COMPARISON OF VARIOUS SINGLE PLY ROOF COVERS FOR FIRE RESISTANCE
|
|
|
- Cathleen Flynn
- 10 years ago
- Views:
Transcription
1 COMPARISON OF VARIOUS SINGLE PLY ROOF COVERS FOR FIRE RESISTANCE Joe Schwetz Director, Technical Services, Canton, MA August, 2012 As Civilization Harnesses Fire, New Risks Threaten Lives and Property The use of controlled fire in domestic applications began approximately 500,000 years ago. This ability to use fire allowed humans to move from the warm tropical areas of the world to the colder climates of Europe, Asia and the western hemisphere. Fire provided a means to warm the living areas, cook food, and provide light. Fire was instrumental in the development of everyday tools and goods from metals to pottery, which allowed for quicker advancement of mankind. As civilization moved forward, people started to develop densely populated cities, mostly for security reasons, often with individual buildings being connected or sharing common walls. Typically these structures had beams made from wood, and the roofs were thatch or similar organic material. Chimneys were often generally short with large openings that allowed burning embers to travel to adjacent roofs, igniting the roofing and other materials. As one can imagine, with the lack of equipment or firefighting methods, fires in ancient cities were catastrophic, often resulting in complete destruction of the city. History has a record of major fires devastating cities from ancient Rome to Western Europe during the medieval times. In 1666, the Great Fire of London burned for five days destroying approximately 2/3 of the city and leaving over 200,000 people homeless. From this event, the first fire departments and fire insurance companies were founded. The fire led to the first recorded use of pumps to fight fires, ladders to be used for fire suppression and rescue as well as fire insurance. New building laws stopped the use of timber, required brick, stone or masonry construction, and widened the streets to limit the damage from flying burning embers. In essence, London enacted the first Fire Code for buildings. Fires were also very common in the early days of settlement in North America. In 1631 Boston banned the use of thatch roofs and wood chimneys after a serious fire; New York followed suit in After a devastating fire in 1653 where a third of the families in Boston were left homeless, the city required every house to have a ladder and a 12 foot long pole with a wet swab to extinguish burning embers on the roofs. There were additional requirements and restrictions enacted by the city but to no avail as the city was devastated at least five more times by massive fires. Throughout the 1700 s and 1800 s and into the first third of the 1900 s, massive, devastating fires continued to plague cities causing a tremendous loss of life as well as extremely costly property damage. Insurance Industry and Fire Codes The insurance industry, after massive fires and economic losses, was instrumental in the development of fire codes. One of the first fire codes that was used as a type of model code was developed by the 1
2 National Board of Fire Underwriters, later renamed the American Insurance Association. After a number of fires with large loss of life, such as the infamous Triangle Building fire, the National Fire Protection Association (NFPA) began issuing pamphlets in the early 1900 s describing the basic requirements for evacuating or exiting buildings safely. These pamphlets led to the development of the NFPA Building Exit Code, later renamed the Life Safety Code. The safety codes along with the insurance driven codes eventually became the foundation for what is currently used in the International Building Code (IBC), the model code developed by the International Code Council (ICC), which has been adopted throughout the country. The International Building Code covers in great detail fire prevention in regard to building construction and design, while the International Fire Code addresses fire issues from the operations of a completed and occupied building. While fire, safety, and building codes in general have greatly improved over the years, losses from fire are still an ongoing issue. The following is taken from the NFPA Journal Sept/Oct 2011, by Mr. Michael J. Karter, Jr.... In 2010, public fire departments responded to 1,331,500 fires in the United States, according to estimates based on data NFPA received from fire departments responding to its 2010 National Fire Experience Survey. An estimated 482,000 structure fires were reported to fire departments in The NFPA estimates that the 1,331,500 fires to which the fire service responded last year caused nearly $11.6 billion in property damage. Fires in structures resulted in $9.7 billion in property damage. Of the reported fires, the NFPA estimates there were 3,120 civilian deaths with the vast majority in residential fires. In addition to the civilian deaths, an estimated 17,700 people were injured in fires during This is approximately a 3.9% increase from 2009 and the highest total since The information noted above from the NFPA reinforces the fact that while the frequencies of fires may be declining, there is still a tremendous impact due to losses from fires. Building codes and insurance requirements have been developed and implemented with the intention of minimizing fire loss. Roof Systems and Fire One of the most vulnerable components of a building when exposed to fire is the roof. Roof systems can burn either from fires from within the building or from the top side down. Fires from within are more complex with a multitude of building systems that may influence the fire. External fires affecting the roof are generally simpler as there are fewer components within the roof system. Codes require that roofing systems are tested and classified to meet certain requirements, depending on the building use and occupancy. There have been various forms of fire codes and insurance requirements for fire protection since the colonial times. What was lacking for construction materials, specifically roofing products, was a method to test products when exposed to fire. It is believed that the first fire test for roofing products was developed by Underwriters Laboratories, Inc. (UL) in This UL test protocol standardized the evaluation of roof coverings based on their ability to withstand ignition, flame spread, and fire penetration from external fires. In 1910, a new standard developed by the NFPA was adopted which set classifications for roof covers. This standard had three tests flame exposure, burning brand, and a radiation exposure. The standard also included an investigation to determine the quality of the raw material, weathering and repairability of the roof coverings as applied to the roof system. 2
3 There were continuing adjustments and refinements to the fire test standards and reporting up to 1955 when the ASTM Standard E-108, Standard Test Methods for Fire Tests of Roof Coverings was adopted. The last major changes were made to the Standard between 1970 and 1975, mostly with regard to format and test criteria, which is the basis for the current version. ASTM E-108 Testing Class A, B, and C Fire Classifications for Roof Coverings ASTM E-108, which is essentially the same as UL 790 and NFPA 256, evaluates the relative fire characteristics of roof coverings when exposed to external fire sources. There are three classifications defined in the standard, Class A, Class B, and Class C. The Class A rating is for roof coverings that can withstand severe test exposure, afford a high degree of protection to the roof deck, will not slip, and do not generate any flying brand or embers. Class B ratings are for roof covers that can withstand moderate test exposures, affording a moderate degree of protection to the roof deck, will not slip, and do not generate any flying brand or embers. Class C ratings cover light test exposures and afford a light degree of protection to the roof deck, will not slip, and do not generate any flying brand or embers. This test standard measures the ability of the roof covering to protect or resist fire from penetrating from the top side of the test deck to the underside. The roof fire penetration tests include the burning brand test (Photo 1) and the intermittent flame exposure test (Photo 2). The standard also measures distance a flame can spread along the top surface, the spread of flame test (Photo 3, a non-penetrating test). If the intent is to test a roof covering over a combustible type roof deck, then all three tests are done. When the roof deck is noncombustible, such as concrete or steel, or if a combustible deck assembly uses a specific type of gypsum board or similar approved thermal barrier, then only the spread of flame test is conducted. The spread of flame test uses a constant flame source and a steady air movement to determine the potential for fire to spread across the surface of the roof cover. The maximum length allowed that still achieves a class A rating is six feet, class B is eight feet, and class C is thirteen feet. In all cases the fire cannot spread laterally to either edge of the test sample. Photo 1 Burning Brand Photo 2 Intermittent Flame 3
4 Photo 2 Spread of Flame Roof Covering Buildup and Deck Slope The main variables in the E-108 test method are the components of the roof covering buildup and the slope of the deck. This test method provides a means for comparing roof covering materials as tested according to the standard. There was some concern with the fire test standard as noted in the MRCA and NRCA report dated January Prior to this report, the MRCA and NRCA did a series of aging evaluations on 109 polymer modified bitumen roof systems. During the study, beginning in 1991, they realized fire resistance is an important attribute for roof covers. In 1996, the MRCA did a limited fire test program following the spread of flame method from ASTM E-108. Four of the roof systems from the study were tested, with half passing. Based on the results, the MRCA conducted additional fire tests on aged materials in 2001, again to see if aged roof systems maintained their listed fire classification or rating. In this study ten samples were taken from five different roof covering categories: coated modified bitumen, granular surfaced modified bitumen, PVC, TPO, and EPDM. All systems were believed to have been installed as classified fire rated systems. From this round of testing, five of the test decks passed the spread of flame tests; both PVC systems, one from each of the modified bitumen and one EPDM. In an effort to better understand the failure of the rated EPDM and TPO materials, the MRCA and NRCA conducted additional fire test evaluations, this time with new and aged systems using these membranes. They wanted see if the aged roof cover systems would maintain the listed fire classification as well as verifying that new roof cover systems would meet the listed ratings. This round of testing evaluated thirty-four assemblies, eight new and ten existing EPDM membranes and ten new and six aged TPO membranes. This round of testing also used four different certified testing laboratories, who were instructed to test for spread of flame. Of the thirty-four test assemblies, only thirteen passed, or met the listed classification. Of the test assemblies that passed, nearly all (12 of the 13) included a cover board. From this round of testing more questions were raised, including the reproducibility of the test method between labs and within the same laboratory, the methods for constructing the test assembles (how the edges are addressed), and how different labs interpret the results (lateral failure to just one or both sides). ASTM Committee E05 is addressing the issues regarding test method E-108, specifically with the 4
5 construction of the test decks, interpreting the results, and adding a precision and bias statement to the document. Tests EPDM, PVC, and TPO Given the results from the various fire test investigations by the MRCA and NRCA, decided to conduct its own test program to compare the fire test properties of fire retardant EPDM, PVC, and TPO membranes. We chose two of the most common substrates used with single ply roof membranes; an ASTM C 1289 Type II, Class 1 Grade 2 isocyanurate insulation board (organic black facer, 20 psi compressive strength) and glass faced gypsum board. The slope for the test program was determined after reviewing the classifications for each membrane type and substrate found in the UL Fire Directory. The highest slope for each type of membrane and board combination was charted. From this information we chose the lowest slope for the membrane and board combination. For example... With gypsum board as the substrate, the greatest slope found in UL s directory for the TPO membrane that achieves a Class A rating is 3 in 12; for PVC it is a 5 in 12 at the time of the study. Similarly, the EPDM membrane over the Dens Deck has a Class A rating of 5 in 12 for unreinforced adhered membrane, and 4 in 12 for reinforced mechanically attached membranes. Based on this information, all fire testing with the Dens Deck substrate was conducted at a slope of 3 in 12. Comparing UL Class A fire ratings with isocyanurate insulation as the substrate, the TPO membrane has a maximum slope of 0.5 inch in 12, the PVC is at a 2 in 12 and the EPDM achieves a Class A at a 0.5 inch in 12 for unreinforced adhered membranes and 0.75 inch in 12 for reinforced mechanically attached membranes. Testing the three membranes to the noted slope per substrate allows for a direct comparison between the membranes and the specific board substrate, providing comparative information on how each membrane burns. All of the membranes were wrapped over the edges and secured to the wood side rails with roofing staples. The test method followed the ASTM E-108 and UL 790 standard for spread of flame. The distance of the flame spread was recorded as well as the lateral distance every twelve inches beginning from the leading edge. The time of ignition as well as the time to reach the maximum flame spread was recorded. All testing was completed in the same day and done by the same technician at the same laboratory. 5
6 ** Lateral spread of flame both to the right and left sides, starting 18 inches from the leading edge and proceeding for 24 inches. Smoke generation was similar for all test frames. The graph below shows the comparison between the three membranes flame spread for each substrate and tested slope combination (Iso at 0.5 and DD at 3 ). The results show that the PVC membrane with a significantly lower flame spread indicating that the membrane has a much greater resistance to spread of flame than the other membranes tested at the same conditions. The time duration for the fire to reach the maximum flame spread was significantly shorter for the PVC membrane than either of the other membrane types, for both substrates. Of important note, the flame on the PVC membrane did not sustain the fire, in essence the membrane self-extinguished. The EPDM membrane burned four times as long and the TPO membrane eight times as long as the PVC membrane with the gypsum substrate. The following graph illustrates the time differences between the membranes 6
7 over each substrate. The shorter the bar on the graph the better the fire performance of the roof cover, as the system is not sustaining the fire. The burn patterns for the PVC show a very uniform triangular shape for both substrates (Photos 6 and 9). The TPO membrane has an elongated triangular shape with the gypsum substrate (Photo 5) and an irregular burn pattern for the isocyanurate (Photo 8). The EPDM membrane has a very irregular burn pattern for both substrates, including a lateral spread off the test deck, (Photo 4 with gypsum board and Photo 7 with Iso). Photo 4 FR rated EPDM over Dens Deck, very irregular flame pattern Photo 5 TPO over Dens Deck 7
8 August, 2012 Photo 6 PVC over Dens Deck Photo 7 FR rated EPDM over Iso, excessive lateral flame spread Photo 8 TPO over Iso Photo 9 PVC over Iso, side view 8
9 Figure 1 Figure 2 Figures 1 and 2 illustrate the measured patterns for the three membranes over the two substrates. The PVC has a very compact burn pattern for both substrates, especially when compared to the other membrane types. The ASTM E-108 spread of flame test, while basically a system test, does offer an opportunity to see how different roof covers burn. The isocyanurate does provide fuel to the test construction, which allows the fire to propagate as shown by the additional lateral spread of flame for all three membranes. When the roof covers are placed on the fire resistant gypsum board, little to no fuel is added to the fire. This assembly provides a good idea on how well the roof membranes resist the spread of fire. The PVC roof cover has almost 60 percent better spread of flame resistance than the other membranes. Vertical Strip Fire Test Another test method to show how different roof membranes perform when exposed to fire is a vertical strip fire test. With this test, samples of roof membrane cut at 75 mm (3 inches) wide by 170 mm (6.7 inches) long strips are fixed to a hanging device. A gas flame is placed in contact with the sample and left in place for 15 seconds, at which time the flame is removed. The test records the time for either the flame to extinguish or consume the sample. An example of this test can be seen at durability/vinyl-fire-performance/index.html. The test recorded on this web site was conducted by 9
10 Southwest Research Laboratories (SwRI) in San Antonio TX. This test shows that the PVC membrane will self-extinguish within seconds of having the gas flame removed. Both the EPDM and TPO membranes will burn until fully consumed. Similar to the spread of flame test deck with the gypsum substrate, this test shows how the different roof membranes react when ignited. PVC and Fire Resistance Real World Examples One of the strengths of a PVC roof membrane is the ability to self-extinguish and resist spreading the fire. There are documented events where the PVC roof membrane helped contain a fire and limit the amount of damage to the building, its occupants, and equipment. One example is the Ballantyne facility in Omaha, NE. The fire started at a heat stack and moved upward to the roof surface. The PVC roof membrane resisted spreading the fire, according to Mike Connolly of D.C.Taylor company, the installing roofing contractor, thus limiting damage to the exterior in the immediate vicinity of the stack, as seen in Photo 10. Photo 10 Heat stack, Ballantyne facility A PVC roof is credited for protecting a number of businesses from being destroyed following a fire in North Bay, Ontario. The fire started in the Motion Canada building and began spreading to other sections. The building owner, who acknowledged that their fire hydrants were not operative, and the fire department, who had little to no water to battle the fire, credit the PVC roof membrane with preventing the fire from spreading. In yet another example, a roof mounted lighting system at the Toyota Center, Houston TX short-circuited on a number of occasions, causing fires. The fires were never able to propagate across the surface of the PVC roof membrane, thereby limiting the damage and preventing a potentially dangerous situation from developing (see Photos 11 and 12, next page). 10
11 Photo 11 Photo 12 With the increased use of the rooftop as a platform for installing solar photovoltaic systems, there is also an increased possibility of a rooftop electrical fire. Fires that may be a result from a rooftop PV installation present unique and dangerous challenges to fire fighters due to the fact that the PV panels continue to generate electricity as long as they are exposed to sunlight, increasing the risk of rapid fire spread across the underlying roof surfaces. With their superior ability to minimize the spread of flame and to self-extinguish, PVC membranes provide important life safety benefits on roofs upon which PV arrays are to be installed. Summary Building codes including fire safety codes continue to evolve and provide additional security for building occupants. While tremendous strides have been made in reducing fires and the resultant property damage, injuries and deaths, the construction industry should work to continuously improve through better construction practices. As part of the building industry, roofing specifiers and contractors must take fire safety seriously in design and specifications. Specified roof systems should at a minimum be a tested and listed assembly with one of the certified testing agencies approved by the building code. However, they must be mindful that specifying to a minimum standard is not necessarily in the best interest of the building owner. Testing by various sources has shown that there is a significant performance difference among various roof membrane types. References Jim Arnold, (2005) Large Building Fires and Subsequent Code Changes, Article through the NFPA Michael J. Karter, Jr., Fire Loss In the United States During 2010, NFPA Journal Sept/Oct 2011 ASTM E Standard Test Methods for Fire Tests of Roof Coverings MRCA, NRCA (2006) Fire Testing of Membrane Roof Systems Southwest Research Institute (2006) Final report, Fire test evaluation in general accordance with SIA test method V280/12 (1996) Vertical burn test S. P. Graveline (2011) Sustainability of Thermoplastic Vinyl Roofing Membrane Systems, IC-Best Symposium 11
12 About the Author Joe Schwetz is the Director, Technical Services for in Canton, Massachusetts, a leading manufacturer worldwide of single ply roofing systems. He has 30 years of experience in the roofing industry and previously held managerial positions with JM and BondCote. He chairs the ASTM committee on PVC roofing and has been involved with numerous technical standards and code development industry advisory groups. 12
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
The Building Group First Tuesdays First Saint Paul s Lutheran Church 1301 North LaSalle Street, Chicago, Illinois
Wiss, Janney, Elstner Associates, Inc. 10 South LaSalle Street, Suite 2600 Chicago, Illinois 60603 312.372.0555 tel 312.372.0873 fax www.wje.com The Building Group First Tuesdays October 2, 2012 Jason
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
ISO Types 1-6: Construction Code Descriptions
ISO 1 Frame (combustible walls and/or roof) Class 1B Buildings where the exterior walls are wood or other combustible materials, including construction where the combustible materials are combined with
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
Dollars & Sense of Compliance!
CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors
LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces
center for the polyurethanes industry October 2009 Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces One of the largest growing uses of spray polyurethane foam (SPF) insulation is in
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663)
HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) Fire-Retardant-Treated Wood Framed Wall Assemblies GENERAL INFORMATION Fire-resistant construction
Fire Classification Rating Testing of Stand-Off Mounted Photovoltaic Modules and Systems
Fire Classification Rating Testing of Stand-Off Mounted Photovoltaic Modules and Systems Prepared by Larry Sherwood Solar America Board for Codes and Standards Bob Backstorm Dwayne Sloan Christopher Flueckiger
Fire Testing of Recycled Materials for Building Applications
Fire Testing of Recycled Materials for Building Applications Robert H. White Abstract To gain wide market acceptance of new building products made from recycled materials, fire testing may be necessary.
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Underwriters Laboratories Testing Information
Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum
If you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015
MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 **Disclaimer: This document is to serve as informational purposes only. This is not a code book or a final interpretation of the
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
EcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
Fire or Ignition Resistant? Building Materials & Vegetation
Fire or Ignition Resistant? Building Materials & Vegetation Steve Quarles, IBHS & Pat Durland, Stone Creek Fire, LLC 2011 Backyards & Beyond Wildland Fire Education Conference Denver, Colorado October
UL Fire Door Inspection Service. UL Fire Alarm Certification Program. A valuable but misunderstood resource for jurisdictions
2013 Issue 2 2 A Strong Foundation 3 Introducing UL Fire Door Inspection Service 6 Enhanced UL Marks Coming Your Way Soon UL Fire Alarm Certification Program A valuable but misunderstood resource for jurisdictions
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Solar America Board for Codes and Standards
Impacts on Photovoltaic Installations of Changes to the 2012 International Codes A Solar ABCs White Paper May 2011 Solar America Board for Codes and Standards www.solarabcs.org Solar America Board for
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
Wood use in Type I and II (noncombustible) construction
Wood use in Type I and II (noncombustible) construction D.G. Bueche Hoover Treated Wood Products, Thomson, Georgia, USA ABSTRACT: As with many products, the building code regulates the use of wood in construction.
THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY
THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY Spray Polyurethane Foam Alliance Copyright 2005 To order copies of this publication, call 800-523-6154 and request SPFA Stock Number AY 126 TECHNICAL
Solar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT
IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT WHAT IS THE RATIONALE BEHIND THE REQUIREMENTS FOR IGNITION RESISTANT CONSTRUCTION? The wildfires of 2003 and 2007 were the largest in California
Fire-Rated Glass and Glazing START
Fire-Rated Glass and Glazing START www.pilkington.com/fire Fire-Rated Glass and Glazing Pilkington Fire Protection Glass North America 946 Kane Street, Suite A Toledo, OH 43612 Provider Number: J200 Course
Product Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail [email protected] Product Guide
Proven roofing SyStemS
Proven Roofing Systems Above all. Roofing challenges are never over our heads At GenFlex, we live to tackle and solve the toughest challenges in roofing. The result is a full line of proven, durable roofing
National Renewable Energy Laboratory
FireRatingsofPVSystems: AGuideforStakeholders Preparedfor: NationalRenewableEnergyLaboratory Golden,Colorado Preparedby: BrooksEngineering 3949JoslinLane Vacaville,CA95688 www.brooksolar.com November2014
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations Fire Protection Review for the Fixed Target ES&H Review Committee September 2010 By James Priest PhD DRAFT Overview: When reviewing
Continuous Insulation Using Polyiso Wall Sheathing
PIMA Technical Bulletin #403 Continuous Insulation Using Polyiso Wall Sheathing What it is, what it does, and why you need it About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70%
How To Test For Premer Retardant
TEST REPORT NEBS COMPLIANCE CHOMERICS PREMIER CONDUCTIVE PLASTIC Prepared by: CHOMERICS R&D 84 DRAGON COURT WOBURN, MA 01801 Test Report Number: TR 1007 EN 0206 Chomerics Approved Signatory: This report
Meeting the Fire Code with Continuous Foam Plastic Insulation
Dow Building Solutions Meeting the Fire Code with Continuous Foam Plastic Insulation The 2012 International Building Code (IBC) specifies the fire tests that must be passed if a foam plastic material is
Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12
Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.
Enclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: [email protected]. The Passive Fire Protection Specialists
Enclosures Sturdy single and double wall fire protection construction Impact resistant Fast & easy installation Pre-manufactured and modular Available in galvanized, stainless steel & other specialty metals
Built to Last. Built for Beauty. Good. Solid. Logix. TM
Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Specifications, Product Testing and Terminology
Specifications, Product Testing and Terminology The following synopsis provides a review of various material and final product testing, which is performed on our products, as well as, many of our competitors.
Chapter 5.8.3. Fire safety 5.8.3
Chapter 5.8.3 5.8.3 TABLE OF CONTENTS INTRODUCTION.................................................................... 1 PURPOSE OF THIS SUB-CHAPTER......................................................
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
FIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
Fire-Retardant-Treated (FRT) Plywood
T e c h n i c a l n o t e Fire-Retardant-Treated (FRT) Plywood Number K320 January 2009 Introduction Codes assure fire safety by controlling such things as size and design of the structure and flame-spread
Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado
Roof Condition Report Academy International School 8550 Charity Drive Colorado Springs, Colorado FOR Mr. Robert Thompson Academy School District 20 10221 Lexington Drive Colorado Springs, Colorado July
Fire Barriers & Fire Stopping
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 [email protected] Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
HIGH-RISE BUILDING FIRES
HIGH-RISE BUILDING FIRES John R. Hall, Jr. September 2013 National Fire Protection Association Fire Analysis and Research Division HIGH-RISE BUILDING FIRES John R. Hall, Jr. September 2013 National Fire
Site Inspection Report
Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G
FIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
Landscaping with Ornamental Trees and Exterior Structure Features Using EcoSmart Fire Model
Landscaping with Ornamental Trees and Exterior Structure Features Using EcoSmart Fire Model Mark A. Dietenberger, Ph.D., USDA, FS, Forest Products Laboratory, Madison, Wisconsin, USA, [email protected]
Roof Insulation Building. Energy. Environment friendly e-library
Roof Insulation Building Codes & Energy Efficiency Environment friendly e-library Building Code Driver Buildings consumer almost 50% of all energy. Experts believe that a 30% increase in building efficiency
Fire Performance Standard
Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant
Reducing Injury and Damage Related to Electric Dryer Fires. Fire Containment Tests for the Second Edition of UL 2158
Reducing Injury and Damage Related to Electric Dryer Fires Fire Containment Tests for the Second Edition of UL 2158 Reducing Injury and Damage Related to Electric Dryer Fires: Fire Containment Tests for
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
Occupancy: Assembly (A-3) and Business -Includes offices, seminar rooms, classrooms, and café facility. Duke University Medical School
Introduction Background The Duke School of Nursing building offers a new three-story state of the art facility that has helped strengthen the quality and integrity of the School of Nursing at Duke. The
FIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
Peel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS The LOGIX wall assembly has no need for an additional vapor barrier, the solid concrete core covered with the low permeance EPS (Type II) foam
COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE
www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com
RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012
RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new
Dow Corning PROPRIETARY. Dow Corning. A Thermal Modelling Comparison of Typical Curtain Wall Systems
Dow Corning A Thermal Modelling Comparison of Typical Curtain Wall Systems Introduction Today s Aim To understand the meaning of a U value and window energy ratings Discuss the drivers for energy efficiency
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
WHITE PAPER Fire & safety performance standards
WHITE PAPER Fire & safety performance standards Terminologies describing Fire Performance Terminologies describing Fire Performance often present a challenge to understand as how they apply to a cable
Composite Panel Firewall Systems
Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
FOAMULAR LT40, 400 and 600 insulations with minimum compressive strengths of
Technical Guide FOAMULAR Extruded Polystyrene Insulation For Cold Storage Applications FOAMULAR extruded polystyrene insulation is suitable for virtually all cold storage insulating needs, including floors,
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name:
STATE OF CALIFORNIA RESIDENTIAL ALTERATIONS - RE-ROOF CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name: CALIFORNIA ENERGY COMMISSION CF-1R-ALT-01-E (Page 1 of 2) Date Prepared: A.
Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual
BR BO-01-02 Effective from June 1, 2000 Revision: March 26, 2002 Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual (Unofficial Manual) Technical Appraisal Department, Building
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
0845 0098 980 www.nicholsonsts.com
0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES
FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES P.L. Senez*, K.D. Calder, Hsing H (Isabella) Li Sereca Fire Consulting Ltd., Canada INTRODUCTION
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10
Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10 This document was developed by the Orange County Fire Chiefs Association, Orange County Fire Marshal Committee.
eading Performance Solutions
eading Solutions Manage Risk Save Time and Money Grow Business Responsive Leadership As a construction professional, you face countless challenges. Every day you are expected to finish projects efficiently
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
GreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
Limited Combustible: The New Standard for Fire Safety
Limited Combustible: The New Standard for Fire Safety Written by Daniel Kennefick Limited Combustible Product Business Manager Berk-Tek, A Nexans Company Since the advent of client server computing in
Annex of the certificate (Page 1/6) Accreditation Scope
As a Testing Laboratory Annex of the certificate (Page 1/6) Accreditation Scope Address: Küçük Çiğli Mh. 8780/1 Sk. No:5 Çiğli 35681 İZMİR / TÜRKİYE Phone : 0 232 376 24 25 Fax : 0 232 386 33 98 E-Mail