OPTIMIZATION OF EARTHING SYSTEM IN INDUSTRIAL PLANT



Similar documents
EARTHING SYSTEM CALCULATION

GroundRod AC Substation Earthing Tutorial

DESIGN OF EARTHING SYSTEM FOR HV/EHV AC SUBSTATION

TABLE OF CONTENT

Substation Grounding Study Specification

12 Appendix 12 Earth Electrodes And Earth Electrode

Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria

Coupling Effect in Substation Ground Measurements

Earth Ground Resistance

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Earthing Guidance Notes

ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES

Fault location on power cables. Fault location on power cables

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

Electrical Safety Tester Verification

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

How Much Voltage Drop Is Acceptable?

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

Lightning Protection Introduction

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Calculation of the Current Transformer Accuracy Limit Factor Application Note

Powerformer chosen for Swedish combined heat and power plant

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Dielectric Withstand Testing in a Production Environment

Section B: Electricity

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

FEASIBILITY OF ELECTRICAL SEPARATION OF PROXIMATE GROUNDING SYSTEMS AS A FUNCTION OF SOIL STRUCTURE

Grounding & Bonding Why it is done And How to Install Properly

Electrical safety requirements in DC distribution systems

Video Camera Installation Guide

Best Methods for Safe Hipot Testing

TECHNICAL DESCRIPTION OF THE DISTRIBUTION SUBSTATION REMOTE MONITORING SYSTEM

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

INTERNATIONAL STANDARD

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

Residual Current Circuit Breaker

Are you aware. Outline

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

Electrical Grounding. Appendix C

The following table shows approximate percentage wise the

Customer Installation Safety Plan. March 2015

Strength and Durability for Life CORROSION CONTROL. The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

GROUNDING AND BONDING ELECTRICAL SYSTEMS

Engineering innovation

Voltage Detection and Indication by Electric Field Measurement

A Practical Guide to Dielectric Testing

SES Training & Certification Programs Welcome to the SES Grounding, EMI and Lightning Academy

Parallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected

Elementary circuits. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

BASIC NEC CODE RULES AND DESIGN PRACTICE

DET3 Contractor Series 3-Terminal Earth/Ground Resistance Testers

Planar versus conventional transformer

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

The Electrical Properties of Materials: Resistivity

A.V.R. R250. Installation and maintenance R250 0V E+ E- VOLT STAB FREQ. & L.A.M. CONFIG. 50Hz. 47.5Hz. 57Hz LAM 1 13% 2 25% OFF LAM OFF 9

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

Experiment NO.3 Series and parallel connection

Seven function digital multimeter

Insulation Resistance Testing of Low Voltage Cables in the Field

The electrical energy produced at the gen

CT Application Guide for the 489 Generator Management Relay

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

SOIL RESISTIVITY MEASUREMENTS

Chapter 9. Bonding and Grounding

A practical guide to earth resistance testing

Linear DC Motors Magnetic Flux Permanent Bar Magnets

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

Estimation of electrical losses in Network Rail Electrification Systems

Hyperlinks are Inactive

Network Standard Advice No. 1420C 9/6/2011

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

Ground Resistance Clamp-On Tester

DET3 Contractor Series

Electrical Resistance Resistance (R)

I = V/r P = VI. I = P/V = 100 W / 6 V = amps. What would happen if you use a 12-volt battery and a 12-volt light bulb to get 100 watts of power?

Neutral Wire Facts and Mythology. White Paper #21

Owner s Manual & Safety Instructions

Consultants Handbook

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

DET3 and 4 Contractor Series Earth/Ground Resistance Testers

THE LIGHTNING PROTECTION INTERNATIONAL STANDARD

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Rule Fast Track Analysis for National Life Insurance Co.

Complete tests for CO 2 and H 2 Link observations of acid reactions to species

Fundamentals of Power

Lab 3 - DC Circuits and Ohm s Law

Radial Distribution Test Feeders

VOLTAGE REGULATOR AND PARALLEL OPERATION

Study on Differential Protection of Transmission Line Using Wireless Communication

DEHNconcept Planning of lightning protection systems.

STUDY MATERIAL FOR CLASS Physics- CURRENT ELECTRICITY. The flow of electric charges in a particular direction constitutes electric current.

Complete Solar Photovoltaics Steven Magee. Health and Safety

WIRE AND CABLE ENGINEERING GUIDE

AORC Technical meeting 2014

Ground Resistance Clamp On Tester

Transcription:

OPTIMIZATION OF EARTHING SYSTEM IN INDUSTRIAL PLANT 1 SUSHMA PATTED, 2 SANGAMESH GOUDAPPANAVAR 1 M. tech student, IEEE member, 2 Associate Professor, IEEE member, PG-Power and energy system, Department of Electrical and Electronics Basaveshwara Engineering College (Autonomous) Bagalkot, India E-mail: 1 sushmapatted042@gmail.com, 2 sangmesh024@gmail.com Abstract - As technology is growing rapidly, grounding or earthing has become an essential part of everyday electricity and one cannot think any electrical installation without proper earthing system but still common tendency is that, it is so simple driven a rod down the earth or install a earth electrode or plate and connect body of the equipment or neutral of the transformer or generator & forget it., Several people lose their lives every year due to this simple belief and face frequently accidents in work area. Electricity has given lot of benefit to society but proper and safer earthing remained as a deadly element. Hence earthing system in the Indian distribution sector is defective which is replaced by earthing mat in industries and substations. Accidents can be avoided up to some extent if design engineer adopt different techniques for safe design there are number of methods available but final aim is high degree of perfection with optimize design. Designing a proper earthing system distributed station of industry is quite complicated. Many parameters affect its design. In order for a earthing design to be safe, it needs to provide a way to carry the electric currents into the ground under both normal and faulted conditions. Also, it must provide assurance that a person in the vicinity would not be endangered. A large number of precious lives could be saved in India if we adopt an earthing system that is testable, observable and controllable. In this project, in 220 KV receiving station of, 33KV/11KV side earthing portion of substation design will be explored. In order to properly plan and design the earthing, calculations of the following will be done: maximum fault current, ground resistance, grid current, safe touch and step voltages, ground potential rise, as well as expected touch and step voltage levels. The calculations are analysed with MATLAB programming. Keywords - Designing Earth Mat, Safety, Step Voltage, Touch Voltage. I. INTRODUCTION Over the years, humans have made some truly remarkable discoveries, one of which has been the importance of grounding electrical systems. Electricity has provided countless benefits to people, but its network still remains one of the most deadly elements in human society, and unless there is an appropriate grounding provided to the electrical systems, there is a rather large risk to human lives. In the era of automation and machine dependence that we are in today GROUNDING or EARTHING assumes special signifince in terms of human and equipment safety in industries. Electrical accidents are frequently reported in various substations and industries in our Nation. And the reason behind the accidents can be summarized as: Leakage of current through deterioted service lines. Breaking of conductors or earth wires. Leakage of current through poles. Not obeys of safety rules and safety tools and Equipments. Improper method of construction and bad workmanship. Overconfidence of the staff. Lack of supervision during work done by Unqualified labour. Natural Cause. To overcome from such accidents, design engineer adopt different safety precaution and latest techniques for safer design, maintenance, testing and measurements. II. PROBLEM STATEMENT Improper grounding system of industrial plant is leading to unsafe for human and equipment. Hence optimization of grounding system in the industrial plant can be achieved by designing proper earth mat system of substation i.e. 33/11 KV substation of plant, In order to design proper earthing system, it needs to provide a. Low impedance path for electric current both under normal and faulted condition. b. To provide safer limits for voltage gradients. Step and touch voltages. III. MOST AFFECTED PARAMETERS FOR DESIGN OF EARTHING SYSTEM ARE a. Magnitude and duration of fault current. b. Soil and surface resistivity at the industrial plant site (soil structure and soil Model) c. Property and cross-section of material used for earth mat conductor.(conductor size) 7

d. Earthing mat geometry (Area covered by Earth mat). e. Permissible touch and step potentials. IV. OBJECTIVES 1. To provide safety or protection to grounding facility to human and equipments from danger of electric shock during fault or normal condition. 2. To provide safer design for earthing (mat) system in industrial plant, the permissible touch and step voltages of plant grid should be greater than actual step and touch voltages. 3. To get the plant ground resistance substation less than 5Ω for achieving safer earthing design. Which will lead to optimize design of earthing system. V. EARTHING MAT DESIGN METHADOLOGY Optimization Of Earthing System In Industrial Plant Steps for grounding design calculation: The design process of a substation grounding system requires many steps. The following steps are for the design of the ground grid: Step 1: The property map and general location plan of the substation should provide good estimates of the area to be grounded. A soil resistivity test will determine the soil resistivity profile and the soil model needed. Step 2: The conductor size is determined. The fault current 3I0 should be the maximum expected future fault current that will be conducted by any conductor in the grounding system, and the time, tc, should reflect the maximum possible clearing time (including backup). Step 3: The tolerable touch and step voltages are [to be] determined. The choice of time, ts, is based on the judgment of the design engineer. Step 4: The preliminary design should include a conductor loop surrounding the entire grounded area, plus adequate cross conductors to provide convenient access for equipment grounds, etc. The initial estimates of conductor spacing and ground rod locations should be based on the current, IG, and the area being grounded. Step 5: Estimates of the preliminary resistance of the grounding system in uniform soil can be determined. For the final design, more accurate estimates of the resistance may be desired. Computer analysis based on modeling the components of the grounding system in detail can compute the resistance with a high degree of accuracy, assuming the soil model is chosen correctly. Step 6: The current, IG, is determined. To prevent overdesign of the grounding system, only that portion of the total fault current, 3I0, that flows through the grid to remote earth should be used in designing the grid. The current, IG, should, however, reflect the worst fault type and location, the decrement factor, and any future system expansion. Step 7: If the GPR of the preliminary design is below the tolerable touch voltage, no further analysis is necessary. Only additional conductor required to provide access to equipment grounds is necessary. Step 8: The calculation of the mesh and step voltages for the grid as designed can be done by the approximate analysis techniques for uniform soil, or by the more accurate computer analysis techniques. Fig.1:Design procedure block diagram Step 9: If the computed mesh voltage is below the tolerable touch voltage, the design may be complete (see Step 10). If the computed mesh voltage is greater 8

than the tolerable touch voltage, the preliminary design should be revised (see Step 11). Step 10: If both the computed touch and step voltages are below the tolerable voltages, the design needs only the refinements required to provide access to equipment grounds. If not, the preliminary design must be revised (see Step 11). Step 11: If either the step or touch tolerable limits are exceeded, revision of the grid design is required. These revisions may include smaller conductor spacing, additional ground rods, etc Optimization Of Earthing System In Industrial Plant Step 12: After satisfying the step and touch voltage requirements, additional grid and ground rods may be required. The additional grid conductors may be required if the grid design does not include conductors near equipment to be grounded. Additional ground rods may be required at the base of surge arresters, transformer neutrals, etc. The final design should also be reviewed to eliminate hazards due to transferred potential and hazards associated with special areas of concern. The block diagram in Fig.1 illustrates the procedure to design the ground grid. Earth Mat is preferable to substations because of space saving on the ground level due to substantial reduction of earth pits which leads to ease of coordination. Earth Mat minimizes the danger of high step or touch voltages in critical operating areas or places that are frequently used by people.. Hence conventional pipe and plate earth pits are replced by earth mat. 33KV/11KV SUBSTATION OF PLANT EARTHING DESIGN CALCULATION: As per designing steps: Area and soil resistivity: As per initial design assessment the area for grounding assume as square 20m 20m grid with no ground rods area A becomes 400 m2 shown in Fig.2 average normal resistivity ρ of 40Ω-m is based on soil resistivity s measurement by wenner s four pin method. Fig.2:earthing mat design without rods ρs- Crushed Rock Resistivity (Wet) in ohm meters Cs - Surface Layer De-rating Factor OR Reduction Factor Grid resistance for Initial design : Maximum grid current IG and GPR(Ground Potential Rise): Mesh voltage E m : Conduct size: The 11KV Bus fault value 5798.69A Should be used to size the grounding conductor. the required cross sectional area of conductor in circular mils is 9 The mesh voltage is greater than that of tolerable touch voltage (i.e. 718.9 versus 701.8 ).The grid design must be modified. The preliminary design will be modified by including 20 ground rods, each 7.5 m (24.6 ft) long, around the perimeter of the grid. As shown in Fig.3

Optimization Of Earthing System In Industrial Plant Table8. Grounding parameters (after modification). Fig.3:Earthing mat design with rods After modification L T = 440 + 20 ( 7. 5) = 590 m, The revised GPR is (9159.8)(0.9) = 8329.2 V, which is still much greater than 701.8 V. Mesh voltage and Step voltages Es: Table9. Results for grounding without rods K S - Geometrical Spacing Factor to Determine Step Voltage Now the calculated mesh voltage is lower than the tolerable touch voltage (650.316V versus 701.8 V), The computedes is well below the tolerable step voltage.that is, 991.65 V is much less than 2333.02 V. Modification of design is not necessary now. Detailed design.a safer design has been obtained. Manual constructions will continue the detail design. Table10. Results for grounding with rods VI. RESULTS Table7. Grounding parameters Table11. Specifications 10

Optimization Of Earthing System In Industrial Plant less than tolerable step and touch voltages. Soil resistivity and earth resistance has been tested and achieved as less than 1Ω for 33KV/11KV grid and small substations,other locations of plant as 1 Ω -5 Ω.This earth resistance values are considered as best values for the plant which provides human and equipment safety. Manual calculation results of earth mat design has been analysed with MATLAB programming results which are more satisfactory results. REFERENCES CONCLUSION Conventional pipe and plate earthing pits are replaced by earth mat where earth mat is preferred for substation earthing of plant because of space saving on ground level. Modification of industrial plant earthing mat design steps and hand calculations account for optimization of earthing system where we have achieved actual step and touch voltages are [1]. "IEEE 80-2000 IEEE Guide for Safety in AC Substation Grounding." [2]. Lim, S.C.; Gomes, C.; Nourirad, G.; Kadir, M.Z.A.A. "Significance of localized soil resistivity in designing a grounding system", 2014 IEEE 8th International Power Engineering and Optimization Conference (PEOCO),, on page(s): 324 329 [3]. Mohammad Ali Adelian, Improvement of Substation Earthing April 2014 (IJEAT) International Journal of Engineering and Advanced Technology Volume-3, Issue-4. [4]. M.H.Shwedi, Umar M.Johar, T. R. SHELTAMI Toward safe grounding to Industrial Plants Saudi Arebia case study 2009 20th International conference on electricity distribution paper 0022.Goren, [5]. Turan Electric Power Distribution System engineeringi. CRC Press. 2008. 11