Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans



Similar documents
Centrifugal Fans and Pumps are sized to meet the maximum

Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County

Commercial & Municipal Retrofit 2015 VFD Rebate

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

Fan Applications & System Guide

Air Conditioning Clinic

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Product Data Bulletin

Chapter 4.5: Electric Motors, Variable Speed Drives

Chapter 3.5: Fans and Blowers

How To Save Energy On A Power Supply

On-Demand Ventilation Energy Saving in Industrial Applications

Electric Motor Brake Horsepower Calculations

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

Fan Basics and Selection Criteria (How to Use)

Variable Frequency Drives and Energy Savings

ENERGY AUDIT REPORT MINIMUM REQUIREMENTS

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency

Agricultural Pumping Efficiency Improvements

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

LEV Integrated with Mechanical Covers to Achieve Energy Savings

Yorkland Controls Ltd. Environmental Solutions TORONTO + MISSISSAUGA + LONDON (T)

Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.

Basic Nameplate Information

Exhaust Calculation Booklet

DUCT DESIGN FOR THE TIME CONSTRAINED WORLD

Natural Air Drying Corn Paul E. Sumner University of Georgia Biological and Agricultural Engineering Department

Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums

PowerFlex Dynamic Braking Resistor Calculator

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08

ENGINEERING DATA. Fan Performance Troubleshooting Guide

Duct Design. Presented by Dave Janquart

How to Build a Data Centre Cooling Budget. Ian Cathcart

Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29

Basic Selection & Proper Application of Overhead Air Distribution Devices

Technical Guide No High Performance Drives -- speed and torque regulation

Characteristics of Evaporators

AABC Specifications for Testing and Balancing HVAC Systems

PNEUMATIC CONTROLS Dual Duct Sequence Descriptions

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs

Sam E. Chapple, P. Eng. Chief Technical / Business Development Officer

Class II, Type A2 Biological Safety Cabinet HEPA Filter Loading Capacity

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Energy Efficiency Business Rebates Other Technology Catalog

G234X-55 Conventional Gas Boiler

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: Date: december 03, 2015 Supersedes: new Date: new

There are two sheets, Diesel and Electric, identified by tabs at the bottom of the sheet.

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Pump Formulas Imperial and SI Units

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Surface Technology. Centrifugal Fan GMD

Enclosure and Airflow Management Solution

Appendix C. Minimum Equipment Efficiency Standards

IDES-EDU. Educational Package Ventilation. Lecture 8: Sizing mechanical ventilation systems IEE/09/631/SI

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Turning Formulas. RPM = n (rev/min) Revolutions per minute. A measure of spindle speed

Section IV VACUUM PUMPS. Vacuum Pumps: Basic Operation

Airmanager Industrial HVAC retrofit results July Location Description:

Benefits of Cold Aisle Containment During Cooling Failure

Glossary of Heating, Ventilation and Air Conditioning Terms

Walnut Drying Design and Operation. Selecting Dryer Type. Tray Drying Before Don Osias Jim Thompson

TABLE OF CONTENT

Energy Efficient Grain Drying. Kenneth Hellevang, Ph.D., P.E. Professor & Extension Engineer

Tips and Tricks for Estimating Energy Savings. Celeste Cizik, P.E. Project Manager E M C Engineers, Inc.

Scope and Sequence KA KB 1A 1B 2A 2B 3A 3B 4A 4B 5A 5B 6A 6B

Heating, Ventilation & Air Conditioning Equipment

Potential Savings with Events2HVAC Event Automation Software

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Sect. 1.3: Factoring

HVAC Air Systems. Recirculation Air System Types

HRV and ERV Best Practices. December 18, 2012 Portland Metro Home Builders Association

ECM Motors Manufactured By Regal Beloit. Products and Applications- What s an ECM? GEXPRO Regal Beloit s distribution arm for all ECM motor products

product application guide

POLYNOMIAL FUNCTIONS

ECM MOTORS IN FAN POWERED TERMINAL UNITS

Energy Efficiency Business Rebates Other Technology Catalog

1.2 GRAPHS OF EQUATIONS. Copyright Cengage Learning. All rights reserved.

Solar Thermal Billing Program in Florida

HVAC Code Requirements

THE PSYCHROMETRIC CHART AND ITS USE

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

Demand Based Static Pressure Reset Control for Laboratories

High Altitude HVAC. Silvertip Integrated Engineering Consultants

BOEING CANADA WINNIPEG RECOGNIZED FOR COMPRESSED AIR PROJECT

Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE

Unidrive M Energy Savings

Fluid Power Formula. These Formula Cover All Fluid Power Applications In This Manual

Electrical Design TABLE OF CONTENTS FOREWORD BASIC ELEMENTS OF ELECTRICITY... 2 Electricity works much like water Ohm s Law

SYNCHRONOUS MACHINES

Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

CITYPLEX TOWERS BOILER INSTALLATION ORU RFP-1138

OPERATING FANS IN PARALLEL IN VIEW OF VARIABLE FLOW RATE OUTPUT

Transcription:

Energy Savings With Adjustable Frequency Drives for Centrifugal Fans

2 Centrifugal Fans Centrifugal Fan Fans are designed to be capable of meeting the maximum demand of the system in which they are installed. Quite often the actual demand varies and may be much less than the designed capacity. The centrifugal fan imparts energy into air by centrifugal force. This results in an increase in pressure and produces airflow at the outlet of the fan. Below is an example of what a typical centrifugal fan can produce at its outlet at a given speed. The curve is a plot of outlet pressure in static inches of water versus the flow of air in cubic feet per minute (CFM). Standard fan curves will usually show a number of curves for different fan speeds and includes fan efficiency and power requirements. These are useful for selecting the optimum fan for any application, and are required to predict fan operation and other parameters when the fan operation is changed.

Centrifugal Fans 3 Methods to Vary Airflow Cycling Outlet Dampers The system curve shows the requirements of the vent system that the fan is used on. It shows how much pressure is required from the fan to overcome system losses and produce airflow. Variable Inlet Vanes Variable Frequency Drives The system curve is a plot of load requirement independent of the fan. The intersection of the fan and the system curve is the natural operating point. It is the actual pressure and flow that will occur at the fan outlet when this system is operated. Without external influences, the fan will operate at this point. Many systems require operation at a wide variety of points. There are several methods used to modulate or vary the flow (or CFM) of a system to achieve the optimum points. These include: Cycling As done in home heating systems. This produces erratic airflow and is unacceptable for commercial or industrial uses. Outlet Dampers Control louvers or dampers are installed at the outlet of the fan. To control airflow, they are turned to restrict the outlet, which reducesthe airflow. Variable Inlet Vanes by modifying the physical characteristics of the air inlet, the fans operating curve is modified which changes the airflow. Variable Frequency Drives By changing the actual fan speed, the performance of the fan changes producing a different airflow.

4 Centrifugal Fans By changing the airflow, or the fan speed, the system or fan curves are affected which produces a different natural operating point. In so doing, they may also change the fan s efficiency and power requirements. Outlet Dampers The outlet dampers affect the system curve by increasing the resistance to airflow. The system curve can be stated as Where: P is the pressure required producing a given flow in the system K is a function of the system that represents the resistance to airflow CFM is the airflow desired The outlet dampers affect the K portion of the formula. The diagram below shows several different system curves indicating different outlet damper positions.

Centrifugal Fans 5 The power requirements for this type of system decrease gradually as flow is decreased as shown in the following diagram. Variable Inlet Vanes This method modifies the fan curve so that it intersects the system curve at a different point. Below is a representation of the changes in the fan curve for different inlet vane settings.

6 Centrifugal Fans The power requirements for this method decrease as airflow decreases, and to a greater extent than the outlet damper. Variable Frequency Drives This method takes advantage of the change in the fan curve that occurs when the speed of the fan is changed. These changes can be quantified in a set of formulas called the affinity laws. Where: N = Fan speed Q = Flow (CFM) P = Pressure (Static Inches of Water) HP = Horsepower

Centrifugal Fans 7 Note that when the flow and pressure laws are combined, the result is a formula that matches the system curve formula P = K x (CFM) 2. By substituting (Q2/Q1)2 for (N2/N1)2 in the first equation gives us: The quantity P 1 /(Q 1 ) 2 coincides with the system constant, K. This shows that the fan will follow the system curve when its speed is changed.

8 Centrifugal Fans As the fan speed is reduced, a significant reduction in power requirement is achieved. The variable speed method achieves flow control in a way that closely matches the system or load curve. This allows the fan to produce the desired results with the minimum of input power.

Centrifugal Fans 9 Fan Energy Savings It is possible to estimate the power consumption for each of these various methods and associate a cost of operation with them. To accomplish this, an actual load profile and fan curve is required as shown below.

10 Centrifugal Fans As an example, a simple analysis of the variable speed method compared to the outlet damper method follows. Using the fan curve shown previously, assume the fan selected is to be run at 300 RPM and 100% CFM is to equal 100,000 CFM as shown on the chart. Assume the following load profile. CFM Duty Cycle (% of Time) 100% 10% 80% 40% 60% 40% 40% 10% For each operating point, we can obtain a required horsepower from the fan curve. This horsepower is multiplied by the percent of time (divided by 100%), that the fan operates at this point. These calculations are then summed to produce a weighted horsepower that represents the average energy consumption of the fan. Outlet Damper Method CFM Duty Cycle Horsepower Weighted HP 100 10 35 3.5 80 40 35 14.0 60 40 31 12.4 40 10 27 2.7 Total 32.6 Similar calculations are done to obtain a weighted horsepower for variable speed operation. However, the fan curve does not have enough information to read all the horsepower values for our operating points. We can use the formulas from the affinity laws to overcome this.

Centrifugal Fans 11 The first point is obtained from the fan curve. 100% flow equals 100% speed equals 35 HP. The flow formula Q2/Q1 = N2/N1 can be substituted into the horsepower formula, HP2/HP1 = (N2/N1) 3 to give us: When Q1 = 100% and HP1 = 35HP, Q2 and HP2 will have the following values: Now sufficient information is available to calculate the weighted horsepower. CFM Duty Cycle Horsepower Weighted HP 100 10 35 3.5 80 40 18 7.5 60 40 7.56 3.024 40 10 2.24 0.224 Total 13.948 Comparing the results of the two methods of control indicates the difference in power consumption. In order to get a dollar value of savings kilowatt-hours used must be known. To calculate this, multiply the horsepower by 0.746 and then multiply the result by the hours the fan will operate in a period of time. This would typically be for a month. This example shows a cost saving of more than $700 per month by using a variable speed method. Note that the example is very basic and does not consider motor and drive efficiency. Outlet Damper Horsepower Weighted HP 32.6 13.948 X kw / HP 0.746 0.746 X Hours per Month 730 730 = kwh per Month 17,753 7,596 X Cost $0.07 $0.07 = Total Cost $1,242.73 $531.07 Calculate your potential energy savings using AC drives for fans at: http://www.rockwellenergycalc.com/

Allen-Bradley, LISTEN. THINK. SOLVE. and Rockwell Software are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication DRIVES-WP009D-EN-P August 2014 Supersedes Publication DRIVES-WP009C-EN-P March 2007 Copyright 2014 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.