Overview The most powerful CPU Can be used in the most sophisticated installations in the upper performance range With two slots for IF modules Technical specifications Product status Firmware version V 4.0 associated programming package Supply voltages Rated value DC 24 V Voltages and currents Feeding of external buffer voltage to CPU Current consumption from backplane bus DC V, Power loss, typ. Backup battery 6ES7 417-4XL04- STEP 7 V.2 SP1 or higher HF3 with HW-update to 1 V DC 1.7 A 6 W Buffer current, typ. 600 µa Buffer current, 1,810 µa Memory Memory RAM - integrated (for program) 10 MByte - integrated (for data) 10 MByte - expandable Load memory - expandable FEPROM ; with Memory card (FLASH) - expandable FEPROM, 64 MByte - integrated RAM, 26 KByte - expandable RAM ; with Memory Card (RAM) - expandable RAM, 16 MByte Backup present with battery without battery ; all data CPU/blocks DB Number, Size, FB 6ES7 417-4XL04-8,192; DB 0 reserved Number, 6,144 Size, FC Number, 6,144 Size, OB Size, Nesting depth per priority class 24 additional within an error OB 2 CPU/processing times for bit operations, min. 0.03 µs for word operations, min. 0.03 µs for fixed point arithmetic, min. 0.03 µs for floating point arithmetic, min. 0.09 µs Times/counters and their remanence S7 counter Number 2,048 Remanence - adjustable - lower limit 0 - upper limit 2,047 - preset From Z 0 to Z 7 Counting range - lower limit 0 - upper limit 999 /30 Siemens ST 70 2007
Technical specifications (continued) IEC counter present Type S7 times 6ES7 417-4XL04- SFB Number 2,048 Remanence - adjustable - lower limit 0 - upper limit 2,047 - preset no timers retentive Time range - lower limit 10 ms - upper limit 9,990 s IEC timer present Type Data areas and their remanence remanent data area, total Flag Number, SFB total working and load memory (with backup battery) Remanence available ; MB 0 to MB 16383 Number of clock memories Address area I/O address area Inputs Outputs 8; 1 memory byte of which, distributed - MPI/DPinterface, inputs 2 KByte - MPI/DP interface, outputs 2 KByte - DP interface, inputs 8 KByte; (For each line that is operated in isochronous mode, i.e. to which an OB 61 to 64 has been assigned, the distributed IO address areas are halved) - DP interface, outputs 8 KByte; (For each line that is operated in isochronous mode, i.e. to which an OB 61 to 64 has been assigned, the distributed IO address areas are halved) Process image Inputs, adjustable Outputs, adjustable Inputs, preset Outputs, preset consistent data, Access to consistent data in process image 1,024 Byte 1,024 Byte 244 Byte Subprocess images Number of subprocess images, Digital channels 6ES7 417-4XL04-1 Inputs 131.072 Outputs 131.072 Inputs, of which central 131.072 Outputs, of which central 131.072 Analog channels Inputs 8.192 Outputs 8.192 Inputs, of which central 8.192 Outputs, of which central 8.192 Hardware config. connectable OPs Central devices, 1 Expansion devices, 63 without message processing, 16 with message processing 21; (of which 6 ER with K-bus) Multicomputing ; 4 CPUs (with UR1 or UR2) IM Number of connectable IMs (total), Number of connectable IM 460s, Number of connectable IM 463s, Number of DP masters integrated 2 via IM 467 4 6 6 4; IM 463-2 via CP 10; via CP 443- Ext. Mixed mode IM + CP permitted via interface module Number of pluggable S modules (via adapter capsule in central device), Number of operable FMs and CPs (recommended) PROFIBUS and Ethernet CPs Time Clock Hardware clock (real-time clock) Battery backed and synchronized Resolution ; IM 467 cannot be used with CP 443- Ext. ; IM 467 cannot be used with CP 443-1 EX40 in PN IO mode 2; IF 964-DP 6 14; incl. CP 443- Ext. and IM 467 1 ms Siemens ST 70 2007 /31
Technical specifications (continued) Operating hours counter Number 8 Clock synchronization supports to MPI, Master to MPI, Slave to DP, Master to DP, Slave in AS, Master in AS, Slave to IF 964 DP S7 message functions Number of login stations for message functions, Symbol-related messages Number of messages 6ES7 417-4XL04- ; as Master or Slave 16 overall, 1,024 Block related messages Alarm 8-blocks Instrumentation & control messages Test commissioning functions Status/control Status/control variable Monitoring functions Forcing Forcing Status block Single step Number of breakpoints 4 Diagnostic buffer present Number of entries, 3,200 adjustable preset 120 Communication functions PG/OP communication Routing Global data communication Size of GD packets, S7 basic communication Useful data per job, 64 Byte ; in MPI mode: via SFC X_SEND, X_RCV, X_GET and X_PUT; in DP master mode: via SFC I_GET and I_PUT 76 Byte S7 communication as server as client Useful data per job, S-compatible communication Useful data per job, Standard communication (FMS) Number of 6ES7 417-4XL04- overall 64 1st interface Physics isolated Functionality MPI DP master DP slave MPI ; via FC AG_SEND and AG_RECV, via 10 CP 443-1 or 443-8 KByte ; via CP and loadable FB RS 48 / PROFIBUS Number of 44 - PG/OP communication - Routing - Global data communication - S7 basic communication - S7 communication Transmission speeds, DP master Number of, - PG/OP communication - Routing - S7 basic communication - S7 communication - equidistance support - Activation/deactivation of DP slaves - direct data exchange (cross traffic) Transmission speeds, Number of DP slaves, 32 32; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1 Address area - Inputs, 2 KByte - Outputs, 2 KByte /32 Siemens ST 70 2007
Technical specifications (continued) Useful data per DP slave - Inputs, 244 Byte - Outputs, 244 Byte DP slave - Routing - Status/control - Programming Transmission speeds, 6ES7 417-4XL04- Transfer memory - Inputs 244 Byte - Outputs 244 Byte Address area, 32 Useful data per address area, Useful data per address area, of which consistent, 2nd interface Physics isolated Functionality DP master DP slave DP master Number of, 32 Byte 32 Byte RS 48 / PROFIBUS - PG/OP communication - Routing - S7 basic communication - S7 communication - equidistance support - Activation/deactivation of DP slaves - direct data exchange (cross traffic) Transmission speeds, Number of DP slaves, 12 32; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1 Address area - Inputs, 8 KByte - Outputs, 8 KByte Useful data per DP slave - Inputs, 244 Byte - Outputs, 244 Byte DP slave - Routing - Status/control - Programming Transmission speeds, 6ES7 417-4XL04- Transfer memory - Inputs 244 Byte - Outputs 244 Byte Address area, 32 Useful data per address area, Useful data per address area, of which consistent, 3rd interface 32 Byte 32 Byte Type of interfaces Pluggable interface module (IF), Technical data as for 2nd interface pluggable interface module 4th interface Type of interface pluggable interface modules Isochronous mode Useful data per isochronous slave, equidistance shortest clock pulse CiR configuration in RUN CiR synchronization time, basic load CiR synchronization time, time per I/O slave CPU/programming Programming language STEP 7 LAD FUP AWL SCL CFC GRAPH HiGraph Nesting levels 8 User program protection/password protection Dimensions and weight Width Height Depth Required slots 2 Weights Weight, approx. IF 964-DP Pluggable interface module (IF), Technical data as for 2nd interface IF 964-DP 244 Byte 1 ms 100 ms 40 µs 0 mm 290 mm 219 mm 1,070 g Siemens ST 70 2007 /33
Ordering data Order. Order. Main memory 20 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFIBUS DP master interface, module slots for 3/4 IF modules, slot for memory card, incl. slot number labels Memory Card RAM 6ES7 417-4XL04-64 KB 6ES7 92-0AF00-0AA0 26 KB 6ES7 92-1AH00-0AA0 1 MB 6ES7 92-1AK00-0AA0 2 MB 6ES7 92-1AL00-0AA0 4 MB 6ES7 92-1AM00-0AA0 8 MB 6ES7 92-1AP00-0AA0 16 MB 6ES7 92-1AS00-0AA0 64 MB 6ES7 92-1AY00-0AA0 FEPROM memory card 64 KB 6ES7 92-0KF00-0AA0 26 KB 6ES7 92-0KH00-0AA0 1 MB 6ES7 92-1KK00-0AA0 2 MB 6ES7 92-1KL00-0AA0 4 MB 6ES7 92-1KM00-0AA0 8 MB 6ES7 92-1KP00-0AA0 16 MB 6ES7 92-1KS00-0AA0 32 MB 6ES7 92-1KT00-0AA0 64 MB 6ES7 92-1KY00-0AA0 MPI cable For connecting SIMATIC S7 and the PG through MPI; m in length IF 964-DP interface module To connect an additional DP line; for CPU 414-3, CPU 414-3 PN/DP, CPU 416-3, CPU 416-3 PN/DP, Slot number plates 1 set (spare part) Manual " programmable controller" incl. instruction list S7-400 operation list 6ES7 901-0BF00-0AA0 6ES7 964-2AA04-6ES7 912-0AA00-0AA0 6ES7 498-8AA04-8AA0 6ES7 498-8AA04-8BA0 6ES7 498-8AA04-8CA0 6ES7 498-8AA04-8DA0 6ES7 498-8AA04-8EA0 6ES7 498-8AA04-8AN0 6ES7 498-8AA04-8BN0 6ES7 498-8AA04-8CN0 6ES7 498-8AA04-8DN0 6ES7 498-8AA04-8EN0 Manual "Communication for SIMATIC S7-300/-400" 6ES7 398-8EA00-8AA0 6ES7 398-8EA00-8BA0 6ES7 398-8EA00-8CA0 6ES7 398-8EA00-8DA0 6ES7 398-8EA00-8EA0 SIMATIC Manual Collection D) 6ES7 998-8XC01-8YE0 Electronic manuals on DVD, five languages: S7-200/300/400, C7, LOGO!, SIMATIC DP, PC, PG, STEP 7, engineering software, runtime software, PCS 7, SIMATIC HMI, SIMATIC NET SIMATIC Manual Collection update service for 1 year Current "Manual Collection" DVD and the three subsequent updates Brochure " programmable controller - Design and application" RS 48 bus connector with 90 cable outlet RS 48 bus connector with angled cable outlet RS 48 bus connector with 90 cable outlet for Fast Connect system RS 48 bus connector with axial cable outlet For SIMATIC OP, for connection to PPI, MPI, PROFIBUS PROFIBUS FastConnect bus cable Standard type with special design for quick mounting, 2-core, shielded, sold by the meter, delivery unit 1000 m, minimum ordering quantity 20 m D) 6ES7 998-8XC01-8YE2 6ES7 498-8AA00-8AB0 6ES7 498-8AA00-8BB0 6ES7 498-8AA00-8CB0 6ES7 498-8AA00-8DB0 6ES7 498-8AA00-8EB0 6ES7 972-0BA12-0XA0 6ES7 972-0BB12-0XA0 6ES7 972-0BA41-0XA0 6ES7 972-0BB41-0XA0 6ES7 972-0BA0-0XA0 6ES7 972-0BB0-0XA0 6GK1 00-0EA02 6XV1 830-0EH10 D) Subject to export regulations: AL: N and ECCN: D992B1 /34 Siemens ST 70 2007
CPU 414-4H, H Overview CPU 414-4H Overview H CPU for H and S7-400F/FH. Can be used in high availability S7-400H systems Can be used with F-runtime license and F-compatible CPU in failsafe S7-400F/FH systems With integrated PROFIBUS DP master interface With 2 slots for sync modules Technical specifications Supply voltages Rated value - 24 V DC Voltages and currents Incoming supply of external backup voltage to the CPU Current consumption from backplane bus V DC, to 1 V DC to 1 V DC 2 A 1.7 A Power dissipation, typical 4. W 6 W - Backup current, typical 0 µa 600 µa - Backup current, 1,30 µa 1,810 µa Memory Working memory - integrated (for 700 KByte program) - integrated (for data) 700 KByte - expandable Load memory - expandable FEPROM ; with Memory Card (FLASH) ; with Memory Card (FLASH) - expandable FEPROM, 64 MByte 64 MByte - integral RAM, 26 KByte 26 KByte - expandable RAM ; with Memory Card (RAM) ; with Memory Card (RAM) - expandable RAM, max 16 MByte 16 MByte Backup - available - with battery ; all data ; all data - without battery CPU for H and S7-400F/FH. Can be used in high availability S7-400H systems Can be used with F-runtime license and F-compatible CPU in failsafe S7-400F/FH systems With integrated PROFIBUS DP master interface With 2 slots for sync modules CPU/blocks DB - Number, 4,09; DB 0 reserved - Size, 8,192; DB 0 reserved FB - Number, 2,048 6,144 - Size, FC - Number, 2,048 6,144 - Size, OB - Number, See instruction list See instruction list - Size, Nesting depth - per priority class 24 24 - additional levels within an error OB 2 CPU/processing times for bit instruction, min. 0.06 µs 0.03 µs for word instruction, min. 0.06 µs 0.03 µs for integer math, min. 0.06 µs 0.03 µs for floating-point math, min. Timers/counters and their retentive characteristics 0.18 µs 0.09 µs S7 counter - Number 2,048 2,048 Siemens ST 70 2007 /3
CPU 414-4H, H Technical specifications (continued) Retentivity - adjustable - lower limit 0 0 - upper limit 2,047 2,047 - preset from Z 0 to Z 7 from Z 0 to Z 7 Counting range - lower limit 0 1 - upper limit 999 999 IEC counter - available - Type SFB SFB S7 times - Number 2.048 2.048 Timing range - lower limit 10 ms 10 ms - upper limit 9,990 s 9,990 s IEC timer - available - Type SFB SFB Data areas and their retentive characteristics Flags - Number 8 KByte - Retentivity ; MB 0 to MB 8191 ; MB 0 to MB 16383 Address area I/O address area - Inputs 8 KByte - Outputs 8 KByte of which distributed - MPI/DP interface, 2 KByte 2 KByte inputs - MPI/DP interface, 2 KByte 2 KByte outputs - DP interface, inputs 6 KByte 8 KByte - DP interface, outputs 6 KByte 8 KByte Process image - Inputs, adjustable 8 KByte - Outputs, adjustable 8 KByte - Inputs, preset 1.024 Byte 1.024 Byte - Outputs, preset 1.024 Byte 1.024 Byte - Number of component process images, 8 8 Digital channels - Inputs - Outputs - Inputs, of which central - Outputs, of which central Analog channels - Inputs 6,36 131,072 6,36 131,072 6,36 131,072 6,36 131,072 4,096 8,192 - Outputs 4,096 8,192 - Inputs, of which central - Outputs, of which central Configuration 4,096 8,192 4,096 8,192 Central units, 1 1 Expansion units, 21 21 Multi-computing IM - Number of pluggable IMs (overall), - Number of pluggable IM 460s, - Number of pluggable IM 463s, 6 6 6 6 6; IM 463-2 6; IM 463-2 Number of DP masters - integral 2 2 - via IM 467 0 0 - via CP 10 10 - Mixed mode of IM + CP permitted ; IM467 cannot be used externally together with CP443- - via interface module 0 0 Number of FMs and CPs that can be operated (recommendation) - FM - CP, point-to-point - CP, LAN Time - Hardware clock (realtime clock) - Battery backed and synchronized 32; limited by the 32; limited by the 32; limited by the Run-time meter - Quantity 8 8 ; IM467 cannot be used externally together with CP443-! 64; limited by the 64; limited by the 64; limited by the Time synchronization - supported S7 message functions Number of stations that can log on for message functions, Test and startup functions Diagnostic buffer - available - Number of inputs, 3,200 - adjustable - preset 120 Communication functions 8 16 PG/OP communication Global data communication - supported S7 basic communication - supported /36 Siemens ST 70 2007
Technical specifications (continued) S7 communication - supported - as server - as client - User data per job, S compatible communication - supported ; via CP and loadable FC ; via CP and loadable FC - User data per job, 8 KByte 8 KByte Standard communication (FMS) - Supported - User data per job, ; via CP and loadable FB depending on the CP Number of - overall 32 64 1st interface ; via CP and loadable FB depending on the CP Physical RS 48/PROFIBUS RS 48/PROFIBUS Isolated Functionality - MPI ; Default setting - DP master - DP slave MPI - Number of 32 44 ; Default setting - PG/OP communication - Global data communication - S7 basic communication - S7 communication - Transmission rates, DP master - Number of, 32 32 - PG/OP communication - S7 basic communication - S7 communication - S7 communication, as client - S7 communication, as server - Equidistance support - Activate/deactivate DP slaves - Direct data exchange (lateral communication) - Transmission rates, - Number of DP slaves, 32; Number of slots, 12 32; Number of slots, 12 Address area - Inputs, 2 KByte 2 KByte - Outputs, 2 KByte 2 KByte CPU 414-4H, H User data per DP Slave - Inputs, 244 Byte 244 Byte - Outputs, 244 Byte 244 Byte 2nd interface Physical RS 48/PROFIBUS RS 48/PROFIBUS Isolated Functionality - DP master ; Default setting - DP slave - Point-to-point connection DP master - Number of, - Number of (of which reserved), 32 16 1 for PG, 1 for OP 1 for PG, 1 for OP - PG/OP communication - S7 basic communication - S7 communication - S7 communication, as client - S7 communication, as server - Equidistance support - Activate/deactivate DP slaves - Direct data exchange (lateral communication) - Transmission rates, - Number of DP slaves, 96 12; Number of slots, 2048 Address area - Inputs, 8 KByte 8 KByte - Outputs, 8 KByte 8 KByte User data per DP Slave - Inputs, 244 Byte 244 Byte - Outputs, 244 Byte 244 Byte CPU/ programming Programming language - STEP 7 ; V.0 SP2 ; V.0 SP2 - KOP - FUP - AWL - SCL - CFC - GRAPH - HiGraph User program protection/password protection Dimensions and weight Width 0 mm 0 mm Height 290 mm 290 mm Depth 219 mm 219 mm Required slots 2 2 Weight, approx. 1,070 g 1,070 g Siemens ST 70 2007 /37
CPU 414-4H, H Ordering data Order. Order. CPU 414-4H For S7-400H and S7-400F/FH; MPI/PROFIBUS DP master interface, 2 slots for Sync modules, slot for memory card, incl. slot number labels, 2 keys Main memory 1,4 MB H For S7-400H and S7-400F/FH; MPI/PROFIBUS DP master interface, 2 slots for Sync modules, slot for memory card, incl. slot number labels, 2 keys Main memory 20 MB Memory Card RAM 1 MB 6ES7 92-1AK00-0AA0 2 MB 6ES7 92-1AL00-0AA0 4 MB 6ES7 92-1AM00-0AA0 8 MB 6ES7 92-1AP00-0AA0 16 MB 6ES7 92-1AS00-0AA0 64 MB 6ES7 92-1AY00-0AA0 FEPROM memory card 1 MB 6ES7 92-1KK00-0AA0 2 MB 6ES7 92-1KL00-0AA0 4 MB 6ES7 92-1KM00-0AA0 8 MB 6ES7 92-1KP00-0AA0 16 MB 6ES7 92-1KS00-0AA0 32 MB 6ES7 92-1KT00-0AA0 64 MB 6ES7 92-1KY00-0AA0 MPI cable For connecting SIMATIC S7 and the PG through MPI; m in length Slot number plates 1 set (spare part) S7 F Systems option pack For programming fail-safe user programs, with F block library F runtime license For using fail-safe programs in H; 1 license required for each S7-400F/FH system Manual "H programmable controller" 6ES7 901-0BF00-0AA0 6ES7 912-0AA00-0AA0 6ES7 833-1CC00-0YX0 6ES7 833-1CC00-6YX0 6ES7 988-8HA11-8AA0 6ES7 988-8HA11-8BA0 6ES7 988-8HA11-8CA0 6ES7 988-8HA11-8DA0 6ES7 988-8HA11-8EA0 Manual "Communication for SIMATIC S7-300/-400" 6ES7 398-8EA00-8AA0 6ES7 398-8EA00-8BA0 6ES7 398-8EA00-8CA0 6ES7 398-8EA00-8DA0 6ES7 398-8EA00-8EA0 SIMATIC Manual Collection D) 6ES7 998-8XC01-8YE0 Electronic manuals on DVD, five languages: S7-200/300/400, C7, LOGO!, SIMATIC DP, PC, PG, STEP 7, engineering software, runtime software, PCS 7, SIMATIC HMI, SIMATIC NET SIMATIC Manual Collection update service for 1 year Current "Manual Collection" DVD and the three subsequent updates Brochure " programmable controller - Design and application" RS 48 bus connector with 90 cable outlet RS 48 bus connector with angled cable outlet Max. transmission rate 1. Mbit/s RS 48 bus connector with 90 cable outlet for Fast Connect system RS 48 bus connector with axial cable outlet For SIMATIC OP, for connection to PPI, MPI, PROFIBUS PROFIBUS FastConnect bus cable Standard type with special design for quick mounting, 2-core, shielded, sold by the meter, delivery unit 1000 m, minimum ordering quantity 20 m D) 6ES7 998-8XC01-8YE2 6ES7 498-8AA00-8AB0 6ES7 498-8AA00-8BB0 6ES7 498-8AA00-8CB0 6ES7 498-8AA00-8DB0 6ES7 498-8AA00-8EB0 6ES7 972-0BA12-0XA0 6ES7 972-0BB12-0XA0 6ES7 972-0BA41-0XA0 6ES7 972-0BB41-0XA0 6ES7 972-0BA30-0XA0 6ES7 972-0BA0-0XA0 6ES7 972-0BB0-0XA0 6GK1 00-0EA02 6XV1 830-0EH10 D) Subject to export regulations: AL: N and ECCN: D992B1 /38 Siemens ST 70 2007