Dry-Type, Air-Core Shunt Reactors



Similar documents
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

Transformers. Special transformers Reactors products

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

Power Transmission and Distribution. Shunt reactors for medium and highvoltage. From development to use

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Electric Power Distribution

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

AMSC s Superconductor Cable Technologies for Electric Utilities

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

Earth Fault Detection Basics in Theory

ECE 586b Course Project Report. Auto-Reclosing

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

Powerformer chosen for Swedish combined heat and power plant

Power Capacitor Units for improved power quality

2012 San Francisco Colloquium

EARTHING SYSTEM CALCULATION

WINDING RESISTANCE TESTING

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

VD4. Vacuum circuit-breaker

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Primary and Secondary Electrical Distribution Systems

An Overview of Lapp Insulator High Voltage Bushing Design

Unified requirements for systems with voltages above 1 kv up to 15 kv

Stephen G. Whitley, Senior Vice President & Chief Operating Officer

The electrical energy produced at the gen

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System

Fault location on power cables. Fault location on power cables

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Hyperlinks are Inactive

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Capacitor Voltage Transformer. Answers for energy.

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Short Circuit Current Calculations

Here is our comprehensive product range dedicated to MV distribution and earthfault compensation.

Table of Contents. TransformerIQ FAQs 1

Power Plant Electrical Distribution Systems

SECTION DRY-TYPE TRANSFORMERS

Transmission Silicone Insulators Line Post 69 kv to 161 kv

Product Data Bulletin

MOHAMMAD KHORAMI. Examiner: Dr. Anh Tuan Le Senior Lecturer, Electric Power Engineering, Chalmers University of Technology. Master of Science Thesis

High-Voltage GIS yesterday - today - tomorrow

Radial Distribution Test Feeders

Presentation of the France Transfo factories

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

HVDC Light, a tool for electric power transmission to distant loads

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

CAPACITOR BANK TESTING SWP

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Transformer Design & Design Parameters

Modeling of Transmission Lines

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

COMPARISON OF AIR-CORE AND IRON-CORE REACTORS FOR MEDIUM-VOLTAGE POWER-QUALITY APPLICATIONS

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

HV Submarine Cable Systems Design, Testing and Installation

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Metal Clad Indoor Instrument Transformer for Plug-In Systems

Shunt Capacitor Bank Fundamentals and Protection

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

Step Voltage Regulators

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

This section applies to the design and installation of transformers.

Presentation to CIGRE Next Generation Network. Visit of Seine substation

Topics. HVDC Fundamentals

GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

Summary of Electric Transmission Assessment Report

Application Note. So You Need to Measure Some Inductors?

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Power transformers. Phase shifting transformers Reliable and efficient power flow control

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2013 RESIBLOC transformers Product presentation. ABB Group October 2, 2013 Slide 1

High Voltage Power Supplies for Analytical Instrumentation

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

(3 )Three Phase Alternating Voltage and Current

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

Electrical Grounding. Appendix C

Lightning current simulation in the laboratory - parameters, procedures and test equipment -

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions

The following table shows approximate percentage wise the

Insulation Resistance Testing of Low Voltage Cables in the Field

3. Cooling System Closed-loop Pure Water-cooling. Rated Voltage: 6 ~ 66kV. Rated Current: 4000A (phase current).

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

ACCURACY OF POTENTIALTRANSFORMERS

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

DS1 Diode-based transient-free capacitor switch

UFES Active protection for switchgear

Generators TEM. for small hydroelectric power stations. Electric Machines

Transcription:

Dry-Type, Air-Core Shunt Reactors

Introduction Shunt Reactors Trench is a supplier of specialized electrical products and a recognized world leader in the design and manufacture of dry type air core reactors for all utility and industrial applications. Trench air core reactors range from small kvar units for applications such as capacitor bank inrush limiting or distribution system short circuit current reduction, to large power reactors for a number of applications, such as shunt reactors that may be over 100 Mvar per coil. Main advantages of air-core, dry-type shunt reactors versus oil immersed types no environmental concern, no oil collection system required no fire hazard, no fire deluge system essentially no efforts and ongoing costs for maintenance less civil work, lower weight less efforts for transport and handling simplicity of insulation to ground (self healing) simple protection scheme no risk of bushing failures no excessive magnetizing inrush current no iron core typically lower investment cost less expenses for spare units (single phase unit only) typically shorter lead time There are two general types of construction used for shunt reactors. These are referred to as dry type and oil immersed. The oil immersed construction typically consists of a winding and an iron core which are together housed in a steel tank that is filled with insulating oil. The dry type solution, on the other hand, consists only of the winding itself and support insulators. There is no iron core or steel tank. The insulation to ground is provided simply by the air space around the reactor winding and the support insulators. The basic dry type shunt reactor configuration is one of single-phase units arranged with adequate clearance between phases, connected in wye, with either a solidlygrounded or ungrounded neutral. If required, the neutral of shunt reactors connected to transmission lines may be grounded through a reactor. The dimensions of the winding depend on several factors. As a matter of course, dimensions and weight will increase with the reactor s power (Mvar) rating. To meet requirements for transportation and installation, the upper limits for outline dimensions of a single reactor unit are in the range of 4.5 meters (14.5 feet) in both, height and diameter. These dimensions translate into a maximum unit power rating per phase of approximately 100 Mvar at 50 Hz (based on a single coil per phase). Higher ratings are possible using multiple coils per phase. In addition to the basic Mvar rating, other factors such as low loss or voltage requirements may also govern the design and dimensions of the reactor. The winding length of air core shunt reactors is selected to meet the voltage stress imposed by the system voltage to which the reactors are connected. Shunt reactors which are approximately 4 m tall may be connected to system voltages up to 110 kv, when configured in wye. For higher voltages, two or more coils per phase may be put in series to keep the winding voltage stresses within acceptable limits. Dry type shunt reactors do not have an iron core or iron shield. Therefore, the magnetic field is not constrained and will occupy the space around the reactor. Although the magnetic field reduces in strength with increased distance from the reactor, the presence of this field, particularly for high power reactors, needs to be taken into consideration for possible effects on metallic components (grounding grids, beam structures, concrete rebar etc.) in the vicinity of the reactor. 2

Application of Shunt Reactors As the name implies, shunt reactors are connected in a parallel (shunt) configuration to the power system to compensate for the capacitive reactive power of transmission and distribution systems and thereby to keep the operating voltages within admissible levels. Two main applications of shunt reactors can be identified: a) reactors that are required permanently in service for stability reasons (especially on long transmission lines), or b) that are needed for voltage control in a meshed system and are switched in only during light load conditions, when there is an excess of capacitive reactive power. Depending on several factors shunt reactors may be connected (1) either to the tertiary winding of a power transformer, or (2) directly to the station busbar, or (3) to transmission line terminations (3), as shown in Fig. 1. Tertiary connected shunt reactors Depending on the customer s requirements the reactive power rating of shunt reactors connected to the tertiary winding of a power transformer may vary from a few Mvar up to approximately 100 Mvar per phase. Because of their cost benefits, distribution class reactors in general and tertiary connected shunt reactors in particular, are usually of dry type design. Since the connection voltage at the tertiary is 34.5 kv or less, the voltage rating of the shunt reactor is usually not a controlling factor in the selection of the winding length. As a result the reactor may be designed with an optimum shape for minimum conductor length and thus for minimum cost. Such designs usually constitute the most cost effective solution for reactive power compensation. Fig. 2 shows a distribution class shunt reactor bank - 20 kv, 45 Mvar 3-phase, 50 Hz. (3) (3) (2) (1) Fig. 1: Shunt reactor application in power systems Fig. 2: 20 kv, 45 Mvar 3-phase tertiary shunt reactor 3

Shunt reactors connected to the high voltage bus or to a high voltage line The majority of shunt reactors which are connected directly to the high voltage bus or transmission line are of oil-filled type. However, a number of shunt reactors of dry type design have already been applied at voltages up to 345 kv and the demand is growing. One factor driving this demand increase is the integration of renewable generation such as wind parks to the grid. The connecting overhead lines or cables require shunt compensation with ratings for reactive compensation in the range of some tens of Mvars. Usually such wind parks are located in environmentally sensitive areas thereby favoring dry type air core technology. For dry type shunt reactors applied at sub-transmission or transmission voltages the steady state voltage drop along the surface of the reactor is a decisive design parameter. As mentioned earlier, reactor windings which are approximately 4 m tall may be connected to system voltages up to 110 kv when connected in wye. For systems with voltage levels above, two single units, stacked one above the other and connected in series are required. Fig. 3 shows two 132 kv, 20 Mvar 3-phase, 60 Hz direct connected shunt reactor banks. Each phase consists of two stacked sub-coils, each being about 4 m tall. As shown in the figure, if required, the reactors can be elevated off the ground using support pedestals, so that live parts are not accessible to station personnel. For higher system voltages more than two coils must be connected in series. In principle, by connecting several coils in series, dry type shunt reactors may be applied at any system voltage. Fig. 4 shows a shunt reactor bank for 345 kv, 20 Mvar 3-phase, 60 Hz, consisting of two series connected reactor stacks, mounted side by side, resulting in a total of four series connected coils per phase. Fig. 3: 132 kv, 20 Mvar 3-phase shunt reactor (2 banks) Fig. 4: 345 kv, 20 Mvar 3-phase shunt reactor 4

Wye connected shunt reactors with the neutral grounded through a neutral reactor The majority of faults on transmission lines are singlephase-to-ground faults caused by flashovers of the air insulation. Clearing of such faults is achieved by making use of the dielectric recovery of the air. For this purpose the affected phase of the line is temporarily isolated by opening the circuit breaker at both line ends and reclosing the breakers after a certain dead time. This operation is termed single-phase auto-reclosing (SPAR). Long EHV transmission lines are usually operated with shunt reactors permanently connected to the lines at their terminal stations, even when the lines are switched-off. Successful SPAR on such compensated lines is hampered by a phenomenon called secondary arcing. Instead of the extinction of the (primary) arc, the arc is further maintained due to capacitive and inductive coupling with the two healthy phases. A successful auto-reclosing is achieved only if this secondary arc extinguishes during the dead time when the breakers are open. For mitigation of secondary arcing it is a well proven practice to increase the zero sequence impedance of the shunt reactor by providing an additional single-phase reactor between the reactor s neutral and ground. During normal operation, the neutral reactor is practically unloaded. In case of a SPAR operation, for less than one or two seconds the reactor is loaded by typically 15 to 25 % of the system voltage, depending on the parameters of the line to which the shunt reactor is connected. The short-time power rating of the neutral reactor is only a few percent of the shunt reactor s continuous power rating. Due to the advantages of dry type over oil type reactors, practically all neutral reactors are dry type, for both oil immersed and dry type shunt reactors. wye-connected shunt reactor with directly grounded neutral X 0 / X 1 1 Fig. 5: Air core dry type neutral grounding reactor Switching of shunt reactors wye-connected shunt reactor with neutral grounded through a reactor X 0 / X 1 > 1 Switching shunt reactors is one of the most severe duties for a circuit breaker. As a consequence, when applying shunt reactors, whether they be dry type or oil immersed, tertiary type or direct connected, it is extremely important to pay particular attention to the switching device which is selected and ensure it is capable of handling the task to which it is being applied. Guidance can be found in IEEE Std. C37.015-2009: IEEE Guide for the Application of Shunt Reactor Switching. X 1 : positive-sequence reactance of the shunt reactor X 0 : zero-sequence reactance of the shunt reactor (including the neutral reactor) 5

Main data of Dry-Type, Air-Core Shunt Reactors Placement of Phase Reactors In line In triangle Table 1: Conceptual data of wye connected air-core, dry-type shunt reactors for 50 Hz systems U (kv) 10 20 33 69 110 Mvar (3-phase) X-50 Hz (ohm) L (mh) I (A) D H1 H2 H3 C 20 5,0 15,9 1155 3100 1100 4200 5200 1600 1900 125 50 2,0 6,4 2887 3300 1300 4400 5400 3200 3500 210 60 1,7 5,3 3465 3400 1450 4550 5500 3500 3800 235 20 20,0 63,7 578 3150 1350 4450 5400 1700 2000 110 50 8,0 25,5 1444 3350 1400 4500 5500 2900 3200 185 100 4,0 12,8 2887 3500 1900 5000 5800 5000 5600 295 20 54,5 173,3 350 2900 2050 5150 5200 2100 2400 110 50 21,8 69,4 875 3100 2100 5200 5600 3200 3500 180 100 10,9 34,7 1750 3200 2300 5500 5700 5100 5700 275 20 238,0 757,8 168 2900 2950 6050 6800 5500 2700 3000 95 50 95,3 303,1 419 3000 3000 6100 6850 5700 5000 5600 165 100 47,7 151,6 837 3400 3100 6200 6950 6300 5600 6200 220 20 605,0 1926,0 105 3100 3600 6700 7450 6200 2900 3200 85 40 302,5 963,0 210 3200 3650 6750 7500 6400 4200 4600 140 60 201,7 642,0 315 3250 3700 6800 7550 6500 6000 6600 170 M1 (kg) M2 (kg) Q 75 C U: rated system voltage (kv) Mvar: reactive power (Mvar) of a bank of three single phase reactors, at rated voltage X-50 Hz: reactance per phase (ohm) I: rated phase current (Amps); the reactors are designed to carry continuously 105 % of rated current without exceeding the temperature class limit Q: quality factor (X/R) of the shunt reactor, at 75 C; the numbers given in the table refer to standard reactor designs for minimum investment cost; reactors with higher Q-factors are feasible, if required. D, H1, H2, H3: reactor dimensions, see sketch C: minimum distance between phase reactors mounted side-by-side, based on a coupling coefficient between reactors of less than 1 % M1: mass per phase reactor, without support elements M2: mass per phase reactor, including support elements 6

Appendix Design Details of Trench Dry-Type, Air-Core Technology The sketch below illustrates the design concept of a Trench dry-type, air-core reactor. 1. winding 2. winding conductor 3. spider 4. terminal 5. duct stick 6. base insulator 7. mounting bracket A dry type air core reactor consists of a cylindrical winding (1) made of one or several concentric layers of film/glass tape insulated aluminum conductor (2). All layers are electrically connected in parallel by welding their top and bottom ends to metallic cross arms, commonly referred to as spiders (3). Each spider carries a terminal (4) for electrical connection of the reactor. The individual layers are configured such that radial voltage stress is virtually nil and the remaining axial voltage stress results in surface stress values that are less than those on porcelain insulators and turn-to-turn steady state operating voltages that are well below the level at which partial discharges can occur. All layers are radially spaced by several glass fiber sticks (5) which form air ducts necessary for the cooling of the winding. Cooling is provided by natural convection of ambient air, which enters at the bottom end of the winding and exits at its top end. The winding is impregnated by epoxy resin resulting (after curing) in a mechanically strong and compact unit. The reactors are mounted on several base insulators (6) and according mounting brackets (7). 7

Trench Factories Trench Austria GmbH Paschinger Strasse 49 Postfach 13 A-4060 Linz-Leonding Austria Phone: +43-732-6793-0 Fax: +43-732-671341 Trench Brasil Ltda Via Expressa de Contagem, 2685 Contagem, Minas Gerais CEP 32370-485 Brazil Phone: +55-31-3391-5959 Fax: +55-31-3391-1828 Trench China MWB (Shanghai) Co., Ltd. No. 3658, Jiancheng Road Minhang, Shanghai P. R. China 200245 Phone: +86-21-54720088 Fax: +86-21-54723118 Trench France S.A. 16, Rue du Général Cassagnou B.P. 70 F-68 302 St. Louis, Cedex France Phone : +33-3-89-70-2323 Fax : +33-3-89-67-2663 Trench Germany GmbH Nürnberger Strasse 199 D-96050 Bamberg Germany Phone: +49-951-1803-0 Fax: +49-951-1803-224 Trench High Voltage Products Ltd., Shenyang No. 2 Zhengliang Er. Road Jing Shen Xi San Street Dao Yi Economic Development Zone Shenyang 110136 P. R. China Phone: +86-24-89722688 Fax: +86-24-289737200 Trench Italia S.r.l. Strada Curagnata, 37 IT-17014 Bragno Cairo, Montenotte (SV) Italy Phone; +39-019-5161-111 Fax: +39-019-5161-401 Trench Limited Coil Products Division 71 Maybrook Drive Scarborough, Ontario Canada M1V 4B6 Phone: +1-416-298-8108 Fax: +1-416-298-2209 Trench Limited Instrument Transformer Division 1865 Clements Road Pickering, Ontario Canada L1W 3R8 Phone: +1-416-751-8570 Fax: +1-416-751-6952 Trench Limited Power Line Carrier Division 330 Finchdene Square Scarborough, Ontario Canada M1X 1A5 Phone: +1-416-847-5400 Fax: +1-416-291-5581 The Trench Group is your partner of choice for electrical power transmission and distribution solutions today and for the development of your new technology solutions of tomorrow.