Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Similar documents
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.43

Three-phase monitoring relay CM-PFE

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Analog signal converters CC-E I/I Current / current isolators

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF19 and EF45

Thermistor motor protection

Three-phase monitoring relays Product group picture

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Grid feeding monitoring according to VDE-AR-N 4105 and BDEW CM-UFD.M31

Pluggable interface relays CR-P Pcb relays

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

EMR measuring and monitoring relays

RM4TG20 three-phase network control relay RM4-T - range V

48 SERIES Relay interface modules 10 A

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

Catalog. Modular DIN rail components Installation contactors

Type: DILM32 10(24V50HZ) Article No.:

Type: DILM50(230V50HZ,240V60HZ) Article No.:

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Type: DILM9 10(24VDC) Article No.:

Manual motor starter MS116

Signal converters Index

PHOENIX CONTACT Features

38 Series - Relay interface modules A

38 Series - Relay interface modules A

Technical catalogue. Modular DIN rail components Installation contactors

Relés e Contatores de Estado Sólido SIRIUS

49 Series - Relay interface modules A. Features

Power Supplies 3. SDN-P DIN Rail Series

Signal converters Index

Safety technique. Emergency stop module BO 5988 safemaster

Bimetallic Overload Relay Specifications

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA

80 Series - Modular timers 16 A. Features

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

MasterINTERFACE 39 Series - Relay interface modules

ZS25 Screw Clamp Terminal Blocks Feed-through

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

ZS10 Screw Clamp Terminal Block

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2CDG1101xxR0011

mecotron Safety relay ESTOP-2 For emergency stop monitoring

Digital input modules

System pro M compact Miniature Circuit Breaker S 200/S 200 M

MasterINTERFACE 39 Series - Relay interface modules

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Fixed - Over/Under voltage limits, ( ) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

R.C.C.B. s two-pole LEXIC

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Voltage Regulator SPAU 341 C. Product Guide

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/2

Redundancy Module QUINT-DIODE/40

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

80 Series - Modular timers 16 A. Features

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

15 Series - Electronic step relay and dimmer. Features SERIE

Technicaldata General

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/2x15DC/1

PHOENIX CONTACT - 01/2007

Thermal-Magnetic Circuit Breaker M1-..

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

Preset Counter signo 721

MINI MCR-SL-R-UI(-SP)

Contact expansion modules

STRATO LED Drivers 70W, Single output

5SV Residual Current Protective Devices

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

ABB i-bus KNX SA/S Switch Actuators Product Manual

Transcription:

Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of phase loss. All devices are available with two different terminal versions. You can choose between the proven screw connection technology (double-chamber cage connecting terminals) and the completely tool-free Easy Connect Technology (push-in terminals). 2CDC 251 061 V0011 Characteristics Monitoring of DC and AC voltages (3-600 V) TRMS measuring principle One device includes 4 measuring ranges Over- or undervoltage monitoring configurable Hysteresis adjustable (3-30 %) Tripping delay T V adjustable (0 s; 0.1-30 s) 3 control supply voltage versions Precise adjustment by front-face operating controls Screw connection technology or Easy Connect Technology available Housing material for highest fire protection classification UL 94 V-0 Tool-free mounting on DIN rail as well as demounting 2 c/o (SPDT) contacts 22.5 mm (0.89 in) width 3 LEDs for status indication Order data Voltage monitoring relays Type Rated control supply voltage Connection technology Measuring ranges Order code CM-ESS.2P 24-240 V AC/DC Push-in terminals 3-30 V, 6-60 V, 30-300 V, 60-600 V 1SVR740830R0400 110-130 V AC 1SVR740831R0400 220-240 V AC 1SVR740831R1400 CM-ESS.2S 24-240 V AC/DC Screw type terminals 3-30 V, 6-60 V, 30-300 V, 60-600 V 1SVR730830R0400 Accessories Approvals / Marks A C R E L / a b Classifcations: EN 50155, IEC 60571, NF F 16-101/102, EN 45545-2 EN 50155, IEC 60571 110-130 V AC 1SVR730831R0400 220-240 V AC 1SVR730831R1400 Type Description Order code ADP.01 Adapter for screw mounting 1SVR430029R0100 MAR.12 Marker label for devices with DIP switches 1SVR730006R0000 COV.11 Sealable transparent cover 1SVR730005R0100 Temp. class Voltage supply S1 S2 C1 C2 Vibration and shock acc to IEC/EN 61373 T3 - Cat 1, Class B no Coated pcb NF F 16-101/102 EN 45545-2 Flammability Opticity and toxicity of index smoke index Risk level achieved I2 F2 HL3

Connection technology Maintenance free Easy Connect Technology with push-in terminals Type designation CM-xxS.yyP Approved screw connection technology with double-chamber cage connecting terminals Type designation CM-xxS.yyS 2CDC 253 026 F0011 2CDC 253 025 F0011 Push-in terminals Tool-free connection of rigid and flexible wires with wire end ferrule Easy connection of flexible wires without wire end ferrule by opening the terminals No retightening necessary One operation lever for opening both connecting terminals For triggering the lever and disconnecting of wires you can use the same tool (Screwdriver according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in)) Constant spring force on terminal point independent of the applied wire type, wire size or ambient conditions (e. g. vibrations or temperature changes) Opening for testing the electrical contacting Gas-tight Double-chamber cage connecting terminals Terminal spaces for different wire sizes One screw for opening and closing of both cages Pozidrive screws for pan- or crosshead screwdrivers according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in) Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage connecting terminals have the same connection geometry as well as terminal position. 2 - Voltage monitoring relays CM-ESS.2 Data sheet

Functions Operating controls 1 Adjustment of the hysteresis 2 Adjustment of the threshold value 3 Indication of operational states U/T: LED green control supply voltage 1 2 R: LED yellow relay status U: LED red over- / undervoltage 4 Adjustment of the measuring range 2CDC 251 052 V0011 3 4 5 5 Adjustment of the tripping delay T V 6 DIP switches (see DIP switch functions) 6 Application The voltage monitoring relays CM-ESS.2 are designed for use in single-phase AC and/or DC systems for over- or undervoltage monitoring as well as detection of phase loss. The devices are available with different supply voltage ranges, provide an adjustable tripping delay and work according to the open-circuit principle. Operating mode The CM-ESS.2 have 2 c/o (SPDT) contacts and include 4 measuring ranges: 3-30 V, 6-60 V, 30-300 V and 60-600 V. The units are adjusted with front-face operating controls. The selection of over- d or undervoltage monitoring c is made with a DIP switch. Potentiometers, with direct reading scale, allow the adjustment of the threshold value U, the hysteresis % and the tripping delay T V. The hysteresis % is adjustable within a range of 3 to 30 % of the threshold value and the tripping delay T V over a range of instantaneous to a 30 s delay. Timing is displayed by a flashing green LED labelled U/T. Data sheet Voltage monitoring relays CM-ESS.2-3

Function diagrams Overvoltage monitoring d The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing green LED. If the measured value exceeds the adjusted threshold value, the tripping delay T V starts and the red LED (overvoltage) glows. Timing of T V is displayed by the flashing W green LED. When T V is complete and the measured value still exceeds the threshold value minus the adjusted hysteresis, the output relays energize and the yellow LED (relay energized) glows. If the measured value drops below the threshold value minus the adjusted hysteresis, the output relays de-energize and the red and yellow LEDs turn off. If control supply voltage is interrupted, the green LED turns off. A1-A2 Threshold Hysteresis Measured value T V < T V 11-14 (15-18) 11-12 (15-16) 21-24 (25-28) 21-22 (25-26) green LED red LED yellow LED 2CDC 252 210 F0205 Undervoltage monitoring c The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing green LED. If the measured value decreases below the adjusted threshold value, the tripping delay T V starts and the red LED (undervoltage) flashes W. Timing of T V is displayed by the flashing W green LED. When T V is complete and the measured value is still below the threshold value plus the adjusted hysteresis, the output relays energize and the yellow LED (relay energized) glows. If the measured value exceeds the threshold value plus the adjusted hysteresis, the output relay de-energizes and the red and yellow LEDs turn off. A1-A2 Measured value Hysteresis Threshold T V < T V 11-14 (15-18) 11-12 (15-16) 21-24 (25-28) 21-22 (25-26) green LED red LED yellow LED 2CDC 252 211 F0205 4 - Voltage monitoring relays CM-ESS.2 Data sheet

Electrical connection A1 11 15 21 25 B B 11 15 21 25 A1-A2 B-C Rated control supply voltage Measuring ranges: 3-30 V, 6-60 V, 30-300 V, 60-600 V 11 15-12 16 /14 18 Output contacts - open- or closed-circuit principle 21 25-22 26 /24 28 C A1 A2 12 16 14 18 22 26 24 28 14 18 12 16 C 24 28 22 26 A2 2CDC 252 207 F0005 Connection diagram DIP switches 2CDC 252 275 F0005 1 ON Undervoltage monitoring OFF Overvoltage monitoring OFF = Default Data sheet Voltage monitoring relays CM-ESS.2-5

Technical data Data at T a = 25 C and rated values, unless otherwise indicated Input circuits Supply circuit A1-A2 Rated control supply voltage U s 110-130 V AC 220-240 V AC 24-240 V AC/DC Rated control supply voltage U s tolerance -15...+10 % Rated frequency 50/60 Hz 50/60 Hz or DC Typical current / power consumption 24 V DC - - 30 ma / 0.75 W 115 V AC 24 ma / 2.6 VA - 17 ma / 1.9 VA 230 V AC - 12 ma / 2.6 VA 11 ma / 2.6 VA Power failure buffering time 20 ms Transient overvoltage protection varistors Measuring circuit B-C Monitoring function over- or undervoltage monitoring configurable Measuring method TRMS measuring principle Measuring inputs terminal connection B-C measuring range 3-30 V, 6-60 V, 30-300 V, 60-600 V input resistance 600 kω pulse overload capacity t < 1 s 800 V continuous capacity 660 V Threshold value adjustable within the indicated measuring range Tolerance of the adjusted threshold value 10 % of the range end value Hysteresis related to the threshold value 3-30 % adjustable Measuring signal frequency range DC / 15 Hz - 2 khz Rated measuring signal frequency range DC / 50-60 Hz Maximum response time AC 80 ms DC 120 ms Accuracy within the rated control supply voltage tolerance ΔU 0.5 % Accuracy within the temperature range ΔU 0.06 % / C Transient overvoltage protection varistors Timing circuit Time delay T V 0 s or 0.1-30 s adjustable Repeat accuracy (constant parameters) ±0.07 % of full scale Tolerance of the adjusted time delay - Accuracy within the rated control supply voltage tolerance Δt 0.5 % Accuracy within the temperature range Δt 0.06 % / C User interface Indication of operational states Control supply voltage U/T: green LED V: control supply voltage applied W: tripping delay T V active Measured value U: red LED V: overvoltage W: undervoltage Relay status R: yellow LED V: output relay energized 6 - Voltage monitoring relays CM-ESS.2 Data sheet

Output circuits Kind of output 11-12/14 relay, 1st c/o (SPDT) contact 21-22/24 relay, 2nd c/o (SPDT) contact Operating principle open-circuit principle (output relay energizes if the measured value exceeds d / falls below c the adjusted threshold value) Contact material AgNi Rated operational voltage U e 250 V Minimum switching voltage / Minimum switching current 24 V / 10 ma Maximum switching voltage / Maximum switching current 250 V AC / 4 A AC Rated operational current I e AC-12 (resistive) at 230 V 4 A AC-15 (inductive) at 230 V 3 A DC-12 (resistive) at 24 V 4 A DC-13 (inductive) at 24 V 2 A AC rating (UL 508) utilization category (Control Circuit Rating Code) B 300 max. rated operational voltage 300 V AC max. continuous thermal current at B 300 5 A max. making/breaking 3600/360 VA apparent power at B 300 Mechanical lifetime 30 x 10 6 switching cycles Electrical lifetime AC-12, 230 V, 4 A 0.1 x 10 6 switching cycles Maximum fuse rating to achieve n/c contact 10 A fast-acting short-circuit protection n/o contact 10 A fast-acting General data MTBF on request Duty time 100 % Dimensions (W x H x D) product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in) Weight packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in) Screw connection technology Easy Connect Technology (Push-in) Net weight Version 24-240 V AC/DC 0.153 kg (0.337 lb) 0.142 kg (0.313 lb) Version 110-130 V AC 0.181 kg (0.399 lb) 0.170 kg (0.375 lb) Version 220-240 V AC 0.181 kg (0.399 lb) 0.170 kg (0.375 lb) Gross weight Version 24-240 V AC/DC 0.176 kg (0.388 lb) 0.164 kg (0.361 lb) Version 110-130 V AC 0.204 kg (0.450 lb) 0.193 kg (0.425 lb) Version 220-240 V AC 0.176 kg (0.388 lb) 0.165 kg (0.364 lb) Mounting DIN rail (IEC/EN 60715), Mounting position Material of housing UL 94 V-0 Degree of protection housing IP50 terminals snap-on mounting without any tool any IP20 Data sheet Voltage monitoring relays CM-ESS.2-7

Electrical connection Screw connection technology Easy Connect Technology (Push-in) Connecting capacity fine strand with(out) wire end ferrule 1 x 0.5-2.5 mm² (1 x 18-14 AWG) 2 x 0.5-1.5 mm² (2 x 18-16 AWG) 2 x 0.5-1.5 mm² (2 x 18-16 AWG) rigid 1 x 0.5-4 mm² (1 x 20-12 AWG) 2 x 0.5-2.5 mm² (2 x 20-14 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) Stripping length 8 mm (0.32 in) Tightening torque 0.6-0.8 Nm (7.08 lb.in) - Environmental data Ambient temperature ranges operation -25...+60 C (-13...+140 F) storage -40...+85 C (-40...+185 F) Damp heat, cyclic (IEC/EN 60068-2-30) 55 C, 6 cycles Vibration, sinusoidal Class 2 Shock Class 2 Isolation data Rated insulation voltage U i supply / measuring circuit / output 600 V output 1 / output 2 250 V Rated impulse withstand voltage U imp supply / measuring circuit / output 6 kv 1.2/50 μs output 1 / output 2 4 kv 1.2/50 μs Pollution degree 3 Overvoltage category III Standards / Directives Standards IEC/EN 60947-5-1, IEC/EN 60255-27, EN 50178 Low Voltage Directive 2014/35/EU EMC Directive 2014/30/EU RoHS Directive 2011/65/EU Railway application standards EN 50155, IEC 60571 temperature class T3 Railway applications Electronic equipment used on rolling stock supply voltage category S1, S2, C1 IEC/EN 61373 Category 1, Class B Railway applications Rolling stock equipment Shock and vibration tests EN 45545-2 Railway applications Fire protection on railway vehicles part 2: HL3 Requirements for fire behavior of materials and components ISO 4589-2 LOI 32.3 % NF X-70-100-1 C.I.T. (T12) 0.45 EN ISO 5659-2 Ds max (T10.03) 104 NF F 16-101: Rolling stock. Fire behaviour. Materials choosing I2 / F2 NF F 16-102: Railway rolling stock. Fire behaviour. Materials choosing, application for electric equipment DIN 5510-2 Preventive fire protection in railway vehicles. Part 2: Fire behaviour and fire fullfilled side effects of materials and parts 8 - Voltage monitoring relays CM-ESS.2 Data sheet

Electromagnetic compatibility Interference immunity to IEC/EN 61000-6-2 electrostatic discharge IEC/EN 61000-4-2 Level 3 radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3 electrical fast transient / burst IEC/EN 61000-4-4 Level 3 surge IEC/EN 61000-4-5 Level 3 conducted disturbances, induced by IEC/EN 61000-4-6 Level 3 radio-frequency fields Interference emission IEC/EN 61000-6-3 high-frequency radiated IEC/CISPR 22, EN 55022 Class B high-frequency conducted IEC/CISPR 22, EN 55022 Class B Technical diagrams Load limit curves V V 300 200 100 80 60 50 40 30 20 10 0.1 0.2 0.5 resistive load 1 2 4 6 10 I A 2CDC 252 194 F0205 V V 300 200 100 80 60 50 40 30 20 10 0.1 0.2 0.5 resistive load 1 2 4 6 10 I A 2CDC 252 193 F0205 AC load (resistive) DC load (resistive) F 1.0 0.9 0.8 0.7 0.6 Switching cycles 250 V resistive load 0.5 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ Derating factor F for inductive AC load 2CDC 252 192 F0205 Switching current [A] 2CDC 252 148 F0206 Contact lifetime Data sheet Voltage monitoring relays CM-ESS.2-9

Dimensions in mm and inches 113.4 4.47 105.9 4.17 22.5 0.89 85.6 3.37 103.7 4.08 2CDC 252 009 F0011 Accessories in mm and inches 22.5 0.89 8 0.32 4.8 0.19 6.5 0.256 62.5 2.461 60 2.362 70 2.756 10 11.5 0.394 0.453 20 0.787 2CDC 252 008 F0010 22.2 0.874 4T22 19.9 0.783 7.85 0.309 2CDC 252 020 F0011 68 2.68 front to back 110.5 4.31 2CDC 252 010 F0011 ADP.01 Adapter for screw mounting MAR.12 Marker label for devices with DIP switches COV.11 Sealable transparent cover Further documentation Document title Document type Document number Electronic products and relays Technical catalogue 2CDC 110 004 C02xx CM-ESS.1, CM-ESS.2 Instruction manual 1SVC 730 590 M0000 You can find the documentation on the internet at www.abb.com/lowvoltage -> Automation, control and protection -> Electronic relays and controls -> Measuring and monitoring relays. CAD system files You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com -> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls. 10 - Voltage monitoring relays CM-ESS.2 Data sheet

Contact us ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Document number 2CDC 112 172 D0201 Rev D (07/2016) Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2016 ABB All rights reserved