REGULATOR TROUBLESHOOTING: A PRACTICAL GUIDE By Keith D. Webb, P.E.

Similar documents
Principles of Direct-Operated Regulators

COUNTERBALANCE VALVES

Select the Right Relief Valve - Part 1 Saeid Rahimi

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

Frequently Asked Questions

Fundamental Principles of Rotary Displacement Meters

SIMPLIFIED VALVE CIRCUIT GUIDE

PULSATION REDUCTION BY ACOUSTIC FILTERS FOR METERING APPLICATIONS. Robert J. McKee Ray G. Durke

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Boiler Preparation, Start-Up and Shutdown

Why and How we Use Capacity Control

REGULATING VALVE APPLICATIONS

Application of the Orifice Meter for Accurate Gas Flow Measurement page 1. Application of the Orifice Meter for Accurate Gas Flow Measurement.

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

PRESSURE REDUCING CONTROL VALVE

Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001

TECHNICAL DATA. Dry 122a. November 12, 2013

Industrial Steam System Process Control Schemes

Vacuum Control. Vacuum Applications. Vacuum Regulators. Vacuum Breakers (Relief Valves) Vacuum Control Devices. Vacuum Terminology

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids

Pressure Relief and Regulating Valves

FUNDAMENTALS OF GAS TURBINE METERS John Gorham Sensus Metering Systems 805 Liberty Blvd. DuBois, PA 15801

Type 99 Pressure Reducing Regulator

Turbo Tech 101 ( Basic )

1805 Series Relief Valves

Signature and ISX CM870 Fuel System

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

Centrifugal Fans and Pumps are sized to meet the maximum

TYPE E Main Valve Sizes 3 /8 through 12

CHAPTER II. This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192.

Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.

Chapter 3.5: Fans and Blowers

Contents. LWN edition:

Steam System Best Practices Condensate System Piping

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

MODEL INSTALLATION INSTRUCTIONS

SIMPLIFIED VALVE CIRCUIT GUIDE

Model RV-1 Pressure Relief Valve 2 to 8 Inch (DN50 to DN200), 250 psi (17,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Hydraulic Trouble Shooting

Type 92S Pilot-Operated Steam Regulator

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS

Types 66R and 66RR Low-Pressure Relief Valves

SELECTION, APPLICATION & MAINTENANCE

PC1131 Electric Air Compressor

TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007

Commercial & Industrial Propane Regulators and Meters

Type HSR Pressure Reducing Regulator for Residential, Commercial or Industrial Applications

Schematic Symbols Chart (Design Hydraulic and Pneumatic circits)

SELECTING PRESSURE TRANSMITTERS TO IMPROVE CENTRIFUGAL COMPRESSOR SAFETY & EFFICIENCY

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS

Type 99 Pressure Reducing Regulator

PC1130 Electric Air Compressor

LPM-06 CONVERSION KIT

PRESSURE REGULATOR SERIES R 4100 R 2100 R 5100 VIRTUAL CATALOGUE FAIL TO OPEN REGULATOR BALANCED VALVE HIGH FLOW COEFFICIENT

C. starting positive displacement pumps with the discharge valve closed.

Pump ED 101. Positive Displacement Pumps. Part I Reciprocating Pumps

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

Example. Fluid Power. Circuits

MAKING MODERN LIVING POSSIBLE. Thermostatic valve AVTA. Technical brochure

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

PRESSURE REDUCER AND RELIEF VALVES WITH METALLIC BELLOW FOR WATER STEAM

Mechanical Engineering Technician- Plant Technician

Triple Service Valve Assembly

AABC Specifications for Testing and Balancing HVAC Systems

Quiz On Information Learned From Chapter 1

Your safety and the safety of others are very important.

OHIO MEDICAL CORPORATION. Medical Gas Panel. Installation and Maintenance Manual

V47 Series Temperature Actuated Modulating Water Valves

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

The Versatile Differential Pressure Transmitter. By David Gunn Honeywell Process Solutions

Unit 24: Applications of Pneumatics and Hydraulics

Research on the Air Conditioning Water Heater System

Flow Measurement Options for Pipeline and Open Channel Flow

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

APPENDIX A CONTROL VALVE TESTING PROCEDURES AND EQUATIONS FOR LIQUID FLOWS

SELECTION, APPLICATION AND MAINTENANCE

Experiment # 3: Pipe Flow

WARNING: IMPROPER SERVICING AND START-UP OF THIS EQUIPMENT MAY CREATE A POTENTIAL HAZARD TO EQUIPMENT AND TO OPERATORS OR PERSONS IN THE BUILDING.

Chapter 7 Hydraulic System Troubleshooting

Water valves REFRIGERATION AND AIR CONDITIONING. Fitters notes

PERPLEXING VARIABLE FREQUENCY DRIVE VIBRATION PROBLEMS. Brian Howes 1

HOT WATER SYSTEMS CONTENTS

FLUID FLOW Introduction General Description

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

OBSERVING BOILER SAFETY RULES

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Sizing, Selection, and Installation of Pressure-relieving Devices in Refineries

NFPA31FuelOilPiping 1 Revised

Installation, Maintenance, & Repair Series 4000B/LF4000B

World-Class Oil Sampling It is Possible

BERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features

Model 43AP Pneumatic Controller, Style B

1 DESCRIPTION OF THE APPLIANCE

Fire Hydrant Troubleshooting

Thermostatic valve Type AVTA

Float and Thermostatic Traps Series H, C and X

Transcription:

REGULATOR TROUBLESHOOTING: A PRACTICAL GUIDE By Keith D. Webb, P.E. This paper is intended to establish some solutions for common field problems associated with gas pressure regulators. It addresses existing field installations as well as the design of new installations. Due to the complex nature of regulator instability, some emphasis is placed in this area; however consideration is given to all problem types. In order to maintain focus on day-to-day regulator problem solving, the theoretic and mathematical constructs associated with pressure regulators are avoided here. SECTION 1: NOMENCLATURE AND DEFINITIONS Pressure regulators are feedback control devices that use mechanical components to actuate a valve and manipulate flow to the downstream. Commonly used service regulators are known as Proportional (P) control devices because they have no automatic method for maintaining the output variable (outlet pressure) such as Integral (reset) or Derivative (rate) control once other variables change. As such, pressure regulators are subject to instability given certain conditions. Pressure regulators are designed to be inherently stable, however, certain field installation conditions may induce instability in the regulator. Over the years many terms have been used to describe the characteristics exhibited by an unstable pressure regulator. Table 1 lists some of the common terms for regulator instability: Table 1 Terms and Definitions Term Pulsation Hunting Buzzing, Chattering, Vibrating Pumping, Panting, Chugging, Surging Meaning A general term referring to a cyclical variation in outlet pressure of the regulator The regulator outlet pressure increases and decreases with no regular frequency A high frequency pulsation of the outlet pressure of the regulator, usually not detectable by a bourdon tube pressure gage or manometer A low frequency pulsation of the outlet pressure of the regulator that can easily be seen on a bourdon tube pressure gage or manometer SECTION 2: INSTALLATION VARIABLES AFFECTING REGULATOR SELECTION It is important to note again that pressure regulators are stable by design. However, in cases where a regulator appears unstable, it is actually the entire system that is unstable. The system refers to the entire installation including: 1) upstream and downstream piping and valving 2) upstream or downstream mechanical devices such as meters or compressors 3) the on/off cycle time(s) of downstream gas equipment 4) other pressure regulators affecting the inlet or outlet pressure of the subject pressure regulator 5) size and length of vent piping extending from the regulator vent

Bear in mind that the regulator, while it appears to be the problem, is merely responding to the system in which it is installed. Through proper regulator selection and installation design, many instability situations may be avoided. 1. THE RATE OF CHANGE OF THE LOAD The choice of a regulator is largely dictated by the type of load that it is intended to serve. Specifically, the speed of response of the regulator relative to changing loads is very important and the correct regulator choice may often help to avoid future customer complaints due to equipment pressure problems. Each regulator type will respond differently to the same change in load. The Figure 1 depicts various regulator response characteristics: Figure 1 Rule of Thumb: Regulator Response Characteristics Slowest Response Pressure Unloading (flexible element or boot) Regulator Type Pilot-Operated Pressure-Loaded (two-path regulator) Fastest Response Spring-Loaded (self-operated) Spring-Loaded regulators react more quickly than other regulator types because their sensing element (the diaphragm) is directly coupled to the main valve. Unfortunately, over a full range of flow conditions spring-loaded regulators do not maintain a constant outlet pressure as well as the other designs. Pilot-Operated regulators are somewhat fast-acting regulators since the pilot diaphragm and the main diaphragm (thus the two-path term) are both subject to the downstream pressure. However, there is more mechanical lag associated with this design due to the necessary response of the pilot. Pressure-Loaded regulators are slightly slower in response compared to a Pilot-Operated design. This is due to the fact that while the main diaphragm is sensing the downstream pressure, the pilot is sensing the loading pressure in the upper diaphragm case of the main valve. The result is that the loading pressure must change in order to make the pilot react. Pressure-Unloading regulators are characteristically slow reacting because they require a series of steps in order to change the position of the main valve. When the load changes, the pilot must react in order to change the loading pressure. The mass of gas in the loading chamber must then change by bleeding out through the pilot or in through the upstream fixed restriction. The relative sizes of the pilot orifice and the fixed restriction will dictate the speed of response of the regulator. If a regulator is routinely subjected to large sudden load changes, it must be capable of reacting quickly enough to avoid downstream pressure problems. For example, let s assume that a regulator is to serve a total load of 10,000 scfh. If the load is comprised of five (5) forced-air furnaces (see Figure 2), the probability that they will all come on or off at the exact same time is low. In this case the regulator need

not be so fast acting. Conversely, if the load is comprised of a single 10,000 scfh boiler (see Figure 3), then the load change will be sudden and the regulator must respond accordingly. If an appropriate regulator is not selected, the result will be a sudden outlet pressure decay when the load comes on, or a sudden outlet pressure rise when the load shuts off. 2. VOLUME BETWEEN THE REGULATOR OUTLET AND THE GAS APPLIANCE The volume between the regulator and the load acts as a mechanical capacitor which stores gas and, therefore, can minimize or maximize the changes in delivery pressure that the gas appliance receives. Rule of thumb: A small volume of pipe between the regulator and the appliance (see Figure 2) will dictate a fast acting regulator such as a spring loaded regulator A large volume of pipe between the regulator and the appliance (see Figure 3) will allow the use of a slower acting regulator such as a Pressure Unloading regulator Load 1 Load 2 Load 3 Load Load 4 Load 5 Figure 1 Diverse Load Figure 2 - Non-diverse Load 3. LOAD DIVERSITY AND TURN-DOWN RATIO Load diversity refers to the probability that all connected gas-fired equipment being served by a given regulator will be operating at the same time. If there are a large number of space-heating gas appliances being served by a regulator such as in Figure 1, the probability they will all be operating at the same time is low and the load is said to be diverse. Therefore, a regulator with capacity to meet approximately 80% of the connected load may be chosen. On the other hand, if the load is a single gas appliance as in Figure 2, it is said to be non-diverse and the regulator must be sized to meet 100% of the connected load.

Turn-Down Ratio is defined as: MaximumLoad TurnDown = MinimumLoad In general, the higher the Turn-Down Ratio, the more likely instability will occur at the minimum load. Rule of thumb: A regulator should be sized to meet the maximum load requirements with minimal excess capacity.

SECTION 3: SYMPTOMS AND SOLUTIONS 1) Orifice is undersized Outlet pressure decays when load increases 2) Restriction between regulator and load 3) Loading ring is missing or not positioned properly 1) Check maximum and minimum load to insure orifice is sized appropriately. 2) Install gage at downstream of regulator and at gas appliance. If pressure difference is significant at high loads, then a restriction (such as a partially closed valve) exists or piping is too small 3) Remove diaphragm case. Insure that loading ring is installed properly (consult manufacturer s documentation) 1) Orifice is oversized Outlet Pressure Pulsation 2) Control line is too small 3) Vent line pipe may be causing instability 4) Rotary meter up-stream may be causing fluctuation in inlet pressure 5) Spring is too light 6) Control line tap is too close to an upstream flow disturbance (valve, elbow, etc) 1) Check maximum and minimum load to insure orifice is sized appropriately 2) Control line should be no smaller than the connection (boss) size on the regulator 3) Vent line should increase one nominal pipe diameter every ten feet 4) Increase distance or pipe size between rotary meter outlet and regulator inlet 5) Replace adjustment spring with heavier spring that will deliver the same outlet pressure (consult factory) 6) Control line tap should be no less than 7-10 pipe diameters from nearest flow disturbance Regulator won t lock-up High lock-up Regulator is relieving gas out vent 1) Debris between valve seat and orifice 2) Valve seat or orifice are damaged 1) Film such as grease or oil on valve seat 1) Debris between valve seat and orifice 1) Remove diaphragm case from valve body; inspect valve seat and orifice for debris; remove debris 2) Inspect orifice and valve seat for damage; replace orifice or valve seat as necessary 1) Remove diaphragm case from valve body; inspect valve seat and orifice for film; clean valve seat and replace 1) Remove diaphragm case from valve body; inspect valve seat

2) Orifice is not torqued to manufacturer s specification and orifice for debris or damage; replace orifice or valve seat as necessary 2) Obtain torque specifications from manufacturer s literature and use torque wrench to correct torque 3) Pipe dope on orifice has dried and is allowing leaks across threads 3) Inspect dope on threads; add dope to threads and retest Regulator is relieving gas when load shuts off (if rotary meter is downstream of regulator) 1) Inertia of rotary meter impellers allows gas to continue to flow after the load has shut off (i.e. meter becomes a compressor). Pressure rises to point of relief of regulator. 1) Increase volume (distance) between regulator and meter 2) Use a static control line regulator with the control line tapped downstream of the rotary meter