CFC changeover of CFC HCFC
More informationINSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
More informationMATERIAL SAFETY DATA SHEET. PRODUCT IDENTIFIER Carbon Dioxide, Refrigerated Liquid
SECTION I- Product Information* MANUFACTURER: EPCO Carbon Dioxide Products, Inc. OFFICE PHONE: 1-800-259-3726 24-HOUR EMERGENCY: 1-800-259-8095 SHIPPING NAME: Carbon Dioxide, Refrigerated Liquid UN NUMBER:
More informationA car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine
A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine G Vicatos J Gryzagoridis S Wang Department of Mechanical Engineering,
More informationPatech. Our Conviction. Quality Service Innovation PATECH FINE CHEMICALS CO., LTD
Our Conviction Quality Service Innovation Product Categories Refrigeration Lubricants POE for HFC Refrigerants POE for HCFC Refrigerants POE for HFO Refrigerants Special Plasticizers Nontoxic Plasticizer
More informationMaterial Safety Data Sheet
1 IDENTIFICATION OF THE SUBSTANCE AND COMPANY a) SUBSTANCE: Natural Gas b) COMPANY: Bord Gáis Éireann PO Box 51 Gasworks Road Cork Telephone: (021) 453 4000 Emergency Telephone: 1850 20 50 50 2 COMPOSITION/INFORMATION
More informationCOMBUSTION. In order to operate a heat engine we need a hot source together with a cold sink
COMBUSTION In order to operate a heat engine we need a hot source together with a cold sink Occasionally these occur together in nature eg:- geothermal sites or solar powered engines, but usually the heat
More informationHCFC phase-out has started.
HCFC phase-out has started. 02 HCFC phase-out has started. HCFC phase-out has started. Are you prepared? Global phase-out of HCFCs is already underway. This will impact the availability and pricing of
More informationVariable Capacity Compressors, a new dimension for refrigeration engineers to explore
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents
More informationSubject: 2005 Air Conditioning Service Guidelines
Date: June 27, 2005 Bulletin Number: 05D-J-114 To: DDG Headquarters and Branches and Jobbers Category: Service From: Steve Sigg, Product Service and Training Line(s): 10 and 15 Subject: 2005 Air Conditioning
More informationPERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A
Int. J. Mech. Eng. & Rob. Res. 213 Jyoti Soni and R C Gupta, 213 Research Paper ISSN 2278 149 www.ijmerr.com Vol. 2, No. 1, January 213 213 IJMERR. All Rights Reserved PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION
More informationSERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)
Form #SB4-304AS AirSourceR SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION) Second only to refrigerant hose leaks, compressors have the highest rate
More informationCertification in the safe and efficient use of alternative refrigerants
Certification in the safe and efficient use of alternative refrigerants Dubai, 29th Oct 2014 Marco Buoni VicePresident, AREA Air Conditioning & Refrigeration European contractors Association (www.area-eur.be)
More informationMATERIAL SAFETY DATA SHEET Product Code: 10033
MATERIAL SAFETY DATA SHEET Product Code: 10033 Product Description: Signal Horn & Refilling Canister in Blister Pack 1. IDENTIFICATION OF THE PRODUCT AND OF THE COMPANY: Product Name: Signal Horn & Refilling
More informationIt s Your Choice Retrofitting Your Car s A/C System 1EPA. 2 Printed on paper that contains at least 20 percent postconsumer fiber.
United States EPA430-F-97-052 Environmental Protection June 1997 Agency 1EPA Air and Radiation (6205J) It s Your Choice Retrofitting Your Car s A/C System 2 Printed on paper that contains at least 20 percent
More informationDuPont ISCEON MO89 refrigerant
This SDS adheres to the standards and regulatory requirements of Great Britain and may not meet the regulatory requirements in other countries. 1. IDENTIFICATION OF THE SUBSTANCE/PREPARATION AND OF THE
More informationHeating and air-conditioning industry
Heating and air-conditioning industry Innovative solutions for your success Dear Readers, We all prefer a nice warm room. As manufacturers of heating and air-conditioning systems, you know just how important
More informationEPA 608 Certification. Study Guide. 1 P a g e
EPA 608 Certification Study Guide 1 P a g e Foreword All HVACR technicians must become certified for the equipment they work on, under the Environmental Protection Agency s (EPA), refrigerant recovery
More informationMATERIAL SAFETY DATA SHEET
MATERIAL SAFETY DATA SHEET PRODUCT IDENTIFIER: DRY ICE I PRODUCT INFORMATION SHIPPING NAME: Dry Ice CHEMICAL NAME: Carbon Dioxide, UN #: 1845 CAS NO.: 124-38-91 Solid MOLECULAR WEIGHT: 44.01 CHEMICAL FAMILY;
More informationA Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential
International Journal of Scientific and Research Publications, Volume 2, Issue 9, September 2012 1 A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of
More informationREFRIGERANT REFERENCE GUIDE
REFRIGERANT REFERENCE GUIDE WORLWIDE REFRIGERANT SUPPLIER 2004 FOURTH EDITION 2004 DISCLAIMER This publication is designed to provide accurate and authoritative information. It is not to be construed as
More informationADVANCING FLAMMABLE REFRIGERANT ADOPTION IN NORTH AMERICA
NEW SCIENCE SUSTAINABLE ENERGY ARTICLE ADVANCING FLAMMABLE REFRIGERANT ADOPTION IN NORTH AMERICA SUMMER 2013 UL.COM/NEWSCIENCE NEW SCIENCE SUSTAINABLE ENERGY OVERVIEW Rising costs, energy efficiency and
More informationDESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
More informationPG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.
International Journal of Emerging Trends in Engineering and Development Issue 3, Vol. (January 23) EFFECT OF SUB COOLING AND SUPERHEATING ON VAPOUR COMPRESSION REFRIGERATION SYSTEMS USING 22 ALTERNATIVE
More informationFujitsu General New Zealand Ltd
Fujitsu General New Zealand Ltd Ozone layer protection Global warming prevention HCFC (R22) Ozone depletion potential : 0.055 Global warming potential : 1,810 1987 Montreal Protocol adoption Complete abolishment
More information: DuPont SUVA 134aUV Leakdetect
This SDS adheres to the standards and regulatory requirements of Great Britain and may not meet the regulatory requirements in other countries. 1. IDENTIFICATION OF THE SUBSTANCE/PREPARATION AND OF THE
More informationGuide to good leak testing
Page 0 Guide to good leak testing The Institute of Refrigeration, working with the Carbon Trust, brings you REAL Zero Refrigerant Emission and Loss Zero. The aim of this project is in the title zero refrigerant
More informationChapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service
BP Lower 48 Onshore Operations Safety Manual Page 4.19 1 Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service I. General Requirements A. After motor vehicle accidents and underground excavation
More informationPerformance of R-438A in R-22 Refrigeration and Air Conditioning Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 21 Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems
More informationrefrigerants DuPont Suva 134a (HFC-134a) for Mobile Air Conditioning Technical Information Introduction Transition to HFC-134a
Technical Information DuPont Suva refrigerants Note: This publication supersedes Bulletin ART-12. ART-27 DuPont Suva 134a (HFC-134a) for Mobile Air Conditioning Introduction In the past almost all mobile
More informationRefrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)
More informationHeating and Cooling Technology and Global Solutions for Food Distribution:
Heating and Cooling Technology and Global Solutions for Food Distribution: Current Status and Future Outlook Current Status and Future Outlook SUGIMOTO, Koji 1. Introduction Food distribution needs are
More information(Adopted July 7, 1989)(Amended December 7, 1990) (Amended May 13, 1994) FUGITIVE EMISSIONS OF VOLATILE ORGANIC COMPOUNDS
(Adopted July 7, 1989)(Amended December 7, 1990) (Amended May 13, 1994) RULE 1173. FUGITIVE EMISSIONS OF VOLATILE ORGANIC COMPOUNDS (a) (b) Purpose This rule is intended to control volatile organic compounds
More informationCertain specific properties of compressed gases make them highly useful in various research activities.
GAS CYLINDER SAFETY Introduction Certain specific properties of compressed gases make them highly useful in various research activities. These gases, however, can be dangerous if not handled in an appropriate
More informationTECHNICAL SPECIFICATION. StirLIN-1 Economy Liquid Nitrogen System
TECHNICAL SPECIFICATION StirLIN-1 Economy Liquid Nitrogen System Reference 80 8120_01 Issue Date August 1, 2015 1. INTRODUCTION Since more than sixty years Stirling Cryogenics has designed and manufactured
More informationDuPont SUVA 123 Refrigerant
This SDS adheres to the standards and regulatory requirements of Great Britain and may not meet the regulatory requirements in other countries. 1. IDENTIFICATION OF THE SUBSTANCE/PREPARATION AND OF THE
More informationUSER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102
USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE
More informationContinuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors
Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors www.static-control.in 1 Introduction The detection or monitoring of flue gases and or hazardous gases has been a complex subject
More informationGlossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
More informationLow GWP Replacements for R404A in Commercial Refrigeration Applications
Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, Samuel.YanaMotta@honeywell.com Abstract
More informationElements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system
AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and
More informationNews in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
More informationR-32. The next generation refrigerant for air conditioners and heat pumps. Superior energy efficiency and low GWP
R-32 The next generation refrigerant for air conditioners and heat pumps Superior energy efficiency and low GWP HFC phase-down and the introduction of R32 The European phase-down of HFCs, which will see
More informationFederal Clean Air Act Section 609 Training Manual & Exam
Federal Clean Air Act Section 609 Training Manual & Exam Table of Contents INTRODUCTION... Who Must Be Certified... Training and Certification... Test Format... Test Administration and Grading... i STRATOSPERIC
More informationEstimation Method For Thermal Stability Of Refrigeration Oil And Automatic Sealed Glass Tube Processing Device
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 Estimation Method For Thermal Stability Of Refrigeration Oil And Automatic
More informationTEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged
More informationSubstitute Aerosol Solvents and Propellants Under SNAP as of August 10, 2012 SNAP Information: http://www.epa.gov/ozone/snap
United States Environmental Protection Agency Air and Radiation Stratospheric Protection Division 6205J Aerosol Solvents and Propellants Under SNAP as of August 10, 2012 SNAP Information: http://www.epa.gov/ozone/snap
More informationThe EC Ozone Regulation. Legislative Update and Strategies for HCFC Phase-out
Information Sheet RAC 8 R22 Phase-out The EC Ozone Regulation Legislative Update and Strategies for HCFC Phase-out 1. Background to HCFC Phase Out The EC Ozone Regulation (EC/2037/2000) provides the legislative
More informationAP ENVIRONMENTAL SCIENCE 2013 SCORING GUIDELINES
AP ENVIRONMENTAL SCIENCE 2013 SCORING GUIDELINES Question 3 (a) Identify the type of solar radiation that is absorbed by stratospheric ozone and describe one human health benefit that results from the
More informationAlarm and Detection/Suppression
Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent
More informationSYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING. Effective From :- UNDER DEVELOPMENT.
SYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING Effective From :- UNDER DEVELOPMENT Prepared by: Curriculum development cell Institute of Research Development
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationPlanning for the ban on R22 in building air conditioning
- ACHPI 32 Planning for the ban on R22 in building air conditioning Those responsible for cooling and heating commercial properties are under increased pressure to improve energy efficiency and negotiate
More informationChapter 7: Greenhouse gases and particulate matter
Additional material for Fundamentals of Sustainable Development, Niko Roorda, 2012. Chapter 7: Greenhouse gases and particulate matter Debates on the anthropogenic greenhouse effect and climate change
More informationMATERIAL SAFETY DATA SHEET
DOT ID No: UN 2187 MATERIAL SAFETY DATA SHEET DOT Hazard Class: 2.2 Emergency No.: +971-6-5336481 Page No. : 1/5 DOT Shipping Label : Non Flammable Gas Date last updated: 22/09/2009 Revision no: 00 1.
More informationDissolved Gas Analysis Guide for Transformers Filled with Beta Fluid
DSI Ventures, Inc. PHONE: (903) 526-7577 FAX: (903) 526-0021 www.dsiventures.com Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid Introduction Analysis of dissolved gases in transformer
More informationEngineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
More informationMATERIAL SAFETY DATA SHEET
MATERIAL SAFETY DATA SHEET 1. PRODUCT AND SUPPLIER IDENTIFICATION Chinese name: PingBanJiaoYinYouMo Trade name: Bauhinia Variegata F1932A English name: Offset Printing Ink -Pantone colors Company name:
More informationA/C refrigerant system, overview
Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -
More informationCOMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
More informationMATERIAL SAFETY DATA SHEET
MATERIAL SAFETY DATA SHEET SECTION 1 : PRODUCT AND COMPANY IDENTIFICATION 1.1.Product Details Product Name: Ferrofluid Name: APG 2100 series Chemical Name: Proprietary product Chemical Formula: Mixture
More informationSpecifications for Refrigerants
AHRI Standard 700 2015 Standard for Specifications for Refrigerants IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components
More informationQuebec Quebec Tel : 418-834-7447 Fax : 418-834-3774 MSDS: P10 (10% Methane in Argon) PRODUCT INFORMATION
Tel: 514-956-7503 Fax: 514-956-7504 Internet: www.megs.ca Email : support@megs.ca Montreal Ottawa St-Laurent Nepean Tel : 514-956-7503 Tel : 613-226-4228 Fax : 514-956-7504 Fax : 613-226-4229 Quebec Quebec
More informationHazardous Substance Class Definitions & Labels
Hazardous Substance Class Definitions & Labels In the IMDG Code, substances are divided into 9 classes. A substance with multiple hazards has one 'Primary Class' and one or more 'Subsidiary Risks'. Some
More informationName: Class: Date: 10. Some substances, when exposed to visible light, absorb more energy as heat than other substances absorb.
Name: Class: Date: ID: A PS Chapter 13 Review Modified True/False Indicate whether the statement is true or false. If false, change the identified word or phrase to make the statement true. 1. In all cooling
More informationNew Trends in the Field of Automobile Air Conditioning
New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic
More information