THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY



Similar documents
RECOMMENDATIONS FOR REPAIR OF SPRAY POLYURETHANE FOAM (SPF) ROOF SYSTEMS DUE TO HAIL AND WIND DRIVEN DAMAGE

Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces

Spray Polyurethane Foam Systems for Cold Storage Facilities Operating Between - 40 o C and + 10 o C (- 40 o F and + 50 o F )

Underwriters Laboratories Testing Information

Fire Testing of Recycled Materials for Building Applications

Meeting the Fire Code with Continuous Foam Plastic Insulation

The Renewal of Spray Polyurethane Foam and Coating Roof Systems

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: TEC-WOOD ( )

THE DOW CHEMICAL COMPANY Issued: August 1, LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN (989)

Fiberglas, Exterior Wall Thermal Insulation

Polyurethane Products

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

Built to Last. Built for Beauty. Good. Solid. Logix. TM

Fire-Rated Glass and Glazing START

Class Number May FM Approvals LLC. All rights reserved.

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

If you are a web registered user of ArlingontPermits.com you may also request an inspection at:

ICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015.

COMMERCIAL BUILDING APPLICATIONS

Wood use in Type I and II (noncombustible) construction

GreenGuard Housewrap Installation Guide

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

03/05/14 REVISOR RSI/JC RD3945

LEGACY REPORT. (800) (562) A Subsidiary of the International Code Council RETAINED ON U.S.

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

Gridstone Gypsum Ceiling Panels

EcoTouch Insulation with PureFiber Technology

INSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

Pyroguard Wired Glass

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors

Fire Life Safety ORC Review Guidelines for PPD Experimental Installations

How To Test For Premer Retardant

Foam Recycling is Viable. A Profitable Industry in the Making

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

Fire Security Systems

CHAPTER 7: Building Systems ROOFING SYSTEMS

eading Performance Solutions

Fire and Concrete Structures

FIRESTOPPING & SMOKE SEALS

HOT WORK PERMIT PROGRAM TRAINING. John Braun

Insulated Roof & Wall Panels. Product Data Sheet. Trapezoidal Insulated Roof Panels KS1000 RW

IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT

Fire Resistance of Brick Masonry

Enclosures DuraSystems Barriers, Inc. The Passive Fire Protection Specialists

09990 MOLD REMEDIATION, LEAD-BASED PAINT ABATEMENT AND ENCASEMENT OF ASBESTOS

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

Fire-Retardant-Treated (FRT) Plywood

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

Gypsum Board Systems Manual

Insulating Basements: Part 3 Basement Wall Systems

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012

Steel Panel Frame. Exterior Steel Sheeting. Optional Rigid Insulation. Optional Steel Insulation Liner

FIRE AND SMOKE PROTECTION FEATURES

Robert H. White, Research Wood Scientist, U.S. Forest Products Lab., Madison, WI, USA, Brian Kukay, Associate Professor of General

Fire Barrier Duct Wrap 15A

Technical Specification Fire Blanket Firemaster Fire Protection-Cables Tray Fire Protection Department

The Case for Cross Laminated Timber: Part 2

Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

Asbestos Management Program

Low-slope reroofing guidelines

Insulation R-Value Comparisons

Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

Continuous Insulation Using Polyiso Wall Sheathing

Double Coated Urethane Foam Tapes

Building Code Clarifications - 7. Fire Resistance

Safety Storage Cabinets

UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS

WARRANTY VINYL SIDING CERTAINTEED CORPORATION LIFETIME LIMITED

UX-30 PERFORMANCE TESTING SUMMARY REPORT Revision 0

Housing Fact Sheets. Insulation Check-Up

GigaCrete Specification PlasterMax

American National Standard For Electrical Rigid Steel Conduit (ERSC)

Tremco Fire Protection Systems Group Technical Bulletin

Approval Standard for Class 1 Fire Rating of Building Panels or Interior Finish Materials

furnishings flammability characteristics

GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER

SECTION CONSTRUCTION FACILITIES AND TEMPORARY CONTROLS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP APPLIED WOOD COATINGS SECTION: SHEATHING REPORT HOLDER:

WHITE PAPER Fire & safety performance standards

September 3, Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

ICC-ES Evaluation Report Reissued September, 2010 This report is subject to re-examination in one year.

Product Guide Specification

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

SECTION PRE-ENGINEERED BUILDING BLANKET INSULATION

Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors.

Approval Standard for Fume Exhaust Ducts or Fume and Smoke Exhaust Ducts

COMPARISON OF VARIOUS SINGLE PLY ROOF COVERS FOR FIRE RESISTANCE

SECTION ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment

cement Masonry Cement Engineered for quality and reliability, Lafarge cements for masonry deliver consistent performance. page 2 Lafarge Cement

New Cable Tie Type Classifications

HOT WORK PERMIT PROCEDURES

Transcription:

THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY Spray Polyurethane Foam Alliance Copyright 2005 To order copies of this publication, call 800-523-6154 and request SPFA Stock Number AY 126

TECHNICAL COMMITTEE MISSION STATEMENT The mission of the Technical Committee is to provide a wide range of technical service to the Spray Polyurethane Foam Industry such as, but not limited to: 1. Review existing documents and serve as a clearing house to endure the Continuity of Value of technical information published by SPFA and others concerning the products and services to the SPF industry; 2. Review, research, develop and issue documents concerning new products, systems and services and; 3. To identify, explore, develop and communicate an understanding of technical issues facing the SPF industry. COMMITTEE MEMBERS Roger Morrison, Chairman North Carolina Foam Industries Mary Bogdan Honeywell Bob Braun Dow Chemical John Courier Equipment & Coatings Technology John Hatfield Penta Engineering Group, Inc. Dan Hensley Hensley Coating Inc. Tim Leonard ERSystems David Lewis Coastal Coatings Inc. Roger Lock Mactec Engineering & Consulting Jack Moore West Roofing Systems, Inc. Bruce Schenke BASF Irene Schwechler Gaco Western, Inc. Chuck Skalski Gaco Western, Inc. Larry Smiley Poly-Tek. Robert Smith Invista John Stahl Preferred Solutions, Inc. Jay Zhang Convenience Products AD HOC MEMBERS: Laverne Dalgleish CUFCA Scott Brown BaySystems North America LLC 2

THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY POLICY STATEMENT It is the policy and recommendation of the Spray Polyurethane Foam Alliance that all interior applied spray polyurethane foams receive a thermal barrier as soon as possible after the initial application, except when specifically approved by a building code authority based on fire tests specific to the application. What Is A Thermal Barrier? A thermal barrier is a material, applied between spray polyurethane foam (SPF) and interior spaces designed to slow the temperature rise of the SPF during a fire situation, and to delay the SPF's involvement in a fire. A building code definition of an approved thermal barrier is one which is equal in fire resistance to 12.7 mm (1/2 inch) gypsum board. Such thermal barriers limit the temperature rise of the underlying SPF to not more than 121 o C (250 o F) after 15 minutes of fire exposure complying with the standard time temperature curve of ASTM E 119 (Test Methods for Fire Tests of Building Construction Materials). Thermal barriers meeting this criterion are termed a 15-minute thermal barrier or classified as having an index of 15. Under specific conditions, the ASTM E 119 fifteen-minute requirement can be waived if approved by building code authorities on the basis of full scale, diversified fire testing representing actual end uses. Many materials which are not 15-minute thermal barriers per ASTM E 119 have earned various building code acceptances for use as thermal barriers over SPF based on diversified fire testing. Such test methods include: UL 1715 Fire Test of Interior Finish Material UL 1040 Insulated Wall Construction 3

FM 4880 Building Corner Fire Test UBC 26-3 Room Fire Test Standard for Interior of Foam Plastic Systems What is an Ignition Barrier? Model building codes allow an exception to the thermal barrier requirement in attics and crawlspaces where entry is made only for the service of utilities. SPF in these spaces must be protected against ignition by 38 mm (1.5 inch) mineral fiber insulation; 6.4 mm (0.25 inch) wood structural panel, particle board, or hardboard; 9.5 mm (0.375 inch) gypsum wallboard; corrosion resistant steel have a base metal thickness of 0.4 mm (0.016 inch); or other approved material installed in such a manner that the foam plastic insulation is not exposed. [2003 IBC, Section 2603.4.1.6] Such materials are commonly called ignition barriers. Ignition barriers do not afford as high a degree of protection from fire as thermal barriers but are considered acceptable for attic and crawlspaces where entry is limited. Building code authorities may accept alternative ignition barrier materials based on full scale, diversified tests such as SwRI Test Procedure 99-02 Crawl Space Fire Test. Where Is A Thermal Barrier Needed? All model building codes require a building code approved thermal barrier on the habitable side of a structure between the interior of the structure and the polyurethane foam. SPF should not be applied to the interior of a building without an approved thermal barrier as defined by the applicable building code. A thermal barrier is not normally required for SPF applied on the exterior of the structure (i.e., roof insulation). Building codes may exclude the installation of a thermal barrier over certain applications of SPF. Review the specific code requirements on a case-by-case basis. 4

Why Do Codes Require Thermal Barriers? SPF, like most other organic materials, is combustible. SPFs are formulated with flame retardants to decrease the flame spread as measured by ASTM E 84 (Standard Test Method for Surface Burning Characteristics of Building Materials) and other tests. However, these flame spread indexes are used solely to measure and describe properties of products in response to heat and flame under controlled laboratory conditions. The numerical flame spread indexes are not intended to reflect hazards presented by SPFs or any other material under actual fire conditions. When exposed to fire sources, such as trash fires, welding arcs, cutting torches, or red-hot metal, unprotected SPF in interior situations may ignite resulting in a flash fire. The burning will be brief, forming a layer of less flammable surface char. This initial burning produces combustible gases and black smoke. In confined interiors, combustible gases can accumulate and ignite resulting in flashover, a dangerous fire situation. Under these conditions, additional foam or other combustibles can become involved in the fire giving off additional combustible gases and feeding the fire. If the heat and gases are not dissipated and the temperature of the SPF rises above approximately 379 o C (700 o F), the surface char will no longer be able to protect the SPF and the SPF will fuel the fire as it degrades under these extreme temperatures. Most SPF fires will involve other flammable materials, however, in a limited number of situations, when other flammable materials are not involved, SPF fires tend to be flash fires of relatively short duration. Codes require thermal barriers for interiors to reduce the risk of a flash fire and to extend the time at which the foam would reach its auto ignition temperature should a fire originate from other sources. (Note: These fire scenarios depend on the accumulation of combustible gases. Exterior applications of SPF, such as roof systems, where combustible gases can dissipate, are less likely to become involved in flash fires and are treated differently under the building codes.) 5

Selection of Thermal Barriers Many types of thermal barriers are available on the market today including but not limited to: 1. Gypsum wallboard 2. Spray applied cementitious materials 3. Spray applied cellulose materials 4. Portland cement plaster 5. Various proprietary materials The thermal barrier should have a currently valid building code evaluation report that lists a report number and effective dates. In some cases, a local building code official will allow the use of a thermal barrier which has been tested to the satisfaction of the official but is not yet evaluated by a code evaluation service. Generally accepted diversified fire tests for building assemblies include: * UL 1715 Fire Test of Interior Finish Material * UL 1040 Insulated Wall Construction * FM 4880 Building Corner Fire Test * U.B.C. Standard 26-3 Room Fire Test Standard for Interior of Foam Plastic Systems. Caution: Just because a material is advertised as a thermal barrier or and ignition barrier does not mean that it has been approved by a code agency or a local code official. Ask for test data and code body approvals, listings, or other written indications of acceptability under the code to be sure that the product selected offers the fire protection that the code demands. 6

This brochure was developed to aid specifiers in choosing a thermal barrier over spray-applied polyurethane foam systems. The information provided herein, based on current customs and practices of the trade, is offered in good faith and believed to be true, but is made WITHOUT WARRANTY, EITHER EXPRESS OR IMPLIED, AS TO FITNESS, MERCHANTABILITY, OR ANY OTHER MATTER, SPI DISCLAIMS ALL LIABILITY FOR ANY LOSS OR DAMAGE ARISING OUT OF ITS USE. Individual manufacturers and contractors should be consulted for specific information. SPI does not endorse the proprietary products or processes of any individual manufacturer, or the services of any individual contractor. Spray Polyurethane Foam Alliance 4400 Fair Lakes Court, Suite 105 Fairfax, VA 22033 800-523-6154 7