SIMATIC S7-400 advanced controller

Size: px
Start display at page:

Download "SIMATIC S7-400 advanced controller"

Transcription

1 Siemens AG 2015 /2 Introduction /4 Central processing units /4 Standard CPUs /4 CPU 412 /8 CPU 414 /13 CPU 41 /18 CPU 417 /21 SIPLUS Standard CPUs /21 SIPLUS S7-400 CPU 412 /22 SIPLUS S7-400 CPU 414 /23 SIPLUS S7-400 CPU 41 /24 SIPLUS S7-400 CPU 417 /25 Fail-safe CPUs /25 CPU 414F /29 CPU 41F /34 High-availability CPUs /34 CPU 412-5H, CPU 414-5H, CPU 41-5H, CPU 417-5H /39 Sync-module for coupling the CPU 41xH /40 Y-link for S7-400H /42 SIPLUS high-availability CPUs /42 SIPLUS S7-400 CPU 412H /43 SIPLUS S7-400 CPU 414H /44 SIPLUS S7-400 CPU 41H /45 SIPLUS S7-400 CPU 417H /4 SIPLUS sync module for connecting the CPU 41xH /47 SIPLUS Y-Link for S7-400H /48 Interface modules /49 SIPLUS S7-400 interface modules /50 Digital modules /5 SIPLUS S7-400 digital modules /58 Analog modules /8 SIPLUS S7-400 analog modules /70 Function modules /70 FM counter module /72 FM 451 positioning module /74 FM 452 cam controller /7 FM 453 positioning module /78 FM 455 controller module /81 FM DP application module /82 FM DP basic module /84 EXM input/output expansion /8 EXM 448 universal communications expansion module /87 D7-SYS /88 Accessories /91 SIPLUS S7-400 function modules /92 Communication /92 CP 440 /93 CP 441-1, CP /95 Loadable drivers for CP and CP 341 /9 CP Basic /98 CP Extended /100 CP /103 CP Advanced /107 CP RNA /109 TIM 4R-IE for WAN and Ethernet, TIM 4R-IE DNP3 /110 SIPLUS S7-400 communication /110 SIPLUS S7-400 CP Extended /111 SIPLUS S7-400 CP /113 SIPLUS S7-400 CP Advanced /115 Connection methods /118 Racks /120 SIPLUS module racks /121 Interface modules /121 IM 40-0 /122 IM 41-0 /123 IM 40-1 /124 IM 41-1 /125 IM 40-3 /12 IM 41-3 /127 IM 43-2 /128 SIPLUS S7-400 interface modules /130 Power supplies /134 SIPLUS power supplies /13 Accessories /13 Labeling sheets /13 Spare parts /137 CPUs for SIMATIC S7-400H and SIMATIC S7-400F/FH /138 Modules for SIMATIC S7-400F/FH Brochures For brochures serving as selection guides for SIMATIC products refer to: printmaterial Siemens ST

2 Introduction S7-400/S7-400H/S7-400F/FH The S7-400 is the most powerful PLC in the family of SIMATIC controllers. It enables successful automation solutions with Totally Integrated Automation (TIA). The S7-400 is an automation platform for system solutions in production and process engineering, and it is characterized primarily by its modularity and performance reserves. S7-400 The power PLC for the mid to high-end performance ranges. The solution for even the most demanding tasks. With a comprehensive range of modules and performancegraded CPUs for optimal adaptation to the automation task. Flexible in use through simple implementation of distributed structures. User-friendly connections. Optimal communication and networking options. User-friendly handling and uncomplicated design without a fan. Can be expanded without problems when the tasks increase. Multicomputing: Simultaneous operation of several CPUs in one S7-400 central controller. Multicomputing distributes the overall performance power of an S For example, complex tasks can be divided into technologies such as open-loop control, computing or communication, and assigned to different CPUs. And every CPU can be assigned its own local I/O. Modularity: The powerful backplane bus of the S7-400 and the communication interfaces that can be connected direct to the CPU enable high-performance operation of a host of communication lines. This enables, for example, division into one communication path for HMI and programming tasks, one for high-performance and equidistant motion control components, and one for a "normal" I/O fieldbus. Additionally required connections to MES/ERP systems or the Internet can also be implemented. Engineering and diagnostics: The S7-400 is configured and programmed extremely efficiently together with the SIMATIC Engineering Tools particularly in the case of extensive automation solutions with a high engineering component. For this purpose, high-level languages such as SCL and graphical engineering tools for sequential controls, state graph programs and technologyoriented diagrams are available, for example. S7-400H Fault-tolerant automation system with redundant design. For applications with high fail-safety requirements. Processes with high restart costs, expensive downtimes, little supervision, and few maintenance options. Redundant central functions. Increases availability of I/O: switched I/O configuration. Also possible to use I/Os with standard availability: singlesided configuration. Hot stand-by: automatic reaction-free switching to the standby unit in the event of a fault. Configuration with two separate or one divided central rack. Connection of switched I/O via redundant PROFIBUS DP or via system reduntant PROFINET IO. /2 Siemens ST

3 Introduction S7-400/S7-400H/S7-400F/FH (continued) S7-400F/FH Failsafe automation system for plants with increased safety requirements Complies with safety requirements to SIL 3 in accordance with IEC 1508, AK in accordance with DIN V and Cat. 4 in accordance with EN If required, also fault tolerant through redundant design Without additional wiring of the safety-related I/O Safety-relevant communication via PROFIBUS DP with PROFIsafe profile Based on S7-400H and distributed IOs ET 200M with fail-safe modules Standard modules for non-safety-related applications can also be used in the automation system Isolation module for joint use of fail-safe and standard modules in safety mode in one ET 200M Technical specifications General technical data SIMATIC S7-400 Degree of protection IP20 Ambient temperature 0 to 0 C Relative humidity 5 to 95 %, no condensation Atmospheric pressure 1080 to 795 hpa (corresponds to an altitude of m to +2,000 m) Electromagnetic compatibility Interference immunity According to EN Emitted interference According to EN Mechanical load Vibration, test according to / IEC (sine) tested with 10 to 58 Hz; constant amplitude mm; 58 to 500 Hz; constant acceleration 1 g; duration of oscillation: 10 frequency sweeps per axis in each direction of the three mutually perpendicular axes Shock, test according to / IEC tested with Type of shock: Half-sine; strength of the shock 10 g (peak value), duration ms direction of shock: 100 shocks in each of the 3 mutually perpendicular axes. General technical data SIPLUS S7-400 Ambient temperature range -25/ /70 C Conformal coating Coating of the printed circuit boards and the electronic components Technical data The technical data of the standard product applies except for the ambient conditions. Ambient conditions Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Relative humidity With condensation, max. Resistance against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Siemens ST /3

4 Central processing units Standard CPUs CPU 412 The low-cost starter solution for the medium performance range Can be used in small and medium-sized systems with requirements of the medium performance range Technical specifications ES7412-1XJ05-0AB0 ES7412-2XJ05-0AB0 ES7412-2EK0-0AB0 CPU412-1, MPI/DP, 288 KB CPU412-2, MPI/DP, 512 KB CPU412-2 PN, 1 MB, 2 INTERFACES Product type designation General information Engineering with Programming package STEP7 V 5.3 SP2 or higher with HW update STEP7 V 5.3 SP2 or higher with HW update STEP7 V5.5 or higher / imap V3.0 + imap STEP7 Add-on V3.0 SP5 Supply voltage Rated value (DC) 24 V DC No; Power supply via system power supply Power losses Power loss, typ. 2.5 W 4W 5.5 W Memory Work memory Integrated 288 kbyte 512 kbyte 1Mbyte Integrated (for program) 144 kbyte 25 kbyte 0.5 Mbyte Integrated (for data) 144 kbyte 25 kbyte 0.5 Mbyte Load memory Expandable FEPROM, max. 4 Mbyte 4 Mbyte 4 Mbyte Integrated RAM, max. 512 kbyte 512 kbyte 512 kbyte Expandable RAM, max. 4 Mbyte 4 Mbyte 4 Mbyte CPU processing times for bit operations, typ. 75 ns 75 ns 75 ns for word operations, typ. 75 ns 75 ns 75 ns for fixed point arithmetic, typ. 75 ns 75 ns 75 ns for floating point arithmetic, typ. 225 ns 225 ns 225 ns Counters, timers and their retentivity S7 counter Number IEC counter present S7 times Number IEC timer present Data areas and their retentivity Flag Number, max. 4kbyte 4kbyte 4 kbyte; Size of bit memory address area /4 Siemens ST

5 Central processing units Standard CPUs CPU 412 Technical specifications (continued) ES7412-1XJ05-0AB0 ES7412-2XJ05-0AB0 ES7412-2EK0-0AB0 CPU412-1, MPI/DP, 288 KB CPU412-2, MPI/DP, 512 KB CPU412-2 PN, 1 MB, 2 INTERFACES Address area I/O address area Inputs 4kbyte 4kbyte 4kbyte Outputs 4kbyte 4kbyte 4kbyte Process image Inputs, adjustable 4kbyte 4kbyte 4kbyte Outputs, adjustable 4kbyte 4kbyte 4kbyte Hardware configuration Slots Required slots Time of day Clock Hardware clock (real-time clock) Operating hours counter Number Interfaces Interface/bus type 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports) Number of RS 485 interfaces Number of other interfaces st interface Interface type Integrated Integrated Integrated Physics RS 485 / PROFIBUS RS 485 / PROFIBUS RS 485 / PROFIBUS + MPI Functionality MPI DP master DP slave DP master Number of DP slaves, max. 32; Max. 544 slots nd interface Interface type Integrated PROFINET Physics RS 485 / PROFIBUS Ethernet RJ45 Number of ports 2 Functionality DP master No DP slave No PROFINET IO Controller PROFINET IO Device PROFINET CBA DP master Number of DP slaves, max. 4 PROFINET IO Controller Max. number of connectable IO 25 devices for RT Number of IO devices with IRT and 25 the option "high flexibility" Number of IO Devices with IRT and 4 the option "high performance", max. Isochronous mode Isochronous operation (application synchronized up to terminal) ; Via PROFIBUS DP or PROFINET interface Siemens ST /5

6 Central processing units Standard CPUs CPU 412 Technical specifications (continued) ES7412-1XJ05-0AB0 ES7412-2XJ05-0AB0 ES7412-2EK0-0AB0 CPU412-1, MPI/DP, 288 KB CPU412-2, MPI/DP, 512 KB CPU412-2 PN, 1 MB, 2 INTERFACES Communication functions PG/OP communication Data record routing Global data communication supported S7 basic communication supported S7 communication supported S5-compatible communication supported ; Via FC AG_SEND and AG_RECV, max. via 10 CP or ; (via CP max. 10 and FC AG_SEND and FC AG_RECV) ; Via FC AG_SEND and AG_RECV, max. via 10 CP or Standard communication (FMS) supported ; Via CP and loadable FB ; Via CP and loadable FB ; Via CP and loadable FB Open IE communication TCP/IP ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 4 ISO-on-TCP (RFC100) Via CP Adv. and loadable FB Via CP Adv. and loadable FB ; Via integrated PROFINET interface or CP Adv. and loadable FBs - Number of connections, max UDP ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 4 Web server supported No; Via CP No; Via CP Number of connections overall Configuration Programming Programming language -LAD -FBD -STL -SCL -CFC - GRAPH - HiGraph Know-how protection User program protection/password protection Block encryption ; With S7 block Privacy Dimensions Width 25 mm 25 mm 25 mm Height 290 mm 290 mm 290 mm Depth 219 mm 219 mm 219 mm Weights Weight, approx. 720 g 720 g 750 g / Siemens ST

7 Central processing units Standard CPUs Ordering data Article No. Article No. CPU 412 CPU ES7412-1XJ05-0AB0 Main memory 288 KB, power supply 24 V DC, MPI/PROFIBUS DP master interface, slot for memory card, incl. slot number labels CPU ES7412-2XJ05-0AB0 Main memory 512 KB, power supply 24 V DC, MPI/PROFIBUS DP master interface, slot for memory card, incl. slot number labels CPU PN ES7412-2EK0-0AB0 Main memory 1 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFINET interface, slot for memory card, incl. slot number labels Memory card RAM 4 KB ES7952-0AF00-0AA0 25 KB ES7952-1AH00-0AA0 1 MB ES7952-1AK00-0AA0 2 MB ES7952-1AL00-0AA0 4 MB ES7952-1AM00-0AA0 8 MB ES7952-1AP00-0AA0 1 MB ES7952-1AS00-0AA0 4 MB ES7952-1AY00-0AA0 FEPROM memory card 4 KB ES7952-0KF00-0AA0 25 KB ES7952-0KH00-0AA0 1 MB ES7952-1KK00-0AA0 2 MB ES7952-1KL00-0AA0 4 MB ES7952-1KM00-0AA0 8 MB ES7952-1KP00-0AA0 1 MB ES7952-1KS00-0AA0 32 MB ES7952-1KT00-0AA0 4 MB ES7952-1KY00-0AA0 MPI cable ES7901-0BF00-0AA0 for connection of SIMATIC S7 and PG via MPI; 5 m in length Slot number plates ES7912-0AA00-0AA0 1 set (spare part) SIMATIC Manual Collection ES7998-8XC01-8YE0 Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection ES7998-8XC01-8YE2 update service for 1 year Current "Manual Collection" DVD and the three subsequent updates RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA12-0XA0 With PG interface ES7972-0BB12-0XA0 RS 485 bus connector with angled cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA42-0XA0 With PG interface ES7972-0BB42-0XA0 RS 485 bus connector with 90 cable outlet for FastConnect connection system Max. transfer rate 12 Mbit/s without PG interface - 1 unit ES7972-0BA52-0XA0-100 units ES7972-0BA52-0XB0 with PG interface - 1 unit ES7972-0BB52-0XA0-100 units ES7972-0BB52-0XB0 RS 485 bus connector GK1500-0EA02 with axial cable outlet For SIMATIC OP, for connection to PPI, MPI, PROFIBUS PROFIBUS FastConnect XV1830-0EH10 bus cable Standard type with special design for fast mounting, 2-core, shielded, sold by the meter; max. delivery unit m, minimum ordering quantity 20 m Siemens ST /7

8 Central processing units Standard CPUs CPU 414 CPUs for high demands in the mid-level performance range Applicable for plants with additional demands on programming scope and processing speed Integrated PROFINET functions in CPU PN/DP Technical specifications ES7414-2XK05-0AB0 ES7414-3XM05-0AB0 ES7414-3EM0-0AB0 CPU414-2, MPI/DP, 1 MB CPU414-3, 2.8 MB, 3 INTERFACES CPU414-3 PN/DP, 4 MB, 3 INTERFACES Product type designation General information Engineering with Programming package STEP7 V 5.3 SP2 or higher with HW update STEP7 V 5.3 SP2 or higher with HW update STEP7 V5.5 or higher / imap V3.0 + imap STEP7 Add-on V3.0 SP5 Supply voltage Rated value (DC) 24 V DC No; Power supply via system power supply Power losses Power loss, typ. 4W 5.5 W.5 W Memory Work memory Integrated 1Mbyte 2.8 Mbyte 4Mbyte integrated (for program) 0.5 Mbyte 1.4 Mbyte 2Mbyte integrated (for data) 0.5 Mbyte 1.4 Mbyte 2Mbyte Load memory expandable FEPROM, max. 4 Mbyte 4 Mbyte 4 Mbyte integrated RAM, max. 512 kbyte 512 kbyte 512 kbyte expandable RAM, max. 4 Mbyte 4 Mbyte 4 Mbyte CPU processing times for bit operations, typ. 45 ns 45 ns 45 ns for word operations, typ. 45 ns 45 ns 45 ns for fixed point arithmetic, typ. 45 ns 45 ns 45 ns for floating point arithmetic, typ. 135 ns 135 ns 135 ns Counters, timers and their retentivity S7 counter Number IEC counter present S7 times Number IEC timer present Data areas and their retentivity Flag Number, max. 8kbyte 8 kbyte; Size of bit memory address area No; Power supply via system power supply 8 kbyte; Size of bit memory address area /8 Siemens ST

9 Central processing units Standard CPUs CPU 414 Technical specifications (continued) ES7414-2XK05-0AB0 ES7414-3XM05-0AB0 ES7414-3EM0-0AB0 CPU414-2, MPI/DP, 1 MB CPU414-3, 2.8 MB, 3 INTERFACES CPU414-3 PN/DP, 4 MB, 3 INTERFACES Address area I/O address area Inputs 8kbyte 8kbyte 8kbyte Outputs 8kbyte 8kbyte 8kbyte Process image Inputs, adjustable 8kbyte 8kbyte 8kbyte Outputs, adjustable 8kbyte 8kbyte 8kbyte Hardware configuration Slots Required slots Time of day Clock Hardware clock (real-time clock) Operating hours counter Number Interfaces Interface/bus type 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable) 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable) Number of RS 485 interfaces Number of other interfaces st interface Interface type Integrated Integrated Integrated Physics RS 485 / PROFIBUS RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI Functionality MPI DP master DP slave DP master Number of DP slaves, max nd interface Interface type Integrated Integrated PROFINET Physics RS 485 / PROFIBUS RS 485 / PROFIBUS Ethernet RJ45 Number of ports 2 Functionality DP master No DP slave No PROFINET IO Controller PROFINET IO Device PROFINET CBA DP master Number of DP slaves, max. 9 9 PROFINET IO Controller Max. number of connectable 25 IO devices for RT Number of IO devices with IRT and 25 the option "high flexibility" Number of IO Devices with IRT and 4 the option "high performance", max. 3rd interface Interface type Pluggable interface module (IF), technical data as for 2nd interface Pluggable interface module (IF) Plug-in interface modules IF 94-DP (MLFB: ES794-2AA04-0AB0) IF 94-DP (MLFB: ES794-2AA04-0AB0) Physics RS 485 / PROFIBUS RS 485 / PROFIBUS Siemens ST /9

10 Central processing units Standard CPUs CPU 414 Technical specifications (continued) ES7414-2XK05-0AB0 ES7414-3XM05-0AB0 ES7414-3EM0-0AB0 CPU414-2, MPI/DP, 1 MB CPU414-3, 2.8 MB, 3 INTERFACES CPU414-3 PN/DP, 4 MB, 3 INTERFACES Functionality MPI No No DP master DP slave DP master Number of DP slaves, max. 9 9 Isochronous mode Isochronous operation (application synchronized up to terminal) Communication functions ; For PROFIBUS only ; Via PROFIBUS DP or PROFINET interface PG/OP communication Data record routing Global data communication supported S7 basic communication supported S7 communication supported S5-compatible communication supported ; (via CP max. 10 and FC AG_SEND and FC AG_RECV) ; Via FC AG_SEND and AG_RECV, max. via 10 CP or ; Via FC AG_SEND and AG_RECV, max. via 10 CP or Standard communication (FMS) supported ; Via CP and loadable FB ; Via CP and loadable FB ; Via CP and loadable FB Open IE communication TCP/IP ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 2 ISO-on-TCP (RFC100) Via CP Adv. and loadable FB Via CP and loadable FB ; Via integrated PROFINET interface or CP Adv. and loadable FBs - Number of connections, max. 2 UDP ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 2 Web server supported No; Via CP No Number of connections overall Configuration Programming Programming language -LAD -FBD -STL -SCL -CFC - GRAPH - HiGraph Know-how protection User program protection/password protection Block encryption ; With S7 block Privacy Dimensions Width 25 mm 50 mm 50 mm Height 290 mm 290 mm 290 mm Depth 219 mm 219 mm 219 mm Weights Weight, approx. 720 g 0.9 kg 900 g /10 Siemens ST

11 Central processing units Standard CPUs Ordering data Article No. Article No. CPU 414 CPU ES7414-2XK05-0AB0 Main memory 1 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, slot for memory card, incl. slot number labels CPU ES7414-3XM05-0AB0 Main memory 2.8 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFIBUS DP master interface, slot for memory card, module slots for 1 IF module, incl. slot number labels CPU PN/DP ES7414-3EM0-0AB0 Main memory 4 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFINET interface, slot for memory card, module slot for 1 IF module, incl. slot number labels Memory card RAM 4 KB ES7952-0AF00-0AA0 25 KB ES7952-1AH00-0AA0 1 MB ES7952-1AK00-0AA0 2 MB ES7952-1AL00-0AA0 4 MB ES7952-1AM00-0AA0 8 MB ES7952-1AP00-0AA0 1 MB ES7952-1AS00-0AA0 4 MB ES7952-1AY00-0AA0 FEPROM memory card 4 KB ES7952-0KF00-0AA0 25 KB ES7952-0KH00-0AA0 1 MB ES7952-1KK00-0AA0 2 MB ES7952-1KL00-0AA0 4 MB ES7952-1KM00-0AA0 8 MB ES7952-1KP00-0AA0 1 MB ES7952-1KS00-0AA0 32 MB ES7952-1KT00-0AA0 4 MB ES7952-1KY00-0AA0 MPI cable ES7901-0BF00-0AA0 for connection of SIMATIC S7 and PG via MPI; 5 m in length IF 94-DP interface module ES794-2AA04-0AB0 To connect an additional DP line; for CPU 414-3, CPU PN/DP, CPU 41-3, CPU 41-3 PN/DP, CPU Slot number plates ES7912-0AA00-0AA0 1 set (spare part) SIMATIC Manual Collection ES7998-8XC01-8YE0 Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection ES7998-8XC01-8YE2 update service for 1 year Current "Manual Collection" DVD and the three subsequent updates PROFIBUS bus components RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA12-0XA0 With PG interface ES7972-0BB12-0XA0 RS 485 bus connector with angled cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA42-0XA0 With PG interface ES7972-0BB42-0XA0 RS 485 bus connector with 90 cable outlet for FastConnect connection system Max. transfer rate 12 Mbit/s without PG interface - 1 unit ES7972-0BA52-0XA0-100 units ES7972-0BA52-0XB0 with PG interface - 1 unit ES7972-0BB52-0XA0-100 units ES7972-0BB52-0XB0 RS 485 bus connector GK1500-0EA02 with axial cable outlet For SIMATIC OP, for connection to PPI, MPI, PROFIBUS PROFIBUS FastConnect XV1830-0EH10 bus cable Standard type with special design for fast mounting, 2-core, shielded, sold by the meter; max. delivery unit m, minimum ordering quantity 20 m RS 485 repeater for PROFIBUS ES7972-0AA02-0XA0 Transmission rate up to 12 Mbit/s; 24 V DC; IP20 enclosure Siemens ST /11

12 Central processing units Standard CPUs CPU 414 Ordering data Article No. Article No. PROFINET bus components IE FC TP standard cable GP 2x2 4-core, shielded TP installation cable for connection to IE FC Outlet RJ45/ IE FC RJ45 Plug; PROFINET-compatible; with UL approval; Sold by the meter FO Standard Cable GP (50/125) Standard cable, splittable, UL approval, sold by the meter SCALANCE X204-2 Industrial Ethernet switch Industrial Ethernet Switches with integral SNMP access, web diagnostics, copper cable diagnostics and PROFINET diagnostics for configuring line, star and ring topologies; four 10/100 Mbit/s RJ45 ports and two FO ports XV1840-2AH10 XV1873-2A GK5204-2BB10-2AA3 IE FC RJ45 plugs RJ45 plug connector for Industrial Ethernet with a rugged metal enclosure and integrated insulation displacement contacts for connecting Industrial Ethernet FC installation cables IE FC RJ45 plug cable outlet 1 unit GK1901-1BB10-2AA0 10 units GK1901-1BB10-2AB0 50 units GK1901-1BB10-2AE0 PROFIBUS/PROFINET See IK PI, CA 01 catalogs bus components For establishing MPI/PROFIBUS/ PROFINET communication /12 Siemens ST

13 Central processing units Standard CPUs CPU 41 High-performance CPUs in the high-end performance range Applicable for plants with high requirements in the high-end performance range Integrated PROFINET functions in CPU 41-3 PN/DP Technical specifications ES741-2XN05-0AB0 ES741-3XR05-0AB0 ES741-3ES0-0AB0 CPU 41-2, MPI, PROFIBUS, 5. MB CPU 41-3, 11.2 MB, 3 INTERFACES CPU41-3 PN/DP, 1 MB, 3 INTERFACES Product type designation General information Engineering with Programming package STEP7 V 5.3 SP2 or higher with HW update STEP7 V 5.3 SP2 or higher with HW update STEP7 V5.5 or higher / imap V3.0 + imap STEP7 Add-on V3.0 SP5 or higher Supply voltage Rated value (DC) 24 V DC No; Power supply via system power supply Power losses Power loss, typ. 4W 5.5 W.5 W Memory Work memory Integrated 5. Mbyte 11.2 Mbyte 1 Mbyte integrated (for program) 2.8 Mbyte 5. Mbyte 8Mbyte integrated (for data) 2.8 Mbyte 5. Mbyte 8Mbyte Load memory expandable FEPROM, max. 4 Mbyte 4 Mbyte 4 Mbyte integrated RAM, max. 1Mbyte 1Mbyte 1Mbyte expandable RAM, max. 4 Mbyte 4 Mbyte 4 Mbyte CPU processing times for bit operations, typ. 30 ns 30 ns 30 ns for word operations, typ. 30 ns 30 ns 30 ns for fixed point arithmetic, typ. 30 ns 30 ns 30 ns for floating point arithmetic, typ. 90 ns 90 ns 90 ns Counters, timers and their retentivity S7 counter Number IEC counter present S7 times Number IEC timer present Data areas and their retentivity Flag Number, max. 1 kbyte 1 kbyte; Size of bit memory address area No; Power supply via system power supply 1 kbyte; Size of bit memory address area Siemens ST /13

14 Central processing units Standard CPUs CPU 41 Technical specifications (continued) ES741-2XN05-0AB0 ES741-3XR05-0AB0 ES741-3ES0-0AB0 CPU 41-2, MPI, PROFIBUS, 5. MB CPU 41-3, 11.2 MB, 3 INTERFACES CPU41-3 PN/DP, 1 MB, 3 INTERFACES Address area I/O address area Inputs 1 kbyte 1 kbyte 1 kbyte Outputs 1 kbyte 1 kbyte 1 kbyte Process image Inputs, adjustable 1 kbyte 1 kbyte 1 kbyte Outputs, adjustable 1 kbyte 1 kbyte 1 kbyte Hardware configuration Slots Required slots Time of day Clock Hardware clock (real-time clock) Operating hours counter Number Interfaces Interface/bus type 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable) 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable) Number of RS 485 interfaces Number of other interfaces st interface Interface type Integrated Integrated Integrated Physics RS 485 / PROFIBUS RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI Functionality MPI DP master DP slave DP master Number of DP slaves, max nd interface Interface type Integrated Integrated PROFINET Physics RS 485 / PROFIBUS RS 485 / PROFIBUS Ethernet RJ45 Number of ports 2 Functionality DP master No DP slave No PROFINET IO Controller PROFINET IO Device PROFINET CBA DP master Number of DP slaves, max PROFINET IO Controller Max. number of connectable 25 IO devices for RT Number of IO devices with IRT and 25 the option "high flexibility" Number of IO Devices with IRT and 4 the option "high performance", max. 3rd interface Interface type Pluggable interface module (IF), technical data as for 2nd interface Pluggable interface module (IF) Plug-in interface modules IF 94-DP (MLFB: ES794-2AA04-0AB0) IF 94-DP (MLFB: ES794-2AA04-0AB0) Physics RS 485 / PROFIBUS RS 485 / PROFIBUS /14 Siemens ST

15 Central processing units Standard CPUs CPU 41 Technical specifications (continued) ES741-2XN05-0AB0 ES741-3XR05-0AB0 ES741-3ES0-0AB0 CPU 41-2, MPI, PROFIBUS, 5. MB CPU 41-3, 11.2 MB, 3 INTERFACES CPU41-3 PN/DP, 1 MB, 3 INTERFACES Functionality MPI No No DP master DP slave DP master Number of DP slaves, max Isochronous mode Isochronous operation (application synchronized up to terminal) Communication functions ; For PROFIBUS only ; Via PROFIBUS DP or PROFINET interface PG/OP communication Data record routing Global data communication supported S7 basic communication supported S7 communication supported S5-compatible communication supported ; (via CP max. 10 and FC AG_SEND and FC AG_RECV) ; Via FC AG_SEND and AG_RECV, max. via 10 CP or ; Via FC AG_SEND and AG_RECV, max. via 10 CP or Standard communication (FMS) supported ; Via CP and loadable FB ; Via CP and loadable FB ; Via CP and loadable FB Open IE communication TCP/IP ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 94 ISO-on-TCP (RFC100) Via CP Adv. and loadable FB Via CP and loadable FB ; Via integrated PROFINET interface or CP and loadable FBs - Number of connections, max. 94 UDP ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 94 Web server supported No; Via CP No Number of connections overall Configuration Programming Programming language -LAD -FBD -STL -SCL -CFC - GRAPH - HiGraph Know-how protection User program protection/password protection Block encryption ; With S7 block Privacy Dimensions Width 25 mm 50 mm 50 mm Height 290 mm 290 mm 290 mm Depth 219 mm 219 mm 219 mm Weights Weight, approx. 720 g 0.9 kg 900 g Siemens ST /15

16 Central processing units Standard CPUs CPU 41 Ordering data Article No. Article No. CPU 41-2 ES741-2XN05-0AB0 Main memory 5. MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFIBUS DP master interface, slot for memory card, incl. slot number labels CPU 41-3 ES741-3XR05-0AB0 Main memory 11.2 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFIBUS DP master interface, module slot for 1 IF module, slot for memory card, incl. slot number labels CPU 41-3 PN/DP ES741-3ES0-0AB0 Main memory 1 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFINET interface, module slot for 1 IF submodule, slot for memory card, incl. slot number labels Memory card RAM 4 KB ES7952-0AF00-0AA0 25 KB ES7952-1AH00-0AA0 1 MB ES7952-1AK00-0AA0 2 MB ES7952-1AL00-0AA0 4 MB ES7952-1AM00-0AA0 8 MB ES7952-1AP00-0AA0 1 MB ES7952-1AS00-0AA0 4 MB ES7952-1AY00-0AA0 FEPROM memory card 4 KB ES7952-0KF00-0AA0 25 KB ES7952-0KH00-0AA0 1 MB ES7952-1KK00-0AA0 2 MB ES7952-1KL00-0AA0 4 MB ES7952-1KM00-0AA0 8 MB ES7952-1KP00-0AA0 1 MB ES7952-1KS00-0AA0 32 MB ES7952-1KT00-0AA0 4 MB ES7952-1KY00-0AA0 MPI cable ES7901-0BF00-0AA0 for connection of SIMATIC S7 and PG via MPI; 5 m in length IF 94-DP interface module ES794-2AA04-0AB0 To connect an additional DP line; for CPU 414-3, CPU PN/DP, CPU 41-3, CPU 41-3 PN/DP, CPU Slot number plates ES7912-0AA00-0AA0 1 set (spare part) SIMATIC Manual Collection ES7998-8XC01-8YE0 Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC-based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection ES7998-8XC01-8YE2 update service for 1 year Current "Manual Collection" DVD and the three subsequent updates PROFIBUS bus components RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA12-0XA0 With PG interface ES7972-0BB12-0XA0 RS 485 bus connector with angled cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA42-0XA0 With PG interface ES7972-0BB42-0XA0 RS 485 bus connector with 90 cable outlet for FastConnect connection system Max. transfer rate 12 Mbit/s Without PG interface - 1 unit ES7972-0BA52-0XA0-100 units ES7972-0BA52-0XB0 With PG interface - 1 unit ES7972-0BB52-0XA0-100 units ES7972-0BB52-0XB0 RS 485 bus connector GK1500-0EA02 with axial cable outlet For SIMATIC OP, for connection to PPI, MPI, PROFIBUS PROFIBUS FastConnect XV1830-0EH10 bus cable Standard type with special design for fast mounting, 2-core, shielded, sold by the meter; max. delivery unit m, minimum ordering quantity 20 m RS 485 repeater for PROFIBUS ES7972-0AA02-0XA0 Transfer rate up to 12 Mbps; 24 V DC; IP20 enclosure /1 Siemens ST

17 Central processing units Standard CPUs Ordering data Article No. Article No. CPU 41 PROFINET bus components IE FC TP standard cable GP 2x2 4-core, shielded TP installation cable for connection to IE FC Outlet RJ45/ IE FC RJ45 Plug; PROFINET-compatible; with UL approval; Sold by the meter FO Standard Cable GP (50/125) Standard cable, splittable, UL approval, sold by the meter SCALANCE X204-2 Industrial Ethernet switch Industrial Ethernet Switches with integral SNMP access, web diagnostics, copper cable diagnostics and PROFINET diagnostics for configuring line, star and ring topologies; four 10/100 Mbit/s RJ45 ports and two FO ports XV1840-2AH10 XV1873-2A GK5204-2BB10-2AA3 IE FC RJ45 plugs RJ45 plug connector for Industrial Ethernet with a rugged metal enclosure and integrated insulation displacement contacts for connecting Industrial Ethernet FC installation cables IE FC RJ45 plug cable outlet 1 unit GK1901-1BB10-2AA0 10 units GK1901-1BB10-2AB0 50 units GK1901-1BB10-2AE0 PROFIBUS/PROFINET See IK PI, CA 01 catalogs bus components For establishing MPI/PROFIBUS/ PROFINET communication Siemens ST /17

18 Central processing units Standard CPUs CPU 417 The most powerful SIMATIC S7-400 CPU Can be used in the most sophisticated installations in the upper performance range With two slots for IF modules Technical specifications Product type designation General information Engineering with Programming package Supply voltage Rated value (DC) 24 V DC ES7417-4XT05-0AB0 CPU 417-4, 30 MB, 4 INTERFACES STEP7 V 5.3 SP2 or higher with HW update No; Power supply via system power supply Power losses Power loss, typ. 7.5 W Memory Work memory Integrated 30 Mbyte integrated (for program) 15 Mbyte integrated (for data) 15 Mbyte Load memory expandable FEPROM, max. 4 Mbyte integrated RAM, max. 1Mbyte expandable RAM, max. 4 Mbyte CPU processing times for bit operations, typ. 18 ns for word operations, typ. 18 ns for fixed point arithmetic, typ. 18 ns for floating point arithmetic, typ. 54 ns Counters, timers and their retentivity S7 counter Number 2048 IEC counter present S7 times Number 2048 IEC timer present Data areas and their retentivity Flag Number, max. 1 kbyte; Size of bit memory address area ES7417-4XT05-0AB0 CPU 417-4, 30 MB, 4 INTERFACES Address area I/O address area Inputs 1 kbyte Outputs 1 kbyte Process image Inputs, adjustable 1 kbyte Outputs, adjustable 1 kbyte Hardware configuration Slots Required slots 2 Time of day Clock Hardware clock (real-time clock) Operating hours counter Number 1 Interfaces Interface/bus type 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 2 x PROFIBUS DP (optionally pluggable) Number of RS 485 interfaces 2 Number of other interfaces 0 1st interface Interface type Integrated Physics RS 485 / PROFIBUS + MPI Functionality MPI DP master DP slave DP master Number of DP slaves, max. 32 2nd interface Interface type Integrated Physics RS 485 / PROFIBUS Functionality DP master DP slave /18 Siemens ST

19 Central processing units Standard CPUs CPU 417 Technical specifications (continued) ES7417-4XT05-0AB0 CPU 417-4, 30 MB, 4 INTERFACES DP master Number of DP slaves, max rd interface Interface type Pluggable interface module (IF), technical data as for 2nd interface Plug-in interface modules IF 94-DP (MLFB: ES794-2AA04-0AB0) Physics RS 485 / PROFIBUS Functionality MPI No DP master DP slave DP master Number of DP slaves, max th interface Interface type Pluggable interface module (IF), technical data as for 2nd interface Plug-in interface modules IF 94-DP (MLFB: ES794-2AA04-0AB0) Isochronous mode Isochronous operation (application ; For PROFIBUS only synchronized up to terminal) Communication functions PG/OP communication Data record routing Global data communication supported S7 basic communication supported S7 communication supported S5-compatible communication supported ; Via FC AG_SEND and AG_RECV, max. via 10 CP or Standard communication (FMS) supported ; Via CP and loadable FB Open IE communication ISO-on-TCP (RFC100) Via CP and loadable FB Web server supported No Number of connections overall 4 Configuration Programming Programming language -LAD -FBD -STL -SCL -CFC -GRAPH - HiGraph Know-how protection User program protection/ password protection Dimensions Width 50 mm Height 290 mm Depth 219 mm Weights Weight, approx. 0.9 kg ES7417-4XT05-0AB0 CPU 417-4, 30 MB, 4 INTERFACES Siemens ST /19

20 Central processing units Standard CPUs CPU 417 Ordering data Article No. Article No. CPU ES7417-4XT05-0AB0 Main memory 30 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFIBUS DP master interface, module slots for up to 2 additional IF modules, slot for memory card, incl. slot number labels Memory card RAM 4 KB ES7952-0AF00-0AA0 25 KB ES7952-1AH00-0AA0 1 MB ES7952-1AK00-0AA0 2 MB ES7952-1AL00-0AA0 4 MB ES7952-1AM00-0AA0 8 MB ES7952-1AP00-0AA0 1 MB ES7952-1AS00-0AA0 4 MB ES7952-1AY00-0AA0 FEPROM memory card 4 KB ES7952-0KF00-0AA0 25 KB ES7952-0KH00-0AA0 1 MB ES7952-1KK00-0AA0 2 MB ES7952-1KL00-0AA0 4 MB ES7952-1KM00-0AA0 8 MB ES7952-1KP00-0AA0 1 MB ES7952-1KS00-0AA0 32 MB ES7952-1KT00-0AA0 4 MB ES7952-1KY00-0AA0 MPI cable ES7901-0BF00-0AA0 for connection of SIMATIC S7 and PG via MPI; 5 m in length IF 94-DP interface module ES794-2AA04-0AB0 To connect an additional DP line; for CPU 414-3, CPU PN/DP, CPU 41-3, CPU 41-3 PN/DP, CPU Slot number plates ES7912-0AA00-0AA0 1 set (spare part) SIMATIC Manual Collection ES7998-8XC01-8YE0 Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection ES7998-8XC01-8YE2 update service for 1 year Current "Manual Collection" DVD and the three subsequent updates RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA12-0XA0 With PG interface ES7972-0BB12-0XA0 RS 485 bus connector with angled cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA42-0XA0 With PG interface ES7972-0BB42-0XA0 RS 485 bus connector with 90 cable outlet for FastConnect connection system Max. transfer rate 12 Mbit/s without PG interface - 1 unit ES7972-0BA52-0XA0-100 units ES7972-0BA52-0XB0 with PG interface - 1 unit ES7972-0BB52-0XA0-100 units ES7972-0BB52-0XB0 RS 485 bus connector GK1500-0EA02 with axial cable outlet For SIMATIC OP, for connection to PPI, MPI, PROFIBUS PROFIBUS FastConnect XV1830-0EH10 bus cable Standard type with special design for fast mounting, 2-core, shielded, sold by the meter; max. delivery unit m, minimum ordering quantity 20 m /20 Siemens ST

21 Central processing units SIPLUS S7-400 Standard CPUs SIPLUS S7-400 CPU 412 The low-cost introduction to the mid performance range Can be used in small and medium-sized plants with requirements in the mid performance range Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added. For further technical documentation on SIPLUS, see: Technical specifications Based on Ambient conditions Ambient temperature in operation Min. Max. Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Relative humidity - With condensation, tested in accordance with IEC , max. Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN AG1412-2EK0-2AB0 ES7412-2EK0-0AB0 SIPLUS S7-400 CPU PN V -25 C; = Tmin 70 C; = 0 C for UL/ATEX/FM use Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. Article No. SIPLUS S7-400 CPU PN CPU with main memory 1 MB (0.5 MB code and 0.5 MB data), 2 interfaces: 1x MPI/DP and PN each Extended temperature range and AG1412-2EK0-2AB0 exposure to media Accessories Memory Card RAM Exposure to media 2 MB AG1952-1AL00-4AA0 Extended temperature range and exposure to media 4 MB AG1952-1AM00-7AA0 8 MB AG1952-1AP00-7AA0 1 MB AG1952-1AS00-7AA0 4 MB AG1952-1AY00-7AA0 RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Extended temperature range and exposure to media without PG interface AG1972-0BA12-2XA0 With PG interface AG1972-0BB12-2XA0 RS 485 bus connector with angled cable outlet Max. transmission rate 12 Mbit/s Extended temperature range and exposure to media Without PG interface AG1972-0BA42-7XA0 With PG interface AG1972-0BB42-7XA0 RS 485 bus connector with axial cable outlet For SIPLUS OP, for connection to PPI, MPI, PROFIBUS Extended temperature range and AG1500-0EA02-2AA0 exposure to media Further accessories see SIMATIC S7-400 CPU 412, page /7 Siemens ST /21

22 Central processing units SIPLUS S7-400 Standard CPUs SIPLUS S7-400 CPU 414 CPUs for high demands in the mid-level performance range Applicable for plants with additional demands on programming scope and processing speed Integrated PROFINET functions in CPU PN/DP Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added. For further technical documentation on SIPLUS, see: Technical specifications Based on Ambient conditions Ambient temperature in operation Min. max. Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude AG1414-3EM0-7AB0 ES7414-3EM0-0AB0 SIPLUS S7-400 CPU PN/DP V -25 C; = Tmin 70 C; = Tmax Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) Relative humidity - With condensation, max. 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. Article No. SIPLUS S7-400 CPU PN/DP CPU with main memory 4 MB (1 MB code and 1 MB data), 3 interfaces: 1x MPI/DP, PN each and for IF94-DP (plug-in) Extended temperature range and AG1414-3EM0-7AB0 exposure to media Accessories Memory Card RAM see SIPLUS S7-400 CPU 412, page /21 IF 94-DP interface module AG194-2AA04-7AB0 For connecting an additional DP line; for SIPLUS CPU PN/DP, CPU 41-3, CPU 41-3 PN/DP, CPU RS 485 bus connector with 90 cable outlet RS 485 bus connector with angled cable outlet RS 485 bus connector with axial cable outlet see SIPLUS S7-400 CPU 412, page /21 see SIPLUS S7-400 CPU 412, page /21 see SIPLUS S7-400 CPU 412, page /21 RS 485 repeater for PROFIBUS Transfer rate up to 12 Mbit/s; 24 V DC; IP20 enclosure Extended temperature range and AG1972-0AA02-7XA0 exposure to media SIPLUS SCALANCE X204-2 Industrial Ethernet Switch with integral SNMP access, Web diagnostics, copper cable diagnostics and PROFINET diagnostics for configuring line, star and ring topologies; four 10/100 Mbit/s RJ45 ports and two FO ports Extended temperature range and AG1204-2BB10-4AA3 exposure to media IE FC RJ45 Plug cable outlet; 1 unit Extended temperature range and AG1901-1BB10-7AA0 exposure to media Further accessories see SIMATIC S7-400 CPU 414, page /11 /22 Siemens ST

23 Central processing units SIPLUS S7-400 Standard CPUs SIPLUS S7-400 CPU 41 High-performance CPUs in the high-end performance range Applicable for plants with high requirements in the high-end performance range Integrated PROFINET functions in CPU 41-3 PN/DP Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added. For technical documentation on SIPLUS, see: Technical specifications AG141-3XR05-4AB0 AG141-3ES0-7AB0 Based on ES741-3XR05-0AB0 ES741-3ES0-0AB0 SIPLUS S7-400 CPU41-3 SIPLUS S7-400 CPU 41-3 PN/DP V Ambient conditions Ambient temperature in operation Min. 0 C; = Tmin -25 C; = Tmin max. 0 C; = Tmax 70 C; = Tmax Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) Relative humidity - With condensation, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75 %) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75%) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. Article No. SIPLUS S7-400 CPU 41-3 CPU with main memory 11.2 MB (5. MB code and 5. MB data), 3 interfaces: 1x MPI/DP, DP each and module slot for 1 IF module Exposure to media SIPLUS S7-400 CPU 41-3 PN/DP CPU with main memory 1 MB (8 MB code and 8 MB data), 3 interfaces: 1x MPI/DP, PN each and module slot for 1 IF module Extended temperature range and exposure to media AG141-3XR05-4AB0 AG141-3ES0-7AB0 SIPLUS accessories see SIPLUS S7-400 CPU 414, page /22 Further accessories see SIMATIC S7-400 CPU 41, page /1 Siemens ST /23

24 Central processing units SIPLUS S7-400 Standard CPUs SIPLUS S7-400 CPU 417 The most powerful SIMATIC S7-400 CPU Applicable for plants with maximum requirements in the high-end performance range With 2 plug-in slots for IF modules Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. For technical documentation on SIPLUS, see: Technical specifications Based on Ambient conditions Ambient temperature in operation Min. max. Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude AG1417-4XT05-4AB0 ES7417-4XT05-0AB0 SIPLUS S7-400 CPU C; = Tmin 0 C; = Tmax Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) Relative humidity - With condensation, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75 %) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. Article No. SIPLUS CPU CPU with main memory 30 MB (15 MB code and 15 MB data), 3 interfaces: 1x MPI/DP, DP each and 2x for IFM modules (plug-in) Exposure to media AG1417-4XT05-4AB0 Accessories Memory card RAM See SIPLUS S7-400 CPU 412, page /21 FEPROM memory card Exposure to media 32 MB AG1952-1KT00-4AA0 RS 485 bus connector with 90 cable outlet RS 485 bus connector with angled cable outlet RS 485 bus connector with axial cable outlet RS 485 repeater for PROFIBUS Transfer rate up to 12 Mbit/s; 24 V DC; IP20 enclosure Extended temperature range and exposure to media See SIPLUS S7-400 CPU 412, page /21 See SIPLUS S7-400 CPU 412, page /21 See SIPLUS S7-400 CPU 412, page /21 AG1972-0AA02-7XA0 Further accessories See SIMATIC CPU 417, page /20 /24 Siemens ST

25 Technical specifications ES7414-3FM0-0AB0 CPU414F-3 PN/DP, 4 MB, 3 INTERFACES Product type designation General information Engineering with Programming package STEP7 V5.5 or higher / imap V3.0 + imap STEP7 Add-on V3.0 SP5 Supply voltage Rated value (DC) 24 V DC No; Power supply via system power supply Power losses Power loss, typ..5 W Memory Work memory Integrated 4Mbyte integrated (for program) 2Mbyte integrated (for data) 2Mbyte Load memory expandable FEPROM, max. 4 Mbyte integrated RAM, max. 512 kbyte expandable RAM, max. 4 Mbyte CPU processing times for bit operations, typ. 45 ns for word operations, typ. 45 ns for fixed point arithmetic, typ. 45 ns for floating point arithmetic, typ. 135 ns Counters, timers and their retentivity S7 counter Number 2048 IEC counter present S7 times Number 2048 IEC timer present Central processing units Fail-safe CPUs CPU 414F For constructing a fail-safe automation system for plants with increased safety requirements CPUs for high demands in the mid-level performance range Applicable for plants with additional demands on programming scope and processing speed Complies with safety requirements to SIL 3 acc. to IEC 1508 and PL e acc. to ISO Standard and safety-related tasks can be performed with a single CPU Integrated PROFINET functions in CPU 414F-3 PN/DP Multi-processor mode is possible Safety-related communication with distributed I/O devices over PROFIBUS DP or PROFINET IO with PROFIsafe profile Fail-safe I/O modules can be connected in a distributed manner via the integrated interfaces (DP and PN with CPU 41F-3 PN/DP) and/or through communication modules (CP Extended and CP Adv.) Central and distributed use of standard modules for non-safety-oriented applications Data areas and their retentivity Flag Number, max. ES7414-3FM0-0AB0 CPU414F-3 PN/DP, 4 MB, 3 INTERFACES 8 kbyte; Size of bit memory address area Address area I/O address area Inputs 8kbyte Outputs 8kbyte Process image Inputs, adjustable 8kbyte Outputs, adjustable 8kbyte Hardware configuration Slots Required slots 2 Time of day Clock Hardware clock (real-time clock) Operating hours counter Number 1 Interfaces Number of RS 485 interfaces 2 Number of other interfaces 0 1st interface Interface type Integrated Physics RS 485 / PROFIBUS + MPI Functionality MPI DP master DP slave Siemens ST /25

26 Central processing units Fail-safe CPUs CPU 414F Technical specifications (continued) ES7414-3FM0-0AB0 CPU414F-3 PN/DP, 4 MB, 3 INTERFACES DP master Number of DP slaves, max. 32 2nd interface Interface type PROFINET Physics Ethernet RJ45 Number of ports 2 Functionality DP master No DP slave No PROFINET IO Controller PROFINET IO Device PROFINET CBA PROFINET IO Controller Max. number of connectable 25 IO devices for RT Number of IO devices with IRT and 25 the option "high flexibility" Number of IO Devices with IRT and 4 the option "high performance", max. 3rd interface Interface type Pluggable interface module (IF) Plug-in interface modules IF 94-DP (MLFB: ES794-2AA04-0AB0) Physics RS 485 / PROFIBUS Functionality MPI No DP master DP slave DP master Number of DP slaves, max. 9 Isochronous mode Isochronous operation (application synchronized up to terminal) Communication functions PG/OP communication Data record routing Global data communication supported S7 basic communication supported S7 communication supported S5-compatible communication supported Standard communication (FMS) supported Open IE communication TCP/IP ; Via PROFIBUS DP or PROFINET interface ; Via FC AG_SEND and AG_RECV, max. via 10 CP or ; Via CP and loadable FB ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 2 ISO-on-TCP (RFC100) ; Via integrated PROFINET interface or CP Adv. and loadable FBs - Number of connections, max. 2 UDP ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 2 ES7414-3FM0-0AB0 CPU414F-3 PN/DP, 4 MB, 3 INTERFACES Web server supported Number of connections overall 4 Configuration Programming Programming language -LAD -FBD -STL -SCL -CFC -GRAPH - HiGraph Know-how protection User program protection/password protection Block encryption ; With S7 block Privacy Dimensions Width 50 mm Height 290 mm Depth 219 mm Weights Weight, approx. 900 g /2 Siemens ST

27 Central processing units Fail-safe CPUs Ordering data Article No. Article No. CPU 414F CPU 414F-3 PN/DP ES7414-3FM0-0AB0 For setting up safety-related automation system; main memory 4 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFINET interface, slot for memory card, module slot for 1 IF module, incl. slot number labels Distributed Safety V5.4 programming tool Task: Engineering tool for configuring fail-safe user programs for SIMATIC S7-300F, S7-400F, WinAC RTX F, ET 200S, ET 200M, ET 200iSP, ET 200pro, ET 200eco Requirement: STEP 7 V5.3 SP3 and higher Floating license ES7833-1FC02-0YA5 Floating license for 1 user, license ES7833-1FC02-0YH5 key download without software or documentation 1) ; address required for delivery Distributed Safety Upgrade ES7833-1FC02-0YE5 From V5.x to V5.4; Floating license for 1 user STEP 7 Safety Advanced V13 Task: Engineering tool for configuring fail-safe user programs for SIMATIC S7-1500F, S7-300F, S7-400F, WinAC RTX F, ET200SP, ET 200S, ET 200M, ET 200iSP, ET 200pro, ET 200eco Requirement: STEP 7 Professional V13 Floating license for 1 user ES7833-1FA13-0YA5 Floating license for 1 user, license ES7833-1FA13-0YH5 key download without software or documentation 1) ; address required for delivery Memory Card RAM 4 KB ES7952-0AF00-0AA0 25 KB ES7952-1AH00-0AA0 1 MB ES7952-1AK00-0AA0 2 MB ES7952-1AL00-0AA0 4 MB ES7952-1AM00-0AA0 8 MB ES7952-1AP00-0AA0 1 MB ES7952-1AS00-0AA0 4 MB ES7952-1AY00-0AA0 FEPROM memory card 4 KB ES7952-0KF00-0AA0 25 KB ES7952-0KH00-0AA0 1 MB ES7952-1KK00-0AA0 2 MB ES7952-1KL00-0AA0 4 MB ES7952-1KM00-0AA0 8 MB ES7952-1KP00-0AA0 1 MB ES7952-1KS00-0AA0 32 MB ES7952-1KT00-0AA0 4 MB ES7952-1KY00-0AA0 MPI cable ES7901-0BF00-0AA0 for connection of SIMATIC S7 and PG via MPI; 5 m in length IF 94-DP interface module ES794-2AA04-0AB0 For connecting an additional DP line Slot number plates ES7912-0AA00-0AA0 1 set (spare part) SIMATIC Manual Collection ES7998-8XC01-8YE0 Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection ES7998-8XC01-8YE2 update service for 1 year Current "Manual Collection" DVD and the three subsequent updates PROFIBUS bus components RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA12-0XA0 With PG interface ES7972-0BB12-0XA0 RS 485 bus connector with angled cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA42-0XA0 With PG interface ES7972-0BB42-0XA0 RS 485 bus connector with 90 cable outlet for FastConnect system Max. transfer rate 12 Mbit/s Without PG interface - 1 unit ES7972-0BA52-0XA0-100 units ES7972-0BA52-0XB0 With PG interface - 1 unit ES7972-0BB52-0XA0-100 units ES7972-0BB52-0XB0 1) For up-to-date information and download availability, see: Siemens ST /27

28 Central processing units Fail-safe CPUs CPU 414F Ordering data Article No. Article No. RS 485 bus connector with axial cable outlet For SIMATIC OP, for connection to PPI, MPI, PROFIBUS PROFIBUS FastConnect bus cable Standard type with special design for quick mounting, 2-core, shielded, sold by the meter, max. delivery unit 1000 m, minimum ordering quantity 20 m RS 485 repeater for PROFIBUS Transmission rate up to 12 Mbit/s; 24 V DC; IP20 enclosure PROFINET bus components IE FC TP standard cable GP 2x2 4-core, shielded TP installation cable for connection to IE FC Outlet RJ45/ IE FC RJ45 Plug; PROFINET-compatible; with UL approval; Sold by the meter FO Standard Cable GP (50/125) Standard cable, splittable, UL approval, sold by the meter GK1500-0EA02 XV1830-0EH10 ES7972-0AA02-0XA0 XV1840-2AH10 XV1873-2A SCALANCE X204-2 Industrial GK5204-2BB10-2AA3 Ethernet Switch Industrial Ethernet Switches with integral SNMP access, Web diagnostics, copper cable diagnostics and PROFINET diagnostics for configuring line, star and ring topologies; four 10/100 Mbit/s RJ45 ports and two FO ports IE FC RJ45 plugs RJ45 plug connector for Industrial Ethernet with a rugged metal enclosure and integrated insulation displacement contacts for connecting Industrial Ethernet FC installation cables IE FC RJ45 plug cable outlet 1 unit GK1901-1BB10-2AA0 10 units GK1901-1BB10-2AB0 50 units GK1901-1BB10-2AE0 PROFIBUS/PROFINET See IK PI, CA 01 catalogs bus components For establishing MPI/PROFIBUS/ PROFINET communication /28 Siemens ST

29 Central processing units Fail-safe CPUs CPU 41F For constructing a fail-safe automation system for plants with increased safety requirements High-performance CPU in the top-end performance range Complies with safety requirements to SIL 3 acc. to IEC 1508 and PL e acc. to ISO Standard and safety-related tasks can be performed with a single CPU Multi-processor mode is possible Safety-related communication with distributed I/O devices over PROFIBUS DP with the PROFIsafe profile Fail-safe I/O modules can be connected decentralized over the integrated interfaces (DP and PN with CPU41F-3 PN/DP) and/or through communication modules (CP443-5 Ext. and CP443-1 Adv.) Standard modules for non-safety-related applications can be operated centrally and decentralized Technical specifications ES741-2FN05-0AB0 ES741-3FS0-0AB0 CPU 41F-2, MPI, PROFIBUS, 5. MB CPU41F-3 PN/DP, 1 MB, 3 INTERFACES Product type designation General information Engineering with Programming package STEP 7 V5.3 SP2 or higher with hardware update, Distributed Safety V5.2 SP2 or higher STEP7 V5.5 or higher / imap V3.0 + imap STEP7 Add-on V3.0 SP5 or higher Supply voltage Rated value (DC) 24 V DC No; Power supply via system power supply No; Power supply via system power supply Power losses Power loss, typ. 4.5 W.5 W Memory Work memory Integrated 5. Mbyte 1 Mbyte integrated (for program) 2.8 Mbyte 8Mbyte integrated (for data) 2.8 Mbyte 8Mbyte Load memory expandable FEPROM, max. 4 Mbyte 4 Mbyte integrated RAM, max. 1Mbyte 1Mbyte expandable RAM, max. 4 Mbyte 4 Mbyte CPU processing times for bit operations, typ. 30 ns 30 ns for word operations, typ. 30 ns 30 ns for fixed point arithmetic, typ. 30 ns 30 ns for floating point arithmetic, typ. 90 ns 90 ns Counters, timers and their retentivity S7 counter Number IEC counter present S7 times Number IEC timer present Data areas and their retentivity Flag Number, max. 1 kbyte; Size of bit memory address area 1 kbyte; Size of bit memory address area Siemens ST /29

30 Central processing units Fail-safe CPUs CPU 41F Technical specifications (continued) ES741-2FN05-0AB0 ES741-3FS0-0AB0 CPU 41F-2, MPI, PROFIBUS, 5. MB CPU41F-3 PN/DP, 1 MB, 3 INTERFACES Address area I/O address area Inputs 1 kbyte 1 kbyte Outputs 1 kbyte 1 kbyte Process image Inputs, adjustable 1 kbyte 1 kbyte Outputs, adjustable 1 kbyte 1 kbyte Hardware configuration Slots Required slots 1 2 Time of day Clock Hardware clock (real-time clock) Operating hours counter Number 1 1 Interfaces Number of RS 485 interfaces 2 2 Number of other interfaces 0 0 1st interface Interface type Integrated Integrated Physics RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI Functionality MPI DP master DP slave DP master Number of DP slaves, max nd interface Interface type Integrated PROFINET Physics RS 485 / PROFIBUS Ethernet RJ45 Number of ports 2 Functionality DP master No DP slave No PROFINET IO Controller PROFINET IO Device PROFINET CBA DP master Number of DP slaves, max. 125 PROFINET IO Controller Max. number of connectable IO 25 devices for RT Number of IO devices with IRT and 25 the option "high flexibility" Number of IO Devices with IRT and 4 the option "high performance", max. 3rd interface Interface type Pluggable interface module (IF) Plug-in interface modules IF 94-DP (MLFB: ES794-2AA04-0AB0) Physics RS 485 / PROFIBUS Functionality MPI No DP master DP slave DP master Number of DP slaves, max. 125 /30 Siemens ST

31 Central processing units Fail-safe CPUs CPU 41F Technical specifications (continued) ES741-2FN05-0AB0 ES741-3FS0-0AB0 CPU 41F-2, MPI, PROFIBUS, 5. MB CPU41F-3 PN/DP, 1 MB, 3 INTERFACES Isochronous mode Isochronous operation (application ; For PROFIBUS only ; Via PROFIBUS DP or PROFINET interface synchronized up to terminal) Communication functions PG/OP communication Data record routing Global data communication supported S7 basic communication supported S7 communication supported S5-compatible communication supported ; Via FC AG_SEND and AG_RECV, max. via 10 CP or ; Via FC AG_SEND and AG_RECV, max. via 10 CP or Standard communication (FMS) supported ; Via CP and loadable FB ; Via CP and loadable FB Open IE communication TCP/IP ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 94 ISO-on-TCP (RFC100) Via CP and loadable FB ; Via integrated PROFINET interface or CP and loadable FBs - Number of connections, max. 94 UDP ; via integrated PROFINET interface and loadable FBs - Number of connections, max. 94 Web server supported No Number of connections overall 4 9 Configuration Programming Programming language -LAD -FBD -STL -SCL -CFC - GRAPH - HiGraph Know-how protection User program protection/password protection Block encryption ; With S7 block Privacy Dimensions Width 25 mm 50 mm Height 290 mm 290 mm Depth 219 mm 219 mm Weights Weight, approx. 0.7 kg 900 g Siemens ST /31

32 Central processing units Fail-safe CPUs CPU 41F Ordering data Article No. Article No. CPU 41F-2 ES741-2FN05-0AB0 For configuring safety-related automation systems; 5. MB RAM, 24 V DC power supply, MPI/PROFIBUS DP master interface, PROFIBUS DP master interface, slot for memory card, incl. slot number labels CPU 41F-3 PN/DP ES741-3FS0-0AB0 For configuring safety-related automation systems; main memory 1 MB, 24 V DC power supply, MPI/PROFIBUS DP master interface, PROFINET interface, PROFIBUS DP master interface, receptacle for 1 IF module, slot for memory card, incl. slot number labels S7 Distributed Safety V5.4 programming tool Task: Engineering tool for configuring fail-safe user programs for SIMATIC S7-300F, S7-400F, WinAC RTX F, ET 200SP, ET 200S, ET 200M, ET 200iSP, ET 200pro, ET 200eco Requirement: STEP 7 V5.3 SP3 and higher Floating license ES7833-1FC02-0YA5 Floating license for 1 user, license ES7833-1FC02-0YH5 key download without software or documentation 1) ; address required for delivery S7 Distributed Safety upgrade ES7833-1FC02-0YE5 From V5.x to V5.4; Floating license for 1 user STEP 7 Safety Advanced V13 Task: Engineering tool for configuring fail-safe user programs for SIMATIC S7-1500F, S7-300F, S7-400F, WinAC RTX F, ET200SP, ET 200S, ET 200M, ET 200iSP, ET 200pro, ET 200eco Requirement: STEP 7 Professional V13 Floating license for 1 user ES7833-1FA13-0YA5 Floating license for 1 user, ES7833-1FA13-0YH5 license key download without software or documentation 1) ; address required for delivery Memory card RAM 4 KB ES7952-0AF00-0AA0 25 KB ES7952-1AH00-0AA0 1 MB ES7952-1AK00-0AA0 2 MB ES7952-1AL00-0AA0 4 MB ES7952-1AM00-0AA0 8 MB ES7952-1AP00-0AA0 1 MB ES7952-1AS00-0AA0 4 MB ES7952-1AY00-0AA0 FEPROM memory card 4 KB ES7952-0KF00-0AA0 25 KB ES7952-0KH00-0AA0 1 MB ES7952-1KK00-0AA0 2 MB ES7952-1KL00-0AA0 4 MB ES7952-1KM00-0AA0 8 MB ES7952-1KP00-0AA0 1 MB ES7952-1KS00-0AA0 32 MB ES7952-1KT00-0AA0 4 MB ES7952-1KY00-0AA0 MPI cable ES7901-0BF00-0AA0 For connection of SIMATIC S7 and PG via MPI; 5 m in length IF 94-DP interface module ES794-2AA04-0AB0 For connecting an additional DP line Slot number plates ES7912-0AA00-0AA0 1 set (spare part) SIMATIC Manual Collection ES7998-8XC01-8YE0 Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC-based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection ES7998-8XC01-8YE2 update service for 1 year Current "Manual Collection" DVD and the three subsequent updates PROFIBUS bus components RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s without PG interface ES7972-0BA12-0XA0 with PG interface ES7972-0BB12-0XA0 RS 485 bus connector with angled cable outlet Max. transfer rate 12 Mbit/s without PG interface ES7972-0BA42-0XA0 with PG interface ES7972-0BB42-0XA0 RS 485 bus connector with 90 cable outlet for FastConnect system Max. transfer rate 12 Mbit/s without PG interface - 1 unit ES7972-0BA52-0XA0-100 units ES7972-0BA52-0XB0 with PG interface - 1 unit ES7972-0BB52-0XA0-100 units ES7972-0BB52-0XB0 RS 485 bus connector GK1500-0EA02 with axial cable outlet For SIMATIC OP, for connection to PPI, MPI, PROFIBUS 1) For up-to-date information and download availability, see: /32 Siemens ST

33 Central processing units Fail-safe CPUs Ordering data Article No. Article No. CPU 41F PROFIBUS FastConnect bus cable Standard type with special design for fast mounting, 2-core, shielded, sold by the meter; max. delivery unit m, minimum ordering quantity 20 m RS 485 repeater for PROFIBUS Transfer rate up to 12 Mbps; 24 V DC; IP20 enclosure PROFINET bus components IE FC TP standard cable GP 2x2 4-core, shielded TP installation cable for connection to IE FC Outlet RJ45/ IE FC RJ45 Plug; PROFINET-compatible; with UL approval; Sold by the meter FO Standard Cable GP (50/125) Standard cable, splittable, UL approval, sold by the meter XV1830-0EH10 ES7972-0AA02-0XA0 XV1840-2AH10 XV1873-2A SCALANCE X204-2 GK5204-2BB10-2AA3 Industrial Ethernet Switch Industrial Ethernet Switches with integral SNMP access, Web diagnostics, copper cable diagnostics and PROFINET diagnostics for configuring line, star and ring topologies; four 10/100 Mbps RJ45 ports and two FO ports IE FC RJ45 plugs RJ45 plug connector for Industrial Ethernet with a rugged metal enclosure and integrated insulation displacement contacts for connecting Industrial Ethernet FC installation cables IE FC RJ45 plug cable outlet 1 unit GK1901-1BB10-2AA0 10 units GK1901-1BB10-2AB0 50 units GK1901-1BB10-2AE0 PROFIBUS/PROFINET See IK PI, CA 01 catalogs bus components For establishing MPI/PROFIBUS/ PROFINET communication Siemens ST /33

34 Central processing units High-availability CPUs CPU 412-5H, CPU 414-5H, CPU 41-5H, CPU 417-5H CPU for SIMATIC S7-400H and S7-400F/FH Can be used in S7-400H high-availability systems Can be used with F runtime license as F-capable CPU in S7-400F/FH safety-related systems With integrated PROFIBUS DP master and combined MPI/PROFIBUS DP master interface With integrated PROFINET interface (2-port switch) Features 2 slots for sync modules Technical specifications ES7412-5HK0-0AB0 ES7414-5HM0-0AB0 ES741-5HS0-0AB0 ES7417-5HT0-0AB0 Product type designation General information Engineering with Programming package Supply voltage Rated value (DC) 24 V DC CPU412-5H PN/DP, 1MB F. S7-400H/F/FH As of STEP 7 V5.5 SP2 with HF1 No; Power supply via system power supply CPU414-5H PN/DP, 4MB F. S7-400H/F/FH As of STEP 7 V5.5 SP2 with HF1 No; Power supply via system power supply CPU41-5H PN/DP, 1MB F. S7-400H/F/FH As of STEP 7 V5.5 SP2 with HF1 No; Power supply via system power supply CPU417-5H PN/DP, 32MB F. S7-400H/F/FH As of STEP 7 V5.5 SP2 with HF1 Power losses Power loss, typ. 7.5 W 7.5 W 7.5 W 7.5 W Memory Work memory Integrated 1Mbyte 4Mbyte 1 Mbyte 32 Mbyte integrated (for program) 512 kbyte 2Mbyte Mbyte 1 Mbyte integrated (for data) 512 kbyte 2Mbyte 10 Mbyte 1 Mbyte Load memory expandable FEPROM, max. 4 Mbyte 4 Mbyte 4 Mbyte 4 Mbyte integrated RAM, max. 512 kbyte 512 kbyte 1Mbyte 1Mbyte expandable RAM, max. 4 Mbyte 4 Mbyte 4 Mbyte 4 Mbyte CPU processing times for bit operations, typ ns ns 12.5 ns 7.5 ns for word operations, typ ns ns 12.5 ns 7.5 ns for fixed point arithmetic, typ ns ns 12.5 ns 7.5 ns for floating point arithmetic, typ. 2.5 ns 37.5 ns 25 ns 15 ns Counters, timers and their retentivity S7 counter Number IEC counter present S7 times Number IEC timer present Data areas and their retentivity Flag Number, max. 8192byte 8192byte byte byte No; Power supply via system power supply /34 Siemens ST

35 Central processing units High-availability CPUs CPU 412-5H, CPU 414-5H, CPU 41-5H, CPU 417-5H Technical specifications (continued) ES7412-5HK0-0AB0 ES7414-5HM0-0AB0 ES741-5HS0-0AB0 ES7417-5HT0-0AB0 Address area I/O address area Inputs 8kbyte 8kbyte 1 kbyte 1 kbyte Outputs 8kbyte 8kbyte 1 kbyte 1 kbyte Process image Inputs, adjustable 8kbyte 8kbyte 1 kbyte 1 kbyte Outputs, adjustable 8kbyte 8kbyte 1 kbyte 1 kbyte Hardware configuration Slots Required slots Time of day Clock Hardware clock (real-time clock) Operating hours counter Number Interfaces Number of RS 485 interfaces Number of other interfaces 2; Fiber-optic interface 2; Fiber-optic interface 2; Fiber-optic interface 2; Fiber-optic interface 1st interface Interface type Integrated Integrated Integrated Integrated Physics RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI Functionality MPI DP master DP slave No No No No DP master Number of DP slaves, max nd interface Interface type PROFINET PROFINET PROFINET PROFINET Physics Ethernet RJ45 Ethernet RJ45 Ethernet RJ45 Ethernet RJ45 Number of ports Functionality DP master No No No No DP slave No No No No PROFINET IO Controller PROFINET IO Device No No No No PROFINET CBA No No No No PROFINET IO Controller Max. number of connectable IO devices for RT 3rd interface Interface type Integrated Integrated Integrated Integrated Physics RS 485 / PROFIBUS RS 485 / PROFIBUS RS 485 / PROFIBUS RS 485 / PROFIBUS Functionality DP master DP slave No No No No DP master Number of DP slaves, max th interface Interface type Pluggable synchronization submodule (FO) Pluggable synchronization submodule (FO) Pluggable synchronization submodule (FO) Pluggable synchronization submodule (FO) Plug-in interface modules CPU412-5H PN/DP, 1MB F. S7-400H/F/FH Synchronization modules ES790-1AA0-0XA0 or ES790-1AB0-0XA0 CPU414-5H PN/DP, 4MB F. S7-400H/F/FH Synchronization modules ES790-1AA0-0XA0 or ES790-1AB0-0XA0 CPU41-5H PN/DP, 1MB F. S7-400H/F/FH Synchronization modules ES790-1AA0-0XA0 or ES790-1AB0-0XA0 CPU417-5H PN/DP, 32MB F. S7-400H/F/FH Synchronization modules ES790-1AA0-0XA0 or ES790-1AB0-0XA0 Siemens ST /35

36 Central processing units High-availability CPUs CPU 412-5H, CPU 414-5H, CPU 41-5H, CPU 417-5H Technical specifications (continued) ES7412-5HK0-0AB0 ES7414-5HM0-0AB0 ES741-5HS0-0AB0 ES7417-5HT0-0AB0 5. Interface Interface type Plug-in interface modules Pluggable synchronization submodule (FO) Synchronization modules ES790-1AA0-0XA0 or ES790-1AB0-0XA0 Pluggable synchronization submodule (FO) Synchronization modules ES790-1AA0-0XA0 or ES790-1AB0-0XA0 Pluggable synchronization submodule (FO) Synchronization modules ES790-1AA0-0XA0 or ES790-1AB0-0XA0 Pluggable synchronization submodule (FO) Synchronization modules ES790-1AA0-0XA0 or ES790-1AB0-0XA0 Isochronous mode Isochronous operation (application No No No No synchronized up to terminal) Communication functions PG/OP communication Data record routing S7 routing Global data communication supported No No No No S7 basic communication supported No No No No S7 communication supported S5-compatible communication supported ; (via CP max. 10 and FC AG_SEND and FC AG_RECV) ; (via CP max. 10 and FC AG_SEND and FC AG_RECV) ; (via CP max. 10 and FC AG_SEND and FC AG_RECV) ; (via CP max. 10 and FC AG_SEND and FC AG_RECV) Standard communication (FMS) supported ; Via CP and loadable FB ; Via CP and loadable FB ; Via CP and loadable FB ; Via CP and loadable FB Open IE communication TCP/IP ; via integrated PROFINET interface and loadable FBs ; via integrated PROFINET interface and loadable FBs ; via integrated PROFINET interface and loadable FBs ; via integrated PROFINET interface and loadable FBs - Number of connections, max ISO-on-TCP (RFC100) ; Via integrated PROFINET interface or CP and loadable FBs ; Via integrated PROFINET interface or CP and loadable FBs ; Via integrated PROFINET interface or CP and loadable FBs ; Via integrated PROFINET interface or CP and loadable FBs - Number of connections, max UDP CPU412-5H PN/DP, 1MB F. S7-400H/F/FH ; via integrated PROFINET interface and loadable FBs CPU414-5H PN/DP, 4MB F. S7-400H/F/FH ; via integrated PROFINET interface and loadable FBs CPU41-5H PN/DP, 1MB F. S7-400H/F/FH ; via integrated PROFINET interface and loadable FBs CPU417-5H PN/DP, 32MB F. S7-400H/F/FH ; via integrated PROFINET interface and loadable FBs - Number of connections, max Web server supported No No No No Number of connections overall Configuration Programming Programming language -LAD -FBD -STL -SCL -CFC - GRAPH - HiGraph Know-how protection User program protection/password protection Block encryption ; With S7 block Privacy ; With S7 block Privacy ; With S7 block Privacy ; With S7 block Privacy Dimensions Width 50 mm 50 mm 50 mm 50 mm Height 290 mm 290 mm 290 mm 290 mm Depth 219 mm 219 mm 219 mm 219 mm Weights Weight, approx. 995 g 995 g 995 g 995 g /3 Siemens ST

37 Central processing units High-availability CPUs CPU 412-5H, CPU 414-5H, CPU 41-5H, CPU 417-5H Ordering data Article No. Article No. CPU 412-5H For S7-400H and S7-400F/FH; 1 MB RAM, 1 combined MPI/ PROFIBUS DP master interface, 1 PROFIBUS DP interface, 2 PROFINET interfaces (switches), 2 slots for sync modules, slot for memory card, incl. slot number labels ES7412-5HK0-0AB0 CPU 417-5H For S7-400H and S7-400F/FH; 32 MB RAM, 1 combined MPI/ PROFIBUS DP master interface, 1 PROFIBUS DP interface, 2 PROFINET interfaces (switches), 2 slots for sync modules, slot for memory card, incl. slot number labels ES7417-5HT0-0AB0 CPU 412-5H system bundle Not assembled, consisting of: UR2-H rack, 2 x PS 405/407 power supply units, 2 x CPU 412-5H, 4 x sync modules (for max. 10 m), 2 x fiber optic cables for sync modules (1 m), 4 x backup batteries; two additional memory cards required (to be ordered separately) CPU 412-5H system bundle, 120/230 V AC, 10 A CPU 412-5H system bundle, 24/48/0 V DC, 10 A CPU 414-5H For S7-400H and S7-400F/FH; 4 MB RAM, 1 combined MPI/ PROFIBUS DP master interface, 1 PROFIBUS DP interface, 2 PROFINET interfaces (switches), 2 slots for sync modules, slot for memory card, incl. slot number labels CPU 414-5H system bundle Not assembled, consisting of: UR2-H rack, 2 x PS 405/407 power supply units, 2 x CPU 414-5H, 4 x sync modules (for max. 10 m), 2 x fiber optic cables for sync modules (1 m), 4 x backup batteries; additional two memory cards required (to be ordered separately) CPU 414-5H system bundle, 120/230 V AC, 10 A CPU 414-5H system bundle, 24/48/0 V DC, 10 A CPU 41-5H For S7-400H and S7-400F/FH; 1 MB RAM, 1 combined MPI/ PROFIBUS DP master interface, 1 PROFIBUS DP interface, 2 PROFINET interfaces (switches), 2 slots for sync modules, slot for memory card, incl. slot number labels CPU 41-5H system bundle Not assembled, consisting of: UR2-H rack, 2 x PS 405/407 power supply units, 2 x CPU 41-5H, 4 x sync modules (for max. 10 m), 2 x fiber optic cables for sync modules (1 m), 4 x backup batteries; two additional memory cards required (to be ordered separately) CPU 41-5H system bundle, 120/230 V AC, 10 A CPU 41-5H system bundle, 24/48/0 V DC, 10 A ES7400-0HR01-4AB0 ES7400-0HR51-4AB0 ES7414-5HM0-0AB0 ES7400-0HR02-4AB0 ES7400-0HR52-4AB0 ES741-5HS0-0AB0 ES7400-0HR03-4AB0 ES7400-0HR53-4AB0 CPU 417-5H system bundle Not assembled, consisting of: UR2-H rack, 2 x PS 405/407 power supply units, 2 x CPU 417-5H, 4 x sync modules (for max. 10 m), 2 x fiber optic cables for sync modules (1 m), 4 x backup batteries; two additional memory cards required (to be ordered separately) CPU 417-5H system bundle, ES7400-0HR04-4AB0 120/230 V AC, 10 A CPU 417-5H system bundle, ES7400-0HR54-4AB0 24/48/0 V DC, 10 A Memory card RAM 1 MB ES7952-1AK00-0AA0 2 MB ES7952-1AL00-0AA0 4 MB ES7952-1AM00-0AA0 8 MB ES7952-1AP00-0AA0 1 MB ES7952-1AS00-0AA0 4 MB ES7952-1AY00-0AA0 FEPROM memory card 1 MB ES7952-1KK00-0AA0 2 MB ES7952-1KL00-0AA0 4 MB ES7952-1KM00-0AA0 8 MB ES7952-1KP00-0AA0 1 MB ES7952-1KS00-0AA0 32 MB ES7952-1KT00-0AA0 4 MB ES7952-1KY00-0AA0 MPI cable ES7901-0BF00-0AA0 For connection of SIMATIC S7 and PG via MPI; 5 m in length Slot number plates ES7912-0AA00-0AA0 1 set (spare part) S7 F Systems RT License ES7833-1CC00-YX0 For processing safety-related user programs, for one S7-400H-based system each with CPU 412-5H, CPU 414-5H, CPU 41-5H or CPU 417-5H S7 F Systems V.1 ES7833-1CC02-0YA5 Programming and configuring environment for creating and operating safety-related STEP 7 programs for an S7-400H-based target system, floating license for 1 user, runs with Windows XP Prof SP2, Windows XP Prof SP2/SP3, Windows Server 2003 SP2 2 languages (English, German) Type of delivery: Certificate of License as well as software and electronic documentation on CD Siemens ST /37

38 Central processing units High-availability CPUs CPU 412-5H, CPU 414-5H, CPU 41-5H, CPU 417-5H Ordering data Article No. Article No. S7 F systems upgrade from V5.x/V.0 to V.1 2 languages (English, German), floating license for 1 user Type of delivery: Certificate of License as well as software and electronic documentation on CD SIMATIC Manual Collection Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC-based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection update service for 1 year Current "Manual Collection" DVD and the three subsequent updates ES7833-1CC02-0YE5 ES7998-8XC01-8YE0 ES7998-8XC01-8YE2 RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA12-0XA0 With PG interface ES7972-0BB12-0XA0 RS 485 bus connector with angled cable outlet Max. transfer rate 12 Mbit/s - Without PG interface ES7972-0BA42-0XA0 - With PG interface ES7972-0BB42-0XA0 Max. transfer rate 1.5 Mbit/s - Without PG interface ES7972-0BA30-0XA0 Bus connector RS 485 with 90 cable outlet for FastConnect connection technology Max. transfer rate 12 Mbit/s Without PG interface -1 unit ES7972-0BA52-0XA0-100 units ES7972-0BA52-0XB0 With PG interface -1 unit ES7972-0BB52-0XA0-100 units ES7972-0BB52-0XB0 RS 485 bus connector with axial cable outlet For SIMATIC OP, for connection to PPI, MPI, PROFIBUS GK1500-0EA02 PROFIBUS FastConnect bus cable Standard type with special design for quick mounting, 2-core, shielded, sold by the meter, max. delivery unit 1000 m, minimum ordering quantity 20 m XV1830-0EH10 /38 Siemens ST

39 Central processing units High-availability CPUs Sync-module for coupling the CPU 41xH For coupling the two CPU 41xH in the S7-400H subunits. Can be plugged direct into the CPU Technical specifications ES790-1AA0-0XA0 ES790-1AB0-0XA0 S7 SYNC-MOD. V F. S7-400H/F/FH S7 SYNC-MOD. V F. S7-400H/F/FH Product type designation Input current from CPU, max. 220 ma 240 ma Power losses Power loss, typ W 0.83 W Dimensions Width 13 mm 13 mm Height 14 mm 14 mm Depth 58 mm 58 mm Weights Weight, approx. 14 g 14 g Ordering data Article No. Article No. Sync module For coupling the CPU 41xH for S7-400H/F/FH; 2 modules required per CPU For patch cable, can be used with fiber-optic cables up to 10 m For patch and installation cables, can be used with fiber-optic cables up to 10 km ES790-1AA0-0XA0 ES790-1AB0-0XA0 Fiber-optic connecting cable For sync module ES790-1AA0-0XA0 1 m ES790-1AA04-5AA0 2 m ES790-1AA04-5BA0 10 m ES790-1AA04-5KA0 For Sync module On request ES790-1AB0-0XA0; fiber-optic monomode LC/LC duplex crossed 9/125 µ (max. 10 km) Siemens ST /39

40 Central processing units High-availability CPUs Y-link for S7-400H Transceiver for the transition from a redundant PROFIBUS DP master system to a single-channel PROFIBUS DP master system To connect devices with a single PROFIBUS DP interface to the redundant PROFIBUS DP master system of the SIMATIC S7-400H Technical specifications Product type designation General information Vendor identification (VendorID) Supply voltage Rated value (DC) 24 V DC permissible range, lower limit (DC) permissible range, upper limit (DC) permissible range (ripple included), lower limit (DC) permissible range (ripple included), upper limit (DC) External protection for supply cables (recommendation) Mains buffering Mains/voltage failure stored energy time Input current Current consumption, max. Inrush current, typ. I²t Output voltage Rated value (DC) Output current for backplane bus (5 V DC), max. Power losses Power loss, typ. Address area Addressing volume Inputs Outputs Hardware configuration Number of modules per DP slave interface, max. ES7153-2BA02-0XB0 ET200M, INTERFACE IM153-2 HF 801Eh 20.4 V 28.8 V 20.4 V 28.8 V 2,5 A 5ms 00 ma 3A 0.1 A² s 5V 1.5 A 5.5 W 244 byte 244 byte 12 Time stamping Accuracy Number of message buffers 15 Messages per message buffer 20 Number of stampable digital inputs, max. ES7153-2BA02-0XB0 ET200M, INTERFACE IM153-2 HF 1 ms; 1ms at up to 8 modules; 10ms at up to 12 modules 128; Max. 128 signals / station; max. 32 signals / slot Time format RFC 1119 Time resolution 0.4 ns Time interval for transmitting the 1000ms message buffer if a message is present Time stamp on signal change rising / falling edge as signal entering or exiting Interfaces Interface physics, RS 485 Interface physics, FOC No PROFIBUS DP Node addresses 1 to 125 permitted Automatic detection of transmission speed Output current, max. 70 ma Transmission rate, max. 12 Mbit/s Transmission procedure RS 485 SYNC capability FREEZE capability Direct data exchange (slave-toslave ; Sender communication) Connector type 9-pin sub D 1st interface DP slave GSD file SI04801.GSG Automatic baud rate search Protocols Bus protocol/transmission protocol PROFIBUS DP to EN Isolation Isolation checked with Isolation voltage 500 V Degree and class of protection Degree of protection to EN 0529 IP20 /40 Siemens ST

41 Central processing units High-availability CPUs Y-link for S7-400H Technical specifications (continued) ES7153-2BA02-0XB0 ET200M, INTERFACE IM153-2 HF Ambient conditions Ambient temperature in operation Min. 0 C max. 0 C Air pressure acc. to IEC Operating altitude above sea level, 3000m max. Configuration Configuration software STEP 7 ; STEP 7 / COM PROFIBUS / non-siemens tools via GSD file Dimensions Width 40 mm Height 125 mm Depth 117 mm Weights Weight, approx. 30 g ES7197-1LB00-0XA0 Y-COUPLER F. BUILDING Y-LINK, REDUNDANT Product type designation General information Requirements for DP master system Length of parameter assignment 244 byte message Supply voltage Description via bus module permissible range, lower limit (DC) 20.4 V permissible range, upper limit (DC) 28.8 V Interfaces PROFIBUS DP Properties of the lower-level DP master systems - Transmission rate, max. 12 Mbit/s; kbit/s to 12 Mbit/s - Termination of lower-level DP master system Active terminating resistor (Bus Terminator) - Use of OLM/OBT - Use of RS 485 repeaters, max. 9 - Number of DP slaves, max. 31; 4 when using RS 485 repeaters or OLM/OBT Protocols PROFIBUS DP AS-Interface No Interrupts/diagnostics/ status information Status indicator No Alarms Alarms No Diagnostic messages Diagnostic functions Galvanic isolation to lower-level DP master system Dimensions Width 40 mm Height 125 mm Depth 130 mm Weights Weight, approx. 200 g Ordering data Article No. Article No. For use with STEP 7 from V5.4 or SIMATIC PCS 7 from V7.0 For use with SIMATIC PCS 7 V.0 or higher Y link For connecting single-channel DP slaves to SIMATIC S7-400H; consisting of: 2 IM 153 interface modules (ES7153-2BA02-0XB0), 1 Y-coupler (ES7197-1LB00-0XA0), 1 BM IM/IM bus module (ES7195-7HD80-0XA0), 1 BM Y-coupler bus module (ES754-7HY00-0XA0) ES7197-1LA04-0XA0 Y link For connecting single-channel DP slaves to SIMATIC S7-400H; consisting of: 2 IM 153 interface modules (ES7153-2BA82-0XB0), 1 Y-coupler (ES7197-1LB00-0XA0), 1 BM IM/IM bus module (ES7195-7HD80-0XA0), 1 BM Y-coupler bus module (ES754-7HY00-0XA0) ES7197-1LA11-0XA0 Accessories Mounting rail For assembling the Y link with active bus modules Length 483 mm Length 530 mm ES7195-1GA00-0XA0 ES7195-1GF30-0XA0 Siemens ST /41

42 Central processing units SIPLUS S7-400 high-availability CPUs SIPLUS S7-400 CPU 412H CPU for SIMATIC S7-400H and S7-400F/FH Usable in high-availability systems such as the S7-400H Usable with F runtime license as F-capable CPU in S7-400F/FH safety-related systems Features a combined MPI/PROFIBUS DP master interface Features 2 slots for sync modules Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. Technical specifications AG1412-5HK0-7AB0 Based on ES7412-5HK0-0AB0 SIPLUS S7-400 CPU 412-5H Ambient conditions Ambient temperature in operation Min. -25 C; = Tmin max. 70 C Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Relative humidity - With condensation, tested in accordance with IEC , max. Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m). For "F-Systems" applications max m above sea level permissible 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75 %) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. Article No. SIPLUS S7-400 CPU 412-5H CPU for S7-400H with 1 MB RAM (0.5 MB code and 0.5 MB data); 5 interfaces: 1x MPI/DP, DP, PN each and 2 slots for sync modules Extended temperature range and AG1412-5HK0-7AB0 exposure to media Accessories Memory card RAM (medial exposure) 2 MB AG1952-1AL00-4AA0 Extended temperature range and exposure to media 4 MB AG1952-1AM00-7AA0 8 MB AG1952-1AP00-7AA0 1 MB AG1952-1AS00-7AA0 4 MB AG1952-1AY00-7AA0 FEPROM memory card Exposure to media 32 MB AG1952-1KT00-4AA0 RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Extended temperature range and exposure to media Without PG interface AG1972-0BA12-2XA0 With PG interface AG1972-0BB12-2XA0 RS 485 bus connector with angled cable outlet Max. transmission rate 12 Mbit/s Extended temperature range and exposure to media Without PG interface With PG interface RS 485 bus connector with axial cable outlet For SIPLUS OP, for connection to PPI, MPI, PROFIBUS Extended temperature range and exposure to media RS 485 repeater for PROFIBUS Transfer rate up to 12 Mbit/s; 24 V DC; IP20 enclosure Extended temperature range and exposure to media Additional accessories AG1972-0BA42-7XA0 AG1972-0BB42-7XA0 AG1500-0EA02-2AA0 AG1972-0AA02-7XA0 See SIMATIC CPU 412-5H, page /37 /42 Siemens ST

43 Central processing units SIPLUS S7-400 high-availability CPUs SIPLUS S7-400 CPU 414H CPU for SIMATIC S7-400H and S7-400F/FH Usable in high-availability systems such as the S7-400H Usable with F runtime license as F-capable CPU in S7-400F/FH safety-related systems With integral PROFIBUS DP master interface Features 2 slots for sync modules Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. Technical specifications AG1414-5HM0-7AB0 Based on ES7414-5HM0-0AB0 SIPLUS S7-400 CPU 414-5H Ambient conditions Ambient temperature in operation Min. -25 C max. 70 C; For "F-Systems" applications max. +0 C permissible Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m). For "F-Systems" applications max m above sea level permissible Relative humidity - With condensation, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75 %) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. Article No. SIPLUS S7-400 CPU 414-5H CPU for S7-400H with 4 MB RAM (2 MB code and 2 MB data); 5 interfaces: 1x MPI/DP, DP, PN each and 2 slots for sync modules Extended temperature range and AG1414-5HM0-7AB0 exposure to media Accessories Memory Card RAM Exposure to media 2 MB AG1952-1AL00-4AA0 Extended temperature range and exposure to media 4 MB AG1952-1AM00-7AA0 8 MB AG1952-1AP00-7AA0 1 MB AG1952-1AS00-7AA0 4 MB AG1952-1AY00-7AA0 FEPROM memory card Exposure to media 32 MB AG1952-1KT00-4AA0 RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Extended temperature range and exposure to media Without PG interface AG1972-0BA12-2XA0 With PG interface AG1972-0BB12-2XA0 RS 485 bus connector with angled cable outlet Max. transmission rate 12 Mbit/s Extended temperature range and exposure to media Without PG interface AG1972-0BA42-7XA0 With PG interface AG1972-0BB42-7XA0 RS 485 bus connector with axial cable outlet For SIPLUS OP, for connection to PPI, MPI, PROFIBUS Extended temperature range and AG1500-0EA02-2AA0 exposure to media RS 485 repeater for PROFIBUS Transfer rate up to 12 Mbit/s; 24 V DC; IP20 enclosure Extended temperature range and AG1972-0AA02-7XA0 exposure to media Additional accessories see SIMATIC S7-400 CPU 414-5H, page /37 Siemens ST /43

44 Central processing units SIPLUS S7-400 high-availability CPUs SIPLUS S7-400 CPU 41H CPU for SIMATIC S7-400H and S7-400F/FH Usable in high-availability systems such as the S7-400H Usable with F runtime license as F-capable CPU in S7-400F/FH safety-related systems With integrated PROFIBUS DP master and combined MPI/ PROFIBUS DP master interface With integrated PROFINET interface (2-port switch) Features 2 slots for sync modules Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. Technical specifications Based on Ambient conditions Ambient temperature in operation Min. max. Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude AG141-5HS0-7AB0 ES741-5HS0-0AB0 SIPLUS S7-400 CPU 41-5H -25 C; = Tmin 70 C; For "F-Systems" applications max. +0 C permissible Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m). For "F-Systems" applications max m above sea level permissible Relative humidity - With condensation, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. SIPLUS S7-400 CPU 41-5H AG141-5HS0-7AB0 (medial exposure) CPU for S7-400H with 1 MB RAM ( MB code and 10 MB data); 5 interfaces: 1x MPI/DP, DP, PN each and 2 slots for sync modules Accessories Memory card RAM Exposure to media 2 MB AG1952-1AL00-4AA0 Extended temperature range and exposure to media 4 MB AG1952-1AM00-7AA0 8 MB AG1952-1AP00-7AA0 1 MB AG1952-1AS00-7AA0 4 MB AG1952-1AY00-7AA0 FEPROM memory card Exposure to media 32 MB AG1952-1KT00-4AA0 RS 485 bus connector with 90 cable outlet Max. transmission rate 12 Mbit/s Extended temperature range and exposure to media Without PG interface AG1972-0BA12-2XA0 With PG interface AG1972-0BB12-2XA0 RS 485 bus connector with angled cable outlet Max. transmission rate 12 Mbit/s Extended temperature range and exposure to media Without PG interface AG1972-0BA42-7XA0 With PG interface AG1972-0BB42-7XA0 RS 485 bus connector with axial cable outlet For SIPLUS OP, for connection to PPI, MPI, PROFIBUS Extended temperature range and AG1500-0EA02-2AA0 exposure to media RS 485 repeater for PROFIBUS Transfer rate up to 12 Mbit/s; 24 V DC; IP20 enclosure Extended temperature range and AG1972-0AA02-7XA0 exposure to media Additional accessories see SIMATIC S7-400 CPU 41-5H, page /37 /44 Siemens ST

45 Central processing units SIPLUS S7-400 high-availability CPUs SIPLUS S7-400 CPU 417H CPU for SIMATIC S7-400H and S7-400F/FH Usable in high-availability systems such as the S7-400H Usable with F runtime license as F-capable CPU in S7-400F/FH safety-related systems With integral PROFIBUS DP master interface Features 2 slots for sync modules Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. Technical specifications AG1417-5HT0-7AB0 Based on ES7417-5HT0-0AB0 SIPLUS S7-400 CPU 417-5H Ambient conditions Ambient temperature in operation Min. -25 C max. 70 C; For "F-Systems" applications max. +0 C permissible Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m). For "F-Systems" applications max m above sea level permissible Relative humidity - With condensation, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. SIPLUS S7-400 CPU 417-5H CPU for S7-400H with 32 MB RAM (1 MB code and 1 MB data); 5 interfaces: 1x MPI/DP, DP, PN each and 2 slots for sync modules Extended temperature range and AG1417-5HT0-7AB0 exposure to media SIPLUS accessories see SIPLUS S7-400 CPU 41H, page /45 Additional accessories see SIMATIC S7-400 CPU 417-5H, page /37 Siemens ST /45

46 Central processing units SIPLUS S7-400 high-availability CPUs SIPLUS sync module for connecting the CPU 41xH For linking the two CPUs 414-4H/417-4H in the subunits of the S7-400H Can be plugged directly into the CPU Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. Technical specifications AG190-1AA0-7XA0 AG190-1AB0-7XA0 Based on ES790-1AA0-0XA0 ES790-1AB0-0XA0 SIPLUS S7-400H IF90-H 10M SIPLUS S7-400H IF90-H 10KM Ambient conditions Ambient temperature in operation Min. -25 C -25 C max. 70 C 70 C Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) Relative humidity - With condensation, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75 %) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75 %) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. Article No. SIPLUS sync module V Extended temperature range and exposure to media for patch cable, can be used with fiber-optic cables up to 10 m for patch and installation cables, can be used with fiber-optic cables up to 10 km AG190-1AA0-7XA0 AG190-1AB0-7XA0 SIPLUS S7-400 FO CABLE 1 m long AG190-1AA04-7AA0 2 m long AG190-1AA04-7BA0 10 m long AG190-1AA04-7KA0 /4 Siemens ST

47 Central processing units SIPLUS S7-400 high-availability CPUs SIPLUS Y-Link for S7-400H Bus coupler for transition from a redundant PROFIBUS DP master system to a single-channel PROFIBUS DP master system For connection of devices with only one PROFIBUS DP interface to the redundant PROFIBUS DP master system of the SIMATIC S7-400H Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. For technical documentation on SIPLUS, see: Technical specifications Based on Ambient conditions Ambient temperature in operation Min. max. Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude AG1197-1LA11-4XA0 ES7197-1LA11-0XA0 SIPLUS S7-400 Y-LINK FOR S7-400H 0 C; = Tmin 0 C; = Tmax Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) Relative humidity - With condensation 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75 %) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. Article No. For use with STEP 7 from V5.4 or PCS 7 from V7.0: SIPLUS Y-Link for S7-400H Accessories SIPLUS S7 BUS MODULE BM Y-coupler for connecting single-channel DP slaves to SIMATIC S7-400H; consisting of 2 IM 153 interface modules, 1 Y-coupler, 1 BM IM/IM bus module, 1 BM Y-coupler bus module Exposure to media AG1197-1LA11-4XA0 to accommodate a Y-coupler incl. bus module cover Extended temperature range and exposure to media Further accessories AG154-7HY00-7XA0 See SIMATIC Y-Link, page /41 Siemens ST /47

48 Central processing units Interface modules PROFIBUS module IF-94 DP To connect distributed I/Os over PROFIBUS DP Max. transmission rate 12 Mbit/s Electrically isolated RS 485 interface Connection via 9-pin sub-d connector The following connection options are available for each S7-400 CPU: - A PROFIBUS module in the CPUs 414-3, 414(F)-3 PN/DP, 41-3, 41(F)-3 PN/DP - Two PROFIBUS modules in the CPU Note: Can only be used with CPUs ES7414-3XM05-0AB0, ES7414-3EM05-0AB0, ES7414-3EM0-0AB0, ES7414-3FM0-0AB0, ES741-3XR05-0AB0, ES741-3ER05-0AB0, ES741-3ES0-0AB0, ES741-3FS0-0AB0 and ES7417-4XT05-0AB0. Technical specifications Product type designation Input current from CPU, max. ES794-2AA04-0AB0 INTERFACE MOD. DP-MASTER F. S ma; Current consumption from S7-400 bus: The module uses no current at 24 V, it provides this voltage only at the DP interface. Total current consumption of the components connected to the DP interface, but maximum 150 ma. Current carrying capacity of the isolated 5 V (P5ext) maximum 90 ma, current carrying capacity of the 24 V maximum 150 ma. Power losses Power loss, typ. 1W Interfaces PROFIBUS DP Cable length - Cable length, max m; At 9. kbit/s: max m; at 12 Mbit/s: max. 100 m 1st interface Physics RS 485 Isolated Functionality DP master ; Default setting DP slave DP master Transmission rate, min. 9. kbit/s Transmission rate, max. 12 Mbit/s Number of DP slaves, max. 125; depending on the CPU used Services - PG/OP communication - Equidistance mode support - SYNC/FREEZE - Direct data exchange (slave-to-slave communication) Address area - Inputs, max. device-dependent -Outputs, max. device-dependent User data per DP slave - Inputs, max. 244 byte -Outputs, max. 244 byte Communication functions Number of connections overall device-dependent Dimensions Width 2 mm Height 54 mm Depth 130 mm Weights Weight, approx. 5 g Ordering data IF 94-DP interface module Interface module with integrated PROFIBUS DP master interface Article No. ES794-2AA04-0AB0 /48 Siemens ST

49 Central processing units SIPLUS S7-400 interface modules SIPLUS S7-400 interface modules Technical specifications To connect distributed I/O via PROFIBUS DP Max. transmission rate 12 Mbit/s Electrically isolated RS 485 interface Connection via 9-pin Sub-D socket One or two PROFIBUS modules can be plugged in for each S7-400 CPU: - CPU 414-3/41-3: 1 module - CPU 417-4: 2 modules Based on Ambient conditions Ambient temperature in operation Min. max. Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Notes: Can only be used with the CPUs AG141-3XR05-4AB0, AG141-3ER05-4AB0 and AG1417-4XT05-4AB0. SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added. For further technical documentation on SIPLUS, see: Ordering data AG194-2AA04-7AB0 ES794-2AA04-0AB0 SIPLUS S7-400 IF94-DP -25 C; = Tmin 70 C; = Tmax Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) Relative humidity - With condensation, max. 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN SIPLUS interface module IF-94 DP Interface module with integrated PROFIBUS DP master interface Extended temperature range and exposure to media ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Article No. AG194-2AA04-7AB0 Siemens ST /49

50 Digital modules SM 421 digital input module Digital inputs for the SIMATIC S7-400 For connecting standard switches and two-wire proximity switches (BERO) Technical specifications ES7421-7BH01-0AB0 ES7421-1BL01-0AA0 ES7421-1EL00-0AA0 SM421, 32DI, DC/AC 120V ES7421-1FH20-0AA0 SM421, 1DE, UC120/230V SM421, 1DI, DC24V, SM421, 32DI, DC24V 0.05MS INPUT DELAY Product type designation Supply voltage Load voltage L+ Rated value (DC) 24 V permissible range, lower limit (DC) 20.4 V permissible range, upper limit (DC) 28.8 V Input current from backplane bus 5 V DC, max. 130 ma 20 ma 200 ma 80 ma 150 ma from supply voltage L+, max. 120 ma Power losses ES7421-7DH00-0AB0 SM421, 1DE, UC24-0V Power loss, max. 5W W 1 W 12 W 8 W; 3.5 W (24 V DC);.5 W (48 V DC); 8.0 W (0 V DC) Digital inputs Number of digital inputs Number of simultaneously controllable inputs all mounting positions - up to 40 C, max up to 0 C, max Input voltage Type of input voltage DC DC AC/DC AC/DC AC/DC Rated value (DC) 24 V 24 V Rated value (UC) 120 V 230 V; 120/230 V UC 24 V; 24 to 0 V UC for signal "0" -30 V DC to +5 V DC -30 V DC to +5 V DC 0 to 20 V UC 0 to 40 V AC/ -40 to +40 V DC for signal "1" 11 V DC to 30 V DC 13 V DC to 30 V DC 79 to 132 V AC; 80 to 132 V DC 74 to 24 V AC; 80 to 24 V DC, -80 to -24 V - to + V DC/ 0 to 5 V AC 15 to 72 V DC; -15 to -72 V DC; 15 to 0 V AC Frequency range Hz Hz 47 to 3 Hz AC / DC /50 Siemens ST

51 Digital modules SM 421 digital input module Technical specifications (continued) Input current for signal "0", max. (permissible quiescent current) 1.3 ma 1mA ma; AC: ma; DC: 2 ma for signal "1", typ. ma;... 8 ma 7mA 2 ma; ma 10 ma; at 120 V: 10 ma AC, 1.8 ma DC; at 230 V: 14 ma AC, 2 ma DC 4 ma; ma Input delay (for rated value of input voltage) for standard inputs - Parameterizable - nominal 0.5 ms; 0.5 / 3 / 10 / 20 ms Cable length shielded, max m; 1000 m/3 ms; 1000m m m 1000m 70 m/0.5 ms; 30 m/0.1 ms; 30 m/0.05 ms Unshielded, max. ES7421-7BH01-0AB0 SM421, 1DI, DC24V, 0.05MS INPUT DELAY 00 m; 00 m: 3 ms; 50 m: 0,5 ms; 20 m: 0,1 ms; 20 m: 0,05 ms ES7421-1BL01-0AA0 SM421, 32DI, DC24V ES7421-1EL00-0AA0 SM421, 32DI, DC/AC 120V ES7421-1FH20-0AA0 SM421, 1DE, UC120/230V ES7421-7DH00-0AB0 SM421, 1DE, UC24-0V 00 m 00 m 00 m 00 m; 00 m: 3, 10, 20 ms; 100 m: 0,5 ms Encoder Connectable encoders 2-wire sensor - Permissible quiescent current 3mA 1.5 ma 1mA 5 ma; AC: 5 ma 0.5 ma; 0.5 to 2 ma (2-wire sensor), max. Interrupts/diagnostics/ status information Alarms Diagnostic alarm ; Parameterizable ; Parameterizable Hardware interrupt ; Parameterizable ; Parameterizable Diagnostic messages Diagnostics ; internal/ external fault ; internal/ external fault Galvanic isolation Galvanic isolation digital inputs between the channels, in groups of between the channels and the backplane bus Isolation Isolation checked with 500 V DC 500 V DC 1500 V AC 1500 V AC 1500 V AC Dimensions Width 25 mm 25 mm 25 mm 25 mm 25 mm Height 290 mm 290 mm 290 mm 290 mm 290 mm Depth 210 mm 210 mm 210 mm 210 mm 210 mm Weights Weight, approx. 00 g 500 g 00 g 50 g 00 g Siemens ST /51

52 Digital modules SM 421 digital input module Ordering data Article No. Article No. SM 421 digital input modules 1 inputs, 24 V DC, ES7421-7BH01-0AB0 with process/diagnostics interrupt 32 inputs, 24 V DC ES7421-1BL01-0AA0 32 inputs, 120 V AC/DC ES7421-1EL00-0AA0 1 inputs, 120/230 V AC/DC, inputs ES7421-1FH20-0AA0 according to IEC Type 2 Labeling sheets for machine inscription DIN A4, for printing using laser printer; pack of 10 petrol light-beige yellow ES7492-2AX00-0AA0 ES7492-2BX00-0AA0 ES7492-2CX00-0AA0 1 inputs, 24 to 0 V AC/DC, with process/diagnostics interrupt Front connector 48-pin with screw contacts, 1 unit with screw contacts, 84 units with spring-loaded terminals, 1 unit with crimp contacts, 1 unit with crimp contacts, 84 units Cover film for labeling strips Spare part ES7421-7DH00-0AB0 ES7492-1AL00-0AA0 ES7492-1AL00-1AB0 ES7492-1BL00-0AA0 ES7492-1CL00-0AA0 ES7492-1CL00-1AB0 ES7492-2XX00-0AA0 red SIMATIC Manual Collection Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection update service for 1 year Current "Manual Collection" DVD and the three subsequent updates ES7492-2DX00-0AA0 ES7998-8XC01-8YE0 ES7998-8XC01-8YE2 /52 Siemens ST

53 Digital modules SM 422 digital output module Digital outputs for the SIMATIC S7-400 For connecting solenoid valves, contactors, low-power motors, lamps and motor starters Technical specifications ES7422-1FH00-0AA0 SM422, 1DO, AC120/230V, 2A ES7422-1HH00-0AA0 SM422, 1DO, AC5-230V, 5A RELAY ES7422-1BH11-0AA0 SM422, 1DO, DC24V, 2A ES7422-1BL00-0AA0 SM422, 32DO, DC24V, 0,5A ES7422-7BL00-0AB0 SM422, 32DO, DC24V, 0,5A Product type designation Supply voltage Load voltage L+ Rated value (DC) 0 V 24 V 24 V 24 V permissible range, lower limit (DC) 1V 20.4 V 20.4 V 20.4 V permissible range, upper limit (DC) 0 V 28.8 V 28.8 V 28.8 V Load voltage L1 Rated value (AC) 230 V; 120/230V AC 230 V permissible range, lower limit (AC) 79 V 2V 20.4 V permissible range, upper limit (AC) 24 V 24 V 28.8 V Input current from load voltage L+ (without load), 1.5 ma 30 ma 30 ma 120 ma max. from load voltage L1 (without load), ma max. from backplane bus 5 V DC, max. 400 ma 1A 10 ma 200 ma 200 ma Power losses Power loss, max. 1 W 25 W 7W 4W 8W Digital outputs Number of digital outputs 1 1; Relays Limitation of inductive shutdown -30 V -27 V L+ (-45 V) voltage to Switching capacity of the outputs on lamp load, max. 50 W 0 W 10 W 5W 5W Output voltage for signal "1", min. L1 (-18.1 V) L+ (-0.5 V) L+ (-0.3 V) L+ (-0.8 V) Siemens ST /53

54 Digital modules SM 422 digital output module Technical specifications (continued) Output current for signal "1" rated value 2A 5A 2A 0.5 A 0.5 A for signal "1" permissible range 10 ma 5mA 5mA 5mA for 0 to 0 C, min. for signal "1" permissible range 2.4 A 0. A 0. A for 0 to 0 C, max. for signal "0" residual current, max. 2. ma 0.5 ma 0.3 ma 0.5 ma Switching frequency with resistive load, max. 10 Hz 10 Hz 100 Hz 100 Hz 100 Hz with inductive load, max. 0.5 Hz 0.1 Hz 0.5 Hz 2Hz Aggregate current of outputs (per group) all mounting positions - up to 0 C, max. 2 A; 5 A with fan subassembly; per 4 adjacent outputs 5 ma; 10 A with fan subassembly 2 A; 2 adjacent outputs each 2 A; 8 adjacent outputs each 2A Relay outputs ES7422-1FH00-0AA0 SM422, 1DO, AC120/230V, 2A ES7422-1HH00-0AA0 SM422, 1DO, AC5-230V, 5A RELAY ES7422-1BH11-0AA0 SM422, 1DO, DC24V, 2A ES7422-1BL00-0AA0 SM422, 32DO, DC24V, 0,5A ES7422-7BL00-0AB0 SM422, 32DO, DC24V, 0,5A Number of operating cycles, max ; (AC 15 / DC 13); mechanical Switching capacity of contacts - with inductive load, max. 5 A; 5 A (30 V DC); 5 A (230 V AC) - with resistive load, max. 5 A; 5 A (30 V DC); 5 A (230 V AC); 1.2 A (0 V DC); 0.2 A (125 V DC) Cable length shielded, max. 1000m 1000m m m 1000m Unshielded, max. 00 m 00 m 00 m 00 m 00 m Interrupts/diagnostics/ status information Alarms Diagnostic alarm ; Parameterizable Diagnostic messages Diagnostics ; internal/ external fault Galvanic isolation Galvanic isolation digital outputs between the channels, in groups of between the channels and the backplane bus Isolation Isolation checked with 1500 V AC 1500 V AC 500 V DC 500 V DC 500 V DC Dimensions Width 25 mm 25 mm 25 mm 25 mm 25 mm Height 290 mm 290 mm 290 mm 290 mm 290 mm Depth 210 mm 210 mm 210 mm 210 mm 210 mm Weights Weight, approx. 800 g 700 g 00 g 00 g 00 g /54 Siemens ST

55 Digital modules Ordering data Article No. Article No. SM 422 digital output module SM 422 digital output modules 1 outputs, 24 V DC; 2 A ES7422-1BH11-0AA0 32 outputs, 24 V DC; 0.5 A ES7422-1BL00-0AA0 32 outputs, 24 V DC, 0.5 A; ES7422-7BL00-0AB0 with diagnostics 1 outputs, 120/230 V AC; 2 A ES7422-1FH00-0AA0 1 outputs, relay contacts ES7422-1HH00-0AA0 Front connector 48-pin with screw contacts, 1 unit ES7492-1AL00-0AA0 with screw contacts, 84 units ES7492-1AL00-1AB0 with spring-loaded terminals, ES7492-1BL00-0AA0 1 unit with crimp contacts, 1 unit ES7492-1CL00-0AA0 with crimp contacts, 84 units ES7492-1CL00-1AB0 Cover film for labeling strips ES7492-2XX00-0AA0 Spare part Labeling sheets for machine inscription DIN A4, for printing using laser printer; pack of 10 petrol light-beige yellow red SIMATIC Manual Collection Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection update service for 1 year Current "Manual Collection" DVD and the three subsequent updates ES7492-2AX00-0AA0 ES7492-2BX00-0AA0 ES7492-2CX00-0AA0 ES7492-2DX00-0AA0 ES7998-8XC01-8YE0 ES7998-8XC01-8YE2 Siemens ST /55

56 SIPLUS S7-400 digital modules SIPLUS S7-400 SM 421 digital input modules Digital inputs for SIMATIC S7-400 For connection of switches and 2-wire proximity switches (BEROs) Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. For technical documentation on SIPLUS, see: Technical specifications AG1421-1BL01-2AA0 Based on ES7421-1BL01-0AA0 SIPLUS S7-400 SM421 32DE Product type designation Input current from backplane bus 5 V DC, max. 20 ma Power losses Power loss, max. W Digital inputs Number of digital inputs 32 Number of simultaneously controllable inputs all mounting positions - up to 40 C, max up to 0 C, max. 32 Input voltage Type of input voltage DC Rated value (DC) 24 V for signal "0" -30 V DC to +5 V DC for signal "1" 13 V DC to 30 V DC Input current for signal "0", max. 1.3 ma (permissible quiescent current) for signal "1", typ. 7mA Cable length shielded, max. 1000m Unshielded, max. 00 m Encoder Connectable encoders 2-wire sensor - Permissible quiescent current 1.5 ma (2-wire sensor), max. Galvanic isolation Galvanic isolation digital inputs between the channels, in groups of 32 between the channels and the backplane bus Isolation Isolation checked with 500 V DC Dimensions Width 25 mm Height 290 mm Depth 210 mm Weights Weight, approx. 500 g Ordering data Article No. SIPLUS S7-400 SM 421 digital input module 32 inputs, 24 V DC Extended temperature range and AG1421-1BL01-2AA0 exposure to media Accessories See SIMATIC S7-400 digital input modules, page /52 /5 Siemens ST

57 SIPLUS S7-400 digital modules SIPLUS S7-400 SM 422 digital output modules Digital outputs for SIMATIC S7-400 For connecting solenoid valves, contactors, small-power motors, lamps and motor starters Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. For technical documentation on SIPLUS, see: Technical specifications AG1422-1BL00-2AA0 Based on ES7422-1BL00-0AA0 SIPLUS S7-400 SM422 32DA Product type designation Digital outputs Number of digital outputs 32 Limitation of inductive shutdown -27 V voltage to Output voltage for signal "1", min. L+ (-0.3 V) Output current for signal "1" rated value 0.5 A for signal "1" permissible range 5mA for 0 to 0 C, min. for signal "1" permissible range 0. A for 0 to 0 C, max. Aggregate current of outputs (per group) all mounting positions - up to 0 C, max. 2 A; 8 adjacent outputs each Galvanic isolation Galvanic isolation digital outputs between the channels, in groups of 32 between the channels and the backplane bus Dimensions Width 25 mm Height 290 mm Depth 210 mm Weights Weight, approx. 00 g Ordering data Article No. SIPLUS S7-400 SM 422 digital output module 32 outputs, 24 V DC Extended temperature range and AG1422-1BL00-2AA0 exposure to media Accessories See SIMATIC S7-400 digital output modules, page /55 Siemens ST /57

58 Analog modules SM 431 analog input module Analog inputs for the SIMATIC S7-400 For connection of voltage and current sensors, thermocouples, resistors and resistance thermometers Resolution from 13 to 1 bit Technical specifications ES7431-0HH00-0AB0 ES7431-1KF20-0AB0 ES7431-1KF00-0AB0 ES7431-1KF10-0AB0 SM431, 1AE, +/-10V, SM431, 8AE, U/I/R, 14BIT, SM431, 8AE, U/I/R, 13BIT SM431, 8AE, U/I/R, 14BIT +/-20MA, 4-20MA 0,41MS ZYKL Product type designation Supply voltage Load voltage L+ Rated value (DC) 24 V; Only required for 24 V; Only required for not necessary supplying 2-wire transmitters supplying 2-wire transmitters Reverse polarity protection Input current from load voltage L+ (without load), max. 400 ma; for 1 connected, fully controlled 2-wire transmitters 200 ma; for 8 connected, fully controlled 2-wire transmitters from backplane bus 5 V DC, max. 100 ma 1000mA 350 ma 00 ma Power losses Power loss, typ. 2W 4.9 W 1.8 W 3.5 W Hardware configuration Slots Required slots Analog inputs Number of analog inputs For voltage/current measurement For resistance measurement permissible input voltage for voltage input (destruction limit), max. 20 V; 20 V DC permanent, 75 V DC for max. 1 s (duty factor 1:20) 18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) 24 V; Only required for supplying 2-wire transmitters 200 ma; for 8 connected, fully controlled 2-wire transmitters 50 V 18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) permissible input current for current 40 ma 40 ma; Permanent 50 ma; 40 ma continuous 40 ma; Permanent input (destruction limit), max. Input ranges (rated values), voltages 1 V to 5 V -1 V to +1 V -10 V to +10 V -2.5 V to +2.5 V -250 mv to +250 mv -5 V to +5 V -500 mv to +500 mv -80 mv to +80 mv /58 Siemens ST

59 Analog modules SM 431 analog input module Technical specifications (continued) ES7431-0HH00-0AB0 ES7431-1KF20-0AB0 ES7431-1KF00-0AB0 ES7431-1KF10-0AB0 SM431, 1AE, +/-10V, +/-20MA, 4-20MA SM431, 8AE, U/I/R, 14BIT, 0,41MS ZYKL SM431, 8AE, U/I/R, 13BIT SM431, 8AE, U/I/R, 14BIT Input ranges (rated values), currents 0 to 20 ma -20 ma to +20 ma 4 ma to 20 ma Input ranges (rated values), thermoelements Type B Type E Type J Type K Type L Type N Type R Type S Type T Type U Input ranges (rated values), resistance thermometer Ni 100 Ni 1000 Pt 100 Pt 1000 Pt Pt 200 Pt 500 Input ranges (rated values), resistors 0 to 150 ohms 0 to 300 ohms 0 to 48 ohms 0 to 00 ohms 0 to 000 ohms ; Usable up to 5000 ohms Thermocouple (TC) Temperature compensation - internal temperature No compensation - external temperature compensation with compensations socket - external temperature compensation with Pt100 - dynamic reference temperature value Characteristic linearization Parameterizable - for thermocouples Type B, E, J, K, L, N, R, S, T, U - for resistance thermometer Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000 Cable length shielded, max. 200 m 200 m 200 m 200 m; 50 m with thermocouples and input ranges <= 80 mv Siemens ST /59

60 Analog modules SM 431 analog input module Technical specifications (continued) ES7431-0HH00-0AB0 ES7431-1KF20-0AB0 ES7431-1KF00-0AB0 ES7431-1KF10-0AB0 SM431, 1AE, +/-10V, SM431, 8AE, U/I/R, 14BIT, SM431, 8AE, U/I/R, 13BIT SM431, 8AE, U/I/R, 14BIT +/-20MA, 4-20MA 0,41MS ZYKL Analog value creation Integration and conversion time/ resolution per channel Resolution with overrange (bit including sign), max. 13 bit 14 bit; 14 / 14 / bit 14 bit; with activated filtering: 1 bits Integration time, parameterizable Basic conversion time (ms) 55 / 5 ms 52 µs 23 / 25 ms 20.1 / 23.5 ms Integration time (ms) 50 / 0 ms 1,7 / 20 ms 1,7 / 20 ms Basic conversion time, including integration time (ms) - additional conversion time 4,3 ms for wire break monitoring - additional conversion time 40.2 / 47 ms for resistance measurement - additional conversion time for wire 5,5 ms break monitoring and resistance measurement Interference voltage suppression for 50 / 0 Hz none / 400 / 0 / 50 Hz 50 / 0 Hz 50 / 0 Hz interference frequency f1 in Hz Encoder Connection of signal encoders for current measurement ; with external transmitter as 2-wire transducer supply for current measurement as 4-wire transducer for resistance measurement with two-wire connection for resistance measurement with three-wire connection for resistance measurement with four-wire connection Errors/accuracies Operational limit in overall temperature range Voltage, relative to input area, (+/-) 0.5 %; 1.0 % at 1 to 5 V; 0.5 % at +/-1 V, +/-10 V ; Line resistances are also measured ; Line resistances are also measured ; Line resistances are also measured ; Line resistances are also measured 0.7 %; +/-0.7 % at +/-1 V; +/-0.9 % at +/-10 V, 1 to 5 V Current, relative to input area, (+/-) 0.5 % 0.8 %; at +/-20 ma, 4 to 20 ma Resistance, relative to input area, (+/-) Resistance thermometer, relative to input area, (+/-) Basic error limit (operational limit at 25 C) Voltage, relative to input area, (+/-) 0.25 %; 0.5 % at 1 to 5 V; 0.25 % at +/-1 V, +/-10 V Current, relative to input area, (+/-) 0.25 %; at +/-20 ma, 4 to 20 ma 1 %; +/-1.0 % at +/-1 V; +/-0. % at +/-10 V; +/-0.7 % at 1 to 5 V ; Line resistances are also measured 0.38 %; +/-0.38 % at +/-80 mv; +/-0.35 % at +/-250 mv, +/-500mV, +/-1 V, +/-2,5 V, +/-5 V, 1 to 5 V, +/-10 V 1 %; at +/-20 ma, 4 to 20 ma 0.35 %; +/-20 ma, 0 to 20 ma, 4 to 20 ma 1% 1.25 %; 0 to 500 ohms (4-conductor measurement, in range of 00 ohms) 0.%; 0.% at +/-1 V; 0.75 % at +/-10 V, 1 to 5 V 0.7 %; at +/-20 ma, 4 to 20 ma 0.7 %; 0.7 % at +/-1 V; 0.4 % at +/-10 V; 0.5 % at 1 to 5 V 0.7 %; at +/-20 ma, 4 to 20 ma 0.5 % 0.5 % 0.15 %; +/-0.15 % (+/-250 mv, +/-500 mv, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/- 10 V); +/-0.17 % (+/- 80 mv); 0.15 %; +/-20 ma, 0 to 20 ma, 4 to 20 ma /0 Siemens ST

61 Analog modules SM 431 analog input module Technical specifications (continued) ES7431-0HH00-0AB0 ES7431-1KF20-0AB0 ES7431-1KF00-0AB0 ES7431-1KF10-0AB0 SM431, 1AE, +/-10V, SM431, 8AE, U/I/R, 14BIT +/-20MA, 4-20MA Resistance, relative to input area, (+/-) SM431, 8AE, U/I/R, 14BIT, SM431, 8AE, U/I/R, 13BIT 0,41MS ZYKL 0.7 %; 0 to 00 ohms 0.8 %; 0 to 500 ohms (4-conductor measurement, in range of 00 ohms) 0.15 %; +/-0.15 % at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 00 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 000 ohms); +/-0.3 % at 0 to 300 ohms (3-conductor measurement), 0 to 00 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 000 ohms) Resistance thermometer, relative to 0.3 % input area, (+/-) Galvanic isolation Galvanic isolation analog inputs Galvanic isolation analog inputs No ; internal / external ; internal / external ; internal / external between the channels No No No No Permissible potential difference between the inputs (UCM) 2 V DC / 2 Vpp AC 8 V AC 30 V AC 120 V AC Isolation Isolation checked with 500 V DC between bus and local ground 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 2120 V DC between analog part and local ground Dimensions Width 25 mm 25 mm 25 mm 25 mm Height 290 mm 290 mm 290 mm 290 mm Depth 210 mm 210 mm 210 mm 210 mm Weights Weight, approx. 500 g 500 g 500 g 500 g 2120 V DC between bus and L+/M; 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground ES7431-7QH00-0AB0 ES7431-7KF00-0AB0 ES7431-7KF10-0AB0 SM 431, 1AE, U/I/R/PT100, 1BIT SM 431, 8AI, U/I/THERMO, 1BIT SM 431, 8AI, RESIST./PT100, 1BIT Product type designation Supply voltage Load voltage L+ Rated value (DC) 24 V; Only required for supplying 2-wire transmitters Reverse polarity protection Input current from load voltage L+ (without load), 400 ma; for 1 connected, fully 400 ma 400 ma max. controlled 2-wire transmitters from backplane bus 5 V DC, max. 700 ma ma 50 ma Power losses Power loss, typ. 4.5 W 4. W 3.3 W Hardware configuration Slots Required slots Siemens ST /1

62 Analog modules SM 431 analog input module Technical specifications (continued) ES7431-7QH00-0AB0 ES7431-7KF00-0AB0 ES7431-7KF10-0AB0 SM 431, 1AE, U/I/R/PT100, 1BIT SM 431, 8AI, U/I/THERMO, 1BIT SM 431, 8AI, RESIST./PT100, 1BIT Analog inputs Number of analog inputs For voltage/current measurement 1 8 For resistance measurement 8 8 permissible input voltage for voltage input (destruction limit), max. 18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) 35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) 35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) permissible input current for current 40 ma 32 ma input (destruction limit), max. Input ranges (rated values), voltages 1 V to 5 V -1 V to +1 V -10 V to +10 V -100 mv to +100 mv -2.5 V to +2.5 V -20 mv to +20 mv -25 mv to +25 mv -250 mv to +250 mv -5 V to +5 V -50 mv to +50 mv -500 mv to +500 mv -80 mv to +80 mv Input ranges (rated values), currents 0 to 20 ma -10 ma to +10 ma -20 ma to +20 ma -3.2 ma to +3.2 ma 4 ma to 20 ma -5 ma to +5 ma Input ranges (rated values), thermoelements Type B Type E Type J Type K Type L Type N Type R Type S Type T Type U Input ranges (rated values), resistance thermometer Ni 100 Ni 1000 ; Different characteristics selectable: Europe/U.S. Pt 100 Pt 1000 Pt 200 Pt 500 /2 Siemens ST

63 Analog modules SM 431 analog input module Technical specifications (continued) ES7431-7QH00-0AB0 ES7431-7KF00-0AB0 ES7431-7KF10-0AB0 SM 431, 1AE, U/I/R/PT100, 1BIT SM 431, 8AI, U/I/THERMO, 1BIT SM 431, 8AI, RESIST./PT100, 1BIT Input ranges (rated values), resistors 0 to 150 ohms 0 to 300 ohms 0 to 48 ohms 0 to 00 ohms 0 to 000 ohms ; Usable up to 5000 ohms Thermocouple (TC) Temperature compensation - internal temperature compensation - external temperature compensation with compensations socket - external temperature compensation with Pt100 - dynamic reference temperature value Characteristic linearization Parameterizable - for thermocouples Type B, E, J, K, L, N, R, S, T, U Type B, E, J, K, L, N, R, S, T, U - for resistance thermometer Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000 Cable length shielded, max. 200 m; 50 m with thermocouples and input ranges <= 80 mv Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000; different characteristics selectable (Europe/U.S.) 200 m 200 m; 50 m with thermocouples and input ranges +/-80 mv Analog value creation Integration and conversion time/ resolution per channel Resolution with overrange 1 bit; 1 / 1 / 1 1 bit 1 bit (bit including sign), max. Integration time, parameterizable Basic conversion time (ms) / 20,1 / 23,5 ms 10 / 1,7 / 20 / / 23 / 25 ms Integration time (ms) 2,5 / 1,7 / 20 ms 2,5 / 1,7 / 20 / ms at 50 Hz (entire module incl. wire break) Basic conversion time, including integration time (ms) - additional conversion time for wire 4.3 / 4.3 / 4.3 ms 110 ms / 4 ms break monitoring - additional conversion time 12 / 40,2 / 47 ms for resistance measurement - additional conversion time for wire 5,5 ms 1 ms (module) none break monitoring and resistance measurement Interference voltage suppression 400 / 0 / 50 Hz none/ 0 / 50 Hz for interference frequency f1 in Hz Encoder Connection of signal encoders for current measurement as 2-wire transducer for current measurement as 4-wire transducer for resistance measurement with two-wire connection for resistance measurement with three-wire connection for resistance measurement with four-wire connection ; Line resistances are also measured Siemens ST /3

64 Analog modules SM 431 analog input module Technical specifications (continued) ES7431-7QH00-0AB0 ES7431-7KF00-0AB0 ES7431-7KF10-0AB0 Errors/accuracies Operational limit in overall temperature range Voltage, relative to input area, (+/-) Current, relative to input area, (+/-) Resistance, relative to input area, (+/-) Resistance thermometer, relative to input area, (+/-) Basic error limit (operational limit at 25 C) Voltage, relative to input area, (+/-) Current, relative to input area, (+/-) Resistance, relative to input area, (+/-) Resistance thermometer, relative to input area, (+/-) SM 431, 1AE, U/I/R/PT100, 1BIT SM 431, 8AI, U/I/THERMO, 1BIT SM 431, 8AI, RESIST./PT100, 1BIT 0.3 %; +/-0.3 % at +/-250 mv, 0.3 % +/-500 mv, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/- 10 V; +/-0.31 % at +/-80 mv; +/-0.32 % at +/-50 mv; +/-0.35 % at +/-25 mv; 0.3 %; at 0 to 20 ma, +/-5 ma, 0.5 % +/-10 ma, +/- 20 ma, 4 to 20 ma 0.3 %; +/-0.3 % at 0 to 48 Ohm (4-conductor measurement), 0 to 150 Ohm (4-conductor measurement), 0 to 300 Ohm (4-conductor measurement), 0 to 00 Ohm (4-conductor measurement), 0 to 5000 Ohm (4-conductor measurement, in range of 000 Ohm); +/-0.4 % at 0 to 300 Ohm (3-conductor measurement), 0 to 00 Ohm (3-conductor measurement), 0 to 5000 Ohm (3-conductor measurement, in range of 000 Ohm); 0.4 % +/-1 C 0.15 %; +/-0.15 % at +/-250 mv, 0.1 % +/-500 mv, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/-10 V; +/-0.17 % at +/-80 mv; +/-0.19 % at +/-50 mv; +/-0.23 % at +/-25 mv; 0.15 %; at 0 to 20 ma, +/-5 ma, 0.17 % +/-10 ma, +/- 20 ma, 4 to 20 ma 0.15 %; +/-0.15 % at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 000 ohms); +/-0.3 % at 0 to 300 ohms (3-conductor measurement), 0 to 00 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 000 ohms) 0.3 % +/-0,2 C Interrupts/diagnostics/ status information Alarms Diagnostic alarm ; Parameterizable ; Parameterizable ; Parameterizable Limit value alarm ; Parameterizable Diagnostic messages Diagnostics ; Parameterizable Galvanic isolation Galvanic isolation analog inputs Galvanic isolation analog inputs ; internal / external ; internal / external ; internal / external between the channels No No Permissible potential difference between the inputs (UCM) 120 V AC 120 V AC none /4 Siemens ST

65 Analog modules SM 431 analog input module Technical specifications (continued) ES7431-7QH00-0AB0 ES7431-7KF00-0AB0 ES7431-7KF10-0AB0 Isolation Isolation checked with SM 431, 1AE, U/I/R/PT100, 1BIT SM 431, 8AI, U/I/THERMO, 1BIT SM 431, 8AI, RESIST./PT100, 1BIT 2120 V DC between bus and L+/M; 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground 1500 V DC 1500 V DC Dimensions Width 25 mm 25 mm 25 mm Height 290 mm 290 mm 290 mm Depth 210 mm 210 mm 210 mm Weights Weight, approx. 500 g 50 g 50 g Ordering data Article No. Article No. SM 431 analog output modules 1 inputs, non-isolated, 13 bit ES7431-0HH00-0AB0 8 inputs, isolated, 13 bit ES7431-1KF00-0AB0 8 inputs, isolated, 14 bit, ES7431-1KF10-0AB0 with linearization 8 inputs, isolated, 14 bit ES7431-1KF20-0AB0 1 inputs, isolated, 1 bit, ES7431-7QH00-0AB0 process interrupt capability 8 inputs, isolated, 1 bit, ES7431-7KF00-0AB0 process interrupt capability, for thermocouples (I, U) 8 inputs, isolated, 1 bit, ES7431-7KF10-0AB0 process interrupt capability, for thermal resistors Front connector 48-pin with screw contacts, 1 unit ES7492-1AL00-0AA0 with screw contacts, 84 units ES7492-1AL00-1AB0 with spring-loaded terminals, ES7492-1BL00-0AA0 1 unit with crimp contacts, 1 unit ES7492-1CL00-0AA0 with crimp contacts, 84 units ES7492-1CL00-1AB0 1 unit; for ES7431-7KF00-0AB0; ES7431-7KF00-AA0 spare part, included in scope of delivery Measuring range module ES7974-0AA00-0AA0 for analog inputs 1 module for 2 inputs (spare part) Cover film for labeling strips Spare part Labeling sheets for machine inscription DIN A4, for printing using laser printer; pack of 10 petrol light-beige yellow red SIMATIC Manual Collection Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection update service for 1 year Current "Manual Collection" DVD and the three subsequent updates ES7492-2XX00-0AA0 ES7492-2AX00-0AA0 ES7492-2BX00-0AA0 ES7492-2CX00-0AA0 ES7492-2DX00-0AA0 ES7998-8XC01-8YE0 ES7998-8XC01-8YE2 Siemens ST /5

66 Analog modules SM 432 analog output module Analog outputs for the SIMATIC S7-400 For the connection of analog actuators Technical specifications ES7432-1HF00-0AB0 SM 432, 8AO, U/I, 13BIT Product type designation Supply voltage Load voltage L+ Rated value (DC) 24 V Input current from backplane bus 5 V DC, max. 150 ma from supply voltage L+, max. 400 ma Power losses Power loss, max. 9W Hardware configuration Slots Required slots 1 Analog outputs Number of analog outputs 8 Voltage output, short-circuit protection Voltage output, short-circuit current, 30 ma max. Current output, no-load voltage, max. 19 V Output ranges, voltage 0 to 10 V 1 V to 5 V -10 V to +10 V Output ranges, current 0 to 20 ma -20 ma to +20 ma 4 ma to 20 ma Load impedance (in rated range of output) with voltage outputs, min. with voltage outputs, capacitive load, max. with current outputs, max. Cable length shielded, max. Analog value creation Integration and conversion time/ resolution per channel Resolution with overrange (bit including sign), max. Conversion time (per channel) ES7432-1HF00-0AB0 SM 432, 8AO, U/I, 13BIT 1kΩ 1µF 500 Ω; 00 ohms if common-modevoltage reduced to <1 V 200 m 13 bit 420 µs; 420 µs in the ranges 1 to 5 V and 4 to 20 ma; 300 µs in all ranges Settling time for resistive load 0.1 ms for capacitive load 3.5 ms for inductive load 0.5 ms Errors/accuracies Operational limit in overall temperature range Voltage, relative to output area, (+/-) 0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V Current, relative to output area, (+/-) 1 %; +/-20 ma, 4 to 20 mv Basic error limit (operational limit at 25 C) Voltage, relative to output area, (+/-) 0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V Current, relative to output area, (+/-) 0.5 %; +/-20 ma, 0 to 20 ma Interrupts/diagnostics/ status information Substitute values connectable No Galvanic isolation Galvanic isolation analog outputs between the channels and the backplane bus Isolation Isolation checked with 2120 V DC between bus and L+/M; 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground Dimensions Width 25 mm Height 290 mm Depth 210 mm Weights Weight, approx. 50 g / Siemens ST

67 Analog modules Ordering data Article No. Article No. SM 432 analog output module SM 432 analog output module ES7432-1HF00-0AB0 SIMATIC Manual Collection ES7998-8XC01-8YE0 8 outputs, isolated, 13 bit Front connector 48-pin with screw contacts, 1 unit with screw contacts, 84 units with spring-loaded terminals, 1 unit with crimp contacts, 1 unit with crimp contacts, 84 units Cover film for labeling strips Spare part Labeling sheets for machine inscription ES7492-1AL00-0AA0 ES7492-1AL00-1AB0 ES7492-1BL00-0AA0 ES7492-1CL00-0AA0 ES7492-1CL00-1AB0 ES7492-2XX00-0AA0 Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection update service for 1 year Current "Manual Collection" DVD and the three subsequent updates ES7998-8XC01-8YE2 DIN A4, for printing using laser printer; pack of 10 petrol ES7492-2AX00-0AA0 light-beige yellow red ES7492-2BX00-0AA0 ES7492-2CX00-0AA0 ES7492-2DX00-0AA0 Siemens ST /7

68 SIPLUS S7-400 analog modules SIPLUS S7-400 SM 431 analog input modules Analog inputs for SIMATIC S7-400 For connecting voltage sensors and current sensors, thermocouples, resistors and resistance thermometers Resolution 13 to 1 bit Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. For technical documentation on SIPLUS, see: Technical specifications Based on Ambient conditions Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Relative humidity - With condensation, tested in accordance with IEC , max. Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN AG1431-0HH00-4AB0 ES7431-0HH00-0AB0 SIPLUS S7-400 SM431 1AI Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. SIPLUS S7-400 SM 431 analog input module 1 inputs, non-floating, 13 bit Exposure to media AG1431-0HH00-4AB0 Accessories See SIMATIC S7-400 analog input modules, page /5 /8 Siemens ST

69 SIPLUS S7-400 analog modules SIPLUS S7-400 SM 432 analog output modules Analog outputs for SIMATIC S7-400 For connection of analog actuators Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. For technical documentation on SIPLUS, see: Technical specifications Based on Ambient conditions Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Relative humidity - With condensation, tested in accordance with IEC , max. Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN AG1432-1HF00-4AB0 ES7432-1HF00-4AB0 SIPLUS_SM432_8AA Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. SIPLUS S7-400 SM 432 analog output module 8 outputs, floating, 13 bit Exposure to media AG1432-1HF00-4AB0 Accessories See SIMATIC S7-400 analog output modules, page /7 Siemens ST /9

70 Function modules FM counter module Two-channel intelligent counter module for simple counting tasks For direct connection of incremental encoders Comparison function with 2 specifiable comparison values Integrated digital outputs for outputting the response when the comparison values are reached Note SIMODRIVE Sensor/Motion Connect 500 feature incremental encoders and preassembled connecting cables for counting and positioning functions. Technical specifications ES7450-1AP01-0AE0 FM 450-1, COUNTER MODULE, 2 CHANNELS Product type designation Supply voltage Load voltage 1L+ Reverse polarity protection Load voltage 2L+ Reverse polarity protection Aux. voltage 1L+, load voltage 2L+ Rated value (DC) 24 V permissible range, lower limit (DC) 20.4 V; Dynamic 18.5 V permissible range, upper limit (DC) 28.8 V; dynamic 30.2 V non-periodic skip -Duration 500 ms - Recovery time 50 s -Value 35 V Input current from load voltage 1L+ (without load), 50 ma max. from load voltage 2L+ (without load), 0 µa max. from backplane bus 5 V DC, max. 300 ma Encoder supply 5 V encoder supply 5 V ; 5.2 V +/-2 % short-circuit protection Output current, max. 300 ma 24 V encoder supply 24 V ; 1L+ (-3 V) short-circuit protection Output current, max. 300 ma Power losses Power loss, typ. W ES7450-1AP01-0AE0 FM 450-1, COUNTER MODULE, 2 CHANNELS Digital inputs Number of digital inputs Functions 1 for gate start, 1 for gate stop, 1 for setting the counter Input voltage for signal "0" V for signal "1" +11 to +28.8V Input current for signal "1", typ. 9mA Input delay (for rated value of input voltage) Input frequency 200 khz (with a time delay of 0.1 ms), max. for standard inputs - Parameterizable - at "0" to "1", max. 2.5 µs; >= 2.5 µs (200 khz); <= 25 µs (20 khz) Digital outputs Number of digital outputs 4 short-circuit protection ; Clocked electronically Limitation of inductive shutdown 2L+ (-39 V) voltage to Output voltage for signal "0", max. 3V for signal "1", min. 2L+ (-1,5 V) Output current for signal "1" rated value 0.5 A; Res. / P.D. 5 W tungsten 24 V DC for signal "1" permissible range 5mA for 0 to 0 C, min. for signal "1" permissible range 0. A for 0 to 0 C, max. Output delay with resistive load "0" to "1", max. 300 µs /70 Siemens ST

71 Function modules FM counter module Technical specifications (continued) ES7450-1AP01-0AE0 FM 450-1, COUNTER MODULE, 2 CHANNELS Encoder Connectable encoders Incremental encoder (symmetrical) ; With 2 pulse trains offset by 90 Incremental encoder (asymmetrical) 24 V initiator 24 V directional element ; 1 pulse train, 1 direction level Counter Number of counter inputs 2; 32 bit or +/-31 bit Counter input 5 V Type RS 422 Terminating resistor 220 Ω Differential input voltage min. 0.5 V Counting frequency, max. 500 khz Counter input 24 V Input voltage, for signal "0" -30 to +5V Input voltage, for signal "1" +11 to +30V Input current, for signal "1", typ. 9mA Counting frequency, max. 200 khz Minimum pulse width >= 2.5 µs (200 khz); >= 25 µs (20 khz) (parameterizable) Parameter Remark Assigned binary addresses: 4 bytes / 4 bytes Galvanic isolation Galvanic isolation digital inputs between the channels and the ; Optocoupler backplane bus Galvanic isolation digital outputs between the channels and the ; Optocoupler backplane bus Galvanic isolation counter between the channels and the ; Optocoupler backplane bus Permissible potential difference between different circuits 75V DC/0V AC Isolation Isolation checked with 500 V Connection method required front connector 1x 48-pin Dimensions Width 25 mm Height 290 mm Depth 210 mm Weights Weight, approx. 50 g Ordering data FM counter module with 2 channels, max. 500 khz; for incremental encoder Front connectors 48-pin with screw contacts, 1 item with screw contacts, 84 items with spring-loaded terminals, 1 item with crimp contacts, 1 item with crimp contacts, 84 items Front covers for CPU and function modules Spare part Article No. ES7450-1AP01-0AE0 ES7492-1AL00-0AA0 ES7492-1AL00-1AB0 ES7492-1BL00-0AA0 ES7492-1CL00-0AA0 ES7492-1CL00-1AB0 ES7492-1XL00-0AA0 Siemens ST /71

72 Function modules FM 451 positioning module Three-channel positioning module for rapid/slow-action drives 4 digital outputs per channel for motor control Displacement measurement incremental or synchronousserial Note Displacement measuring systems and precut/preassembled cables for counting and positioning functions are available under SIMODRIVE Sensor or Motion Connect Technical specifications ES7451-3AL00-0AE0 FM 451 positioning module Product type designation Supply voltage Rated value (DC) 24 V DC Input current Current consumption, max. 550 ma Encoder supply 5 V encoder supply 5 V Output current, max. 210 ma Cable length, max. 35 m; at max. 210 ma 24 V encoder supply 24 V Output current, max. 300 ma Cable length, max. 100 m; at max. 300 ma Absolute encoder (SSI) encoder supply Absolute encoder (SSI) Type of output voltage 24 V DC Output current, max. 300 ma Cable length, max. 300 m; At max. 15 kbit/s Digital inputs Number of digital inputs 12; 4 per axis Functions Reference cams, reversing cams, flying actual value setting, start/stop positioning Input voltage Rated value (DC) 24 V for signal "0" -3 to +5V for signal "1" +11 to +30V Input current for signal "1", typ. ma for 2-wire sensor - for signal "1", typ. 30 ma ES7451-3AL00-0AE0 FM 451 positioning module Digital outputs Number of digital outputs 12; 4 per axis Functions Rapid traverse, creep, run right, run left short-circuit protection Output voltage for signal "1", min. UP - 3 V Output current for signal "1" permissible range 00 ma; with UPmax for 0 to 55 C, max. for signal "0" residual current, max. 0.5 ma Encoder Connectable encoders Incremental encoder (symmetrical) Incremental encoder (asymmetrical) Absolute encoder (SSI) Encoder signals, incremental encoder (symmetrical) Trace mark signals A, nota, B, notb Zero mark signal N, notn Input signal 5 V difference signal (phys. RS 422) Input frequency, max. 1MHz Encoder signals, incremental encoder (asymmetrical) Trace mark signals A, B Zero mark signal N Input voltage 24 V Input frequency, max. 50 khz; for 25 m cable length, 25 khz for 100 m cable length Cable length, shielded, max. 100 m Encoder signals, absolute encoder (SSI) Input signal 5 V difference signal (phys. RS 422) Data signal DATA, notdata Clock signal CL, notcl Message frame length, 13 or 25 bit serial parameterizable Clock frequency, max MHz Gray code 1 Cable length, shielded, max. 300 m; At max. 15 kbit/s /72 Siemens ST

73 Technical specifications (continued) Galvanic isolation Galvanic isolation digital inputs Galvanic isolation digital inputs Galvanic isolation digital outputs Galvanic isolation digital outputs Degree and class of protection Degree of protection to EN 0529 IP20 Ambient conditions Ambient temperature in operation Min. 0 C max. 55 C Storage/transport temperature Min. -40 C max. 70 C Relative humidity Humidity class F Connection method required front connector 1x 48-pin Dimensions Width 50 mm Height 290 mm Depth 210 mm Weights Weight, approx. 1300g Ordering data FM 451 positioning module for rapid traverse and creep speed drives Front connector 48-pin with screw contacts, 1 item with screw contacts, 84 items with spring-loaded terminals, 1 item with crimp contacts, 1 item with crimp contacts, 84 items Front covers for CPU and function modules Spare part ES7451-3AL00-0AE0 FM 451 positioning module Article No. ES7451-3AL00-0AE0 ES7492-1AL00-0AA0 ES7492-1AL00-1AB0 ES7492-1BL00-0AA0 ES7492-1CL00-0AA0 ES7492-1CL00-1AB0 ES7492-1XL00-0AA0 Ordering data Function modules FM 451 positioning module Article No. Signal cable Pre-assembled for HTL encoder, FX50 2-2AL00- UL/DESINA Pre-assembled for SSI absolute FX50 2-2CC11- encoder, UL/DESINA Pre-assembled for TTL encoder FX50 2-2CD01- FX2001-1, UL/DESINA Pre-assembled for TTL encoder 24 V, FX50 2-2CD24- UL/DESINA Not crimped 0 Module end crimped, connector case 1 supplied Motor end crimped, connector case 4 supplied 0 m m m 3 0 m A 10 m B 20 m C 30 m D 40 m E 50 m F 0 m G 70 m H 80 m J 90 m K 0 m A 1 m B 2 m C 3 m D 4 m E 5 m F m G 7 m H 8 m J 0 m K 0.0 m m m m m m 5 0. m 0.7 m m 8 Siemens ST /73

74 Function modules FM 452 cam controller Very high speed electronic cam controller Low-cost alternative to mechanical cam controllers 32 cam tracks, 1 onboard digital outputs for direct output of actions Incremental or synchronous-serial position feedback Note: We offer position measuring systems and preassembled connecting cables for counting and positioning functions under SIMODRIVE Sensor or Motion Connect Technical specifications ES7452-1AH00-0AE0 FM 452 electronic cam controller Product type designation Supply voltage Rated value (DC) 24 V DC Input current Current consumption, max. 500 ma Encoder supply 5 V encoder supply 5 V Output current, max. 300 ma Cable length, max. 32 m 24 V encoder supply 24 V Output current, max. 300 ma Cable length, max. 100 m Digital inputs Number of digital inputs 11 Functions Reference point switch, flying actual value setting/length measurement, brake release, enable track output nos. 3 to 10 ES7452-1AH00-0AE0 FM 452 electronic cam controller Input voltage Rated value (DC) 24 V for signal "0" V for signal "1" +11 to +28.8V Input current for signal "0", max. 2mA (permissible quiescent current) for 2-wire sensor - for signal "1", typ. 9mA Digital outputs Number of digital outputs 1 Functions Cam track short-circuit protection Output voltage Rated value (DC) 24 V for signal "1", min. UP V Output current for signal "1" permissible range 00 ma; with UPmax for 0 to 55 C, max. for signal "0" residual current, max. 0.5 ma Encoder Connectable encoders Incremental encoder (symmetrical) Incremental encoder (asymmetrical) Absolute encoder (SSI) 2-wire sensor Encoder signals, incremental encoder (symmetrical) Trace mark signals A, nota, B, notb Zero mark signal N, notn Input signal 5 V difference signal (phys. RS 422) Input frequency, max. 1MHz Encoder signals, incremental encoder (asymmetrical) Trace mark signals A, B Zero mark signal N Input voltage 24 V Input frequency, max. 50 khz; 50 khz for 25 m cable length; 25 khz for 100 m cable length Encoder signals, absolute encoder (SSI) Input signal 5 V difference signal (phys. RS 422) Data signal DATA, notdata Clock signal CL, notcl Message frame length, 13 or 25 bit serial parameterizable Clock frequency, max. 1MHz Gray code 1 Cable length, shielded, max. 300 m; at max. 125 khz Galvanic isolation Galvanic isolation digital inputs Galvanic isolation digital inputs No Galvanic isolation digital outputs Galvanic isolation digital outputs No Degree and class of protection Degree of protection to EN 0529 IP20 /74 Siemens ST

75 Technical specifications (continued) ES7452-1AH00-0AE0 FM 452 electronic cam controller Ambient conditions Ambient temperature in operation Min. 0 C max. 55 C Storage/transport temperature Min. -40 C max. 70 C Relative humidity Humidity class F Connection method required front connector 1x 48-pin Dimensions Width 25 mm Height 290 mm Depth 210 mm Weights Weight, approx. 50 g Ordering data Function modules FM 452 electronic cam controller Front covers for CPU and function modules Spare part Front connector 48-pin with screw contacts, 1 item with screw contacts, 84 items Article No. FM 452 cam controller ES7452-1AH00-0AE0 ES7492-1XL00-0AA0 ES7492-1AL00-0AA0 ES7492-1AL00-1AB0 with spring-loaded terminals, 1 item ES7492-1BL00-0AA0 with crimp contacts, 1 item ES7492-1CL00-0AA0 with crimp contacts, 84 items ES7492-1CL00-1AB0 Signal cable Pre-assembled for HTL and TTL FX5002-2CA12- encoder, without Sub-D connector, UL/DESINA Pre-assembled for SSI absolute FX5002-2CC12- encoder FX2001-5, without Sub-D connector, UL/DESINA Length code see FM 451, page /73 Siemens ST /75

76 Function modules FM 453 positioning module Positioning module for servo and/or stepper motors in machines with high clock-pulse rates Can be used for simple point-to-point positioning and for complex traversing profiles Up to 3 independent motors can be controlled Note: We offer position measuring systems and preassembled connecting cables for counting and positioning functions under SIMODRIVE Sensor or Motion Connect 500. Further information can be found on the Internet at: Technical specifications ES7453-3AH00-0AE0 FM 453 positioning module Product type designation Supply voltage Auxiliary voltage Rated value (DC) 24 V dynamic range 18.5 to 30.2 V static area 20.4 to 28.8V Input current from load voltage1l+, max. 1 A; with 24 V position encoder; 1 A for 5 V position encoder from load voltage 2L+ to 4L+, max. 2 A; Per channel from backplane bus 5 V DC, max. 1. A; Rated current Encoder supply 5 V encoder supply 5 V Output current, max. 300 ma Cable length, max. 35 m; at max. 210 ma; 25 m at max. 300 ma 24 V encoder supply 24 V Cable length, max. 100 m; at max. 300 ma Power losses Power loss, max. 8W Digital inputs Number of digital inputs ; for each channel / axis Functions configurable Input voltage Rated value (DC) 24 V for signal "0" -3 to +5 V (max. 3 ma) for signal "1" 11 to 30 V (max. 7 ma) Input delay (for rated value of input voltage) for standard inputs - at "0" to "1", max. 15 µs; via input voltage range, 8 µs at 24 V DC - at "1" to "0", max. 45 µs; via input voltage range ES7453-3AH00-0AE0 FM 453 positioning module Digital outputs Number of digital outputs 4; for each channel / axis Functions configurable short-circuit protection Output voltage Rated value (DC) 24 V for signal "1", min. UP - 0,3 V Output current for signal "1" rated value 0.5 A; at 40 C; 0.1 A at 0 C for signal "1" permissible range 5mA for 0 to 40 C, min. for signal "1" permissible range 0. A for 0 to 40 C, max. for signal "1" permissible range 5mA for 40 to 0 C, min. for signal "1" permissible range 0.12 A for 40 to 0 C, max. for signal "0" residual current, max. 2mA Switching frequency with resistive load, max. 100 Hz with inductive load, max Hz Encoder Connectable encoders Incremental encoder (symmetrical) Absolute encoder (SSI) Encoder signals, incremental encoder (symmetrical) Input signal 5 V difference signal (phys. RS 422) Input frequency, max. 1 MHz; for 10 m cable length; 0.5 MHz for 35 m cable length Encoder signals, absolute encoder (SSI) Input signal 5 V difference signal (phys. RS 422) Clock frequency, max Mbit/s at 10 cable length (2.5 Mbit/s available soon) Cable length, shielded, max. 250 m; At max. 15 kbit/s /7 Siemens ST

77 Technical specifications (continued) ES7453-3AH00-0AE0 FM 453 positioning module Drive interface Signal input I Type Drive interface step, signal input "READY 1" Function "Power section ready" where Ui < 1 V, Ii = 2mA Signal output I Type 5 V (phys. RS 422) Function Clock pulse, direction, enable, current control Differential output voltage, min. 2 V; RL = 100 ohms Differential output voltage 1.1 V; Io = 30 ma for signal "0", max. Differential output voltage, 3.7 V; Io = -30 ma for signal "1", min. Load impedance 55 Ω Pulse frequency 200 khz; 500 khz available soon Cable length, max. 35 m; 35 m with symm. transmission; 10 m with asymm. transmission Signal output II Type Contact relay Function Drive disconnection for operation Load 1 A/50 V / 30 VA DC Signal output III Type Analog output Function Drive interface Servo: Setpoint output for drive Output current -3 to +3 ma Cable length, max. 30 m Galvanic isolation Galvanic isolation digital inputs Galvanic isolation digital inputs ; Optocoupler Galvanic isolation digital outputs Galvanic isolation digital outputs ; Optocoupler Degree and class of protection Degree of protection to EN 0529 IP20 Ambient conditions Ambient temperature in operation Min. 0 C max. 55 C Storage/transport temperature Min. -40 C max. 70 C Relative humidity Humidity class F No Connection method required front connector 1x 48-pin Dimensions Width 50 mm Height 290 mm Depth 210 mm Weights Weight, approx. 120g Ordering data Function modules FM 453 positioning module with 3 channels/axes Setpoint connecting cable for 3 servo motors for 3 stepper motors for 2 servo motors / 1 stepper motor for 1 servo motor / 2 stepper motors FM 453 positioning module Article No. ES7453-3AH00-0AE0 FX2002-3AD FX2002-3AB FX2002-3AB FX2002-3AB Length code See page /73 Front connector 48-pin with screw contacts, 1 item ES7492-1AL00-0AA0 with screw contacts, 84 items ES7492-1AL00-1AB0 with spring-loaded terminals, 1 item ES7492-1BL00-0AA0 with crimp contacts, 1 item ES7492-1CL00-0AA0 with crimp contacts, 84 items ES7492-1CL00-1AB0 Front covers for CPU ES7492-1XL00-0AA0 and function modules Spare part Signal cable Pre-assembled for SSI absolute FX5072-2CC encoder, UL/DESINA Pre-assembled for TTL encoder FX5072-2CD FX2001-1, UL/DESINA Pre-assembled for TTL encoder 24 V, FX5072-2CD UL/DESINA Length code See page /73 Siemens ST /77

78 Function modules FM 455 controller module 1-channel closed-loop control module for universal control tasks Can be used for temperature, pressure and flow controls Convenient online self-optimization for temperature controls Predefined controller structures 2 control algorithms 2 versions: - FM 455 C as continuous controller - FM 455 S as step or pulse controller With 1 analog outputs (FM 455 C) or 32 digital outputs (FM 455 S) for actuators Technical specifications ES7455-0VS00-0AE0 FM 455 C controller module Product type designation Supply voltage Load voltage L+ Rated value (DC) 24 V 24 V permissible range, lower limit (DC) 20.4 V 20.4 V permissible range, upper limit (DC) 28.8 V 28.8 V Input current from load voltage L+ (without load), max. Power losses 440 ma; typ. 370 ma ES7455-1VS00-0AE0 FM 455 S controller module 400 ma; typ. 330 ma Power loss, typ. 12 W 10.7 W Power loss, max W 1.2 W Digital inputs Number of digital inputs 1 1 Input characteristic curve in accordance with IEC 1131, type 2 Input voltage Rated value (DC) 24 V 24 V for signal "0" -3 to +5V -3 to +5V for signal "1" 13 to 30V 13 to 30V Input current for signal "1", typ. 7mA 7mA Cable length shielded, max m 1000m Unshielded, max. 00 m 00 m Digital outputs Number of digital outputs 32 short-circuit protection ; Electronic Limitation of inductive shutdown L+ (-1.5 V) voltage to Controlling a digital input Switching capacity of the outputs on lamp load, max. 5W Load resistance range lower limit 240 Ω upper limit 4kΩ Output voltage for signal "1", min. L+ (-2.5 V) Output current for signal "1" rated value 0.1 A for signal "1" permissible range 5mA for 0 to 0 C, min. for signal "1" permissible range 150 ma for 0 to 0 C, max. for signal "0" residual current, max. 0.5 ma Parallel switching of 2 outputs for logic links Switching frequency with resistive load, max. 100 Hz with inductive load, max. 0.5 Hz on lamp load, max. 100 Hz Cable length shielded, max m Unshielded, max. 00 m Analog inputs Number of analog inputs 1; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection permissible input voltage for voltage input (destruction limit), max. permissible input current for current input (destruction limit), max. ES7455-0VS00-0AE0 FM 455 C controller module 20 V 20 V 40 ma 40 ma ES7455-1VS00-0AE0 FM 455 S controller module 1; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection /78 Siemens ST

79 Function modules FM 455 controller module Technical specifications (continued) Input ranges (rated values), voltages 0 to +10 V V to V -80 mv to +80 mv Input ranges (rated values), currents 0 to 20 ma 0 to 23.5 ma -3.5 ma to ma 4 ma to 20 ma Input ranges (rated values), thermoelements Type B Type J Type K Type R Type S Input ranges (rated values), resistance thermometer Pt 100 Thermocouple (TC) Temperature compensation - internal temperature compensation - external temperature compensation with Pt100 Characteristic linearization ES7455-0VS00-0AE0 FM 455 C controller module ; Parameterizable ; Parameterizable ES7455-1VS00-0AE0 FM 455 S controller module ; Parameterizable ; Parameterizable Parameterizable - for thermocouples Type B, J, K, R, S Type B, J, K, R, S - for resistance thermometer Pt100 (standard) Pt100 (standard) Cable length shielded, max. 200 m; 50 m at 80 mv and thermocouples 200 m; 50 m at 80 mv and thermocouples Analog outputs Number of analog outputs 1 Voltage output, short-circuit protection Voltage output, short-circuit current, 25 ma max. Current output, no-load voltage, max. 18 V Output ranges, voltage 0 to 10 V -10 V to +10 V Output ranges, current 0 to 20 ma -20 ma to +20 ma 4 ma to 20 ma Connection of actuators for voltage output two-wire connection for current output two-wire connection Load impedance (in rated range of output) with voltage outputs, min. with voltage outputs, capacitive load, max. with current outputs, max. with current outputs, inductive load, max. Cable length shielded, max. 1kΩ 1µF 500 Ω 1mH 200 m; 50 m at 80 mv and thermocouples Analog value creation Measurement principle integrating integrating Integration and conversion time/ resolution per channel Resolution with overrange (bit including sign), max. Conversion time (per channel) ES7455-0VS00-0AE0 FM 455 C controller module 14 bit; 12 or 14 bit, parameterizable 1.7 ms; for 12 bit: 1 2/3 ms for 0 Hz, 20 ms for 50 Hz; for 14 bit: 100 ms for 50 and 0 Hz ES7455-1VS00-0AE0 FM 455 S controller module 14 bit; 12 or 14 bit, parameterizable 1.7 ms; for 12 bit: 1 2/3 ms for 0 Hz, 20 ms for 50 Hz; for 14 bit: 100 ms for 50 and 0 Hz Settling time for resistive load 0.2 ms 0.1 ms for capacitive load 3.3 ms 3.3 ms for inductive load 0.5 ms 0.5 ms Encoder Connection of signal encoders for voltage measurement for current measurement as 4-wire transducer Connectable encoders 2-wire sensor - Permissible quiescent current 1.5 ma 1.5 ma (2-wire sensor), max. Errors/accuracies Linearity error 0.05 % 0.05 % (relative to input range), (+/-) Temperature error %/K %/K (relative to input range), (+/-) Linearity error 0.05 % (relative to output range), (+/-) Temperature error 0.02 %/K (relative to output range), (+/-) Operational limit in overall temperature range Voltage, relative to input area, (+/-) +/-0. to +/-1 % +/-0. to +/-1 % Current, relative to input area, (+/-) +/-0. to +/-1 % +/-0. to +/-1 % Resistance thermometer, +/-0. to +/-1 % +/-0. to +/-1 % relative to input area, (+/-) Voltage, relative to output area, (+/-) 0.5 % Current, relative to output area, (+/-) 0. % Siemens ST /79

80 Function modules FM 455 controller module Technical specifications (continued) Basic error limit (operational limit at 25 C) Voltage, relative to input area, (+/-) +/-0.4 to +/-0. % +/-0.4 to +/-0. % Current, relative to input area, (+/-) +/-0.4 to +/-0. % +/-0.4 to +/-0. % Resistance thermometer, +/-0.4 to +/-0. % +/-0.4 to +/-0. % relative to input area, (+/-) Voltage, relative to output area, (+/-) 0.4 % Current, relative to output area, (+/-) 0.5 % Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency Series mode interference (peak value of interference < rated value of input range), min. 40 db 40 db common mode voltage (USS < 2.5 V), min. Interrupts/diagnostics/ status information Substitute values connectable Control technology ES7455-0VS00-0AE0 FM 455 C controller module 70 db 70 db ; Parameterizable Number of closed-loop controllers 1; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection ES7455-1VS00-0AE0 FM 455 S controller module ; Parameterizable 1; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection Galvanic isolation Galvanic isolation controller between the channels No No between the channels and the ; Optocoupler ; Optocoupler backplane bus Permissible potential difference between inputs and MANA (UCM) 2.5 V DC 2.5 V DC between M internally and the inputs 75V DC/0V AC 75V DC/0V AC Isolation Isolation checked with 500 V DC 500 V DC Connection method required front connector 2x 48-pin 2x 48-pin Dimensions Width 50 mm 50 mm Height 290 mm 290 mm Depth 210 mm 210 mm Weights Weight, approx g 1400g Ordering data FM 455 C controller module with 1 analog outputs for 1 continuous controllers FM 455 S controller module with 32 digital outputs for 1 step or pulse controllers Front connectors 48-pin with screw contacts, 1 item with screw contacts, 84 items with spring-loaded terminals, 1 item with crimp contacts, 1 item with crimp contacts, 84 items Article No. ES7455-0VS00-0AE0 ES7455-1VS00-0AE0 ES7492-1AL00-0AA0 ES7492-1AL00-1AB0 ES7492-1BL00-0AA0 ES7492-1CL00-0AA0 ES7492-1CL00-1AB0 /80 Siemens ST

81 Function modules FM DP application module Introduction SIMATIC FM DP integrated in SIMATIC S7-400 Designed for high-performance and user-configurable closed-loop control tasks in the SIMATIC S Can be adapted to individual requirements as required, such as: Controlling, computing, closed-loop control as well as motion control. Can therefore be used flexibly for a wide variety of applications. Extensive library with approx. 300 function blocks: E.g. simple functions such as AND, ADD and OR through to complex GMC (general motion control) blocks as virtual master or gear functions. User-friendly graphical configuration with the SIMATIC engineering tool CFC (Continuous Function Chart) and the D7-SYS add-on software package: Optimum code generation by the compiler, therefore SCL is not required. PROFIBUS DP interface onboard. SIMATIC FM DP is based on more than 15 years experience with high-performance control systems and combines this know-how with the advantages of SIMATIC the leading automation system for decades. In contrast to other function modules with static structures/functions, the FM DP application module can be configured flexibly and adapted to individual requirements. Siemens ST /81

82 Function modules FM DP application module FM DP basic module Basic module for handling arithmetic, closed-loop control and open-loop control tasks PROFIBUS DP interface for connection of distributed I/O and drives Modular design with expansion modules for I/O and communication Technical specifications DD107-0AA2 FM458-1 DP APPLICATION MODULE Product type designation Supply voltage Rated value (DC) 5 V DC 24 V DC permissible range (ripple included), 4.8 V lower limit (DC) permissible range (ripple included), 5.25 V upper limit (DC) Input current Current consumption, typ. 1.5 A Current consumption, max. 3A Memory Backup present ; SRAM Battery Backup battery Battery operation Backup current, max. 15 µa Hardware configuration Slots Required slots 1 Time of day Clock Hardware clock (real-time clock) Resolution 500 ms Digital inputs Number of digital inputs 8; Connector X2 Input voltage Rated value (DC) 24 V for signal "0" -1 to + V for signal "1" 13.5 V to 33 V DD107-0AA2 FM458-1 DP APPLICATION MODULE Input current for signal "0", max. 0mA (permissible quiescent current) for signal "1", typ. 3 ma; at 24 V Input delay (for rated value of input voltage) for standard inputs - at "0" to "1", max. 5µs Interfaces PROFIBUS DP equidistance ; With connection to interrupt tasks Direct data exchange (slave-to-slave communication) Interrupts/diagnostics/ status information Alarms Alarms Galvanic isolation Galvanic isolation digital inputs Galvanic isolation digital inputs No; only via optional interface modules Weights Weight, approx. 1000g /82 Siemens ST

83 Function modules FM DP application module Ordering data Article No. Article No. FM DP basic module FM DP application module DD107-0AA2 Basic module for computing, closed-loop control and open-loop control tasks; with PROFIBUS DP interface Micro Memory Card for FM DP basic module 2 MB ES7953-8LL31-0AA0 4 MB ES7953-8LM31-0AA0 8 MB ES7953-8LP31-0AA0 FM DP Know-How-Protect DD107-0GA0 for protection of technological application modules against unauthorized copying SC 4 interface cable DD184-0GE0 To connect FM to the serial port of a programming device/ PC SB10 interface module DD181-0AE2 To connect 8 binary I/Os to FM DP SB1 interface module DD181-0EB3 To connect 8 binary I/Os to FM DP, input voltage: 24/48 V DC SU12 interface module DD181-0AJ1 To connect 10 signals to FM DP RS 485 bus connector with 90 cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA12-0XA0 With PG interface ES7972-0BB12-0XA0 RS 485 bus connector with angled cable outlet Max. transfer rate 12 Mbit/s Without PG interface ES7972-0BA42-0XA0 With PG interface ES7972-0BB42-0XA0 RS 485 bus connector with 90 cable outlet for FastConnect connection system Max. transfer rate 12 Mbit/s Without PG interface 1 unit ES7972-0BA52-0XA0 100 units ES7972-0BA52-0XB0 With PG interface 1 unit ES7972-0BB52-0XA0 100 units ES7972-0BB52-0XB0 PROFIBUS FastConnect bus cable Standard type with special design XV1830-0EH10 for quick mounting, 2-core, shielded, sold by the meter, max. delivery unit 1000 m, minimum ordering quantity 20 m Preferred lengths: 20 m XV1830-0EN20 50 m XV1830-0EN m XV1830-0ET10 Siemens ST /83

84 Function modules FM DP application module EXM input/output expansion Optional plug-in expansion module for the FM DP basic module For input and output of time-critical signals With digital and analog inputs/outputs Incremental and absolute value encoders can be connected 4 high-resolution analog outputs Fan-free operation up to 40 C Technical specifications DD107-0CA1 EXM I/O EXPANSION Product type designation Supply voltage Rated value (DC) 5 V DC 24 V DC ; to be set up externally Input current Current consumption, typ. 1.5 A Encoder supply Output voltage about 14 V (non-isolated) short-circuit protection ; Electronic Output current Rated value 100 ma Hardware configuration Slots Required slots 1 Digital inputs Number of digital inputs 1 Input voltage Rated value (DC) 24 V for signal "0" -1 to + V or input open for signal "1" +13 to +33 V Input current for signal "0", max. 0mA (permissible quiescent current) for signal "1", typ. 3mA Input delay (for rated value of input voltage) for standard inputs - at "0" to "1", max. 200 µs Digital outputs Number of digital outputs 8 short-circuit protection ; electronic/thermal Response threshold, typ. 250 ma Limitation of inductive shutdown Supply voltage +1 V voltage to DD107-0CA1 EXM I/O EXPANSION Output voltage for signal "0", max. 3V for signal "1", max. Supply voltage -2.5 V Output current for signal "1" rated value 50 ma for signal "1" permissible range 100 ma for 0 to 40 C, min. for signal "0" residual current, max. 20 µa Total switching current 80 % at 50 C all outputs 50 ma Output delay with resistive load "0" to "1", max. 15 µs Analog inputs Number of analog inputs 5; Differential inputs Input ranges (rated values), voltages -10 V to +10 V ; -10 V: +/-4 LSB; to +10 V: +/-4 LSB (1 LSB = 4.88 mv) Input resistance (-10 V to +10 V) 470 kω Analog outputs Number of analog outputs 8; 4 outputs 1 bit; 4 outputs12 bit Voltage output, short-circuit protection ; relative to frame Voltage output, short-circuit current, 1 bits: 27 ma; 12 bits: 100 ma max. Output ranges, voltage -10 to +10 V Analog value creation Integration and conversion time/ resolution per channel Resolution with overrange (bit including sign), max. Conversion time (per channel) Encoder Number of connectable encoders, max. 4 AO: 1 bits, 4 AO: 12 bits, 5 AI: 12 bits 4 AO (1 bits):2 µs; 4 AO (12 bits): 4 µs; 5 AI: 45 µs 12; 8 incremental encoders (synchronizable), 4 absolute encoders /84 Siemens ST

85 Function modules FM DP application module EXM input/output expansion Technical specifications (continued) DD107-0CA1 EXM I/O EXPANSION Connectable encoders Incremental encoder (symmetrical) Incremental encoder (asymmetrical) Absolute encoder (SSI) ; Single or multiturn encoder with SSI (synchronous serial) or EnDat interface Encoder signals, incremental encoder (symmetrical) Trace mark signals 1) for tracks A and B (90 out of phase), poss. with zero pulse N; 2) for separate forward and backward track Input signal With 0 signal: -5 to 0 V; with 1 signal: +3 to +5 V; permissible input voltage range: differential voltage -5 to +5 V; max. input current: 15 ma (important: not limited on module side!) Encoder signals, incremental encoder (asymmetrical) Trace mark signals Track A and B (phase-shifted by 90 degrees), possibly with zero pulse N Input voltage with 0 signal: -30 to +4 V (at 15 ma load); with 1 signal: +8 to 30 V (at 15 ma load); permissible input voltage range: differential voltage -30 to +30 V Encoder signals, absolute encoder (SSI) Input signal 5 V acc. to RS 422 Data signal Dual-, Gray-, Gray-Excess-Code Clock frequency, max. 2 MHz; 100 khz to 2 MHz (depending on cable length) Errors/accuracies Linearity error (relative to output (+/- 1 LSB ) range), (+/-) Galvanic isolation Galvanic isolation digital inputs Galvanic isolation digital inputs No Galvanic isolation digital outputs Galvanic isolation digital outputs No Galvanic isolation analog inputs Galvanic isolation analog inputs No Galvanic isolation analog outputs Galvanic isolation analog outputs No Weights Weight, approx. 1kg Ordering data EXM input/output expansion for direct exchange of digital and analog signals between FM DP and the plant SB10 interface module To connect 8 binary inputs or outputs to FM DP SB1 interface module To connect 8 binary inputs to FM DP, input voltage: 24/48 V DC SB71 interface module To connect 8 binary outputs to FM DP, output voltage: 24/48 V DC SU12 interface module To connect 10 signals to FM DP SU13 interface module To connect 50 signals to FM DP SC 2 interface cable To connect EXM with up to 5 SBxx or SU12 SC 3 interface cable To connect EXM with an SU13 Article No. DD107-0CA1 DD181-0AE2 DD181-0EB3 DD181-0DH1 DD181-0AJ1 DD181-0GK0 DD184-0GC0 DD184-0GD0 Siemens ST /85

86 Function modules FM DP application module EXM 448 universal communications expansion module Technical specifications DD107-0EA0 S7-400, EXM 448 F. FM458 Product type designation Supply voltage Rated value (DC) 5 V DC Hardware configuration Slots Required slots 1 Weights Weight, approx. 0.8 kg Optional expansion module for the FM DP basic module For fast communication over PROFIBUS DP or SIMOLINK EXM 448: With vacant slot for a MASTERDRIVES option module Ordering data EXM 448 universal communications expansion module For fast communication, for example, with drives; with free slot for MASTERDRIVES option module Article No. DD107-0EA0 EXM universal communications expansion module Technical specifications DD107-0EA2 SIMATIC S7-400 EXM COMM.-EXPANS. Product type designation Supply voltage Rated value (DC) 5 V DC Hardware configuration Slots Required slots 1 Weights Weight, approx. 0.9 kg Optional plug-in expansion module for the FM DP basic module For high-speed communication over up to 2 SIMOLINK interfaces For coupling several FM DP application modules in synchronism with the sampling time Ordering data EXM universal communications expansion For high-speed communication with drives; for establishing two SIMOLINK fiber optic connections Article No. DD107-0EA2 /8 Siemens ST

87 Function modules FM DP application module D7-SYS Ordering data Article No. SIMATIC D7-SYS V8.0 Task: Function block library for configuring closed-loop control and automation tasks Target system: SIMATIC S7-400/FM 458/ SIMATIC TDC/T400/ SIMADYN Requirement: Windows XP, Windows 7 32/4-bit, Windows Server 2003/2008 Type of delivery: on CD, German, English, with electronic documentation Floating license ES7852-0CC03-0YA5 Upgrade License V7.x and higher Software Update Service 1) ES7852-0CC03-0YE5 ES7852-0CC01-0YL5 SIMATIC D7 FB Gen V2.1 DD1805-5DA0 Function block generator Add-on for STEP 7/CFC/SFC for configuration of control and automation tasks with T400, FM 458, SIMADYN D or SIMATIC TDC Contains function blocks for every application Scope of delivery: Software packages D7-SYS, CFC, SFC, TH-PO Optional: D7-FB-Gen, function block generator for the creation of customized function blocks SIMATIC Manual Collection Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection update service for 1 year ES7998-8XC01-8YE0 ES7998-8XC01-8YE2 Current "Manual Collection" DVD and the three subsequent updates 1) For more information on the software update service, see Section 11, page 11/3. Siemens ST /87

88 Function modules FM DP application module Accessories SC4 interface cable SC3 interface cable (Similar to figure) Interface cable for FM DP basic module and SB10, SB0, SB1 and SU12 interface modules. SC2 interface cable This cable is used to connect the SIMATIC TDC SM500 peripheral (I/O) module or the SIMATIC S7-400 EXM expansion module to a SU13 interface module. SB10 interface module This cable is used to connect the SIMATIC TDC SM500 peripheral module (I/O) or the SIMATIC S7-400 EXM expansion module to up to 5 interface modules SB10, SB0, SB70, SB1 SB71 and/ or SU12. (Similar to figure) The interface module is used to connect 8 digital inputs or outputs. /88 Siemens ST

89 Function modules FM DP application module Accessories SB1 interface module SU12 interface module It is used to connect 8 digital inputs with conversion from 24/48 V DC to 24 V DC. SB71 interface module The interface module is used to connect 10 signals; there is no electronic conversion. SU13 interface module The interface module is used to connect 8 digital outputs with conversion of the 24 V DC voltage on the module side to a max. of 24/48 V DC/AC on the plant side using transistors. This interface module can be used to connect 50 signals; there is no electronic conversion. Siemens ST /89

90 Function modules FM DP application module Accessories Technical specifications Ordering data Article No. Technical specifications SB10 interface module SC4 interface cable DD184-0GE0 Number of digital inputs or outputs 8 Electrical isolation No Max. cable cross-section 1.5 mm 2 Dimensions (W x H x D) in mm 45 x 130 x 15 Weight 0.3 kg Technical specifications SB1 interface module Number of digital inputs for 8 Input voltage 24/48 V DC Electrical isolation, via optocoupler Max. cable cross-section 1.5 mm 2 Dimensions (W x H x D) in mm 45 x 130 x 15 Weight 0.32 kg Technical specifications SB71 interface module Number of digital outputs 8 Output voltage, max 24/48 V DC Output current, max. 40 ma, short-circuit proof Electrical isolation, via optocoupler Max. cable cross-section 1.5 mm 2 Dimensions (W x H x D) in mm 45 x 130 x 15 Weight 0.32 kg Technical specifications SU12 interface module between FM DP (X2) module with SBxx or SU12 interface module, 2 m long SC2 interface cable between SM500 or EXM module and max. 5 SB10, SB0, SB70, SB1 SB71 interface modules and/or SU12, 2 m long SC3 interface cable between SM500 or EXM module and SU13 interface module, 2 m long SB10 interface module 8 digital inputs/outputs 24 V DC SB1 interface module 8 digital inputs 24/48 V DC SB71 interface module 8 digital outputs with transistors, 24/48 V DC SU12 interface module with plug-in connector, 10-pole SU13 interface module with screw-type plug-in connector DD184-0GC0 DD184-0GD0 DD181-0AE2 DD181-0EB3 DD181-0DH1 DD181-0AJ1 DD181-0GK0 Number of signal cables which can be connected 10 Signal amplitude per signal, max. 0 V, 0.5 A Electrical isolation No Max. cable cross-section 1.5 mm 2 Dimensions (W x H x D) in mm 45 x 130 x 15 Weight 0.28 kg Technical data S312 interface module Number of signal cables which can be connected 50 Signal amplitude per signal, max. 0 V, 0.5 A Electrical isolation No Max. cable cross-section 1.5 mm 2 Dimensions (W x H x D) in mm 45 x 130 x 15 Weight 0.3 kg /90 Siemens ST

91 SIPLUS S7-400 function modules SIPLUS DCF 77 radio clock module Technical specifications Radio clock module SIPLUS DCF 77 Radio frequency 77.5 Hz Power supply 24 V DC (20.4 to 28.8 DC) Power consumption, typ. 50 ma Dimensions (W x H x D) 75 mm x 125 mm 1) x 75 mm 1) Additionally 25 mm (0.98 in) for heavy duty threaded joint and bending radius for cables This module can be used to synchronize the real-time clock of the SIMATIC/SIPLUS S7-200, S7-300 and S7-400 automation systems with the official time of the DCF 77 time signal transmitter of the Physikalisch-Technische Bundesanstalt Braunschweig, Germany. The time is received by means of a DCF receiver (antenna with electronics) which is connected via two digital inputs on the SIMATIC PLC and SIPLUS together with a software driver available as a download (function block FB): - Support - Tools and Downloads! Ordering data SIPLUS DCF 77 radio clock module For synchronizing SIMATIC S7-200, S7-300 and S7-400 with the official time of the DCF 77 time signal transmitter of the Physikalisch- Technische Bundesanstalt Braunschweig, Germany Article No. AG1057-1AA03-0AA0 Siemens ST /91

92 Communication CP 440 For high-performance transmission of messages via point-to-point connections (high message rate) Physical interface: RS 422/RS 485 (X.27) Up to 32 nodes Protocol implemented: ASCII, 394 (R) Simple parameterization via a parameterization tool integrated into STEP 7 Technical specifications ES7440-1CS00-0YE0 CP 440-1, PTP-CONNECTIONS, 1 CHANNEL Product type designation Supply voltage Rated value (DC) 5 V DC 24 V DC Input current from backplane bus 5 V DC, max. 30 ma Power losses Power loss, typ. 1.7 W Memory Memory requirements per interface in 1 to 5 Kbytes for parameters memory card of S7-CPU Interfaces Number of interfaces 1 Interface physics, RS 422/RS 485 (X.27) RS 422/485, cable length, shielded, 1200m max. Point-to-point Integrated protocol driver (R) -ASCII Transmission speed, RS 422/485 - with 394 (R) protocol, max kbit/s - with ASCII protocol, max kbit/s Configuration Configuration software STEP 7 ; own parameter assignment forms Dimensions Width 25 mm Height 290 mm Depth 210 mm Weights Weight, approx. 00 g Ordering data Article No. CP 440 ES7440-1CS00-0YE0 communications processor with one RS 422/485 (X.27) interface RS 422/485 connecting cable for linking to SIMATIC S7 5 m ES7902-3AB00-0AA0 10 m ES7902-3AC00-0AA0 50 m ES7902-3AG00-0AA0 /92 Siemens ST

93 Communication CP 441-1, CP For fast, high-performance serial data exchange via point-to-point connection 2 versions: - CP with 1 variable interface for easy point-to-point coupling. - CP with 2 variable interfaces for high-performance point-to-point connection. Plug-in interface modules for different physical transmission properties: RS 232C (V.24), 20 ma (TTY) or RS 422/RS 485 (X.27) Implemented protocols: ASCII, 394 (R), printer driver; for CP additional RK 512 and Modbus RTU (reloadable) Simple parameter assignment using tool integrated in STEP 7 Technical specifications ES7441-1AA05-0AE0 ES7441-2AA05-0AE0 CP 441-1, PTP-CONN., 1 CHANNEL CP 441-2, PTP-CONN., 2 CHANNELS Product type designation Supply voltage Rated value (DC) 5 V DC 24 V DC Input current from backplane bus 5 V DC, max. 300 ma 300 ma Power losses Power loss, typ. 2.1 W; incl. 1x20 ma TTY module 2.7 W; incl. 2x20mA TTY module Memory Memory requirements per interface in memory card of S7-CPU Interfaces 1 to 5 KB for parameters; 0 to 55 KB for message texts 1 to 5 KB for parameters; 0 to 55 KB for message texts; 0 to 4 KB for loadable drivers Number of interfaces 1; variable 2; variable Interface physics, 20 ma (TTY) Interface physics, RS 232C (V.24) Interface physics, RS 422/RS 485 (X.27) 20 ma (TTY), cable length, shielded, m; At 900 bps m; At 900 bps max. RS 232, cable length, shielded, max. 15 m; At bps 15 m; At bps RS 422/485, cable length, shielded, m; At bps m; At bps max. Point-to-point Transmission rate, max kbit/s; Min. 300 bps kbit/s; Min. 300 bps supported printers HP-Deskjet, HP-Laserjet, IBM-Proprinter, user-defined HP-Deskjet, HP-Laserjet, IBM-Proprinter, user-defined Integrated protocol driver (R) -ASCII - RK512 No -Printer - customer-specific drivers No No reloadable Transmission speed, 20 ma (TTY) - with 394 (R) protocol, max kbit/s 19.2 kbit/s - with ASCII protocol, max kbit/s 19.2 kbit/s - with printer driver, max., 19.2 kbit/s 19.2 kbit/s - with RK 512 protocol, max kbit/s Siemens ST /93

94 Communication CP 441-1, CP Technical specifications (continued) ES7441-1AA05-0AE0 ES7441-2AA05-0AE0 CP 441-1, PTP-CONN., 1 CHANNEL CP 441-2, PTP-CONN., 2 CHANNELS Transmission speed, RS 422/485 - with 394 (R) protocol, max kbit/s kbit/s - with ASCII protocol, max kbit/s kbit/s - with printer driver, max., kbit/s kbit/s - with RK 512 protocol, max kbit/s Transmission speed, RS232 - with 394 (R) protocol, max kbit/s kbit/s - with ASCII protocol, max kbit/s kbit/s - with printer driver, max., kbit/s kbit/s - with RK 512 protocol, max kbit/s Ambient conditions Ambient temperature in operation Min. 0 C 0 C max. 0 C 0 C Relative humidity Operation, max. 95 % 95 % Dimensions Width 25 mm 25 mm Height 290 mm 290 mm Depth 210 mm 210 mm Weights Weight, approx. 580 g; Interface modules: 80 g 580 g; Interface modules: 80 g Ordering data Article No. Article No. Communication module CP ES7441-1AA05-0AE0 With 1 variable interface for interface submodules; including configuration package on CD Communication module CP ES7441-2AA05-0AE0 With 2 variable interfaces for interface submodules; including configuration package on CD Interface submodules RS 232C (V.24) ES793-1AA10-0AA0 20 ma (TTY) ES793-2AA10-0AA0 RS 422/485 (X.27) ES793-3AA10-0AA0 RS 232 connecting cable 5 m ES7902-1AB00-0AA0 10 m ES7902-1AC00-0AA0 15 m ES7902-1AD00-0AA0 TTY connecting cable 5 m ES7902-2AB00-0AA0 10 m ES7902-2AC00-0AA0 50 m ES7902-2AG00-0AA0 RS 422/485 connecting cable 5 m ES7902-3AB00-0AA0 10 m ES7902-3AC00-0AA0 50 m ES7902-3AG00-0AA0 Loadable drivers for CP Modbus master (RTU format) Single license ES7870-1AA01-0YA0 Single license, without software ES7870-1AA01-0YA1 or documentation Modbus slave (RTU format) Single license ES7870-1AB01-0YA0 Single license, without software ES7870-1AB01-0YA1 or documentation /94 Siemens ST

95 Drivers for Modbus protocol with RTU message format; communication as master or slave Downloadable onto CP 341 and CP (ES7441-2AA04-0AE0) Technical specifications Parameterization software Loadable drivers for CP and CP 341 Type of license Simple license, copy license Target system SIMATIC CP 341, SIMATIC CP Technical specifications Adjustable parameters Modbus Master Modbus protocol with RTU format Master/slave coupling: SIMATIC S7 is master Function codes implemented: 01, 02, 03, 04, 05, 0, 07, 08, 11,12,15,1 No V.24 control and signal lines CRC polynomial: x 1 + x 15 + x 2 +1 Interfaces: TTY (20 ma); V.24 (RS 232 C); X.27 (RS 422/485) 2-wire or 4-wire Receive mailbox specified on BRCV Character delay time 3.5 characters or multiple thereof Broadcast message possible Transmission rate 300 bit/s up to 7800 bit/s (TTY up to bit/s) Character frame With/without RS 485 operation for 2-wire connections With/without modem operation (ignore smudge characters) Response monitoring time 100 ms to 25.5 s in steps of 100 ms Factor for the character delay time 1-10 Default setting of receive line when using the X.27 interface module Modbus slave Modbus protocol with RTU format Master/slave coupling: SIMATIC S7 is slave Function codes implemented: 01, 02, 03, 04, 05, 0, 08, 15, 1 No V.24 control and signal line CRC polynomial: x 1 + x 15 + x 2 +1 Interfaces: TTY (20 ma), V.24 (RS 232C), X.27 (RS 422/485) 2-wire or 4-wire Communications FB 180, instance DB 180 (use of a multi-instance) Conversion of the Modbus data address to S7 data areas. Data areas which can be processed: DB, bit memories, outputs, inputs, timers, counters Character delay time 3.5 characters or multiple thereof Adjustable parameters Ordering data Modbus Master V3.1 Communication Task: Communication via Modbus protocol with RTU format, SIMATIC S7 as master Requirement: CP 341 or CP 441-2; STEP 7 V4.02 and higher Delivery package: Driver program/documentation, English, German, French Single license Single license, without software and documentation Modbus Slave V3.1 Task: Communication via Modbus protocol with RTU format, SIMATIC S7 as slave Requirement: CP 341 or CP 441-2; STEP 7 V4.02 and higher Delivery package: Driver program/documentation, English, German, French Single license Single license, without software and documentation SIMATIC Manual Collection Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection update service for 1 year Current "Manual Collection" DVD and the three subsequent updates Loadable drivers for CP and CP 341 Transmission rate 300 bit/s up to 7800 bit/s (TTY up to bit/s) Character frame Slave address of CP (1 to 255) With/without RS 485 operation for 2-wire connection With/without modem operation (ignore smudge characters) Factor for the character delay time 1-10 Number of work DB (for FB processing) Enabling of memory areas for writing by the master Default setting of receive line when using the X.27 interface module Conversion of Modbus addresses to S7 data areas Article No. ES7870-1AA01-0YA0 ES7870-1AA01-0YA1 ES7870-1AB01-0YA0 ES7870-1AB01-0YA1 ES7998-8XC01-8YE0 ES7998-8XC01-8YE2 Siemens ST /95

96 Communication CP Basic Connection of the S7-400 to PROFIBUS Communication services: - PG/OP communication - S7 communication - Open communication (SEND/RECEIVE) - PROFIBUS FMS Time synchronization Easy programming and configuration over PROFIBUS Cross-network programming device communication through S7 routing Can be easily integrated into the SIMATIC S7-400 system Modules can be replaced without the need for a PG SIMATIC H system operation for redundant S7 communication Technical specifications GK7443-5FX02-0XE0 Product type designation CP Basic Transmission rate Transfer rate at the 1st interface acc. to 9. kbit/s Mbit/s PROFIBUS Interfaces Number of interfaces 0 acc. to Industrial Ethernet Number of electrical connections at the 1st interface acc. to 1 PROFIBUS Type of electrical connection at the 1st interface acc. to 9-pin Sub-D socket (RS 485) PROFIBUS Supply voltage, current consumption, power loss Type of voltage of the supply voltage DC Supply voltage 1 from backplane bus 5V Supply voltage 5V Relative symmetrical tolerance for DC at 5 V 5% Consumed current from backplane bus for DC 1A at 5 V typical from external supply voltage 1.2 A for DC at 24 V typical Active power loss 5W Permitted ambient conditions Ambient temperature during operation C during storage C during transport C Relative humidity at 25 C without 95 % condensation during operation maximum Protection class IP IP20 Design, dimensions and weight Module format Compact module S7-400 single width Width 25 mm Height 290 mm Depth 210 mm Net weight 0.5 kg Product properties, functions, components general Number of units per CPU maximum 14 Note depending on CPU type Performance data open communication Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum 32 Amount of data as user data per connection for open 240 byte communication by means of SEND/ RECEIVE blocks maximum /9 Siemens ST

97 Technical specifications (continued) GK7443-5FX02-0XE0 Product type designation CP Basic Performance data FMS functions Number of possible connections 48 for FMS connection maximum Amount of data of the variables for READ job maximum 237 byte for WRITE job maximum 233 byte Number of variables Configurable from server 512 to FMS partner Loadable from server to FMS partner 240 Performance data S7 communication Number of possible connections for S7 communication maximum 48 Performance data multi-protocol mode Number of possible connections of 59 which 2 reserved for PG/OP communication with multi-protocol mode maximum Performance data telecontrol Protocol is supported TCP/IP No Product functions management, configuration Configuration software required STEP 7 V5.2 SP1 or higher and NCM S7 for PROFIBUS Ordering data Communication CP Basic communications processor Communications processor for connection of S7-400 to PROFIBUS, FMS, open communication, PG/OP and S7 communication; with electronic manual on CD-ROM STEP 7 Version 5.5 Target system: SIMATIC S7-300/-400, SIMATIC C7, SIMATIC WinAC Requirements: Windows XP Prof., Windows 7 Professional/Ultimate Type of delivery: German, English, French, Spanish, Italian; including license key on USB stick, with electronic documentation Floating License on DVD Rental license for 50 hours Software Update Service on DVD (requires current software version) Floating License upgrade 3.x/4.x/5.x to V5.4; on DVD Trial License STEP 7 V5.4; on DVD, operational for 14 days Accessories PROFIBUS FastConnect RS 485 connection plugs With 90 cable outlet; insulation displacement technology, max. transmission rate 12 Mbit/s Without PG interface With PG interface PROFIBUS IP20 bus connectors With connection to PPI, MPI, PROFIBUS Without PG interface With PG interface PROFIBUS bus terminal 12M Bus terminal for connection of PROFIBUS nodes at up to 12 Mbit/s with connecting cable Article No. GK7443-5FX02-0XE0 ES7810-4CC10-0YA5 ES7810-4CC10-0YA ES7810-4BC01-0YX2 ES7810-4CC10-0YE5 ES7810-4CC10-0YA7 ES7972-0BA52-0XA0 ES7972-0BB52-0XA0 ES7972-0BA12-0XA0 ES7972-0BB12-0XA0 GK1500-0AA10 CP Basic Siemens ST /97

98 Communication CP Extended PROFIBUS DP master with electrical interface for connecting the SIMATIC S7-400 to PROFIBUS at up to 12 Mbit/s (including Kbit/s) For setting up additional PROFIBUS DP lines Communication services: - PROFIBUS DP - PG/OP communication - S7 communication - Open communication (SEND/RECEIVE) Time synchronization Easy programming and configuration over PROFIBUS Cross-network programming device communication through S7 routing Can be easily integrated into the SIMATIC S7-400 system Module replacement without PG SIMATIC H system operation for redundant S7 communication or DP master communication Data record routing (PROFIBUS DP) Adding or modifying distributed I/O during operation Technical specifications GK7443-5DX05-0XE0 Product type designation CP Extended Transmission rate Transfer rate at the 1st interface acc. to 9. kbit/s Mbit/s PROFIBUS Interfaces Number of interfaces 0 acc. to Industrial Ethernet Number of electrical connections at the 1st interface acc. to 1 PROFIBUS Type of electrical connection at the 1st interface acc. to 9-pin Sub-D socket (RS 485) PROFIBUS Supply voltage, current consumption, power loss Type of voltage of the supply voltage DC Supply voltage 1 from backplane bus 5V Relative symmetrical tolerance for DC at 5 V 5% Consumed current from backplane bus for DC at 5 V 0. A typical Active power loss 3W Permitted ambient conditions Ambient temperature during operation C during storage C during transport C Relative humidity at 25 C without 95 % condensation during operation maximum Protection class IP IP20 Design, dimensions and weight Module format Compact module S7-400 single width Width 25 mm Height 290 mm Depth 210 mm Net weight 0.5 kg Product properties, functions, components general Number of units per CPU maximum 14 Note The number of CPs that can be operated as DP masters depends on the number of CP Advanced processors operating in the S7-400 station as PROFINET IO controllers. Up to 10 CPs can be operated in total: up to 4 as PROFINET IO controllers (CP Advanced); up to 10 as DP masters (CP Extended) /98 Siemens ST

99 Technical specifications (continued) GK7443-5DX05-0XE0 Product type designation CP Extended Performance data open communication Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum 32 Amount of data as user data per connection for 240 byte open communication by means of SEND/RECEIVE blocks maximum Performance data PROFIBUS DP Service as DP master DPV1 Number of DP slaves 125 on DP master usable Amount of data of the address area 409byte of the inputs as DP master total of the address area 409byte of the outputs as DP master total of the address area 244 byte of the inputs per DP slave of the address area 244 byte of the outputs per DP slave Performance data S7 communication Number of possible connections for S7 communication maximum 48 Performance data multi-protocol mode Number of active connections with multi-protocol mode without DP maximum 59 with DP maximum 54 Performance data telecontrol Protocol is supported TCP/IP No Product functions management, configuration Configuration software required STEP 7 V5.4 SP4 or higher / STEP 7 Professional V12 (TIA Portal) or higher Ordering data Communication CP Extended communications processor for connection of the SIMATIC S7-400 to PROFIBUS Extended version for PROFIBUS DP; with electronic manual on CD-ROM Accessories PROFIBUS FastConnect connection plug RS 485 With 90 cable outlet; insulation displacement technology, max. transmission rate 12 Mbit/s Without PG interface With PG interface PROFIBUS bus connector IP20 With connection to PPI, MPI, PROFIBUS Without PG interface With PG interface PROFIBUS FC Standard Cable 2-core bus cable, shielded, special design for fast mounting, delivery unit: max m, minimum order 20 m, sold by the meter PROFIBUS bus terminal 12M Bus terminal for connection of PROFIBUS nodes up to 12 Mbps with connecting cable Article No. GK7443-5DX05-0XE0 ES7972-0BA52-0XA0 ES7972-0BB52-0XA0 ES7972-0BA12-0XA0 ES7972-0BB12-0XA0 XV1830-0EH10 GK1500-0AA10 CP Extended Note: You can find order information for software for communication with PC systems in the IK PI catalog. Siemens ST /99

100 Communication CP ISO TCP/ UDP PN MRP IP-R PG/OP S7/S5 Communications processor for connecting a SIMATIC S7-400 to Industrial Ethernet networks, also as PROFINET IO controller or in SIMATIC H systems. The CP supports: PG/OP communication S7 communication Open communication (SEND/RECEIVE) PROFINET communication IT communication The communications processor can also be used for redundant S7 communication in SIMATIC H systems and for fail-safe applications (PROFIsafe) in connection with an S7-400 F-CPU. IT G_IK10_XX_10152 Technical specifications GK7443-1EX30-0XE0 Product type designation CP Transmission rate Transfer rate at the 1st interface Mbit/s Interfaces Number of interfaces 2 acc. to Industrial Ethernet Number of electrical connections at the 1st interface 2 acc. to Industrial Ethernet Type of electrical connection at the 1st interface RJ45 port acc. to Industrial Ethernet design of the removable No storage C-PLUG Supply voltage, current consumption, power loss Type of voltage of the supply voltage DC Supply voltage 1 from backplane bus 5V Relative symmetrical tolerance for DC at 5 V 5% Consumed current from backplane bus for DC 1.4 A at 5 V typical Active power loss 7.25 W Permitted ambient conditions Ambient temperature during operation C during storage C during transport C Relative humidity at 25 C without 95 % condensation during operation maximum Protection class IP IP20 Design, dimensions and weight Module format Compact module S7-400 single width Width 25 mm Height 290 mm Depth 210 mm Net weight 0.7 kg Product properties, functions, components general Number of units per CPU maximum 14 Note max. 4 as PN IO ctrl. /100 Siemens ST

101 Communication CP Technical specifications (continued) GK7443-1EX30-0XE0 Product type designation CP Performance data open communication Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum 4 Amount of data as user data per ISO connection for 8Kibyte open communication by means of SEND/RECEIVE blocks maximum as user data per ISO on TCP connection for open communication by means of SEND/RECEIVE blocks maximum as user data per TCP connection for open communication by means of SEND/RECEIVE blocks maximum 8Kibyte 8Kibyte as user data per UDP connection for 2Kibyte open IE communication by means of SEND/RECEIVE blocks maximum Number of possible connections for open communication by means of T blocks maximum 4 Amount of data as user data per ISO on TCP 1452byte connection for open communication by means of T blocks maximum Performance data S7 communication Number of possible connections for S7 communication maximum 128 with PG connections maximum 2 Note when using several CPUs Performance data multi-protocol mode Number of active connections 128 with multi-protocol mode Performance data PROFINET communication as PN IO-Controller Product function PROFINET IO controller Number of PN IO devices on 128 PROFINET IO controller usable total Number of PN IO IRT devices on 4 PROFINET IO controller usable Number of external PN IO lines 4 with PROFINET per rack Amount of data as user data for input variables as 4Kibyte PROFINET IO controller maximum as user data for input variables as 4Kibyte PROFINET IO controller maximum as user data for input variables 1433byte per PN IO device as PROFINET IO controller maximum as user data for output variables per PN IO device as PROFINET IO controller maximum as user data for input variables per PN IO device for each sub-module as PROFINET IO controller maximum as user data for output variables per PN IO device for each sub-module as PROFINET IO controller maximum 1433byte 240 byte 240 byte GK7443-1EX30-0XE0 Product type designation CP Performance data telecontrol Protocol is supported TCP/IP Product functions management, configuration Product function MIB support Protocol is supported SNMP v1 DCP LLDP Configuration software required STEP 7 V5.5 SP3 or higher / STEP 7 Professional V12 (TIA Portal) or higher Product functions Diagnosis Product function Web-based diagnostics Product functions switch Product feature Switch Product function switch-managed No with IRT PROFINET IO switch Configuration with STEP 7 Product functions Redundancy Product function Ring redundancy Redundancy manager Protocol is supported Media Redundancy Protocol (MRP) Product functions Security Product function password protection No for Web applications ACL - IP-based ACL - IP-based for PLC/routing No switch-off of non-required services Blocking of communication via physical ports log file for unauthorized access No Product functions Time Product function SICLOCK support Product function pass on time synchronization Protocol is supported NTP Siemens ST /101

102 Communication CP Ordering data Article No. Article No. CP communications processor GK7443-1EX30-0XE0 IE FC TP Standard Cable GP 2 x 2 (Type A) XV1840-2AH10 For connecting SIMATIC S7-400 to Industrial Ethernet through TCP/IP, ISO and UDP; PROFINET IO Controller, MRP; integrated real-time switch ERTEC with two ports; 2 x RJ45 interface; S7 communication, open communication (SEND/RECEIVE) with FETCH/WRITE, with and without RFC 100, DHCP, SNMP V2, diagnostics, multicast, access protection over IP access list, initialization over LAN 10/100 Mbps with electronic manual on DVD Accessories IE FC RJ45 Plug x 2 RJ45 plug-in connector for Industrial Ethernet with a rugged metal enclosure and integrated insulation displacement contacts for connecting Industrial Ethernet FC installation cables; with 180 cable outlet; for network components and CPs/ CPUs with Industrial Ethernet interface 1 pack = 1 unit 1 pack = 10 units 1 pack = 50 units GK1901-1BB10-2AA0 GK1901-1BB10-2AB0 GK1901-1BB10-2AE0 4-core, shielded TP installation cable for connection to IE FC Outlet RJ45/IE FC RJ45 Plug; PROFINET-compatible; with UL approval; sold by the meter; max. order length 1000 m, minimum order 20 m IE FC TP Standard Cable GP 4 x 2 8-core, shielded TP installation cable for connection to IE FC RJ45 modular outlet for universal applications; with UL approval; sold by the meter; max. order quantity 1000 m, minimum order 20 m AWG22, for connection to IE FC RJ45 Modular Outlet AWG24, for connection to IE FC RJ45 Plug 4 x 2 IE FC Stripping Tool Pre-adjusted stripping tool for fast stripping of the Industrial Ethernet FC cables SCALANCE X204-2 Industrial Ethernet Switch XV1870-2E XV1878-2A GK1901-1GA00 GK5204-2BB10-2AA3 IE FC RJ45 Plug 4 x 2 RJ45 plug connector for Industrial Ethernet (10/100/1000 Mbps) with a rugged metal enclosure and integrated insulation displacement contacts for connecting Industrial Ethernet FC installation cables; 180 cable outlet; for network components and CPs/CPUs with Industrial Ethernet interface 1 pack = 1 unit 1 pack = 10 units 1 pack = 50 units GK1901-1BB11-2AA0 GK1901-1BB11-2AB0 GK1901-1BB11-2AE0 Industrial Ethernet Switches with integral SNMP access, Web diagnostics, copper cable diagnostics and PROFINET diagnostics for configuring line, star and ring topologies; four 10/100 Mbps RJ45 ports and two FO ports Industrial Ethernet Switch SCALANCE X x 1000 Mbps multimode fiberoptic cable ports (SC sockets), 1 x 10/100/1000 Mbps RJ45 port, 7 x 10/100 Mbps RJ45 ports; for glass fiber-optic cable (multimode) up to max. 750 m GK5308-2FL00-2AA3 Note: You'll find ordering data for software for communication to PC systems in catalog IK PI. /102 Siemens ST

103 Communication CP Advanced Communications processor for connecting a SIMATIC S7-400 to Industrial Ethernet networks, also as PROFINET IO controller or in SIMATIC H systems. The CP supports: PG/OP communication S7 communication Open communication (SEND/RECEIVE) PROFINET communication IT communication Security functionality, firewall and VPN The communications processor can also be used for redundant S7 communication in SIMATIC H systems and for fail-safe applications (PROFIsafe) in connection with an S7-400 F-CPU. In addition, the CP Advanced provides functions and user-created Web pages, offering ideal support for maintenance and quality assurance. The Internet functions such as FTP even allow connection to the most diverse PC-based systems. This CP is therefore the bridge between the field level and the management level for the S The CP Advanced connects seamlessly to the security structures of the office and IT worlds. Technical specifications GK7443-1GX30-0XE0 Product type designation CP Advanced Transmission rate Transfer rate at the 1st interface Mbit/s at the 2nd interface Mbit/s Interfaces Number of interfaces 5 acc. to Industrial Ethernet Number of electrical connections at the 1st interface 1 acc. to Industrial Ethernet at the 2nd interface 4 acc. to Industrial Ethernet Type of electrical connection at the 1st interface RJ45 port acc. to Industrial Ethernet at the 2nd interface RJ45 port acc. to Industrial Ethernet design of the removable storage C-PLUG Supply voltage, current consumption, power loss Type of voltage of the supply voltage DC Supply voltage 1 from backplane bus 5V Relative symmetrical tolerance for DC at 5 V 5% Consumed current from backplane bus for DC 1.8 A at 5 V typical Active power loss 9W Permitted ambient conditions Ambient temperature during operation C during storage C during transport C Relative humidity at 25 C without 95 % condensation during operation maximum Protection class IP IP20 Design, dimensions and weight Module format Compact module S7-400 single width Width 25 mm Height 290 mm Depth 210 mm Net weight 0.7 kg Product properties, functions, components general Number of units per CPU maximum 14 Note max. 4 as PN IO ctrl. Siemens ST /103

104 Communication CP Advanced Technical specifications (continued) GK7443-1GX30-0XE0 Product type designation CP Advanced Performance data open communication Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum 4 Amount of data as user data per ISO connection for 8Kibyte open communication by means of SEND/RECEIVE blocks maximum as user data per ISO on TCP connection for open communication by means of SEND/RECEIVE blocks maximum as user data per TCP connection for open communication by means of SEND/RECEIVE blocks maximum 8Kibyte 8Kibyte as user data per UDP connection for 2Kibyte open IE communication by means of SEND/RECEIVE blocks maximum Number of possible connections for open communication by means of T blocks maximum 4 Amount of data as user data per ISO on TCP 1452byte connection for open communication by means of T blocks maximum Performance data S7 communication Number of possible connections for S7 communication maximum 128 with PG connections maximum 2 Note when using several CPUs Performance data multi-protocol mode Number of active connections with 128 multi-protocol mode Performance data IT functions Number of possible connections as client by means of FTP maximum 20 as server by means of FTP maximum 10 as server by means of HTTP 4 maximum as client maximum 1 Amount of data as user data 8Kibyte for maximum Storage capacity of the user memory as flash memory file system 30 Mibyte as RAM 1 Mibyte additionally buffered as RAM via 512 Kibyte central backup battery Number of possible write cycles of the flash memory cells Performance data PROFINET communication as PN IO-Controller Product function PROFINET IO controller Number of PN IO devices on 128 PROFINET IO controller usable total Number of PN IO IRT devices on 4 PROFINET IO controller usable Number of external PN IO lines with 4 PROFINET per rack Product type designation Amount of data as user data for input variables as PROFINET IO controller maximum as user data for input variables as PROFINET IO controller maximum as user data for input variables per PN IO device as PROFINET IO controller maximum as user data for output variables per PN IO device as PROFINET IO controller maximum as user data for input variables per PN IO device for each submodule as PROFINET IO controller maximum as user data for output variables per PN IO device for each sub-module as PROFINET IO controller maximum Performance data PROFINET CBA Number of remote connection partners with PROFINET CBA Number of connections with PROFINET CBA total Amount of data as user data for digital inputs with PROFINET CBA maximum as user data for digital outputs with PROFINET CBA maximum as user data for arrays and data types in the case of acyclic transmission with PROFINET CBA maximum as user data for arrays and data types with PROFINET CBA with cyclical transfer maximum as user data for arrays and data types with PROFINET CBA in the case of local interconnection maximum Performance data PROFINET CBA remote connection with acyclic transmission Refresh time of the remote interconnections in the case of acyclic transmission with PROFINET CBA Number of remote connections to input variables in the case of acyclic transmission with PROFINET CBA maximum Number of remote connections to output variables in the case of acyclic transmission with PROFINET CBA maximum Amount of data as user data for remote interconnections with input variables in the case of acyclic transmission with PROFINET CBA as user data for remote interconnections with output variables in the case of acyclic transmission with PROFINET CBA Performance data PROFINET CBA remote connection with cyclic transmission Refresh time of the remote interconnections with PROFINET CBA with cyclical transfer GK7443-1GX30-0XE0 CP Advanced 8Kibyte 8Kibyte 1433byte 1433byte 240 byte 240 byte Kibyte 8Kibyte 8Kibyte 250 byte 2400byte 100 ms Kibyte 8Kibyte 10 ms /104 Siemens ST

105 Communication CP Advanced Technical specifications (continued) Product type designation Number of remote connections to input variables with PROFINET CBA with cyclical transfer maximum Number of remote connections to output variables with PROFINET CBA with cyclical transfer maximum Amount of data as user data for remote interconnections with input variables with PROFINET CBA with cyclical transfer maximum as user data for remote interconnections with output variables with PROFINET CBA with cyclical transfer maximum Performance data PROFINET CBA HMI variables via PROFINET acyclic Number of connectable HMI stations for HMI variables in the case of acyclic transmission with PROFINET CBA Refresh time of the HMI variables in the case of acyclic transmission with PROFINET CBA Number of HMI variables in the case of acyclic transmission with PROFINET CBA maximum Amount of data as user data for HMI variables in the case of acyclic transmission with PROFINET CBA maximum Performance data PROFINET CBA device-internal connections Number of internal connections with PROFINET CBA maximum Amount of data of the internal connections with PROFINET CBA maximum Performance data PROFINET CBA connections to constants Number of connections with constants with PROFINET CBA maximum Amount of data as user data for interconnections with constants with PROFINET CBA maximum Performance data PROFINET CBA PROFIBUS proxy functionality Product function with PROFINET CBA PROFIBUS proxy functionality Performance data telecontrol Protocol is supported TCP/IP GK7443-1GX30-0XE0 CP Advanced byte 2000byte ms 200 8Kibyte byte byte No GK7443-1GX30-0XE0 Product type designation CP Advanced Product functions management, configuration Product function MIB support Protocol is supported SNMP v1 SNMP v3 DCP LLDP Configuration software required STEP 7 V5.5 SP3 or higher / STEP 7 Professional V12 (TIA Portal) or higher for PROFINET CBA required SIMATIC imap V3.0 SP1 and higher Product functions Diagnosis Product function Web-based diagnostics Product functions switch Product feature Switch Product function switch-managed No with IRT PROFINET IO switch Configuration with STEP 7 Product functions Redundancy Product function Ring redundancy Redundancy manager Protocol is supported Media Redundancy Protocol (MRP) Product functions Security Firewall version stateful inspection Product function with VPN connection IPSec Type of encryption algorithms with VPN connection Type of authentication procedure with VPN connection Type of hashing algorithms with VPN connection Number of possible connections with VPN connection Product function password protection for Web applications ACL - IP-based ACL - IP-based for PLC/routing switch-off of non-required services Blocking of communication via physical ports log file for unauthorized access Product functions Time Product function SICLOCK support Product function pass on time synchronization Protocol is supported NTP AES-25, AES-192, AES-128, 3DES-18, DES-5 Preshared key (PSK), X.509v3 certificates MD5, SHA-1 32 No Siemens ST /105

106 Communication CP Advanced Ordering data Article No. Article No. Communications processor CP Advanced IE FC TP Standard Cable GP 2 x 2 (Type A) XV1840-2AH10 for connecting the SIMATIC S7-400 CPU to Industrial Ethernet: 1 x 10/100/1000 Mbit/s; 4 x 10/100 Mbit/s (IE SWITCH); RJ45 ports; ISO; TCP; UDP; PROFINET IO controller, S7 communication; open communication (SEND/RECEIVE); S7 routing; IP configuration via DHCP/block; IP Access Control List; time synchronization; expanded web diagnostics; Fast Startup; PROFIenergy support; IP routing; FTP; web server; ; PROFINET CBA With security functionality (firewall and VPN) Accessories IE FC RJ45 Plug x 2 RJ45 plug-in connector for Industrial Ethernet with a rugged metal enclosure and integrated insulation displacement contacts for connecting Industrial Ethernet FC installation cables; with 180 cable outlet; for network components and CPs/ CPUs with Industrial Ethernet interface 1 pack = 1 unit 1 pack = 10 units 1 pack = 50 units IE FC RJ45 Plug 4 x 2 RJ45 plug connector for Industrial Ethernet (10/100/1000 Mbit/s) with a sturdy metal enclosure and integrated insulation displacement contacts for connecting Industrial Ethernet FC installation cables; 180 cable outlet; for network components and CPs/CPUs with Industrial Ethernet interface 1 pack = 1 unit 1 pack = 10 units 1 pack = 50 units GK7443-1GX30-0XE0 GK1901-1BB10-2AA0 GK1901-1BB10-2AB0 GK1901-1BB10-2AE0 GK1901-1BB11-2AA0 GK1901-1BB11-2AB0 GK1901-1BB11-2AE0 4-core, shielded TP installation cable for connection to IE FC Outlet RJ45/IE FC RJ45 Plug; PROFINET-compatible; with UL approval; sold by the meter; max. length 1000 m, minimum order quantity 20 m IE FC TP Standard Cable GP 4 x 2 8-core, shielded TP installation cable for connection to IE FC RJ45 Modular Outlet for universal applications; with UL approval; sold by the meter; max. quantity 1000 m, minimum order 20 m AWG22, for connection to IE FC RJ45 Modular Outlet AWG24, for connection to IE FC RJ45 Plug 4 x 2 IE FC Stripping Tool Preadjusted stripping tool for fast stripping of the Industrial Ethernet FC cables Industrial Ethernet Switch SCALANCE X204-2 Industrial Ethernet Switches with integral SNMP access, Web diagnostics, copper cable diagnostics and PROFINET diagnostics for configuring line, star and ring topologies; four 10/100 Mbit/s RJ45 ports and two FO ports Industrial Ethernet Switch SCALANCE X x 1000 Mbit/s multimode fiberoptic cable ports (SC sockets), 1 x 10/100/1000 Mbit/s RJ45 port, 7 x 10/100 Mbit/s RJ45 ports; for glass fiber-optic cable (multimode) up to max. 750 m XV1870-2E XV1878-2A GK1901-1GA00 GK5204-2BB10-2AA3 GK5308-2FL00-2AA3 Note: You can find order information for software for communication with PC systems in the IK PI catalog. /10 Siemens ST

107 Communication CP RNA ISO TCP/ UDP PN PRP IP-R PG/OP S7/S5 Communication processor for connecting a SIMATIC S7-400/S7-400H to Industrial Ethernet networks. The CP supports: PG/OP communication S7 communication Open communication (SEND/RECEIVE) The communications processor can be used in SIMATIC H systems and for fail-safe applications (PROFIsafe) in connection with an S7-400 F-CPU. The CP RNA (Redundant Network Access) 1) offers the option of using the PRP procedure (Parallel Redundancy Protocol in accordance with IEC ) to connect an S7-400 or S7-400H to parallel, separate networks where high availability is required. The PRP functionality can be deactivated so that standard Industrial Ethernet communication is also possible with the CP. The PRP redundancy procedure is based on double transmission of message frames over two separate networks (LAN A, LAN B). In the event of a fault in one of the two networks, transmission of the message frame from the second network is ensured without delay. A reconfiguration time (switchover of the communication paths) for the network, such as is required with other redundancy procedures, is thus not necessary. 1) At Siemens Industry, RNA stands for hardware and software to implement redundancy solutions. RNA contains the PRP V1 protocol in accordance with the IEC standard (Parallel Redundancy Protocol) as well as the HSR protocol in accordance with IEC (High-availability Seamless Redundancy Protocol). IT G_IK10_XX_10151 Technical specifications GK7443-1RX00-0XE0 Product type designation CP RNA Transmission rate Transfer rate at the 1st interface Mbit/s at the 2nd interface 100 Mbit/s Interfaces Number of interfaces 3 acc. to Industrial Ethernet Number of electrical connections at the 1st interface 1 acc. to Industrial Ethernet at the 2nd interface 2 acc. to Industrial Ethernet Type of electrical connection at the 1st interface RJ45 port acc. to Industrial Ethernet at the 2nd interface RJ45 port acc. to Industrial Ethernet Supply voltage, current consumption, power loss Type of voltage of the supply voltage DC Supply voltage 1 from backplane bus 5V Relative symmetrical tolerance for DC at 5 V 5% Consumed current from backplane bus for DC 1.8 A at 5 V typical Active power loss 9W Permitted ambient conditions Ambient temperature during operation C during storage C during transport C Relative humidity at 25 C without 95 % condensation during operation maximum Protection class IP IP20 Design, dimensions and weight Module format Compact module S7-400 single width Width 25 mm Height 290 mm Depth 210 mm Net weight 0.7 kg Product properties, functions, components general Number of units per CPU maximum 14 Performance data open communication Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum 4 Amount of data as user data per ISO connection for 8Kibyte open communication by means of SEND/RECEIVE blocks maximum as user data per ISO on TCP 8Kibyte connection for open communication by means of SEND/RECEIVE blocks maximum as user data per TCP connection for 8Kibyte open communication by means of SEND/RECEIVE blocks maximum Siemens ST /107

108 Communication CP RNA Technical specifications (continued) Ordering data Article No. GK7443-1RX00-0XE0 Product type designation CP RNA Amount of data (continued) as user data per UDP connection for 2Kibyte open IE communication by means of SEND/RECEIVE blocks maximum Number of possible connections for open communication by means of T blocks maximum 4 Amount of data as user data per ISO on TCP 1452byte connection for open communication by means of T blocks maximum Performance data S7 communication Number of possible connections for S7 communication maximum 128 with PG connections maximum 2 Note when using several CPUs Performance data multi-protocol mode Number of active connections 128 with multi-protocol mode Performance data telecontrol Protocol is supported TCP/IP Product functions management, configuration Product function MIB support Protocol is supported SNMP v1 DCP Configuration software required STEP 7 V5.5 SP2 + HSP or higher Product functions Diagnosis Product function Web-based diagnostics Product functions Redundancy Product function Ring redundancy No Redundancy manager No Parallel Redundancy Protocol (PRP) Protocol is supported Media No Redundancy Protocol (MRP) Product functions Security Product function ACL - IP-based ACL - IP-based for PLC/routing switch-off of non-required services Blocking of communication via physical ports log file for unauthorized access No Product functions Time Product function SICLOCK support Product function pass on time synchronization Protocol is supported NTP CP RNA communications processor for connecting the SIMATIC S7-400/ S7-400H CPU to Industrial Ethernet Accessories SCALANCE X-200RNA Industrial Ethernet network access points Industrial Ethernet network access points with integrated SNMP access, web diagnostics and PROFINET diagnostics, for connecting non-prp-enabled terminal equipment to PRP networks; incl. operating instructions, Industrial Ethernet network manual and configuration software on CD-ROM; with electrical and optical ports for glass multimode fiber optic cables up to 5 km SCALANCE X204RNA with four 100 Mbit/s RJ45 ports SCALANCE X204RNA EEC with two 100 Mbit/s RJ45 ports and two RJ45/SFP combo ports SCALANCE X204RNA EEC with two 100 Mbit/s RJ45 ports and two RJ45/SFP combo ports with PRP or HSR support SOFTNET-IE RNA Software for connecting PCs to PRP-enabled networks with integrated SNMP, runtime software, software and electronic manual on CD-ROM, license key on USB flash drive, Class A SOFTNET-IE RNA V12 for 32/4-bit Windows 7 Professional/Ultimate; for Windows 2008 Server R2; for 32/4-bit Windows 8 Professional/Enterprise; for Windows Server 2012 German/English Single license for one installation SOFTNET-IE RNA V8.1 for 32-bit Windows XP; German/English Single license for one installation Software Update Service for 1 year with automatic extension; requirement: Current software version GK7443-1RX00-0XE0 GK5204-0BA00-2KB2 GK5204-0BS00-3LA3 GK5204-0BS00-3PA3 GK1711-1EW12-0AA0 GK1711-1EW08-1AA0 GK1711-1EW00-3AL0 /108 Siemens ST

109 Communication TIM 4R-IE for WAN and Ethernet, TIM 4R-IE DNP3 TIM 4R-IE for WAN and Ethernet TIM 4R-IE DNP3 SINAUT communications module TIM with four interfaces for SIMATIC S7-300 or as self-contained unit for the S7-400 for use in the wide area network (WAN) For universal use in a SINAUT station, node station and control center Internet communication via integrated MSC-VPN tunnel with direct connection to DSL router or operation via IPsec VPN with additional SIMATIC NET components Wireless communication via GPRS router, GPRS modem, or radio devices Wired communication via Ethernet, DSL, dialup modems or dedicated line modem Complete migration of existing wireless, dedicated line and dial-up technology to IP-based network Message frame memory for complete recording of data and support of redundant communication paths Simple configuration and operation without specialist IT knowledge For further information, see chapter 5, page 5/223. In a station for the S7-CPU, the communication module TIM 4R-IE DNP3 (TeleControl Interface Module) handles the data exchange with the assigned SIMATIC PCS7 TeleControl V8.0 master system using the open DNP3 protocol. In addition, the V3.0 module now also supports master and node functionality. With the double-width S7-300 housing, the module can be fully integrated into the S7-300 system Can be connected as a stand-alone module to a SIMATIC S7-400 and SIMATIC S7-400 H System Two RS 232/RS 485 interfaces support connection of an external modem for data transmission via a conventional WAN or of a Modbus RTU slave to an S7-300 system The module has two RJ45 interfaces for data transmission via IP-based networks By using physically separate connection paths, the module permits media redundancy without loss of data during the switchover For further information, see chapter 5, page 5/228. Siemens ST /109

110 SIPLUS S7-400 communication SIPLUS S7-400 CP Extended DP-V1 master connection of the S7-400 to PROFIBUS For setting up additional PROFIBUS DP lines Communication services: - PROFIBUS DP - PG/OP communication - S7 communication - S5-compatible communication (SEND/RECEIVE) Clock synchronization Easy programming and configuration over PROFIBUS Cross-network programming device communication through S7 routing Can be easily integrated into the SIMATIC S7-400 system Module replacement without PG SIMATIC H system operation for redundant S7 communication or DP master communication Data record routing (PROFIBUS DP) Adding or modifying distributed I/O during operation Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added. SIPLUS CP Extended Article No. AG DX05-4XE0 Article No. based on GK DX05-0XE0 Ambient temperature range C Conformal coating Coating of the printed circuit boards and the electronic components Technical specifications The technical specifications of the standard product apply, except for the ambient conditions Ambient conditions Relative humidity 100 %, condensation/frost permissible. No commissioning if condensation present. Biologically active substances, compliance with EN Chemically active substances, compliance with EN Mechanically active substances, compliance with EN Air pressure (depending on the highest positive temperature range specified) For technical documentation on SIPLUS, see: Ordering data Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! Class 3C4 incl. salt spray in accordance with EN (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation! Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation! hpa ( m) see ambient temperature range hpa ( m) derating 10 K hpa ( m) derating 20 K Article No. SIPLUS S7-400 CP Extended communications processor for connecting SIMATIC S7-400 to PROFIBUS; Extended Version for PROFIBUS DP; with electronic manual, on CD-ROM Exposure to media AG1443-5DX05-4XE0 Accessories See SIMATIC CP Extended, page /99 /110 Siemens ST

111 SIPLUS S7-400 communication SIPLUS S7-400 CP ISO TCP/ UDP PN MRP IP-R PG/OP S7/S5 Connection of SIMATIC S7-400 to Industrial Ethernet - 2 x RJ45 interface for 10/100 Mbit/s full/half-duplex connection with auto-sensing/auto-negotiation and auto-crossover function - Integrated real-time switch ERTEC with two ports - Multi-protocol operation for ISO, TCP/IP, UDP and PROFINET IO protocols - Adjustable Keep Alive function Communication services: - Open communication (ISO, TCP/IP, and UDP) - PROFINET IO Controller with real-time properties RT and IRT - PG/OP communication: Cross-network by means of S7 routing - S7 communication Media redundancy (MRP); the CP supports the media redundancy procedure MRP within an Ethernet network with ring topology. Multicast for UDP Access protection via configurable access list Support for fail-safe programmable controllers together with SIMATIC S7-400 CPU 41F-3PN/DP Module replacement without PG Operation in the SIMATIC H system for redundant S7-communication Configuration with STEP 7 Diagnostics possibilities in STEP 7 and via web browser Automatic CPU-clock setting via Industrial Ethernet with NTP or SIMATIC procedure Integration of network management systems via SNMP (MIB II diagnostic information) Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. IT G_IK10_XX_10152 SIPLUS CP Article No. AG EX20-4XE0 based on GK EX20-0XE0 Ambient temperature range C Conformal coating Coating of the printed circuit boards and the electronic components Technical data The technical data of the standard product applies, except for the ambient conditions Ambient conditions Relative humidity 100 %, condensation/frost permissible. No commissioning if condensation present. Biologically active substances, compliance with EN Chemically active substances, compliance with EN Mechanically active substances, compliance with EN Air pressure (depending on the highest positive temperature range specified) For technical documentation on SIPLUS, see: Class 3B2 mold spores, fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! Class 3C4 incl. salt spray in accordance with EN (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation! Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation! hpa ( m) see ambient temperature range hpa ( m) derating 10 K hpa ( m) derating 20 K Siemens ST /111

112 SIPLUS S7-400 communication SIPLUS S7-400 CP Ordering data Article No. Article No. SIPLUS CP communications processor For connecting SIMATIC S7-400 to Industrial Ethernet through TCP/IP, ISO and UDP; PROFINET IO Controller, MRP; integrated real-time switch ERTEC with two ports; 2 x RJ-45 interface; S7 communication, open communication (SEND/ RECEIVE) with FETCH/WRITE, with and without RFC 100, DHCP, SNMP V2, diagnostics, multicast, access protection over IP access list, initialization over LAN 10/100 Mbit/s with electronic manual on DVD Exposure to media AG1443-1EX20-4XE0 Accessories SIPLUS SCALANCE X204-2 Industrial Ethernet Switch Industrial Ethernet Switches with integral SNMP access, Web diagnostics, copper cable diagnostics and PROFINET diagnostics for configuring line, star and ring topologies; four 10/100 Mbit/s RJ45 ports and two FO ports Extended temperature range and AG1204-2BB10-4AA3 exposure to media IE FC RJ45 Plug cable outlet; 1 unit Extended temperature range and AG1901-1BB10-7AA0 exposure to media Further accessories See SIMATIC CP 443-1, page /102 /112 Siemens ST

113 SIPLUS S7-400 communication SIPLUS S7-400 CP Advanced Connection of SIMATIC S7-400 to Industrial Ethernet - Multi-protocol operation for ISO, TCP/IP, UDP and PROFINET IO protocols - Adjustable keep-alive function Two separate interfaces (integrated network separation): - Gigabit interface with one RJ45 port with 10/100/1 000 Mbit/ s, full/half-duplex with auto-sensing capability - PROFINET interface with four RJ45 ports with 10/100 Mbit/s, full/half duplex with autosensing and autocrossover functionality via integrated 4-port switch Communication services via both interfaces - Open communication (ISO, TCP/IP and UDP), multicast with UDP, including routing between both interfaces - PG/OP communication: Cross-network by means of S7 routing - S7 communication (client, server, multiplexing) including routing between both interfaces - IT communication: HTTP communication supports access to process data via own Web pages; client function, sending of s with authentication directly from user program; FTP communication supports program-controlled FTP client communication; access to data blocks through FTP server Communication services via PROFINET interface - PROFINET IO controller with real-time properties (RT and IRT) - PROFINET CBA - IP address assignment via DHCP, simple PC tool or via the user program (e.g. HMI) - Support of the prioritized startup of PROFINET IO devices - Configuration with STEP 7 Media redundancy (MRP); the CP supports the media redundancy procedure MRP within an Ethernet network with ring topology. Access protection by means of configurable IP access list Module replacement without programming device; all information is stored on the C-PLUG (also file system for IT functions) Extensive diagnostic functions for all modules in the rack Integration into network management systems through the support of SNMP V1 MIB-II Operation in the SIMATIC H system for redundant S7-communication Operation in fail-safe applications (PROFIsafe) in combination with SIMATIC S7-400 CPU 41F Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. SIPLUS CP Advanced Article No. AG1443-1GX30-4XE0 based on GK7443-1GX30-0XE0 Ambient temperature range C Conformal coating Coating of the printed circuit boards and the electronic components Technical data The technical data of the standard product applies, except for the ambient conditions Ambient conditions Relative humidity 100 %, condensation/frost permissible. No commissioning if condensation present. Biologically active substances, compliance with EN Chemically active substances, compliance with EN Mechanically active substances, compliance with EN Air pressure (depending on the highest positive temperature range specified) For technical documentation on SIPLUS, see: Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! Class 3C4 incl. salt spray in accordance with EN (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation! Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation! hpa ( m) see ambient temperature range hpa ( m) derating 10 K hpa ( m) derating 20 K Siemens ST /113

114 SIPLUS S7-400 communication SIPLUS S7-400 CP Advanced Ordering data Article No. Article No. SIPLUS S7-400 CP Advanced communications processor For the connection of SIMATIC S7-400 to Industrial Ethernet; PROFINET IO Controller with RT and IRT, MRP, PROFINET CBA, TCP/IP, ISO and UDP; S7 communication, open communication (SEND/RECEIVE) with FETCH/ WRITE, with and without RFC 100, diagnostic expansions, multicast, clock synchronization via SIMATIC procedure or NTP, access protection via IP access list, FTP client/server, HTTP server, HTML diagnostics, SNMP, DHCP, , data storage on C-PLUG; PROFINET interface: 4 x RJ-45 (10/100 Mbit/s) over switch; Gigabit interface: 1 x RJ45 (10/100/1000 Mbit/s) Exposure to media AG1443-1GX30-4XE0 Accessories SIPLUS SCALANCE X204-2 Industrial Ethernet Switch Industrial Ethernet Switches with integral SNMP access, Web diagnostics, copper cable diagnostics and PROFINET diagnostics for configuring line, star and ring topologies; four 10/100 Mbit/s RJ45 ports and two FO ports Extended temperature range and exposure to media SIPLUS SCALANCE X308-2 Industrial Ethernet Switch 2 x 1000 Mbit/s multimode fiber-optic ports (SC sockets), 1 x 10/100/1000 Mbit/s RJ45 port, 7 x 10/100 Mbit/s RJ45 ports; for glass fiber-optic cable (multimode) up to max. 750 m Exposure to media SIPLUS NET RJ45 Plug 180 AG1204-2BB10-4AA3 AG1308-2FL00-4AA3 180 cable outlet; 1 unit Extended temperature range and exposure to media AG1901-1BB10-7AA0 SIPLUS NET RJ45 Plug cable outlet; 1 unit Extended temperature range and exposure to media AG1901-1BB20-7AA0 Further accessories See SIMATIC CP Advanced, page /10 /114 Siemens ST

115 Connection methods Front connectors Ordering data Article No. Front connectors 48-pin for signal modules, function modules; 1 unit With screw contacts With spring-loaded terminals With crimp contacts ES7492-1AL00-0AA0 ES7492-1BL00-0AA0 ES7492-1CL00-0AA0 48-pin for signal modules, function modules; 84 units per pack With screw contacts With crimp contacts ES7492-1AL00-1AB0 ES7492-1CL00-1AB0 for ES KF00-0AB0; spare part, included in scope of delivery; 1 piece ES7431-7KF00-AA0 Crimp contacts XX units Crimping tool XX3071 for crimping the contacts For simple and user-friendly connection of sensors and actuators For retaining the wiring when replacing modules With coding to avoid mistakes when replacing modules Front cover for front connector units Connection terminal for modules units SIMATIC Manual Collection ES7492-2XL00-0AA0 ES7490-1BA00-0AA0 ES7998-8XC01-8YE0 Electronic manuals on DVD, multilingual: LOGO!, SIMADYN, SIMATIC bus components, SIMATIC C7, SIMATIC distributed I/O, SIMATIC HMI, SIMATIC Sensors, SIMATIC NET, SIMATIC PC Based Automation, SIMATIC PCS 7, SIMATIC PG/PC, SIMATIC S7, SIMATIC Software, SIMATIC TDC SIMATIC Manual Collection update service for 1 year ES7998-8XC01-8YE2 Current "Manual Collection" DVD and the three subsequent updates Siemens ST /115

116 Connection methods System cabling for SIMATIC S7-400 Wiring of SIMATIC S7 I/O modules with the sensors/actuators is a significant factor with respect to time/cost overhead, configuring, control cabinet installation, procurement and ease of service. With SIMATIC TOP connect system cabling, it is simple and quick to establish a reliable connection for your SIMATIC S7-300/ 400. With the TIA Selection Tool, a mouse click is all that is required to configure the connection from the SIMATIC S7 module to the I/O. The program automatically checks for plausibility and generates a parts list for the selected connection components that can then be ordered in the Industry Mall. Further information can be found on the Internet at Flexible connection Flexible connection enables fast, direct connection of the SIMATIC S7-300/400 input/output modules to the individual elements in the control cabinet. Attached single cores reduce the wiring outlay. Wire cross-sections of 0.5 mm 2 allow higher currents, too. /11 Siemens ST

117 Connection methods S7-400 front connector with single cores Technical specifications Front connector with single cores Rated operating voltage 24 V DC Max. permissible continuous current 1.0 A with simultaneous load on all cores Permissible ambient temperature 0 to +0 C Core type H05V-K or with UL style 1007/159 CSA TR4 Number of cores 4 Core cross-section 0.5 mm 2,Cu Bundle diameter in mm approx. 17 Core color Blue, RAL 5010 Designation of cores Numbered 3 to 48 (adapter contact = core number) Assembly Screw-type or crimp contacts Can be used for modules of the SIMATIC S The front connectors with single wires replace the standard SIMATIC connectors: - ES7492-1AL00-0AA0 - ES7492-1BL00-0AA0 - ES7492-1CL00-0AA0 Ordering data Article No. Front connector with single cores for 32-channel module SIMATIC S7-400, 4 x 0.5 mm 2 Core type H05V-K Screw connection Packaging unit: 1 unit Length: 2.5 m ES7922-4BC50-0AD0 3.2 m ES7922-4BD20-0AD0 5 m ES7922-4BF00-0AD0 Custom lengths On request Packaging unit: 5 units Length: 2.5 m ES7922-4BC50-5AD0 3.2 m ES7922-4BD20-5AD0 5 m ES7922-4BF00-5AD0 Crimp connection Packaging unit: 1 unit Length: 2.5 m ES7922-4BC50-0AE0 3.2 m ES7922-4BD20-0AE0 5 m ES7922-4BF00-0AE0 Custom lengths On request Packaging unit: 5 units Length: 2.5 m ES7922-4BC50-5AE0 3.2 m ES7922-4BD20-5AE0 5 m ES7922-4BF00-5AE0 Core type UL/CSA-certified Screw-type version Packaging unit: 1 unit 3.2 m ES7922-4BD20-0UD0 5 m ES7922-4BF00-0UD0 Custom lengths On request Siemens ST /117

118 Racks Racks The basic mechanical framework of the SIMATIC S7-400/S7-400H For accommodating the modules, supplying them with operating voltage and connecting them via the backplane bus Several versions for configuring central controllers and expansion racks UR1 (Universal Rack) For setting up central controllers and expansion units For holding up to 18 modules Also suitable for S7-400H Also available as aluminum rack UR2 (Universal Rack) For setting up central controllers and expansion units For holding up to 9 modules Also suitable for S7-400H Also available as aluminum rack CR2 (Central Rack) For setting up central controllers For holding up to 18 modules Segmented rack: For operating two mutually independent S7-400 CPUs without S7-400 Multicomputing, but with communication between the CPUs over the backplane bus (C bus). Both CPUs can address their own local I/O modules (segmented P bus). CR3 (Central Rack) For configuring central racks Optimized for distributed automation solutions due to holding up to 4 modules UR2-H For configuring a complete S7-400H system in one subrack Also suitable for S7-400: Operation of 2 separate CPUs with their own I/O (separate P and C buses) Can also be used as an expansion unit For holding up to 18 modules Also available as aluminum rack ER1 (Extension Rack) For setting up expansion units economically For holding up to 18 modules with restricted functionality Also suitable for S7-400H Also available as aluminum rack ER2 (Extension Rack) For setting up expansion units economically For holding up to 9 modules with restricted functionality Also suitable for S7-400H Also available as aluminum rack Technical specifications ES7400-1TA01-0AA0 S7-400, UR1 RACK, 18 SLOTS ES7400-1TA11-0AA0 S7-400, UR1 RACK ALU, 18 SLOTS ES7400-1JA01-0AA0 S7-400, UR2 RACK, 9 SLOTS ES7400-1JA11-0AA0 S7-400 RACK ALU UR2, 9 SLOTS ES7401-2TA01-0AA0 SIMATIC S7-400, CR2 RACK, 18 SLOTS ES7401-1DA01-0AA0 S7-400 CR3 RACK, 4 SLOTS Product type designation Hardware configuration Rack Communication bus P bus Slots Number of single-width slots, max ; 2 segments 4 with 8 or 10 slots Dimensions Width mm mm mm mm mm 130 mm Height 290 mm 290 mm 290 mm 290 mm 290 mm 290 mm Depth 27.5 mm 27.5 mm 27.5 mm 27.5 mm 27.5 mm 27.5 mm Weights Weight, approx. 4200g g g 1500g g 750 g /118 Siemens ST

119 Racks Racks Technical specifications (continued) ES7400-2JA00-0AA0 SIMATIC S7-400H, UR2-H RACK, 18 SLOTS ES7400-2JA10-0AA0 S7-400 MOD.TR ALU UR2-H, 18 SLOTS ES7403-1TA01-0AA0 SIMATIC S7-400, ER1 EXP. RACK, ES7403-1TA11-0AA0 S7-400, ER1 EXPANSION RACK ALU, 18 SLOTS ES7403-1JA01-0AA0 SIMATIC S7-400, ER2 EXP. RACK, Ordering data Article No. Article No. ES7403-1JA11-0AA0 S7-400, ER2 EXPANSION RACK ALU, 9 SLOTS Product type designation Hardware configuration Rack Communication bus P bus Slots Number of single-width slots, max Dimensions Width mm mm mm mm mm mm Height 290 mm 290 mm 290 mm 290 mm 290 mm 290 mm Depth 27.5 mm 27.5 mm 27.5 mm 27.5 mm 27.5 mm 27.5 mm Weights Weight, approx. 4200g g g 2500g g 1250g UR1 rack ES7400-1TA01-0AA0 UR2-H rack ES7400-2JA00-0AA0 for central controllers and expansion units, 18 slots UR1 aluminum rack for central controllers and expansion units, 18 slots UR2 rack for central controllers and expansion units, 9 slots UR2 aluminum rack for central controllers and expansion units, 9 slots CR2 rack for segmented central controllers, 18 slots, 2 local segments CR3 rack for central controllers and expansion units, 4 slots; optimized for distributed automation solutions ES7400-1TA11-0AA0 ES7400-1JA01-0AA0 ES7400-1JA11-0AA0 ES7401-2TA01-0AA0 ES7401-1DA01-0AA0 for split CCs, 18 slots UR2-H aluminum rack for split CCs, 18 slots ER1 rack for expansion units, P bus only, 18 slots ER1 aluminum rack for expansion units, P bus only, 18 slots ER2 rack for expansion units, P bus only, 9 slots ER2 aluminum rack for expansion units, P bus only, 9 slots Slot cover 10 units (spare part) ES7400-2JA10-0AA0 ES7403-1TA01-0AA0 ES7403-1TA11-0AA0 ES7403-1JA01-0AA0 ES7403-1JA11-0AA0 ES7490-1AA00-0AA0 Siemens ST /119

120 SIPLUS module racks SIPLUS S7-400 racks The mechanical basic structure of SIPLUS S7-400/S7-400H For accommodating the modules, operating voltage supply, and connection of the modules via a backplane bus Several versions for setting up central controllers and expansion units SIPLUS rack material: Aluminum Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added. For further technical documentation on SIPLUS, see: Technical specifications AG1400-1TA11-7AA0 AG1400-1JA11-7AA0 AG1400-2JA10-7AA0 Based on ES7400-1TA11-0AA0 ES7400-1JA11-0AA0 ES7400-2JA10-0AA0 SIPLUS S7-400 RACK UR1 18SLOT ALU SIPLUS S-400 RACK UR2 9SLOT ALU Ambient conditions Ambient temperature in operation Min. -25 C; = Tmin -25 C; = Tmin -25 C max. 70 C; = Tmax 70 C; = Tmax 70 C Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Relative humidity Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) SIPLUS S7-400 BGT UR2-H 2X9SLOT ALU - With condensation, max. 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75%) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75%) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 (RH < 75 %) incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. Article No. SIPLUS S7-400 rack UR1 aluminum rack for central controllers and expansion units, 18 slots Extended temperature range and exposure to media UR2 aluminum rack for central controllers and expansion units, 9 slots Extended temperature range and exposure to media UR2-H aluminum rack for central controllers and expansion units, 9 slots Extended temperature range and exposure to media Accessories AG1400-1TA11-7AA0 AG1400-2JA10-7AA0 See SIMATIC rack S7-400, page /119 AG1400-1JA11-7AA0 /120 Siemens ST

121 Interface modules IM 40-0 Send interface module for central expansion to 5 m Transmission of P and K bus Can be plugged into the central controller Up to 8 expansion racks can be connected (up to 4 per interface) Can be used exclusively with IM 41-0 Technical specifications Product type designation Input current from backplane bus 5 V DC, max. Power losses Power loss, max. Hardware configuration Cable length between first and last interface module, max. Dimensions Width Height Depth Weights Weight, approx. Ordering data IM 40-0 interface module ES740-0AA01-0AB0 TRANSMITT. INTERF.MOD. IM40-0, W. K BUS 140 ma 700 mw 5m 25 mm 290 mm 217 mm 00 g Article No. ES740-0AA01-0AB0 Send interface module for central connection up to 5 m; with C bus transmission 48-1 connecting cable between IM 40-0 and IM 41-0; IM 40-3 and IM m ES748-1AH50-0AA0 1.5 m ES748-1BB50-0AA0 5 m ES748-1BF00-0AA0 Siemens ST /121

122 Interface modules IM 41-0 Receive interface for centralized expansion up to 5 m Transmission of P and K bus Can be plugged into expansion rack To be used exclusively with IM 40-0 Technical specifications Product type designation Input current from backplane bus 5 V DC, max. Power losses Power loss, max. Hardware configuration Cable length between first and last interface module, max. Dimensions Width Height Depth Weights Weight, approx. Ordering data IM 41-0 interface module ES741-0AA01-0AA0 RECEIVER INTERF. MOD. IM41-0, W. K-BUS 290 ma 1450mW 5m 25 mm 290 mm 217 mm 10 g Article No. ES741-0AA01-0AA0 Receive interface module for central connection up to 5 m; with C bus transmission 48-1 connecting cable between IM 40-0 and IM 41-0; IM 40-3 and IM m ES748-1AH50-0AA0 1.5 m ES748-1BB50-0AA0 5 m ES748-1BF00-0AA0 Terminating connector ES741-0AA00-7AA0 for IM 41-0 /122 Siemens ST

123 Interface modules IM 40-1 Send interface module for central expansion to 1.5 m Transmission of P bus With voltage supply for expansion units Can be plugged into the central controller Up to 2 expansion racks can be connected (up to 1 per interface) Can be used exclusively with IM 41-1 Technical specifications Product type designation Input current from backplane bus 5 V DC, max. Power losses Power loss, max. Hardware configuration Cable length between first and last interface module, max. Dimensions Width Height Depth Weights Weight, approx. Ordering data IM 40-1 interface module ES740-1BA01-0AB0 TRANSMITT. INTERF.MOD. IM40-1,W/O K BUS 85 ma 425 mw 1.5 m 25 mm 290 mm 217 mm 00 g Article No. ES740-1BA01-0AB0 Send interface module for central connection up to 1.5 m; with 5 V power supply, without C bus transmission 48-3 connecting cable between IM 40-1 and IM 41-1; 0.75 m ES748-3AH50-0AA0 1.5 m ES748-3BB50-0AA0 Siemens ST /123

124 Interface modules IM 41-1 Technical specifications Product type designation Input current from backplane bus 5 V DC, max. Power losses Power loss, max. Hardware configuration Cable length between first and last interface module, max. Dimensions Width Height Depth Weights Weight, approx. ES741-1BA01-0AA0 RECEIVER INTERF. MOD. IM41-1, W/O K-BUS 120 ma 00 mw 1.5 m 25 mm 290 mm 217 mm 10 g Receive interface connection for centralized extension up to 1.5 m Transmission of P bus With voltage supply for expansion units Can be plugged into expansion unit Can only be used with IM 40-1 Ordering data IM 41-1 interface module Article No. ES741-1BA01-0AA0 Receive IM for central coupling up to max. 1.5 m; without C bus transfer 48-3 connecting cable For connecting IM 40-1 and IM m ES748-3AH50-0AA0 1.5 m ES748-3BB50-0AA0 /124 Siemens ST

125 Interface modules IM 40-3 Send interface module for distributed expansion to 102 m Transmission of K and P bus Can be plugged into the central controller Up to 8 expansion racks can be connected (up to 4 per interface) Can be used exclusively with IM 41-3 Technical specifications Product type designation Input current from backplane bus 5 V DC, max. Power losses Power loss, max. Hardware configuration Cable length between first and last interface module, max. Dimensions Width Height Depth Weights Weight, approx. Ordering data IM 40-3 interface module ES740-3AA01-0AB0 TRANSMITT. INTERF.MOD- IM40-3,UP TO 102M 1550mA 7750mW m 25 mm 290 mm 217 mm 30 g Article No. ES740-3AA01-0AB0 Send interface module for distributed connection up to 102 m; with C bus transmission 48-1 connecting cable between IM 40-3 and IM m ES748-1AH50-0AA0 1.5 m ES748-1BB50-0AA0 5 m ES748-1BF00-0AA0 10 m ES748-1CB00-0AA0 25 m ES748-1CC50-0AA0 50 m ES748-1CF00-0AA0 100 m ES748-1DB00-0AA0 Siemens ST /125

126 Interface modules IM 41-3 Receive interface for distributed expansion up to 102 m Transmission of data from the P-bus and C-bus Can be plugged into expansion rack To be used exclusively with IM 40-3 Technical specifications Product type designation Input current from backplane bus 5 V DC, max. Power losses Power loss, max. Hardware configuration Cable length between first and last interface module, max. Dimensions Width Height Depth Weights Weight, approx. Ordering data IM 41-3 interface module ES741-3AA01-0AA0 RECEIVER INTERF. MOD. IM41-3,UP TO 102M 20 ma 3100mW m 25 mm 290 mm 217 mm 20 g Article No. ES741-3AA01-0AA0 Receive interface module for distributed connection up to 102 m; with C bus transmission 48-1 connecting cable between IM 40-3 and IM m ES748-1AH50-0AA0 1.5 m ES748-1BB50-0AA0 5 m ES748-1BF00-0AA0 10 m ES748-1CB00-0AA0 25 m ES748-1CC50-0AA0 50 m ES748-1CF00-0AA0 100 m ES748-1DB00-0AA0 Terminating connector ES741-3AA00-7AA0 for IM 41-3 /12 Siemens ST

127 Interface modules IM 43-2 Technical specifications Product type designation Input current from backplane bus 5 V DC, max. Power losses Power loss, max. Hardware configuration Cable length between first and last interface module, max. Dimensions Width Height Depth Weights Weight, approx. ES743-2AA00-0AA0 TRANSMITT. INTERF.MOD- IM43-2, COUPL. M. S5 1320mA 00mW 00 m 25 mm 290 mm 217 mm 30 g Send interface for distributed expansion with SIMATIC S5 expansion racks up to 00 m Can be plugged into the central controller Up to 8 SIMATIC S5 expansion racks can be connected (up to 4 per interface) Can be used exclusively with IM 314 Ordering data IM 43-2 interface module Receiving IM for distributed coupling of SIMATIC S5-EUs up to max. 00 m Article No. ES743-2AA00-0AA0 Siemens ST /127

128 SIPLUS S7-400 interface modules SIPLUS S7-400 IM 40-0 Send interface module for centralized expansion up to 5 m Transfer from P and K Bus Plug into central controller You may connect up to 8 expansion units (max. 4 per port) Usable exclusively with IM 41-0 Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. For technical documentation on SIPLUS, see: Technical specifications Based on Ambient conditions Ambient temperature in operation Min. max. Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude AG140-0AA01-2AB0 ES740-0AA01-0AB0 SIPLUS S7-400 IM40-0 TX -25 C; = Tmin 0 C; = Tmax Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) Relative humidity - With condensation 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. SIPLUS S7-400 interface module IM 40-0 Send IM for central coupling up to 5 m; with K-bus transfer Extended temperature range and AG140-0AA01-2AB0 exposure to media Accessories See SIMATIC IM 40-0, page /122 /128 Siemens ST

129 SIPLUS S7-400 interface modules SIPLUS S7-400 IM 41-0 Receive interface connection for central extension up to 5 m Transfer from P and K Bus Pluggable in extension device Usable exclusively with IM 40-0 Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. For technical documentation on SIPLUS, see: Technical specifications Based on Ambient conditions Ambient temperature in operation Min. max. Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude AG141-0AA01-2AA0 ES741-0AA01-0AA0 SIPLUS S7-400 IM41-0 RX -25 C; = Tmin 0 C; = Tmax Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) Relative humidity - With condensation 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! Ordering data Article No. SIPLUS S7-400 interface module IM 41-0 Receiver IM for central coupling up to 5 m; with C-bus transfer Extended temperature range and AG141-0AA01-2AA0 exposure to media Accessories See SIMATIC IM 41-0, page /123 Siemens ST /129

130 Power supplies PS 405/407 power supplies Power supplies for SIMATIC S7-400 For conversion of AC or DC line voltages to the 5 V DC and 24 V DC operating voltages required 4 A, 10 A and 20 A output currents In addition: - SIPLUS power supply AG1405-0KA02-2AA0 for temperature range of -25 to +0 C and use under medium load (e.g. chlorine/sulfur atmosphere). Technical specifications similar to ES7405-0KA02-0AA0 - SIPLUS power supply AG1407-0KA02-4AA0 for use under medium load (e.g. chlorine/sulfur atmosphere). Technical specifications similar to ES7407-0KA02-0AA0 - SIPLUS power supply AG1407-0KR02-4AA0 for use under medium load (e.g. chlorine/sulfur atmosphere). Technical specifications as for ES7407-0KR02-0AA0 Technical specifications ES7405-0DA02-0AA0 ES7405-0KA02-0AA0 ES7405-0KR02-0AA0 ES7405-0RA02-0AA0 PS405 POWER SUPPLY, DC24/48/0V, DC5V/4A POWER SUPP. PS405, DC24/48/0V, DC5V/10A POWER SUPP. PS405, DC24/48/0V, DC5V/10A, RED PS405 POWER SUPPLY, DC24/48/0V, DC5V/20A Product type designation Supply voltage Rated value (DC) 24 V DC 48 V DC 0 V DC permissible range, lower limit (DC) 19.2 V; Dynamic 18.5 V 19.2 V; Dynamic 18.5 V 19.2 V; Dynamic 18.5 V 19.2 V; Dynamic 18.5 V permissible range, upper limit (DC) 72 V; dynamic 75.5 V 72 V; dynamic 75.5 V 72 V; dynamic 75.5 V 72 V; dynamic 75.5 V Mains buffering Mains/voltage failure stored energy 20 ms 20 ms 20 ms 20 ms time Mains buffering according to NAMUR recommendation Input current Rated value at 24 V DC 2A 4A 4A 7A Rated value at 48 V DC 1000mA 2A 2A 3.2 A Rated value at 0 V DC 800 ma 1. A 1. A 2.5 A Inrush current, max. 18 A; Full width at half maximum 20 ms 18 A; Full width at half maximum 20 ms 18 A; Full width at half maximum 20 ms 5 A; Full width at half maximum 1.5 ms Output voltage Type of output voltage DC DC DC DC Rated value (DC) 5 V DC 24 V DC Output current for backplane bus (5 V DC), max. 4 A; no base load required 10 A; no base load required 10 A; no base load required 20 A; no base load required for backplane bus (24 V DC), max. 0.5 A; idling-proof 1 A; idling-proof 1 A; idling-proof 1 A; idling-proof short-circuit protection Power Power consumption, typ. 48 W 95 W 95 W 18 W Power losses Power loss, typ. 1 W 20 W 20 W 44 W Battery Backup battery Backup battery - Backup battery (optional) ; 1 x lithium AA; 3. V/2.3 Ah ; 2 x lithium AA; 3. V/2.3 Ah ; 2 x lithium AA; 3. V/2.3 Ah ; 2 x lithium AA; 3. V/2.3 Ah /130 Siemens ST

131 Power supplies PS 405/407 power supplies Technical specifications (continued) ES7405-0DA02-0AA0 ES7405-0KA02-0AA0 ES7405-0KR02-0AA0 ES7405-0RA02-0AA0 PS405 POWER SUPPLY, DC24/48/0V, DC5V/4A POWER SUPP. PS405, DC24/48/0V, DC5V/10A POWER SUPP. PS405, DC24/48/0V, DC5V/10A, RED PS405 POWER SUPPLY, DC24/48/0V, DC5V/20A Hardware configuration Slots Required slots Galvanic isolation primary/secondary Degree and class of protection Protection class 1; with protective conductor 1; with protective conductor 1; with protective conductor 1; with protective conductor Standards, approvals, certificates FM approval ; Ta: 0 C to 0 C T4 ; Ta: 0 C to 0 C T4 ; Ta: 0 C to 0 C T4 ; Ta: 0 C to 0 C T4 Connection method Connecting cables/cross sections 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm Dimensions Width 25 mm 50 mm 50 mm 50 mm Height 290 mm 290 mm 290 mm 290 mm Depth 217 mm 217 mm 217 mm 217 mm Weights Weight, approx. 70 g 1200g 1200g 1300g ES7407-0DA02-0AA0 ES7407-0KA02-0AA0 ES7407-0KR02-0AA0 ES7407-0RA02-0AA0 POWER SUPPLY PS407, 120/230V UC, 5V DC/4A PS407 POWER SUPPLY, 120/230V UC, 5V DC/10A POWER SUPP. PS407, UC120/230V, DC5V/10A, RED. PS407 POWER SUPPLY, 120/230V UC, 5V DC/20A Product type designation Supply voltage Rated value (DC) 120 V DC 230 V DC permissible range, lower limit (DC) 88 V 88 V 88 V 88 V permissible range, upper limit (DC) 300 V 300 V 300 V 300 V Rated value (AC) 120 V AC 230 V AC permissible range, lower limit (AC) 85 V 85 V 85 V 85 V permissible range, upper limit (AC) 24 V 24 V 24 V 24 V Line frequency Rated value 50 Hz Rated value 0 Hz permissible frequency range, 47 Hz 47 Hz 47 Hz 47 Hz lower limit permissible frequency range, 3 Hz 3 Hz 3 Hz 3 Hz upper limit Mains buffering Mains/voltage failure stored 20 ms 20 ms 20 ms 20 ms energy time Mains buffering according to NAMUR recommendation Input current Rated value at 110 V DC 350 ma; at 120 V DC 1 A; at 120 V DC 1 A; at 120 V DC 1.4 A; at 120 V DC Rated value at 230 V DC 190 ma 0.5 A 0.5 A 0.7 A Rated value at 120 V AC 0.42 A 0.9 A 0.9 A 1.4 A Rated value at 230 V AC 0.22 A 0.5 A 0.5 A 0.7 A Inrush current, max A; Full width at half maximum 5 ms 3 A; Full width at half maximum 1 ms 3 A; Full width at half maximum 1 ms 88 A; Full width at half maximum 1.1 ms Siemens ST /131

132 Power supplies PS 405/407 power supplies Technical specifications (continued) ES7407-0DA02-0AA0 ES7407-0KA02-0AA0 ES7407-0KR02-0AA0 ES7407-0RA02-0AA0 POWER SUPPLY PS407, 120/230V UC, 5V DC/4A Output voltage Type of output voltage DC DC DC DC Rated value (DC) 5 V DC 24 V DC Output current for backplane bus (5 V DC), max. 4 A; no base load required 10 A; no base load required 10 A; no base load required 20 A; no base load required for backplane bus (24 V DC), max. 0.5 A; idling-proof 1 A; idling-proof 1 A; idling-proof 1 A; idling-proof short-circuit protection Power Power consumption, typ. 52 W 95 W 95 W 158 W Power losses Power loss, typ. 20 W 20 W 20 W 35 W Battery Backup battery Backup battery - Backup battery (optional) ; 1 x lithium AA; 3. V/2.3 Ah Hardware configuration Slots PS407 POWER SUPPLY, 120/230V UC, 5V DC/10A ; 2 x lithium AA; 3. V/2.3 Ah POWER SUPP. PS407, UC120/230V, DC5V/10A, RED. ; 2 x lithium AA; 3. V/2.3 Ah PS407 POWER SUPPLY, 120/230V UC, 5V DC/20A ; 2 x lithium AA; 3. V/2.3 Ah Required slots Galvanic isolation primary/secondary EMC Compliance with line harmonic distortion limits Observance of line harmonic distortion acc. to IEC , IEC Degree and class of protection Protection class 1; with protective conductor 1; with protective conductor 1; with protective conductor 1; with protective conductor Standards, approvals, certificates FM approval ; Ta: 0 C to 0 C T4 ; Ta: 0 C to 0 C T4 ; Ta: 0 C to 0 C T4 ; Ta: 0 C to 0 C T4 Connection method Connecting cables/cross sections 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm Dimensions Width 25 mm 50 mm 50 mm 50 mm Height 290 mm 290 mm 290 mm 290 mm Depth 217 mm 217 mm 217 mm 217 mm Weights Weight, approx. 70 g 1200g 1200g 1300g /132 Siemens ST

133 Power supplies Ordering data Article No. Article No. PS 405/407 power supplies PS 405 power supply modules 24 V DC; 5 V DC, 24 V DC 4 A ES7405-0DA02-0AA0 10 A, wide range ES7405-0KA02-0AA0 10 A, redundant, wide range ES7405-0KR02-0AA0 20 A, wide range ES7405-0RA02-0AA0 Power plug for PS 405 ES7490-0AA00-0AA0 Spare part Backup battery ES7971-0BA00 Type AA; 3. V/2.3 Ah PS 407 power supply modules 120/230 V AC; 5 V DC, 24 V DC 4 A ES7407-0DA02-0AA0 10 A ES7407-0KA02-0AA0 10 A, redundant ES7407-0KR02-0AA0 20 A ES7407-0RA02-0AA0 Power plug for PS 407 ES7490-0AB00-0AA0 Spare part Backup battery ES7971-0BA00 Type AA; 3. V / 2.3 Ah SITOP power supplies Refer to Catalog KT 10.1 For the 24 V supply of motors or sensors Add-on modules and DC-UPS Refer to Catalog KT 10.1 To increase system availability Siemens ST /133

134 SIPLUS power supplies SIPLUS S7-400 power supplies Power supplies for SIPLUS S7-400 For conversion of AC or DC line voltages to the 5 V DC and 24 V DC operating voltages required 4 A, 10 A and 20 A output currents Note: SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added. For technical documentation on SIPLUS, see: Technical specifications AG1405-0KA02-7AA0 AG1405-0KR02-7AA0 AG1407-0KA02-7AA0 AG1407-0KR02-7AA0 Based on ES7405-0KA02-0AA0 ES7405-0KR02-0AA0 ES7407-0KA02-0AA0 ES7407-0KR02-0AA0 SIPLUS PS A SIPLUS S7-400 PS405 DC 10A RED SIPLUS S7-400 PS407 UC 10A SIPLUS S7-400 PS407 UC 10A RED Ambient conditions Ambient temperature in operation Min. -25 C; = Tmin -25 C; = Tmin; using the external battery box SIPLUS AG1971-0AA00-7AA0 for buffer mode max. 70 C; = Tmax 70 C; = Tmax; using the external battery box SIPLUS AG1971-0AA00-7AA0 for buffer mode Extended ambient conditions Relative to ambient temperatureatmospheric pressure-installation altitude Relative humidity Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) - With condensation, max. 100 %; RH incl. condensation / frost permitted (no commissioning under condensation conditions) Resistance - against biologically active substances / conformity with EN against chemically active substances / conformity with EN against mechanically active substances / conformity with EN Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) 100 %; RH incl. condensation/frost (no commissioning if there is condensation). In buffer mode, use battery box SIPLUS AG1971-0AA00-7AA0 for high humidity -25 C; using the external battery box SIPLUS AG1971-0AA00-7AA0 for buffer mode 70 C; using the external battery box SIPLUS AG1971-0AA00-7AA0 for buffer mode Tmin... Tmax at 1080 hpa hpa (-1000 m m) // Tmin... (Tmax - 10K) at 795 hpa hpa (+2000 m m) // Tmin... (Tmax - 20K) at 58 hpa hpa (+3500 m m) 100 %; RH incl. condensation/frost (no commissioning if there is condensation). In buffer mode, use battery box SIPLUS AG1971-0AA00-7AA0 for high humidity -25 C; using the external battery box SIPLUS AG1971-0AA00-7AA0 for buffer mode 70 C; using the external battery box SIPLUS AG1971-0AA00-7AA0 for buffer mode Tmin... Tmax at 1080 hpa hpa (-1000 m m) 100 %; RH incl. condensation/frost (no commissioning if there is condensation). In buffer mode, use battery box SIPLUS AG1971-0AA00-7AA0 for high humidity ; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! ; Class 3C4 incl. salt spray according to EN (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! ; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! /134 Siemens ST

135 SIPLUS power supplies Ordering data Article No. Article No. SIPLUS S7-400 power supplies SIPLUS S7-400 PS 405 power supply modules In: 24/48/0 V DC - wide range ( V DC); Out: 24 V DC/1 A, 5 V DC/10 A Extended temperature range and exposure to media In: 24/48/0 V DC - wide range ( V DC); Out: 24 V DC/1 A, 5 V DC/10 A; for redundant use Extended temperature range and exposure to media AG1405-0KA02-7AA0 AG1405-0KR02-7AA0 SIPLUS S7-400 PS 407 power supply modules In: 110/230 V DC; 120/230 V AC; Out: 24 V DC/1 A, 5 V DC/10 A Extended temperature range and AG1407-0KA02-7AA0 exposure to media In: 110/230 V DC; 120/230 V AC; Out: 24 V DC/1 A, 5 V DC/10 A; for redundant use Extended temperature range and AG1407-0KR02-7AA0 exposure to media Accessories See SIMATIC PS 405/407 power supplies, page /133 Siemens ST /135

136 Accessories Labeling sheets Ordering data Labeling sheets Labeling sheets Film sheets for application-specific labeling of DIN A4, for printing using laser SIMATIC S7-400 I/O modules with commercial laser printers printer; 10 pieces Single-color films, tear-resistant, dirt-resistant Petrol Easy handling: Light beige - Pre-perforated labeling sheets in DIN A4 format to allow Yellow easy separation of the labeling strips - The separated strips can be inserted directly into the Red I/O modules Cover film for labeling strips Different colors for distinction between module types or 10 pieces (spare part) preferred areas of application: The labeling sheets are available in the colors teal, light beige, red and yellow. Yellow is reserved for failsafe systems. Label cover Film to cover and hold user-made labeling strips on normal paper Accessories, 10 pieces Spare parts Ordering data Cover film for labeling strips Cover foil for labeling strip Petrol-colored film for covering and fixing labeling strips 10 units (spare part) created by the user Range card for analog input On normal paper modules Spare part 1 card for 2 inputs; 2 units (spare part) Measuring range module for analog input modules Slot covers Pluggable module for selecting the input ranges in the case of for racks; 10 units (spare part) analog modules Power plug for PS module for 2 inputs Spare part Spare part Power plug for PS 407 Slot cover Spare part Cover plates for unused slots in module racks Spare part, 10 units Power supply connectors Plug for connecting the PS 405 and PS 407 power supply modules to the network Spare part Article No. ES7492-2AX00-0AA0 ES7492-2BX00-0AA0 ES7492-2CX00-0AA0 ES7492-2DX00-0AA0 ES7492-2XX00-0AA0 Article No. ES7492-2XX00-0AA0 ES7974-0AA00-0AA0 ES7490-1AA00-0AA0 ES7490-0AA00-0AA0 ES7490-0AB00-0AA0 /13 Siemens ST

137 CPUs for SIMATIC S7-400H and SIMATIC S7-400F/FH High-availability CPUs 4 high-availability CPUs (CPU 412-5H, CPU 414-5H, CPU 41-5H, CPU 417-5H) Graded performance spectrum for a wide range of different applications For further information, see pages /34 and /38. Siemens ST /137

138 Modules for SIMATIC S7-400F/FH ET 200M, Fail-safe I/O modules ET 200M Fail-safe I/O modules Modular I/O system with IP20 degree of protection, particularly suitable for user-specific and complex automation tasks. Consists of a PROFIBUS DP or PROFINET interface module IM 153, up to 8 or 12 I/O modules of the S7-300 automation system (structure with bus connection or with active bus modules), and a power supply if applicable Can be expanded with S7-300 automation system signal, communication and function modules Applicable Ex analog input or output modules with HART optimize the ET 200M for use in process engineering. Can be used in redundant systems (S7-400H, S7-400F/FH) Modules can be replaced during operation (hot swapping) with the bus modules active Transmission rates up to 12 Mbit/s Ex approval to Cat. 3 for Zone 2 acc. to ATEX100 a Failsafe digital in/outputs as well as analog inputs for safetyoriented signal processing in accordance with PROFIsafe Support of modules with expanded user data, e.g. HART modules with HART minor variables For further information, see chapter 9, page 9/28 ff. Failsafe input/output modules for use with the SIMATIC S7-400F/FH With integrated safety functions Can only be plugged into the ET 200M Achievable safety classes in safety operation: SIL 2, SIL 3 to IEC 1508, AK 4, AK to DIN V 19250, Category 3, 4 to EN Use in standard mode with high diagnostics requirements Also suitable for redundant operation For further information, see chapter 5, page 5/108. /138 Siemens ST

Siemens AG 2013. 6/56 Digital modules 6/56 SM 421 digital input module 6/59 SM 422 digital output module

Siemens AG 2013. 6/56 Digital modules 6/56 SM 421 digital input module 6/59 SM 422 digital output module Siemens AG 2013 SIMATIC S7-400 /2 Introduction /4 Central processing units /4 Standard CPUs /4 CPU 412 /8 CPU 414 /13 CPU 41 /18 CPU 417 /21 SIPLUS Standard CPUs /21 SIPLUS CPU 412 /22 SIPLUS CPU 414 /23

More information

CPU 319-3 PN/DP. Function

CPU 319-3 PN/DP. Function CPU 319-3 PN/DP Function Password protection; a password concept protects the user program from unauthorized access. Block encryption; the functions (FCs) and function blocks (FBs) can be stored in the

More information

CPUs - CPU 315-2 PN/DP

CPUs - CPU 315-2 PN/DP Overview The CPU with a medium program memory and quantity framework High processing performance in binary and floating-point arithmetic Used as a central controller on production lines with central and

More information

SIMATIC S7-300, CPU 315-2DP CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 128 KBYTE WORKING MEMORY 2

SIMATIC S7-300, CPU 315-2DP CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 128 KBYTE WORKING MEMORY 2 6ES7315-2AG10-0AB0 Page 1 Product data sheet 6ES7315-2AG10-0AB0 SIMATIC S7-300, CPU 315-2DP CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 128 KBYTE WORKING MEMORY 2. INTERFACE DP-MASTER/SLAVE

More information

SIMATIC S7-1500 advanced controller

SIMATIC S7-1500 advanced controller Siemens AG 2015 /2 Introduction /2 SIMATIC S7-1500/S7-1500F, SIPLUS S7-1500 /5 Central processing units /5 Standard CPUs /15 SIPLUS Standard CPUs /19 Fail-safe CPUs /28 /28 Digital modules /28 SM 521 digital

More information

6ES7 313-6BE01-0AB0 6ES7 313-5BE01-0AB0

6ES7 313-6BE01-0AB0 6ES7 313-5BE01-0AB0 4 SIMATIC S7-300 Central processing units CPU 312C to CPU 317F-2 DP CPU 317F-2 DP The failsafe CPU with a large program memory and quantity framework for demanding applications For configuration of a failsaf

More information

http://support.automation.siemens.com/ww/view/en/4067870&td=1

http://support.automation.siemens.com/ww/view/en/4067870&td=1 6ES7316-2AG00-0AB0 SIMATIC S7-300, CPU 316 Technical / CAx data nmlkji Technical Data nmlkj CAx data As of 2010-01-24 Power supply Input voltage Rated value (DC) permissible range, lower limit (DC) permissible

More information

SIMATIC S7-300. 5/30 SIPLUS digital modules 5/30 SIPLUS SM 322 digital output module. 5/31 Analog modules 5/31 SM 331 analog input module

SIMATIC S7-300. 5/30 SIPLUS digital modules 5/30 SIPLUS SM 322 digital output module. 5/31 Analog modules 5/31 SM 331 analog input module /2 Central processing units /2 Standard CPUs /2 CPU 312 /2 CPU 314 /2 CPU 31-2 DP /2 CPU 31-2 PN/DP /3 CPU 317-2 PN/DP /17 Fail-safe CPUs /17 CPU 31F-2 DP /17 CPU 31F-2 PN/DP /18 CPU 317F-2 PN/DP /30 SIPLUS

More information

6ES7313-5BF03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A

6ES7313-5BF03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A 6ES7313-5BF03-0AB0 Page 1 Product data sheet 6ES7313-5BF03-0AB0 SIMATIC S7-300, CPU 313C, COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO 1 PT100, 3 FAST COUNTERS (30 KHZ), INTEGRATED 24V DC POWER SUPPLY,

More information

6ES7314-6CG03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A

6ES7314-6CG03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A 6ES7314-6CG03-0AB0 Page 1 Product data sheet 6ES7314-6CG03-0AB0 SIMATIC S7-300, CPU 314C-2DP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED DP INTERFACE, INTEGRATED

More information

S7-1500/S7-1500F Technical Data

S7-1500/S7-1500F Technical Data Standard CPUs CPU 1511-1 PN CPU 1513-1 PN CPU 1515-2 PN Type Standard CPU Standard CPU Standard CPU Dimensions 35 x 147 x 129 mm 35 x 147 x 129 mm 70 x 147 x 129 mm Spare part availability after 10 years

More information

The CP 342-5 provides access to different communication services of the PROFIBUS bus system:

The CP 342-5 provides access to different communication services of the PROFIBUS bus system: SIPLUS CP 342-5 Function The CP 342-5 provides access to different communication services of the PROFIBUS bus system: PROFIBUS DP (according to IEC 61158/61784, master or slave) PG/OP communication S7

More information

S7-1500/S7-1500F Technical Data

S7-1500/S7-1500F Technical Data CPU 1511-1 PN CPU 1513-1 PN CPU 1515-2 PN Type Standard CPU Standard CPU Standard CPU Dimensions 35 x 125 x 130 mm 35 x 125 x 130 mm 70 x 147 x 129 mm Spare part availability after 10 years 10 years 10

More information

CP 342-5. Page 1342 Mar 2008 Siemens ITS

CP 342-5. Page 1342 Mar 2008 Siemens ITS CP 342-5 Function The CP 342-5 provides access to different communication services of the PROFIBUS bus system: PROFIBUS DP (according to IEC 61158/61784, master or slave) PG/OP communication S7 communication

More information

The CP 342-5 FO provides access to different communication services of the PROFIBUS bus system:

The CP 342-5 FO provides access to different communication services of the PROFIBUS bus system: CP 342-5 FO Function The CP 342-5 FO provides access to different communication services of the PROFIBUS bus system: PROFIBUS DP (according to IEC 61 158/61784, master or slave) PG/OP communication S7

More information

Data sheet SLIO CPU 015 (015-CEFPR00)

Data sheet SLIO CPU 015 (015-CEFPR00) Data sheet SLIO CPU 015 (015-CEFPR00) Technical data Order no. 015-CEFPR00 SLIO CPU 015 Module ID - General information Note - Features SPEED7 technology 256 kb work memory Memory extension (max. 512 kb)

More information

SIMATIC S7-1200 basic controller

SIMATIC S7-1200 basic controller Siemens AG 2015 /2 Introduction /4 Central processing units /4 Standard CPUs /4 CPU 1211C /8 CPU 1212C /12 CPU 1214C /16 CPU 1215C /20 CPU 1217C /2 SIPLUS standard CPUs /2 SIPLUS CPU 1211C /26 SIPLUS CPU

More information

SIMATIC S7-300. 4/2 Introduction. 4/4 Central processing units. 4/34 Digital modules. 4/44 Analog modules. 4/55 F digital /analog modules

SIMATIC S7-300. 4/2 Introduction. 4/4 Central processing units. 4/34 Digital modules. 4/44 Analog modules. 4/55 F digital /analog modules /2 Introduction / Central processing units /3 Digital modules / Analog modules /55 F digital /analog modules /61 Ex input/output modules /65 Function modules /65 FM 350-1 counter module /67 FM 350-2 counter

More information

LOGO! logic module. 2/2 Introduction 2/2 LOGO! logic module

LOGO! logic module. 2/2 Introduction 2/2 LOGO! logic module Siemens AG 013 / Introduction / /3 /3 basic variants /7 SIPLUS basic variants /9 pure variants /1 SIPLUS pure variants /14 expansion modules /19 SIPLUS expansion modules /3 LOGO! CM EIB/KNX communication

More information

SIMATIC S7-300 4/2 Introduction Function modules (continued) 4/4 Central processing units 4/38 SIPLUS central processing units 4/40 Digital modules

SIMATIC S7-300 4/2 Introduction Function modules (continued) 4/4 Central processing units 4/38 SIPLUS central processing units 4/40 Digital modules /2 Introduction /2 S7-300/S7-300F / Central processing units / CPU 312C to CPU 317F-2 DP /38 SIPLUS central processing units /38 SIPLUS CPU 312C, CPU 313C, CPU 31, CPU 315-2 DP /0 Digital modules /0 SM

More information

SIMATIC NET. S7-CPs for PROFIBUS. CP 443-5 Basic. Manual Part B3

SIMATIC NET. S7-CPs for PROFIBUS. CP 443-5 Basic. Manual Part B3 SIMATIC NET S7-CPs for PROFIBUS Manual Part B3 CP 443-5 Basic 6GK7 443-5FX02-0XE0 Version 1 and higher (firmware version V4.0 and higher) for SIMATIC S7-400 / S7-400H Status and fault LEDs Mode selector

More information

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL E04

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL E04 Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL PROFINET with IO Controller CPU 315F-2 PN/DP and IO Device ET 200S T I A Training Document Page 1 of

More information

CP 343-1 BACnet 6FL4343-1CX10-0XE0 DESIGO S7. Used with DESIGO S7, Building Solution & Building Integration

CP 343-1 BACnet 6FL4343-1CX10-0XE0 DESIGO S7. Used with DESIGO S7, Building Solution & Building Integration s 9 291 9291P01 DESIGO S7 CP 343-1 BACnet 6FL4343-1CX10-0XE0 Used with DESIGO S7, Building Solution & Building Integration SIMATIC S7.300 CP 343-1 for Industrial Ethernet TCP/IP with BACnet communications

More information

PROFINET the Industrial Ethernet standard. Siemens AG 2013. Alle Rechte vorbehalten.

PROFINET the Industrial Ethernet standard. Siemens AG 2013. Alle Rechte vorbehalten. the Industrial Ethernet standard is 100% Ethernet is Ethernet Ethernet is the established standard in the IT world for fast exchange of data (IEEE 802.3) is always full duplex simultaneous communication

More information

SIMATIC Controllers. The innovative solution for all automation tasks SIMATIC. Answers for industry. Edition April 2013. Overview.

SIMATIC Controllers. The innovative solution for all automation tasks SIMATIC. Answers for industry. Edition April 2013. Overview. The innovative solution for all automation tasks SIMATIC Overview Edition April 2013 Answers for industry. System-wide engineering, communications and diagnostics SIMATIC Modular Controllers Your benefits

More information

The most powerful PLC. Product Brief January 2003

The most powerful PLC. Product Brief January 2003 The most powerful PLC Product Brief January 00 Introduction The S7-00 is the most powerful PLC in the SIMATIC Controller family; the range that enables successful automation solutions with Totally Integrated

More information

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE T I A Training Document Page 1 of 25 Module This document has been written by Siemens AG for training

More information

SIMATIC S7-1200. It s the Interplay that makes the difference. Siemens AG 2010. All Rights Reserved.

SIMATIC S7-1200. It s the Interplay that makes the difference. Siemens AG 2010. All Rights Reserved. SIMATIC S7-1200 It s the Interplay that makes the difference SIMATIC S7-1200 Controller SIMATIC S7-1200 CPUs CPU 1211C 3 configurations per CPU Dimensions W x H x D (mm) CPU 1212C CPU 1214C DC/DC/DC, AC/DC/RLY,

More information

LOGO! Logic module. Brochures For brochures serving as selection guides for SIMATIC products refer to: http://www.siemens.com/simatic/ printmaterial

LOGO! Logic module. Brochures For brochures serving as selection guides for SIMATIC products refer to: http://www.siemens.com/simatic/ printmaterial Siemens AG 010 / / SIPLUS basic versions /5 SIPLUS Pure versions /8 analog expansion modules /9 SIPLUS expansion modules Brochures For brochures serving as selection guides for SIMATIC products refer to:

More information

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2 Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male

More information

CPU systron S 200 - S 250 - S 250c. systron S 200 - S 250 - S 250c. CPUs to the process modules. Stand-alone PLC

CPU systron S 200 - S 250 - S 250c. systron S 200 - S 250 - S 250c. CPUs to the process modules. Stand-alone PLC E031019 000823 systron S 200 - S 250 - S 250c CPU systron S 200 - S 250 - S 250c 45 mm width Flexible and expandable Easy to use software for bus connection (S 250/ S 250c) CPUs to the process modules

More information

S7-300/S7-300F S7-300F

S7-300/S7-300F S7-300F S7-300/S7-300F Overview S7-300 The modular mini PLC system for the low and mid-performance ranges With comprehensive range of modules for optimum adaptation to the automation task Flexible use through

More information

Siemens AG 2011. 3/42 Analog modules 3/42 EM 231 3/42 EM 232 3/42 EM 235 3/47 EM 231 thermocouple module 3/49 EM 231 RTD module

Siemens AG 2011. 3/42 Analog modules 3/42 EM 231 3/42 EM 232 3/42 EM 235 3/47 EM 231 thermocouple module 3/49 EM 231 RTD module Siemens AG 2011 /2 Introduction /4 Central processing units /4 CPU 221 /4 CPU 222 /4 CPU 224 /4 CPU 224 XP, CPU 224 XPsi /4 CPU 226 /24 SIPLUS central processing units /24 SIPLUS CPU 221 /25 SIPLUS CPU

More information

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE E05

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE E05 Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE PROFINET with IO-Controller CP343-1 Advanced and IO-Device ET 200S T I A Training Document Page 1 of

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET safe via BUS or NET AS-i 3.0 Gateways, safe via NET or BUS safe and Safe Link in one device up to 450 devices 2 / 1 Master, NET / BUS Slave AS-i Safety input slaves report via safe AS-i Safety output slaves

More information

Overview and Applications of PROFINET. Andy Verwer Verwer Training & Consultancy Ltd

Overview and Applications of PROFINET. Andy Verwer Verwer Training & Consultancy Ltd Overview and Applications of PROFINET Andy Verwer Verwer Training & Consultancy Ltd What exactly is PROFINET? PROFINET is an open Industrial Ethernet standard developed by the PROFIBUS Organisation. PROFINET

More information

HARTING mcon 1000 Introduction and features

HARTING mcon 1000 Introduction and features Introduction and features HARTING mcon 1000 es, managed, for mounting onto top-hat mounting rail in control cabinets General Description Features Supporting Ethernet (10 Mbit/s), Fast Ethernet (100 Mbit/s)

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

PROFINET. The leading. Industrial. Ethernet. Standard. The Benefits of PROFINET

PROFINET. The leading. Industrial. Ethernet. Standard. The Benefits of PROFINET PROFINET The leading The Benefits of PROFINET Industrial Ethernet Standard Automation Structure 2 ))) Automation system Industrial Ethernet Automation Structure 3 Network standard Ethernet High transmission

More information

SIMATIC NET. S7-CPs for Industrial Ethernet. CP 343-1 Lean. Manual Part B8. Version 1 or higher (Firmware Version V1.0) for SIMATIC S7-300 / C7-300

SIMATIC NET. S7-CPs for Industrial Ethernet. CP 343-1 Lean. Manual Part B8. Version 1 or higher (Firmware Version V1.0) for SIMATIC S7-300 / C7-300 SIMATIC NET S7-CPs for Industrial Ethernet Manual Part B8 CP 343-1 Lean 6GK7 343-1CX00-0XE0 for SIMATIC S7-300 / C7-300 Version 1 or higher (Firmware Version V1.0) LED displays TP port: 8-pin RJ-45 jack

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

Programmable set for Ethernet Modbus/TCP in IP20 TI-BL20-PG-EN-8

Programmable set for Ethernet Modbus/TCP in IP20 TI-BL20-PG-EN-8 CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps LEDs for display of supply voltage, group and bus errors as well as status and diagnostics Connection

More information

Panel PC SIMATIC HMI IPC577C

Panel PC SIMATIC HMI IPC577C Product Data Sheet Rugged, expandable industry PC for demanding tasks in the area of PC-based automation with various control units (front panels): Rugged and compact design for industrial use Full PC

More information

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0 FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION

More information

Digital input modules

Digital input modules 8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a

More information

154 PHOENIX CONTACT Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370 Main Office: (650) 588-9200-Outside Local

154 PHOENIX CONTACT Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370 Main Office: (650) 588-9200-Outside Local 154 PHOENIX CONTACT PROFINET The future-oriented system solution PROFINET is the realtime Ethernet approach that can be used in all industrial motion control fields - from factory automation to process

More information

1 Application Description... 3. 1.1 Objective... 3 1.2 Goals... 3

1 Application Description... 3. 1.1 Objective... 3 1.2 Goals... 3 Contents Moxa Technical Support Team support@moxa.com 1 Application Description... 3 1.1 Objective... 3 1.2 Goals... 3 2 System Topology... 3 3 Hardware and Software Requirements... 4 4 Configuration...

More information

CPU 317-2 PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device

CPU 317-2 PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device SIMATIC PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device Introduction 1 Preparation 2 Learning units 3 Further Information

More information

Set for PROFINET IO in IP20 TI-BL20-EN-PN-4

Set for PROFINET IO in IP20 TI-BL20-EN-PN-4 Cable max. 50 m between interface and read/write head Connection of up to 4 read/write heads via BL ident extension cables Mixed operation of HF and UHF read/ write heads Connectors /S2500 Type code Ident

More information

SIMATIC. C7-621, C7-621 AS-i Control Systems. Volume 2 Working with C7 A B C D E. Contents. User Information. Introduction. Startup.

SIMATIC. C7-621, C7-621 AS-i Control Systems. Volume 2 Working with C7 A B C D E. Contents. User Information. Introduction. Startup. Contents User Information Introduction 1 Startup 2 SIMATIC C7-621, C7-621 AS-i Control Systems Volume 2 Working with C7 Manual Controlling Controlling with the C7 CPU 3 Addessing, Parameter Assignment,

More information

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK Field busses are industrial control systems using Programmable Logic lers (PLC) to control and manage field devices found in industrial environments. The communication

More information

SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

Configuration limits for products of the SIMATIC NET PC Software V12 SIMATIC NET. Configuration limits for products of the SIMATIC NET PC Software V12

Configuration limits for products of the SIMATIC NET PC Software V12 SIMATIC NET. Configuration limits for products of the SIMATIC NET PC Software V12 Configuration limits for products of the SIMATIC NET PC Software V12 Communications partners and configuration limits for HARDNET-PB DP-Base 1 software Configuration limits, SOFTNET-PB DP 2 SIMATIC NET

More information

PROFINET Diagnostics Software and Tools

PROFINET Diagnostics Software and Tools PROFINET Diagnostics Software and Tools Dr. Xiu Ji Static wiring test, diagnostics Live system diagnostics Basics of PROFINET Content PROFINET Diagnostics by Dr. Xiu Ji, Page 2 What is PROFINET? PROFINET

More information

DATA COMMUNICATION BETWEEN PROGRAMMABLE LOGIC CONTROLLERS IN THE INDUSTRIAL DISTRIBUTION APPLICATIONS

DATA COMMUNICATION BETWEEN PROGRAMMABLE LOGIC CONTROLLERS IN THE INDUSTRIAL DISTRIBUTION APPLICATIONS DATA COMMUNICATION BETWEEN PROGRAMMABLE LOGIC CONTROLLERS IN THE INDUSTRIAL DISTRIBUTION APPLICATIONS Anna BYSTRICANOVA 1, Andrej RYBOVIC 1 1 Department of Mechatronics and Electronics, Faculty of Electrical

More information

AS-i 3.0 PROFIBUS Gateways with integrated Safety Monitor

AS-i 3.0 PROFIBUS Gateways with integrated Safety Monitor AS-i 3.0 Gateways AS-i 3.0 Gateways 2 / 1 AS-i Master, Slave 1 AS-i Safety Monitor for 2 s Operation using a single Monitor! Monitor processes safety slaves on two s Coupling between the two networks superfluous

More information

HARTING econ 3000 Introduction and features

HARTING econ 3000 Introduction and features HARTING Introduction and features HARTING es, unmanaged, for installation in control cabinets General Description Features The Fast es of the product family HARTING are suitable for industrial applications

More information

SIMATIC S7-1200 Basic Controller in the TIA Portal

SIMATIC S7-1200 Basic Controller in the TIA Portal Technical slides SIMATIC S7-1200 Basic Controller in the TIA Portal Frei verwendbar / Siemens AG 2015. Alle Rechte vorbehalten. www.siemens.com/s7-1200 SIMATIC Controller S7-1200 Efficient engineering

More information

SIMATIC. S7-300 and M7-300 Programmable Controllers Module Specifications. Preface, Contents. General Technical Specifications. Power Supply Modules

SIMATIC. S7-300 and M7-300 Programmable Controllers Module Specifications. Preface, Contents. General Technical Specifications. Power Supply Modules SIMATIC S7-300 and M7-300 Programmable Controllers Module Specifications Reference manual This manual is part of the following documentation packages with order nos: S7 300 Programmable Controller: 6ES7

More information

S-series SQ Controller

S-series SQ Controller DeltaV Distributed Control System Product Data Sheet December 2015 S-series SQ Controller Scalable controllers Quick assembly Easy-to-use Field proven architecture Designed for Electonic Marshalling Advanced

More information

Siemens AG 2011 SINAMICS V60. The perfect solution for basic servo applications. Brochure May 2011 SINAMICS. Answers for industry.

Siemens AG 2011 SINAMICS V60. The perfect solution for basic servo applications. Brochure May 2011 SINAMICS. Answers for industry. The perfect solution for basic servo applications Brochure May 2011 SINAMICS Answers for industry. with 1FL5 servomotors The solution for basic servo applications There is a requirement to automate motion

More information

SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M

SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M Compact Operating Instructions Legal information Qualified Personnel The product/system described in this documentation

More information

Communication Unit 560CMU05 Data sheet

Communication Unit 560CMU05 Data sheet RTU560 product line Communication Unit 560CMU05 Data sheet E1 10/100 MB LAN E2 10/100 MB LAN CP1, CP2 RS232C or RS485 Ethernet Controller Ethernet Controller USART Processor bus MPU ELAN520 /Flash Memory

More information

DCS Data and communication server

DCS Data and communication server 8 58 PLD.TOWER PLD.RACK VISONIK DCS Data and communication server PLD.TOWER PLD.RACK Data and communication servers (DCS) are used as management stations in building automation and control (BAC). With

More information

SIMATIC. ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.

SIMATIC. ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Preface. Properties 1. Diagnostics 2. SIMATIC ET 200S distributed I/O SIMATIC Preface Properties 1 Diagnostics 2 ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Manual 04/2007 A5E01077339-01 Safety Guidelines

More information

Parameterization, Configuration and Visualization with SIRIUS

Parameterization, Configuration and Visualization with SIRIUS Parameterization, Configuration and Visualization with SIRIUS Price groups 200, 346, 42B, 42C, 42D, 42H, 42J, 4N1 /2 Introduction /5 Soft Starter ES /9 SIRIUS 3RW44 soft starter block library for SIMATIC

More information

Automation Unit TM 1703 ACP Flexible automation and telecontrol

Automation Unit TM 1703 ACP Flexible automation and telecontrol Automation Unit Flexible automation and telecontrol Power Transmission and Distribution Outstanding performance: Automate simply with Highly complex and yet fully transparent automation solutions are not

More information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

SIMATIC. PC Adapter USB. Preface, Contents Properties of the PC Adapter USB 1. Package Components

SIMATIC. PC Adapter USB. Preface, Contents Properties of the PC Adapter USB 1. Package Components s SIMATIC Manual Preface, Contents Properties of the 1 Package Components 2 Requirements for Operation 3 Hardware Design of the 4 Working with the 5 on the MPI/DP Network 6 Firmware Update 7 Error Diagnostics

More information

SIMATIC NET. S7-CPs for PROFIBUS Configuring and Commissioning

SIMATIC NET. S7-CPs for PROFIBUS Configuring and Commissioning SIMATIC NET S7-CPs for PROFIBUS Configuring and Commissioning Manual Part A General Application Preface, Contents Communication over S7-CPs 1 Characteristics of the PROFIBUS CPs 2 NCM S7 for PROFIBUS CPs

More information

NX safety stand-alone

NX safety stand-alone NX-S@ NX safety stand-alone stand-alone into machine automation Expandable safety system up to 32 safety connections or 63 standard connections controller flexible system lets your freely mix safety I/O

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

PROFINET IO Diagnostics 1

PROFINET IO Diagnostics 1 PROFINET IO is a very cost effective and reliable technology. However, extensive installations can have thousands of PROFINET IO devices operating on many networks. The reliable operation of these networks

More information

LCM Design Engineering SPECIFICATION FOR LCD MODULE TYPE ITEM NO.: MDLS16265-04 MDLS16265-LV-G-LED04G (BB) (DOC. REVISION 1.0)

LCM Design Engineering SPECIFICATION FOR LCD MODULE TYPE ITEM NO.: MDLS16265-04 MDLS16265-LV-G-LED04G (BB) (DOC. REVISION 1.0) VARITRONIX LIMITED LCM Design Engineering SPECIFICATION FOR LCD MODULE TYPE ITEM NO.: MDLS16265-04 MDLS16265-LV-G-LED04G (BB) (DOC. REVISION 1.0) DEPARTMENT NAME SIGNATURE EFFECTIVE DATE PREPARED BY PHILIP

More information

What ensures easy and fast wiring?

What ensures easy and fast wiring? What ensures easy and fast wiring? SIMATIC TOP connect: the system cabling for connecting sensors and actuators to SIMATIC S7. Answers for industry. More efficient cabling made easy: SIMATIC TOP connect

More information

HMIGTO4310 advanced touchscreen panel 640 x 480 pixels VGA- 7.5" - TFT - 96 MB

HMIGTO4310 advanced touchscreen panel 640 x 480 pixels VGA- 7.5 - TFT - 96 MB Product datasheet Characteristics HMIGTO4310 advanced touchscreen panel 640 x 480 pixels VGA- 7.5" - TFT - 96 MB Main Range of product Product or component type Display colour Display size Supply Magelis

More information

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

RFID systems. Communications modules ASM 450 4/139. Overview

RFID systems. Communications modules ASM 450 4/139. Overview Overview The low-cost communications module ASM 50 is an autonomous PROFIBUS DP slave for the operation of MOBY components via the PROFIBUS DP: SIMATIC S7 (including FB/FC software) SINUMERIK SICOMP IMC,

More information

Set for Profibus DPV1 in IP20 TI-BL20-DPV1-8

Set for Profibus DPV1 in IP20 TI-BL20-DPV1-8 Type code Ident no. 1545007 Number of channels 8 Dimensions (W x L x H) 110.3 x 128.9 x 74.4 mm Cable max. 50 m between interface and read/write head 2 decimal rotary coding switches for the adjustment

More information

Operator Control and Monitoring Devices

Operator Control and Monitoring Devices Operator Control and Monitoring Devices Siemens AG 008 Overview Benefits Integral component of Totally Integrated Automation (TIA): Increased productivity, minimum engineering overhead, reduction in life-cycle

More information

Remote Monitoring and REC 501 Control Unit Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the

More information

HARTING mcon 3000 Introduction and features

HARTING mcon 3000 Introduction and features Introduction and features HARTING mcon 3000 es, managed, for mounting onto top-hat mounting rail in control cabinets General Description Features The fully managed es of the product family HARTING mcon

More information

Application. Characteristics RTU560. Data Sheet Communication Unit 560CMD11. Communication Unit 560CMD11

Application. Characteristics RTU560. Data Sheet Communication Unit 560CMD11. Communication Unit 560CMD11 Communication Unit 560CMD11 The SLC works as master for the RTU560 serial peripheral bus (I/O-Interface/ Wired-OR-Bus ). The MPU is responsible for the other tasks. The MPU handles the absolute time and

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

TRAINING INDEX SIEMENS SIMATIC S7-200 S7-200 BASIC COURSE S7-200 ADVANCED COURSE SIEMENS SIMATIC S5 S5 STARTER S5 EXPERT

TRAINING INDEX SIEMENS SIMATIC S7-200 S7-200 BASIC COURSE S7-200 ADVANCED COURSE SIEMENS SIMATIC S5 S5 STARTER S5 EXPERT TRAINING INDEX SIEMENS SIMATIC S7-300/400 S7 BASIC COURSE S7 ADVANCED COURSE S7 ADVANCED DIAGNOSTICS S7 COMMUNICATION S7 ETHERNET S7 AS-I S7 OPC S7 PROFINET S7 LOOP CONTROL S7 GRAPH S7 SCL S7 DISTRIBUTED

More information

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no. 6814053.

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no. 6814053. PROFINET slave Integrated Ethernet switch 100 Mbps supported 2 x M12, 4-pin, D-coded, Ethernet fieldbus connection Glass-fiber reinforced housing Shock and vibration tested Potted module electronics Protection

More information

BATRON DOCUMENT NUMBER AND REVISION VL-FS-BTHQ 21605VSS-02 REV.A (BTHQ 21605VSS-FSTF-LED05W(1 DIE)) Feb/2002 BTHQ 21605-FSTF-LED WHITE 1/15

BATRON DOCUMENT NUMBER AND REVISION VL-FS-BTHQ 21605VSS-02 REV.A (BTHQ 21605VSS-FSTF-LED05W(1 DIE)) Feb/2002 BTHQ 21605-FSTF-LED WHITE 1/15 Feb/2002 1/15 DOCUMENT NUMBER AND REVISION VL-FS-BTHQ 21605VSS-02 REV.A (BTHQ 21605VSS-FSTF-LED05W(1 DIE)) 2/15 DOCUMENT REVISION HISTORY 1: DOCUMENT REVISION DATE DESCRIPTION CHANGED BY FROM TO A 2002.01.09

More information

Controllers. The integrated standard software guarantees highest quality standards! Simple and safe operation. Specific and clear indication

Controllers. The integrated standard software guarantees highest quality standards! Simple and safe operation. Specific and clear indication Screwdriving technology Automation Air motors Air tools Controllers Sequence Controllers for Screwdrivingand Assembly Stations The integrated standard software guarantees highest quality standards! Simple

More information

Foxboro Evo Process Automation System

Foxboro Evo Process Automation System Foxboro Evo Process Automation System Product Specifications PSS 31H-2Z32 FBM232 Field Device System Integrator Module, 10/100 Mbps Ethernet, Single The FBM232 Field Device System Integrator (FDSI) module

More information

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware Substation Automation Products Relion 670/650 series IEC and ANSI Hardware ABB Group 1MRG014097 October 2013 Relion 670/650 series hardware Contents Relion 670/650 series Relion Hardware Relion Common

More information

Ha-VIS FTS 3000 Introduction and features

Ha-VIS FTS 3000 Introduction and features Ha-VIS Introduction and features Ethernet Switch Ha-VIS FTS 3100s-A 10-port Ethernet Switch with Fast Track Technology configurable via USB General Description Features The Fast Ethernet Switches of the

More information

Hirschmann Networking Interoperability in a

Hirschmann Networking Interoperability in a Automation and Network Solutions Hirschmann Networking Interoperability in a PROFInet Environment Hirschmann Interoperability White Paper Rev. 1.1 Contents Hirschmann Networking Interoperability in a Profinet

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Bar Code Reader Series BCL 20 A flexible reader for a variety of applications

Bar Code Reader Series BCL 20 A flexible reader for a variety of applications Bar Code Reader Series BCL 20 A flexible reader for a variety of applications PRODUCT INFORMATION The benchmark for flexibility. Laser scanners of the BCL 20 series as variable as your requirements demand.

More information

M-series Virtual I/O Module 2

M-series Virtual I/O Module 2 DeltaV Distributed Control System Product Data Sheet M-series Virtual I/O Module 2 Non-intrusive DeltaV I/O simulation Powerful integration solution Easy to use Modular, flexible packaging The M-series

More information

AS-i 3.0 Gateways, PROFIsafe via PROFINET or PROFIBUS

AS-i 3.0 Gateways, PROFIsafe via PROFINET or PROFIBUS via PROFINET or AS-i 3.0 Gateways, via PROFINET or 2 / 1 Master, PROFINET / Slave AS-i Safety input slaves report via AS-i Safety output slaves switch via 1 Safety Monitor for 2 AS-i networks Operation

More information

6AV3617-1JC30-0AX1. Type of voltage. UPS connectable (serial) Backup battery. minimum backup duration Memory. Flash / RAM.

6AV3617-1JC30-0AX1. Type of voltage. UPS connectable (serial) Backup battery. minimum backup duration Memory. Flash / RAM. 6AV3617-1JC30-0AX1 Page 1 Product data sheet 6AV3617-1JC30-0AX1 OPERATOR PANEL OP17/DP12 LC DISPLAY, BACKLIT LED 4X20/8X40 LINESXCHARACTERS SIMATIC S5, 505, S7, M7, NATIVE DRIVERS, PROFIBUS-DP 12 MBAUD,

More information