SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches



Similar documents
ASCO SERIES 185 Power Transfer Switches

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

Continuous Power... Continuous Protection

GTEC transfer switch open transition

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Transfer Equipment Controls

How To Operate A Gec Transfer Switch Open Transition Amp Power Supply

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Diesel Engine Driven Generators Page 1 of 6

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance/Non-Service Entrance

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SECTION VARIABLE FREQUENCY DRIVES

Eaton Automatic Transfer Switches

Low Voltage Transformers Sealed, General Purpose, Dry Type

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

RM4TG20 three-phase network control relay RM4-T - range V

Series TS Amp. Automatic Transfer Switches

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

8146/5 Series Breaker Panelboards

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

SECTION LOW VOLTAGE LIGHTING CONTROLS

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Transfer switch BTPC open, closed or delayed transition

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

MasterINTERFACE 39 Series - Relay interface modules

NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Zenith Controls ISO R-1000C 5/99

MCC Ratings. Voltage Rating

Bypass transfer switch mechanisms

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

CTS SERIES AUTOMATIC TRANSFER SWITCH


SECTION STANDBY GENERATOR TESTING AND COMMISSIONING

MasterINTERFACE 39 Series - Relay interface modules

Digital input modules

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

SURGE PROTECTIVE DEVICES

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

Fundamentals of Power

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

38 Series - Relay interface modules A

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

ATC-300 Automatic Transfer Switch Controller

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

How To Test A Power Switch On A Power Supply

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

ELECTRICAL: AUTOMATIC TRANSFER SWITCHES

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

SECTION SWITCHBOARDS

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Owner's Manual. Automatic Transfer Switch. This manual should remain with the unit.

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page Phase Simplex Page 8-13

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

CalMod Design-Build Electrification Services

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Bulletin 150 SMC Flex Smart Motor Controller Specifications

ELECTRICAL INSPECTION BULLETIN (Effective )

Voltage Regulator SPAU 341 C. Product Guide

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Generator DoCKInG StatIonS

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Procurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier

Circuit Breakers. Next Generation of Protection Capabilities

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Safety technique. Emergency stop module BO 5988 safemaster

MTS Power Products MIAMI FL ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual

Three-phase monitoring relay CM-PFE

GLOLAB Two Wire Stepper Motor Positioner

38 Series - Relay interface modules A

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Mini Power-Zone Unit Substation

HM-W536 Install Guide

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

SUGGESTED SPECIFICATION For Medium Voltage Automatic Transfer Switches

Transcription:

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand and close-on current ratings as shown on the plans. Each automatic transfer shall consist of an inherently double throw power transfer switch unit and a microprocessor controller, interconnected to provide complete automatic operation. All transfer switches and controllers shall be the product of the same manufacturer. B. Furnish an enclosure for the ATS that is suitable for service entry. It shall provide all of the proper disconnecting, protection, grounding and bonding required by the NEC and UL 1008 for service entrance equipment. 1.02 Acceptable Manufacturers Service Entrance Automatic transfer switches shall be ASCO Series 185SE. Any alternate shall be submitted in writing at least 10 days prior to bid. Each alternate bid must list any deviations from the specification. 1.03 Codes and Standards The automatic transfer switches and controls shall conform to the requirements of: A. UL 1008 - Standard for Automatic Transfer Switches B. CSA 22.2 No. 178 C. NFPA 70 - National Electrical Code D. International Standards Organization ISO 9001: 2000 E. UL 508 Industrial Control Equipment F. IEC 947-6-1 Automatic Transfer Switches G. NEMA Standard ICS 10 Standard for Automatic Transfer Switches 01-2009 1 Publication 3208

PART 2 PRODUCTS 2.01 Mechanically Held Transfer Switch A. The transfer switch unit shall be electrically operated and mechanically held. The electrical operator shall be a momentarily energized, single-solenoid mechanism. Main operators which include overcurrent disconnect devices, or linear motors shall not be acceptable. The switch shall be mechanically interlocked to ensure only two possible positions, normal or emergency. B. The switch shall be positively locked and unaffected by momentary outages so that contact pressure is maintained at a constant value and temperature rise at the contacts is minimized for maximum reliability and operating life. C. All main contacts shall be silver alloy composition. D. Inspection of all contacts shall be possible from the front of the switch without disassembly of operating linkages and without disconnection of power conductors. A manual operating handle shall be provided for maintenance purposes. The handle shall permit the operator to manually stop the contacts at any point throughout their entire travel to inspect and service the contacts when required. E. Designs utilizing components of molded-case circuit breakers, contactors, or parts thereof which are not intended for continuous duty, repetitive switching or transfer between two active power sources are not acceptable. F. Where neutral conductors are to be solidly connected, a neutral terminal plate with fully-rated AL-CU pressure connectors shall be provided. 2.02 Microprocessor Controller with Membrane Interface Panel A. The controller shall direct the operation of the transfer switch. The controller's sensing and logic shall be controlled by a built-in microprocessor for maximum reliability and minimum maintenance. The controller shall be connected to the transfer switch by an interconnecting wiring harness. The harness shall include a keyed disconnect plug to enable the controller to be disconnected from the transfer switch for routine maintenance. B. The controller shall be self contained and be mounted separate from the transfer switch unit for safety and ease of maintenance. Sensing and control logic shall be provided on a printed circuit board. C. The controller shall meet or exceed the requirements for Electromagnetic Compatibility (EMC) as follows: 1. IEC 1000-4-2 (1995) Electrostatic Discharge Immunity 2. IEC 1000-4-3 (1995) Radiated EM Field Immunity 3. IEC 1000-4-4 (1995) Electrical Fast Transient Immunity 4. IEC 1000-4-5 (1995) Surge Immunity 5. IEC 1000-4-6 (1995) Conducted RF Disturbance Immunity 6. EN 55011 Radiated and Conducted Emissions 7. EMC Directive 93/68/ECC CISPR Class A 01-2009 2 Publication xxxx

2.03 Enclosure A. The ATS shall be furnished in a NEMA type 1 enclosure with a hinged door unless otherwise shown on the plans. B. Type 3R outdoor enclosures shall include a hinged door and shall be fabricated of an aluminum alloy to resist corrosion. C. Provisions for mounting an optional strip heater with thermostat for Type 3R enclosure requirements shall be provided. D. Controller shall include a flush-mounted display with LED indicators for switch position, source availability, and for engine exerciser. It shall also include test and generator exerciser/bypass membrane-type switches. E. The complete assembly shall be degreased and thoroughly cleaned through a fivestage aqueous process. The finish shall be light gray RAL 7035 textured polyester powder coat suitable for indoor and outdoor environments. F. The connection between the normal disconnecting device and the ATS shall be made with the appropriate size cable. G. Provide main bonding jumper to connect both the neutral and ground conductors. The main bonding jumper shall be installed in the disconnected position. H. Control wiring shall be rated for 600 Volts, UL 1015. Wires shall be placed in wire duct or harnessed, and shall be supported to prevent sagging or breakage from weight or vibration. All wiring to hinged doors shall be run through door terminal blocks or connection plugs. 2.04 Disconnecting and Overcurrent Protection Device A. The normal connection shall be provided with a thermal magnetic, 2 pole, rated molded case circuit breaker with current ratings as shown on the plans. It shall have a thermal magnetic trip unit. 01-2009 3 Publication 3208

PART 3 OPERATION 3.01 Voltage and Frequency Sensing A. The operating frequency shall be set at 60Hz nominal, with the option to change operating frequency to 50Hz. B. The voltage of each phase of the normal source shall be monitored, with pickup (source acceptable) set at 198 volts, and dropout (source unacceptable) set at 187 volts. The option to change pickup to 209 volts, and to change dropout to 198, 176, or 154 volts, shall be available. C. The frequency of the alternate source shall be monitored with pickup (source acceptable) set at 57 Hz, and dropout (source unacceptable) set at 51 Hz. For 50Hz nominal operating frequency, the pickup and dropout will be set to 48Hz and 43 Hz, respectively. 3.02 Time Delays A. A time delay shall be provided to ignore preferred (utility) source outages, adjustable to 1 or 3 second time periods. B. A time delay shall be provided to ignore alternate (generator) source outages fixed at 4 seconds. C. A time delay shall be provided to transfer to alternate (generator) source fixed at 10 seconds. D. A time delay shall be provided to retransfer to preferred (utility) source fixed at 5 minutes. E. A time delay shall be provided for generator cooldown after retransfer to utility, adjustable to 2 or 5 minute periods. F. A generator exerciser and bypass switch shall be provided. An optional programmable generator excerciser clock shall be available. 3.03 Additional Features A. The controller shall provide one set of form C contacts to be used to signal the generator to run. These contacts shall be rated at 1 A / 30 V dc or 5 A / 30 V dc. B. A push-button type test switch shall be provided to simulate normal source failure. C. A push-button type switch shall be provided to deactivate generator exerciser period. D. Indicating lights shall be provided, one to indicate when the ATS is connected to the normal source (green), and one to indicate when the ATS is connected to the emergency source (red). Also provide indicating lights for both normal and emergency source availability. E. The option to connect communication and remote annunciation features to the transfer switch controller shall be available. 01-2009 4 Publication xxxx

PART 4 ADDITIONAL REQUIREMENTS 4.01 Withstand and Closing Ratings A. The ATS shall be rated to close on and withstand the available RMS symmetrical short circuit current at the ATS terminals with the type of overcurrent protection shown on the plans. B. WCR ATS ratings to be as follows when used with a molded case circuit breaker: 4.02 Tests and Certification ATS Size Withstand & Closing Rating MCCB W/CLF 200 225 10,000A 200,000 400 42,000A 1 200,000 1 Specific breaker rating A. The complete ATS shall be factory tested to ensure proper operation of the individual components and correct overall sequence of operation and to ensure that the operating transfer time, voltage, frequency, and time delay settings are in compliance with the specification requirements. B. Upon request, the manufacturer shall provide a notarized letter certifying compliance with all of the requirements of this specification including compliance with the above codes and standards, and withstand and closing ratings. The certification shall identify, by serial number(s), the equipment involved. No exceptions to the specifications, other than those stipulated at the time of the submittal, shall be included in the certification. C. The ATS manufacturer shall be certified to ISO 9001:2000 International Quality Standard and the manufacturer shall have third party certification verifying quality assurance in design/development, production, installation, and servicing in accordance with ISO 9001:2000. 4.03 Record Retention and Replacement Parts A. The manufacturer shall maintain records of each switch, by serial number, for a minimum of 20 years. B. For ease of maintenance and parts replacement, the ATS switch nameplate shall include a unique serial number and bill of material number for traceability purposes. 01-2009 5 Publication 3208