White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?



Similar documents
White Paper. Power over Ethernet Plus Update and Cabling Considerations

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

10 Gigabit Ethernet over copper: Unshielded, unprotected?

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

Data Communications Competence Center

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER

Cat. 6 A EL Incredibly fast Get more

The Next Generation of Cable Technology. A technology primer from NORDX/CDT By, Eric d Allmen

The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges

How To Get 40G Over Copper (Wired) And 40G On Coaxian (Wireless) Cable (Wired Coaxian) (Wired Cable) (Wireline) (Powerline) And 50G Over Coaxian Cable (Wire Coaxian

Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk

How To Plan A Data Center Network

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems

Total Solutions Verification

Category-6 / Class-E Cabling

Category 8 Cabling Standards Update

Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka

The High Cost of a Low-Cost Cable Certification Tester

Gigabit Ethernet on Copper Cabling Infrastructures

STRUCTURED CABLING SYSTEMS

Enhanced Category 5 Cabling System Engineering for Performance

Copper Patch Cords. Impact On Network Performance and Reliability

Category 6 UTP - Cabling System

with Component Rating A Simple Perspective

Network Design. Yiannos Mylonas

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

How to Choose the Right Cable Category

White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems

Network Engineers Everywhere:

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8

Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer

Things You Must Know About Gigabit Ethernet 1. Understanding Gigabit Ethernet

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel

Discussion Paper Category 6 vs Category 5e Cabling Systems and Implications for Voice over IP Networks

How To Get A Better Signal From A Fiber To A Coax Cable

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram

Cabling Standards Update 2014

SMARTen 24 UTP Patch Panels

What are the requirements for a Home Network?

SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS

01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS

Nathan Dayton ADNET. ADNET SYSTEMS, Inc. Slide Number 1

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT

CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE

Security & Surveillance Cabling Systems

Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek

Ethernet Patch Cord Wiring

Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

What is ? Why are standards important?

SMARTen 24 STP Patch Panels

The Effect of Network Cabling on Bit Error Rate Performance. By Paul Kish NORDX/CDT

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

White Paper I ethercon. Next generation ethernet CAT6A

GigaSPEED X10D Solution How

Local Area Networks (LAN)

Cabling for 10GBASE-T and Beyond - A Tangled Web

IT Cabling Solutions

Abstract: This document examines the alien NEXT performance of various bundled cables and measures the impact upon various networks performance.

Accelerating Light. Copper Cabling Solutions. Category 6A

Fibre Channel Fiber Cabling

Power over Ethernet with Panduit Copper Cabling

HP ProCurve High-Speed Transceivers Installation Guide

Advantages of 4 th Generation CAT 6A UTP Cables. Antonio Cartagena Business Development - Caribbean Leviton Network Solutions

HARTING Ethernet Cabling 8-poles Overview

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)

The Need for Low-Loss Multifiber Connectivity

Broadband Video over Twisted Pair Cabling. By Paul Kish Director, IBDN Systems & Standards NORDX/CDT

Ethernet 102: The Physical Layer of Ethernet

Data Centre & Enterprise Solutions. RapidNet

Datasheet: DSX-5000 CableAnalyzer

The Elements of GigE Vision

Chapter 4 Connecting to the Internet through an ISP

Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels

Obsolete Fiber Technology? Not in my Data Center!

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

Overcoming OM3 Performance Challenges

This paper will explain some of the more important factors on how UTP wires work; specifically it will cover the following:

Implementing Fast Ethernet

Component 4: Introduction to Information and Computer Science

Category 8 Cable Transmission Measurements Comparative Study between 4-port single wire measurements and 2-port balun measurements

With the advent of Gigabit Ethernet

MTP Optical Fibre Configurations

Panduit 28 AWG Patch Cords Installation Guideline

An Ethernet Cable Discharge Event (CDE) Test and Measurement System

THE OSI REFERENCE MODEL LES M C LELLAN DEAN WHITTAKER SANDY WORKMAN

Specifying an IT Cabling System

Impedance Matching. Throughput SOLUTIONS NETWORK PERFORMANCE. Only the TrueNet Impedance-matched System Protects Network Performance

Transcription:

White Paper Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care?

Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? TABLE OF CONTENTS 1. Introduction...3 2. Component Standards Follow...4 3. Confusing Names...6 4. Why Does ISO/IEC Take Longer?...7 5. Recommendation...8 6. Sources and Additional Information...8 Copyright 2009 Reichle & De-Massari AG (R&M). All rights reserved. Dissemination and reproduction of this publication or parts hereof, for any purpose and in any form whatsoever, are prohibited without the express written approval of Reichle & De Massari AG. Information contained in this publication may be altered without prior notice. This document was produced with the greatest possible care; it presents the state of the art at the time of preparation. The right to make technical changes is reserved. White Paper Cat. 6A vs. Cat. 6 A v1.1 en 06/2009 2

Cat. 6A and Cat. 6 A With the advent of 10Gigabit Ethernet over copper twisted pair cabling, new classes of cabling standards were introduced. EIA/TIA released the Cat. 6A standard in February 2008 and ISO/IEC the Class E A channel standard in the same timeframe. Unfortunately, these two standards do not define the same performance, leading to confusion in the market. This confusion is compounded when looking at the components, especially the connecting hardware. EIA/TIA and ISO/IEC specify different performance for the modules, but the component naming is very similar. Therefore special care must be taken or users will not obtain the performance they expect. Application: Technology: Format: Topics: Target: Target groups: Authors: Enterprise Cabling, Datacenter Cabling Copper cabling, 10 Gigabit Ethernet, IP applications White paper Published: June 2009 Standardisation process EIA/TIA and ISO/IEC, Cat. 6A vs. Cat. 6 A, 10Gigabit Ethernet, Channel and module performance Differentiation of new standards for high end copper cabling, criteria and recommendation for choice of best performance System integrators, planners, installers, users, IT procurement Regina Good-Engelhardt 1. Introduction The IEEE protocol for 10Gb Ethernet over copper twisted pair cabling (802.3an) was released in July 2006. Because it increased the used frequency range to 500MHz and Cat. 6 cabling was only defined to 250 MHz, it was clear that new cabling standards would be required to support this protocol. Of course, Cat. 7 cabling which is specified to 600 MHz was an option from the beginning, but with a world-wide market share of only 4%, it would not ensure the success of this new Ethernet protocol. In the 802.3an standard, IEEE specified the minimum channel requirements the cabling needed to achieve in order for the protocol to work. In fact, a good Cat. 6 shielded system which operates stably at higher frequencies could meet these minimum requirements, as evidenced by the R&M Real10 shielded systems. However, alien crosstalk posed a problem for unshielded systems. Due to the higher frequencies used, as well as complex coding methods, the low signal strength with 10GbE is much more susceptible to outside disturbances than was the case with previous protocols. This translated to a length limitation with standard Cat. 6 unshielded systems. The various cabling bodies thus began work on specifying new cabling classes to 500 MHz which are based on RJ45 technology. EIA/TIA released their Cat. 6A standard in February 2008 and in the same timeframe ISO/IEC approved the channel requirements for Class E A. Unfortunately these standards do not specify the same performance. The chart below (Fig. 1) shows the differences with the Channel NEXT parameter. White Paper Cat. 6A vs. Cat. 6 A v1.1 en 06/2009 3

Fig. 1: The differences with the Channel NEXT parameter ISO/IEC specifies a straight line up to 500 MHz. R&M The EIA/TIA Cat. 6A channel requirements show a relaxed slope of 27 db starting at 330MHz, whereas the ISO/IEC Class E A channel specifies a straight line, thus offering the highest performance available using RJ45 technology. At 500MHz, this means that Class E A requires 1.8 db better NEXT performance than a Cat. 6A channel. In practice, this higher performance translates to higher operational reliability which minimizes errors. In addition, the life of the cabling infrastructure is maximized. 2. Component Standards Follow With channel standards clear, the next step is to define the component standards. EIA/TIA defined channel, permanent link and component specifications together and all are included in the ratified Cat. 6A standard (568B.2-10). ISO/IEC defined the channel specifications in Amendment 1 and is working on the permanent link and component definitions which will be released in Amendment 2. The need for component standards first arose with the customer requirement for interoperability, or the ability to mix and match components from various vendors and still be guaranteed to reach the corresponding channel performance. For example, a Cat. 6 module from vendor X, a Cat. 6 installation cable from vendor Y and a Cat. 6 patch cord from vendor Z should combine to achieve Class E performance. In order to ensure this, de-emdedded testing was introduced in 2003. In this testing procedure, a defined known reference jack is used to test plugs in a mated connection. The effects of the reference jack are subtracted or de-embedded from the mated connection values, giving the NEXT characterization of the plug. This method is used to qualify 12 reference plugs in the low, mid and high range which are then used to test the connecting hardware. White Paper Cat. 6A vs. Cat. 6 A v1.1 en 06/2009 4

In the case of 10 Gigabit Ethernet, initially systems were offered which would meet the channel requirements of the protocol. The new component requirements will enable interoperability, or mix and match systems, as in the past. For Cat. 6A (EIA/TIA) and Cat. 6 A (ISO) components, re-embedded testing has been introduced. The overall idea is similar to de-embedded testing, but in this case a reference plug is first qualified by a new, more accurate measurement setup called direct probing. The difference of this reference plug to the 12 de-embedded reference plugs is then calculated. At this point, the connecting hardware is tested with the one reference plug. Afterwards, the results which would have been obtained with the 12 de-embedded reference plugs are calculated rather than individually tested. In essence, the process of finding and testing the 12 de-embedded reference plugs is replaced by one accurate measurement and subsequent difference calculations, thus ensuring faster, but also more consistent testing results. As with the channel, a Cat. 6 A connector as specified by ISO will achieve higher performance than a Cat. 6A connector as specified by EIA/TIA. The current draft specifies a 40 db slope starting at 250MHz for Cat. 6A, and a 30 db slope for Cat. 6 A. At 500 MHz this means that a Cat. 6 A module must achieve at least 3dB better NEXT performance than a Cat. 6A module (Fig. 2). ISO/IEC Cat 6 A vs. TIA Cat 6A Connecting Hardware NEXT Values 55.0 50.0 45.0 40.0 35.0 30.0 25.0 20.0 100 500 ISO/IEC TIA TIA ISO/IEC Fig. 2: The differences with the connectors. R&M White Paper Cat. 6A vs. Cat. 6 A v1.1 en 06/2009 5

3. Confusing Names With component standards for connectivity and cabling, it now starts to get confusing. The component specifications needed to achieve a Cat. 6A (EIA/TIA) channel are clearly different and less stringent than those required to achieve a Class E A (ISO) channel. Therefore, users who want to ensure Class E A channel performance must use components that meet Cat. 6 A specifications. A channel composed of components meeting Cat. 6A (EIA/TIA) specifications won t guarantee Class E A performance. Therefore, the difference in the A, specifically whether or not it is written as a subscript, is very important: Cat. 6A Cat. 6 A. Channel Components Cable Connectivity EIA/TIA 568B.2-10 Cat. 6A Relaxed slope ~27dB/Dec Cat. 6A Cat. 6A ISO/IEC 11801 Class E A NEXT slope straight Amendment 1 Table 1: New standards for Channel and Components. Cat. 6 A Not defined yet Amendment 2 Table 1 shows the two new cabling classes and the associated component naming. Further complicating the situation is that the Cat. 6 A specifications have not yet been ratified. Amendment 2 is in progress and the timeframe for release is currently unclear. White Paper Cat. 6A vs. Cat. 6 A v1.1 en 06/2009 6

4. Why Does ISO/IEC Take Longer? You may wonder why ISO/IEC is taking longer to specify the components compared to EIA/TIA. One reason is the difference in organization. ISO/IEC includes different organizations who are responsible for the cabling, cable and connecting hardware specifications. Coordination between the various groups naturally takes longer than in the case of EIA/TIA where all of the interested parties are in the same group. However, another reason is technical complexity and really, forging into new territory. Until now, we have understood the behaviors of the components and how they work together very well up to 250 MHz. We are now doubling the frequency and the modeling methodology to be used for those higher frequencies is not stable. The modeling must take into account second and third effects such as cross modal coupling which significantly increases the complexity. These phenomenon are not as prevalent with Cat. 7 connecting hardware due to the contact geometry which separates the pairs from each other. Fig. 3: The influence of high frequency is the challenge with Cat. 6 A. R&M In order to achieve Class E A channel performance, we have seen that a Cat. 6 A module must have 3 db better NEXT at 500 MHz than a Cat. 6A module (Fig. 3). This is significant. To achieve this, it means that new modules need to be developed from the ground up as opposed to modifying existing designs, which is often the case with current Cat. 6A modules on the market. Specifically, more compensation elements are needed to compensate for the additional coupling seen. More care needs to be taken to separate the pairs from each other in the termination. Also, the termination process should be very precise and error-proof to ensure consistent performance. White Paper Cat. 6A vs. Cat. 6 A v1.1 en 06/2009 7

5. Recommendation Today, a Class E A channel is the highest performance channel available based on the prevalent RJ45 technology. It not only ensures support for the 10 Gigabit Ethernet application, but it also extends the life of the cabling and ensures higher operational reliability. For these reasons, R&M recommends installing a Class E A channel in new installations. If interoperability is a requirement, then it is important to choose Cat. 6 A connecting hardware. Cat. 6A modules simply cannot guarantee the higher Class E A performance. Although the Cat. 6 A component standards are taking longer, it will be worth the wait for the added performance the cabling system will achieve, which will translate to less headaches for the user. 6. Sources and Additional Information IEEE 802.3an ISO/IEC 11801 Amendment 1, Amendment 2 (draft) EIA/TIA 568B.2-10 For more information on R&M products and solutions, visit our website: www.rdm.com White Paper Cat. 6A vs. Cat. 6 A v1.1 en 06/2009 8