Instrument Transformers By: Kiran Kelapure

Similar documents
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Current & Instrument Transformers

VOLTAGE REGULATOR AND PARALLEL OPERATION

Enhanced Quality with a Touch of Style

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

Current Transformers

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

T Substation Maintenance and Commissioning Test Equipment

Measurement of Power in single and 3-Phase Circuits. by : N.K.Bhati

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:

Vario-Series Accessories

Instrument Transformers Application Guide

Using Current Transformers with the 78M661x

Type SA-1 Generator Differential Relay

Unified requirements for systems with voltages above 1 kv up to 15 kv

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007

AC Generators. Basic Generator

Capacitor Voltage Transformer. Answers for energy.

Kit Watt Audio Amplifier

How To Choose A Transformer

Guidance for upgrading to GB (IEC : 2005, MOD)

Current transformers (CT) & Shunts

Application Note. So You Need to Measure Some Inductors?

GUIDE FOR TESTING POWER TRANSFORMERS

Current Transformers Ratio / Polarity / Types

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Unit 6 Transformers. Lead-in. Basic principles. Task 1. Task 2. What applications of transformers do you know?

CURRENT TRANSFORMERS INSTALLATION GUIDE

Medium-voltage transformers

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21,

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Safety technique. Emergency stop module BO 5988 safemaster

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Three-phase monitoring relay CM-PFE

Table of Contents. TransformerIQ FAQs 1

Presentation of the France Transfo factories

Earth Fault Detection Basics in Theory

Thermistor motor protection

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

Tamura Closed Loop Hall Effect Current Sensors

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Lab 14: 3-phase alternator.

Line Reactors and AC Drives

Circulating Current Relay. Type IRXm

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

CAPACITOR BANK TESTING SWP

understanding medium frequency induction melting furnace and its components

How To Build A Low Voltage Capacitor Lvcp

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Automatic Voltage Regulator User s Manual

LOW-VOLTAGE CURRENT TRANSFORMERS

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

Power transformers. Special transformers Railway

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Properties of electrical signals

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

Current and Temperature Ratings

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Measurement devices Accessories for analogue and digital instruments

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

Short Circuit Current Calculations

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

Release: 2. UEENEEJ194A Solve problems in low voltage refrigeration circuits

5. Measurement of a magnetic field

Tape Wound, Split Core and Ebony Current Transformers

DS 600. A contact free flux gate based current measurement sensor 600A rms

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

1. The diagram below represents magnetic lines of force within a region of space.

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

Transformer Calculations

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB

Physics 3330 Experiment #2 Fall DC techniques, dividers, and bridges R 2 =(1-S)R P R 1 =SR P. R P =10kΩ 10-turn pot.

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS

ES250: Electrical Science. HW7: Energy Storage Elements

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Pilot-wire differential relay for lines with two or more terminals

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

R.C.C.B. s two-pole LEXIC

Medium voltage circuit breaker

CT Analyzer: Coming to the Rescue. Introduction. Equivalent Circuit. Construction. Classification of a CT. Tony Porrelli, OMICRON, UK

Voltage Regulator SPAU 341 C. Product Guide

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 NUCLEAR MAGNETIC RESONANCE

Current transformer selection guide

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Transcription:

Yadav Measurements Pvt. Ltd. Instrument Transformers By: Kiran Kelapure A specifically designed programme for Da Afghanistan Breshna Sherkat (DABS) Afghanistan 1

Electricity Metering technologies and systems Areas Covered Under this Module 1. Understand importance of instrument transformers in revenue metering. 2. Voltage and Current transformers (Types, Definitions, Testing methods). 3. Standards applicable 2

Metering Unit (CT & PT) Sources of errors Secondary wiring Mete r Typical setup at HT customers 3

Importance Metering system accuracy is governed by instrument transformers, if used in LT CT or HT CT/VT systems. ( HT3 or HT 4) All errors add algebraically. Meter errors CT Errors VT (PT) Errors ENERGY METERING System ACCURACY 4

Importance Meters may be of high accuracy, but are instruments transformers too?, generally not, may be one class lower. 5

Let us view process of Error drifting in CT / PT

Error Drifting It may saturate the Core of the CT Fault Current will pass through Metering CT X M ω R Over a period the CT Error may drift 7

Error Drifting These Surges are reflected on PT Switching On & Off the Load always generate Switching Surges PT ωω M R It may damage the PT winding & Insulation M Switching Surges are also passing through CT Over a period the PT Error may drift Over a period the CT Error may drift Over a period the CT/PT may develop inter turn short Over a period, the wiring may get damaged 8 M M Thunder lightening also generates Surges

To Summarise Accuracy of instrument transformers do change due to Aging Error Drifting Environmental effects like ambient temperature, temperature cycling, humidity etc line transients and surges leading to insulation leakage, shorted turns fault currents leading to saturation of cores, 9

Other Factors Higher ratio CTs when used at lower loads, may have large errors as they may operate at lower % load. With static meters burden being low, if higher burden CT/PT are used, their performance at lower burden is questionable, as not even specified by standards. Drop across leads in VTs, depending on burden connected. If a PT or CT is used for indication only, then ratio errors are important, phase error doesn t matter. 10

Instrument transformers Voltage transformers Current transformers Combined CT/PT units or metering Units 11

Instrument transformers A transformer intended to supply input to measuring instruments, meters, relays and other similar apparatus. These provide isolation and a measurable (standardized) signal at safe voltage levels. Safety of persons and equipments which are interfaced 12

Current Transformers 13

Current transformer An instrument transformer in which the secondary current, in normal conditions of use is substantially proportional to the primary current and differs in phase from it by an angle which is approximately zero for an appropriate direction of the connections. 14

Types of CTs by application Measuring current transformer A current transformer intended to supply indicating instruments, integrating meters and similar apparatus. Protective current transformer A current transformer intended to supply protective relays and similar apparatus. 15

Types of CTs. by construction Window type or ring type current transformer A current transformer having no primary winding as an integral part of the structure. This current transformer has an opening in the center to accommodate a primary conductor through it. Wound-primary current transformer A current transformer in which the primary winding consists of a single turn loop or multi-turn coil integral with the transformer. Bar-primary current transformer A current transformer in which the primary winding consists of a bar of suitable size and material forming an integral part of the current transformer the primary conductor is the equivalent of a single primary turn. 16

Types of CTs. by construction Multiple secondary current transformer A current transformer having more than one secondary winding on a common core. One secondary winding is closed, other unused secondary should be left open circuit and not closed or short circuited. Multiple-primary current transformer A current transformer having more than one primary winding on a common core. Multiple ratio current transformer A current transformer from which more than one transformation ratio can be obtained by the use of taps on the primary or secondary windings or both, or by series / parallel connection of separate primary or secondary windings on a common core, or by other means. 17

Types of CTs...by insulation Tape wound CTs: these are ring type CTs, with polyester or fiber glass tape. Resin cast CTs: these are ring type CTs, with polyester or PVC tape and then cast into resin. Resin works as insulation as well as provides environmental protection. Terminals and supporting clamps are also cast in the resin. Oil filled CTS: these are generally HT type of CTS. In these, oil is used as insulation and provides cooling also. 18

Types of CTs by application Interposing current transformer A current transformer which is intended to amend the ratio of a main current transformer by having its primary winding connected to secondary winding of the main current transformer and its secondary winding connections to the burden. Summation current transformer A current transformer which is intended to summate the currents in a number of feeders in association with the feeder current transformer Core balance current transformers. The core balance current transformers are intended for providing earth leakage protection on 3 phase electrical system. 19

Some definitions Rated primary current: The value of primary current which appear in the designation or rating plate and on which CT performance is based. The value of current which is to be transformed to a lower value. In CT parlance, the "load" of the CT refers to the primary current. Rated secondary current: The current in the secondary circuit and on which the performance of the CT is based. Typical values of secondary current are 1 A or 5 A. Rated burden: The apparent power of the secondary circuit in Voltamperes expressed at the rated secondary current and at a specific power factor (0.8 for almost all standards) 20

Some definitions. Contd. Accuracy class: In the case of metering CT s, accuracy class is typically, 0.2, 0.5, 1 or 3. This means that the errors have to be within the limits specified in the standards for that particular accuracy class. The metering CT has to be accurate from 5% to 120% of the rated primary current, at 25% and 100% of the rated burden at the specified power factor. 21

Some definitions. Contd. Short time rating: The value of primary current (in ka) that the CT should be able to withstand both thermally and dynamically without damage to the windings, with the secondary circuit being short-circuited. The time specified is usually 1 or 3 seconds. Instrument security factor (factor of security): This typically takes a value of less than 5 or less than 10 though it could be much higher if the ratio is very low. If the factor of security of the CT is 5, it means that the composite error of the metering CT at 5 times the rated primary current is equal to or greater than 10%. This means that heavy currents on the primary are not passed on to the secondary circuit and instruments are therefore protected. In the case of double ratio CT's, FS is applicable for the lowest ratio only. 22

CT errors ( Ratio error ) The error which a transformer introduces into the measurement of a current and which arises from the fact that the actual transformation ratio is not equal to the rated transformation ratio. The current ratio error expressed in percent is given by the formula. (KnIs Ip) x 100 CURRENT ERROR % = ------------------- Ip Where Kn = the rated transformation ratio ip = the actual primary current is = the actual secondary current when 23

Phase displacement or error The difference in phase between the primary and secondary current vectors, the direction of the vectors being so chosen that the angle is zero for a perfect transformer. The phase displacement is said to be positive when the secondary current vector leads the primary current vector. (this definition is correct for sinusoidal currents) 24

Some facts about CTs CT is a variable flux device, unlike PT, which is a constant flux device. CT secondary shall never be open circuited, when primary is energised, it produces very high voltages, which may be fatal, as well cause damage to equipments. 25

Some facts about CTs CTs may saturate due to Open secondary winding. Due to DC current in secondary, like for testing resistance using a multi-meter. Due to short circuit fault Due to saturated core, ratio and Phase errors increases on negative side Such CTs shall be demagnetised. 26

Testing of current transformers Comparision Method: or Primary injection method: This is a modification of the basic bridge methods. Instead of reading the primary and secondary currents, the secondary current of a calibrated standard / reference current transformer and the transformer undergoing test are compared with each other by nulling method using a bridge, or direct error computation. The comparision method, of course requires the use of a Standard current transformer with a rating which corresponds to that of each current transformer involved in calibrating. We require a source, reference CT, calibrated burden set, and a comparator. Reference temp specified is 40 deg C 27

28

% Error +1.5% At 25% VA Burden CT Performance For Class 0.5 +1.0% +0.5% -0.5% 5% 20% 100% 120% ==Ł % Rated current -1.0% -1.5% At 100% VA Burden 29

Permissible Ratio errors (0.5 Class CT) 1.50 1.00 +/- 1.5% +/- 0.75% +/- 0.5% % Ratio error Limits 0.50 0.10-0.10-0.50 1% I 5% I 20% I 100% I 120% I % I -1.00-1.50 Limits for class 0.5 CTs Limits are more stringent for expensive class s CTs Limits for class 0.5s CTs 30

Permissible Phase errors (0.5 Class CT) +/- 90 min 90 Phase error Limits (minutes) 70 50 30 10-10 -30-50 +/- 45 min +/- 30 min 1% I 5% I 20% I 100% I 120% I % I -70-90 Limits for class 0.5 CTs Limits are more stringent for expensive class s CTs Limits for class 0.5s CTs 31

Limits of errors. AS PER IS 2705/1992 AND IEC 60044.1/1996. ACCURACY CLASS + % CURRENT (RATIO) ERROR AT % of RATED CURRENT. PHASE DISPLACEMENT IN MINUTES % OF RATED CURRENT 5 20 100 120 5 20 100 120 0.1 0.4 0.2 0.1 0.1 15 8 5 5 0.2 0.75 0.35 0.2 0.2 30 15 10 10 0.5 1.5 0.75 0.5 0.5 90 45 30 30 1.0 3.0 1.5 1.0 1.0 180 90 60 60 32

Voltage Transformers 33

Voltage transformer An instrument transformer in which, in normal conditions of use and for an appropriate direction of the connections. Secondary voltage, is substantially proportional to the primary voltage. Differs in phase from it by an angle which is approximately zero 34

Electromagnetic voltage transformer A voltage transformer which transforms the primary voltage to the secondary voltage entirely by electromagnetic phenomena. 35

Capacitor voltage transformer A voltage transformer comprising a capacitor divider unit and an electromagnetic unit so designed and interconnected that the secondary voltage of the electromagnetic unit is substantially proportional to and in phase with the primary voltage applied to the capacitor divider unit. 36

Definitions Rated Primary Voltage / Secondary Voltages The rms values of the voltage upon which the performance of the voltage transformer is based. Rated Transformation Ratio The ratio of the rated primary voltage to the rated secondary voltage. Normal System Voltage The rms line-to-line voltage by which the system is designated. 37

Voltage error (ratio error) Errors in VTs, definitions Introduces into the measurement of a voltage and which arises when the actual transformation ratio is not equal to the rated transformation ratio. The voltage error, expressed in percent, is given by the formula : kn. Us Up VOLTAGE ERROR = --------------- X 100% Up Where kn = The rated transformation ratio, Us = The actual secondary voltage, when Up is applied under the conditions of measurement, and Up = The actual primary voltage 38

Errors in VTs, definitions Phase errors The difference in phase between the primary voltage and the secondary voltage vectors, the direction of the vectors being so chosen that the angle is zero for a perfect transformer. This phase displacement is said to be positive when the secondary voltage vector leads the primary voltage vector and negative when it lags. It is usually expressed in minutes. ( definition is strictly correct for sinusoidal voltage only.) 39

Rated insulation level That combination of voltage values which characterized the insulation of a transformer with regard to its capability to withstand dielectric stresses. Eg.: 12 / 28 / 75 KVp Impulse withstand voltage power frequency withstand voltage Highest system voltage 40

Voltage Transformer construction Basic elements of construction of voltage transformer are Magnetic circuit (core) Electrical circuit i.e. Primary and secondary windings Insulation, basic and additional Housing and other mechanical details Terminals and mounting arrangements Earthing facility. 41

Voltage Transformer construction Potential transformer consists of two separate windings on a common magnetic steel core. One winding consist of relatively large number of turns of fine wire, called primary winding. The other winding consists of fewer turns of heavier wire and is called secondary winding. The core material used is generally, GOSS. Sec. winding is made of thicker wire, with tight coupling between primary and secondary windings. These help to keep resistances of coils as well as leakage inductance low. Which in turn help to keep errors low. Suitable insulation between primary and secondary and to the body is maintained. 42

Voltage transformer design The VT normally works on a constant magnetic flux density. Never short circuit the secondary terminals of a potential transformer. A secondary short circuit will cause the unit to over heat and fail in a very short period of time. For protection, there may be fuses in Primary or secondary or both. For reasons of tamper, these days fuses are not used. 43

Testing a VT Many methods, like voltmeter, with standard PTs, resistor or capacitor dividers with voltmeters. Comparision Method:: This is a modification of the basic potentiometer method. Instead of reading the primary and secondary voltages, the secondary voltage of a calibrated standard transformer and the transformer undergoing test are compared with each other by nulling method using a bridge, or direct error computation. The comparision method, of course requires the use of a Standard potential transformer with a rating which corresponds to that of each potential transformer involved in calibrating. Reference temp specified is 40 deg C 44

45

LIMITS OF VOLTAGE ERRORS AND PHASE DISPLACEMENT AS PER IS 3156 / 1992 & IEC 60044-2 / 1997 CLASS PERCENTAGE VOLTAGE (RATIO) ERROR PHASE DISPLACEMENT (MINUTES) 0.1 +/-0.1% +/- 5 0.2 +/- 0.2% +/- 10 0.5 +/- 0.5% +/- 20 1.0 +/- 1.0% +/- 40 3.0 +/- 3.0% Not specified 46

Effect of load power factor on phase error PF Angle in error in error in Effective Effective Deg Min Deg angle PF % error 0.5 60 1 0.0166667 59.98333333 0.50025 0.050 0.6 53.1301 1 0.0166667 53.11343569 0.60023 0.039 0.7 45.573 1 0.0166667 45.55632933 0.70021 0.030 0.8 36.8699 1 0.0166667 36.85323098 0.80017 0.022 0.9 25.84193 1 0.0166667 25.8252661 0.90013 0.014 0.95 18.19487 1 0.016667 18.1782057 0.95009 0.00956 47

THANK YOU 48