Category 8 Cabling Standards Update
|
|
|
- Shannon Johns
- 10 years ago
- Views:
Transcription
1 White Paper Category 8 Cabling Standards Update TIA TR42.7 Study Group for Class II Limits
2 Contents 1 Background 3 2 Impact of this approval on Category 7 A cabling 3 3 Differences between Class I and Class II cabling Will connectors used in Class II channels be backward compatible to existing cabling? Will connectors used in Class II channels be backward compatible to LAN and SAN equipment? 4 4 Category 7/7 A market share 5 5 Summary 5 6 References 6 2
3 1 Background At the TIA TR42 plenary meeting on June 12, 2013 in Portland, Oregon, the TR42.7 formulating sub-committee approved the formation of a task group to study the concept of adding ISO/IEC TR Class II limits to the draft ANSI/TIA-568-C.2-1 Category 8 cabling standard. The study group is expected to review existing Class II specifications in teleconference calls and submit recommendations to TR42.7 at the next meetings on July 30-31, 2013 and October 8-9, This approval will allow members of TR42.7, who see advantages in PIMF cabling, an opportunity to contribute towards the development of Class II cabling specifications, as well as category 8.2 component specifications. The work in TR42.7 will have to be carefully coordinated with the ongoing work in ISO/IEC/JTC1/SC25/WG3 developing Class II specifications, IEC 46C developing Category 8.2 cable specifications, and IEC 48B developing Category 8.2 component specifications. 2 Impact of this approval on Category 7 A cabling The formation of the study group for Class II recognizes advances in transmission technology needed for 40 G applications. TIA TR42.7 technical experts had previously rejected a proposal to develop Category 7 A cabling. The decision to develop Class II instead is further confirmation of the need for higher bandwidth and technical improvements beyond Category 7 A needed for 40 G applications. The decision to develop Class II up to 2000 MHz is a clear indication that Category 7 A cabling specified up to 1000 MHz will not be sufficient for 40 G applications. 3 Differences between Class I and Class II cabling The key difference between Class I and Class II cabling is the fact that Class II allows three different styles of connectors that are not compatible with one another, or with the RJ45 connector. This presents a dilemma to the customer who may not have detailed information on the advantages of each connector family. And, since the overwhelming majority of equipment ports, or MDIs, continue to use the RJ45, Class II cabling will require hybrid equipment cords. Class I, on the other hand, uses a fully backward-compatible RJ45-type interface with vastly improved performance relative to Category 6 A connectors and is specified up to 2000 MHz. Another difference between the Category 8 cabling classes is that Class II cabling has higher NEXT and FEXT performance because each of the four pairs are individually shielded. The additional isolation provided by the shield improves NEXT and FEXT of a Category 8.2 cable by about 20 db over Category 8.1 cable used in Class I. This difference is largely immaterial as on-board noise cancellers remove excess internal noise from the channel. The shield effectiveness can only be maintained in the channel if the connectors also have individually shielded pairs and shield continuity is maintained 360 degrees around through the connector. 3
4 3.1 Will connectors used in Class II channels be backward compatible to existing cabling? The Class II specifications in ISO TR do not cover connector types and, by default, refer to ISO for standardized interface connectors. This means that three different types of connectors allowed in ISO and ISO data center cabling for Category 7A including the GG45, ARJ45, and the TERA connectors are allowed in Class II. If the GG45 connector is used, Class II cabling would be backward compatible to other categories if the GG45 jack is mated to an RJ45 plug. However, the GG45 plug is not backward compatible to the RJ45 jack; so, existing cabling with RJ45 interfaces cannot be used with GG45 cords. In addition, the TERA and ARJ45 connectors allowed in the Class II standards will require the use of adapter cords to interface to existing cabling and equipment (see Figure 1 Illustration of TERA jack and ARJ45 plug showing non-compatibility to RJ45 jacks). TERA needs adapter cords to interface to equipment with RJ45 ARJ45 plug with keys on side does not fit into RJ45 jack Figure 1 Illustration of TERA jack and ARJ45 plug showing non-compatibility to RJ45 jacks 3.2 Will connectors used in Class II channels be backward compatible to LAN and SAN equipment? The three connector types allowed for Class II will need to use adapter cords when interfacing to existing equipment that use RJ45 interfaces. As shown in Figure 2: Illustration of GG45 plug from IEC standard, the GG45 system has keys on both sides of the plug with matching slots in the GG45 jack that activate a switch in the GG45 jack, allowing the connector to operate in Category 7 A mode or other category modes. Because of this backward compatibility issue and the complexity of the GG45 system, its adoption in the market will continue to be an issue when Class II is deployed in data centers that have lots of equipment with RJ45 interfaces. TERA is a registered trademark of The Siemon Company, and is not associated or affiliated in any way with CommScope, Inc. ARJ45 is a registered trademark of Bel Fuse Ltd. of Hong Kong, and is not associated or affiliated in any way with CommScope, Inc. GG45 is a registered trademark of Nexans Limited Company France and is not associated or affiliated in any way with CommScope, Inc. 4
5 4 Category 7/7 A market share Recent market data from BSRIA (Building Services Research and Information Association) indicates that the adoption rates of Category 7/7 A cabling and connector interfaces is expected to be around 1.5 percent of the total market in 2013, growing to just 1.9 percent of the market by In our view, this data confirms the issues that each customer and the market in general see in Category 7 A /Class F A cabling solutions, and confirms that the market share remains low. 5 Summary Protruding keys in GG45 plug will not allow it to mate to RJ45 jack Figure 2: Illustration of GG45 plug from IEC standard The approval of the new task group to study Class II channels is a recognition of the advances in PIMF cabling technology needed to support the use of balanced twisted copper cabling for 40 G applications. This recognition is somewhat tempered by the fact that TIA TR42.7 has to deal with the issue of three different connector types allowed for Class II. It is not clear whether TR42.7 will continue to require a single interface allowing portability and interoperability of cabling, LAN, and SAN equipment in data centers that generally use the RJ45 connector as the standard ubiquitous interface for balanced twisted pair cabling. Recent market data from BSRIA indicates that the adoption rates of Category 7/7 A cabling will continue to remain below two percent of the total market through Our view is that this confirms the issues customers and the market in general face with Category 7 A /Class F A cabling and may continue to haunt the market acceptance and adoption of Class II cabling. A likely reason for this poor adoption is the lack of a standardized interface connector for Class II cabling. 6 References 1. TIA TR42.7 Meeting report from Portland, Oregon, June BSRIA Telecommunications cabling market report, April Visit our website or contact your local CommScope representative for more information CommScope, Inc. All rights reserved. All trademarks identified by or are registered trademarks or trademarks, respectively, of CommScope, Inc. This document is for planning purposes only and is not intended to modify or supplement any specifications or warranties relating to CommScope products or services. WP EN (07/13)
CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE
ORTRONICS : UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE Cindy Montstream, RCDD/NTS, EE, CPLP Director of elearning and Standards DATA COMMUNICATIONS Legrand, North America
Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk
Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk Introduction At the IEEE 802.3 Working Group meeting in July of 2012, the Next Generation BASE-T Call for
Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8
Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC by Paul Kish NORDX/CDT Chair TIA TR 41.8 Outline Market trends Standards development where we were where we are where we are going Beyond Category
Copper Patch Cords. Impact On Network Performance and Reliability
Copper Patch Cords Impact On Network Performance and Reliability 1 The Impact of Copper Patch Cords on Network Performance and Reliability As network infrastructures continue to have a higher impact on
Category-6 / Class-E Cabling
Category-6 / Class-E Cabling IEEE 802 Tutorial July 7, 1998 San Diego, CA by: Luc Adriaenssens SYSTIMAX Systems Applications Director Bell Labs of Lucent Technologies How were the ISO Cat-6 Targets set?
HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks
HIGHSPEED ETHERNET THE NEED FOR SPEED Jim Duran, Product Manager - Americas WHITE PAPER Molex Premise Networks EXECUTIVE SUMMARY Over the years structured cabling systems have evolved significantly. This
Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable
Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable June 10, 2010 Contributors: Yinglin (Frank) Yang CommScope, Inc. Charles Seifert Ixia Ethernet Alliance 3855 SW 153 rd
TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report
TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report Peter L. Pondillo Standards Committee Chairman Corning Incorporated March 2012 Liz to update Fiber Optics LAN Section Overview: Part
Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek
Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek Supporters Mike Grimwood Broadcom Will Bliss Broadcom Dariush Dabiri APM Dan
Data Communications Competence Center
Importance of Cable Balance For Improving Noise Susceptibility Data Communications Competence Center DCCC03101702 July 11, 2007 Summary In a study of category 5e and category 6 UTP cables, a strong correlation
Laying the groundwork for a new level of Power over Ethernet
White Paper Laying the groundwork for a new level of Power over Ethernet June, 2014 Contents Laying the groundwork for a new level of Power over Ethernet 3 PoE basics 4 PoE standards development 5 Four-pair
HARTING Ethernet Cabling 8-poles Overview
Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs
Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer
SYSTIMAX Solutions Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer Issue 2 Draft 1 June 2010 Contents Overview 3 GigaSPEED X10D Guaranteed Channel Performance
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
Accelerating Light. Copper Cabling Solutions. Category 6A
Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity
PROFINET New Cabling for Gigabit Ethernet End-to-End Link (E2E) Dipl.-Ing. Rainer Schmidt HARTING
PROFINET New Cabling for Gigabit Ethernet End-to-End Link (E2E) Dipl.-Ing. Rainer Schmidt HARTING Gigabit Ethernet the Technology Driver Gigabit Ethernet state-of-the-art Protocol in the IT More Speed
White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?
White Paper Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? TABLE OF CONTENTS 1. Introduction...3 2. Component Standards
An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware
for CAT 6A Connecting Hardware Written by: Antoine Pelletier Engineer, Global Cabling Products Intertek www.intertek-etlsemko.com 1-800-WORLDLAB Introduction The telecommunication industry recently achieved
Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER
Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER Questions to Ask When Planning the Cabling Plant Planning a copper cabling plant to support 10Gbps transmission
40GBASE-T Advantages and Use Cases
40GBASE-T Advantages and Use Cases Andy Jimenez Anixter Inc. 40GBASE-T Task Force San Diego, California USA July, 2014 1 Contributors Masood Shariff Frank Straka - Commscope - Panduit 2 Supporters Wayne
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations White Paper www.commscope.com Contents Introduction 3 CommScope solution overview 3 InstaPATCH
The Next Generation of Cable Technology. A technology primer from NORDX/CDT By, Eric d Allmen
A technology primer from NORDX/CDT By, Eric d Allmen Foreword The Telecommunications Industry Association (TIA) and the International Standards Organization (ISO/IEC) are actively engaged in the development
InstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges Table of contents Channel, Basic Link and Permanent Link defined....................... 2 Critical Performance Parameters......
with Component Rating A Simple Perspective
Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America
Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications
3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition
TIA Releases Guidelines for Maintaining Polarity Using Array Connectors
Corning Cable Systems TIA Releases Guidelines for Maintaining Polarity Using Array Connectors What is new? ANSI/TIA-568-B.1-7-2006 Commercial Building Telecommunications Cabling Standard, Part 1 General
How To Properly Maintain A Fiber Optic Infrastructure
How To Properly Maintain A Fiber Optic Infrastructure Best Practices to Minimize Damage and Failures in Fiber Optic Infrastructures White Paper Rodney Casteel, RCDD, NTS, OSP, Technical Manager, CommScope
Upgrading Path to High Speed Fiber Optic Networks
SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method
Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair
Presentation; Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair 5 th April 2010 Paul Mathews MInstSMM, CCNA, MIEEE Global Channel Manager Media Types Physical Layer Cabling;
Things You Must Know About Gigabit Ethernet 1. Understanding Gigabit Ethernet
Things You Must Know About Gigabit Ethernet 1. Understanding Gigabit Ethernet Today s network managers know that modern demands on a network by its users can shrink bandwidth dramatically. Faster computers,
Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram
Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram www.psiberdata.com Agenda Market Market Trend and Trend business and and business case for case higher
SYSTIMAX Solutions. GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions. www.commscope.
SYSTIMAX Solutions GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions www.commscope.com The SYSTIMAX GigaSPEED X10D Shielded Solution provides unprecedented performance
Top of Rack: An Analysis of a Cabling Architecture in the Data Center
SYSTIMAX Solutions Top of Rack: An Analysis of a Cabling Architecture in the Data Center White paper Matthew Baldassano, Data Center Business Unit CommScope, Inc, June 2010 www.commscope.com Contents I.
GigaSPEED X10D Solution How
SYSTIMAX Solutions GigaSPEED X10D Solution How White Paper June 2009 www.commscope.com Contents Modal Decomposition Modeling and the Revolutionary 1 SYSTIMAX GigaSPEED X10D Performance MDM An Introduction
How To Get 40G Over Copper (Wired) And 40G On Coaxian (Wireless) Cable (Wired Coaxian) (Wired Cable) (Wireline) (Powerline) And 50G Over Coaxian Cable (Wire Coaxian
Copper for Beyond 10GBASE-T David Zambrano Agenda Market Drivers Standards Cabling and Ethernet Field Test Considerations Agenda Market Drivers Standards Cabling and Ethernet Field Test Considerations
The High Cost of a Low-Cost Cable Certification Tester
The High Cost of a Low-Cost Cable Certification Tester How much does it cost? That is typically the first question a cabling contractor or network owner asks when considering a new certification tester
White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems
White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems Asef Baddar, RCDD Principal Engineer / Applications Engineering Supervisor Leviton Network Solutions C/7 - #1928 Table of Contents Background
Category 8 Cable Transmission Measurements Comparative Study between 4-port single wire measurements and 2-port balun measurements
Category 8 Cable Transmission Measurements Comparative Study between 4-port single wire measurements and 2-port balun measurements Stefan Estevanovich Rafael Herrera, Nadim Kafati Hitachi Cable USA NDC
Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications
Data Sheet Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output
Terminal and Dimension
Ethernet Extender Model Number: SJ-L-DSL Product Description Product Features SJ-L-DSL is a network signal extension device, which consists of remote unit and local unit. It can transmit network signal
R&Mfreenet Advanced Cat 6 A Unshielded Connection Module
R&Mfreenet Advanced R&Mfreenet Advanced Cat 6 A Connection Module The R&Mfreenet Cat 6 A unshielded connection modules, part of the Advanced cabling system, are ideal for voice, fast data transmissions
784 INTELLIGENT TRANSPORTATION SYSTEMS NETWORK DEVICES. (REV 11-17-11) (FA 1-5-12) (7-12)
784 INTELLIGENT TRANSPORTATION SYSTEMS NETWORK DEVICES. (REV 11-17-11) (FA 1-5-12) (7-12) SUBARTICLE 784-1.2.2 (of the Supplemental Specifications) is deleted and the 784-1.2.2 Networking Standards: Ensure
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
Current access technologies overview
White Paper Current access technologies overview In this paper, we explore six basic technology choices for deploying broadband services to the end customer xdsl, DOCSIS, G.fast, satellite, wireless and
How To Get A Better Signal From A Fiber To A Coax Cable
Gigabit Transmission What s the Limit? Fanny Mlinarsky Page 1 What s the Limit? Speed Faster higher frequency higher attenuation less headroom Distance Longer higher attenuation more jitter less headroom
Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company
Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs
Panduit 28 AWG Patch Cords Installation Guideline
Panduit 28 AWG Installation Guideline Introduction Panduit is a leading supplier of Structured Cabling Systems and Unified Physical Infrastructure. Panduit solutions enable the physical infrastructure
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide
Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka
Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka What is a network? A computer network is two or more computers connected together using a telecommunication system for the purpose
The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT
The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings Focus on the IBDN System 4800LX from NORDX/CDT Table of Contents Introduction... 3 Bandwidth and Information
Cabling Standards Update 2014
Cabling Standards Update 2014 Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of Greek National Committee, CENELEC
Total Solutions Verification
Total Solutions Verification 3rd Party Electrical Performance Testing Author: Tom Boucino Applications Engineer Uniprise Solutions CommScope has always designed cables with connectivity in mind. Our engineers
Data Center Design for 40/100G
Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an
Data Centre & Enterprise Solutions. RapidNet
H E L L E R M A N N T Y T O N Data Centre & Enterprise Solutions RapidNet data centre & Enterprise solutions HellermannTyton is a leading global manufacturer of network cabling solutions which connect,
Obsolete Fiber Technology? Not in my Data Center!
Obsolete Fiber Technology? Not in my Data Center! White Paper October 2011 Author: James Young Technical Director, Asia Pacific www.commscope.com Do you remember when people used to say fiber optics are
ECONOMICS OF DATA CENTER OPTICS SPIE PHOTONICS WEST INVITED PAPER (9775-2) FEBRUARY 16, 2016
ECONOMICS OF DATA CENTER OPTICS SPIE PHOTONICS WEST INVITED PAPER (9775-2) FEBRUARY 16, 2016 Lisa Huff, CDCM Principal Analyst, Discerning Analytics [email protected] AGENDA Discerning
10GBASE-T for Broad 10 Gigabit Adoption in the Data Center
WHITE PAPER 10GBASE-T Ethernet Network Connectivity 10GBASE-T for Broad 10 Gigabit Adoption in the Data Center The increasing use of virtualization and unified networking places extreme I/O demands on
100BASE-SX Fast Ethernet:
100BASE-SX Fast Ethernet: A Cost Effective Migration Path for Fiber in the Horizontal Prepared by the Fiber Optics LAN Section of the Telecommunications Industry Association February 2000 2000 TIA Fiber
Innovative Connectivity Solution for Maximum Performance and Security
Innovative Connectivity Solution for Maximum Performance and Security Financial Institutions Supports high performance backbone which enables transfer of real-time financial information through voice,
Datasheet: DSX-5000 CableAnalyzer
Datasheet: DSX-5000 CableAnalyzer The DSX-5000 CableAnalyzer is the copper certification solution and is part of the Versiv cabling certification product family. The Versiv line also includes fiber OLTS
10 Gigabit Ethernet over copper: Unshielded, unprotected?
Technical Article 10 Gigabit Ethernet over copper: Unshielded, unprotected? Copyright 2005 Reichle & De-Massari AG (R&M). All rights reserved. Transmission and reproduction of this publication or parts
CommScope Intelligent Building Infrastructure Solutions (IBIS)
SYSTIMAX Solutions CommScope Intelligent Building Infrastructure Solutions (IBIS) Questions & Answers Q. What is an Intelligent Building? A. An intelligent building can be defined as one which provides
Optimizing Infrastructure Support For Storage Area Networks
Optimizing Infrastructure Support For Storage Area Networks December 2008 Optimizing infrastructure support for Storage Area Networks Mission critical IT systems increasingly rely on the ability to handle
Enhanced Category 5 Cabling System Engineering for Performance
Engineering for Performance Table of Contents 2 Introduction 2 Where Did It Come From? 2 Enhanced Category 5 Performance What to Test The Link The Channel Don t Forget the Cable Assembly 4 Performance
White Paper. Power over Ethernet Plus Update and Cabling Considerations
White Paper Power over Ethernet Plus Update and Cabling Considerations Power over Ethernet Plus Update and Cabling Considerations TABLE OF CONTENTS 1. Introduction...3 2. Application Objectives...5 3.
IT Cabling Solutions
IT Cabling Solutions Signamax & Hitachi Cable America System Performance Signamax & Hitachi Cable America (Hitachi) system quality assurance testing is based on the worst-case model - four-connector 100-meter
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G FIBER POLARITY: 10G and 40/100G OPTIONS Why is this significant in the data center? Data centers will be one of the first places where we
Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com
Design Guide SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution www.commscope.com Contents Introduction 3 How Does a TAP Work? 3 The TAP Ecosystem 4 InstaPATCH 360 TAP Module Family 4 InstaPATCH
Application Note: How to Connect a Lantronix Embedded Module to a Wired Ethernet Port
Application Note: How to Connect a Lantronix Embedded Module to a Wired Ethernet Port This app note applies to the following Lantronix Products: WiPort BG WiPort NR MatchPort BG MatchPort AR XPort Direct+
10GBASE T for Broad 10_Gigabit Adoption in the Data Center
10GBASE T for Broad 10_Gigabit Adoption in the Data Center Contributors Carl G. Hansen, Intel Carrie Higbie, Siemon Yinglin (Frank) Yang, Commscope, Inc 1 Table of Contents 10Gigabit Ethernet: Drivers
Ethernet 102: The Physical Layer of Ethernet
Ethernet 102: The Physical Layer of Ethernet Scott Kipp President of the Ethernet Alliance (Brocade) Frank Yang Marketing Chair, Next Generation Cabling Subcommittee (CommScope) February 27th, 2012 1 The
HARTING Ethernet Cabling 4-poles Overview
Overview RJ45 Connectors [on page 8] System cables [on page 10] Distribution modules and Outlets [on page 20] HARTING PushPull Connectors [on page 22] System cables [on page 24] Panel feed-throughs [on
Communication Setup Application Note
Communication Setup Application Note This Application Note describes how to install and set up communication between the inverter and the SolarEdge Monitoring Server. This document contains the following
Category 6 Cabling Questions and Answers
Category 6 Cabling Questions and Answers by Paul Kish NORDX/CDT July 2002 Introduction On June 20th, 2002, TIA finally published the Category 6 cabling standard. Now that this standard is a reality, many
E Series. E Series. Category 6 and 5e. Features
E Series Category 6 and 5e CommScope, world leader in copper and fiber connectivity, offers the E Series product line as the ideal solution to all your infrastructure needs for safe and reliable data transmission.
A Simple Model of Relative Power vs. Reach
A Simple Model of Relative Power vs. Reach, Broadcom Corp. Sept. 17, 2012 for IEEE 802.3 Next Generation BASE-T study group Geneva 0 Supporters Brad Booth Valerie Maguire Rick Rabinovitch Dave Chalupsky
Structured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
Implementing Fast Ethernet
Implementing Fast Ethernet R The Next Generation of Ethernet Fast Ethernet (also known as IEEE 802.3u or 100BASE-T) is quickly becoming the successor to Ethernet as the network topology of choice. Fast
What are the Requirements for an Accurate DSL Line Simulator? Paradyne International, France
Title: Source: Author: Contact: What are the Requirements for an Accurate DSL Line Simulator? Paradyne International, France Jack Douglass Jack Douglass Paradyne Networks, Inc. Voice: 949-233-3558 Email:
BICSI :Building Industry Consulting Service International
BICSI :Building Industry Consulting Service International - Lead the information and communications technology community with excellence in publications, education and knowledge assessment. - Advance our
SYSTIMAX Copper Solutions Designed for the Digital Generation
SYSTIMAX Copper Solutions Designed for the Digital Generation SYSTIMAX Structured Connectivity Solutions www.systimax.com SYSTIMAX Solutions is the global leader in the enterprise cabling sector with a
Fibre optic testing best practices
Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is
Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel
Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Introduction When network managers decide on a cabling system,
Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village
Brno, Marec 2014 Physical Infrastructure trends and certification requirements for Datacenters Ing. Peter Potrok PROFiber Networking s.r.o. Psiber s Global Village London Munich San Diego Boston Paris
SHDSL LAN EXTENDER H301A. User Manual
SHDSL LAN EXTENDER H301A User Manual Rev. 1.0 Yoda Communications, Inc. Yoda Communications, Inc. Address 2F, No. 3-1, Industry East Road IX, Science Based Industrial Park, HsinChu, Taiwan Tel 886-3-5632323
Terminal and Dimension
Ethernet Extender Model Number: SJ-L-DSL Complete Installation Guide Product Description Product Features SJ-L-DSL is network signal extension device, which consists of remote unit and local unit. It can
Gigabit Ethernet on Copper Cabling Infrastructures
Gigabit Ethernet on Copper Cabling Infrastructures Overview of Gigabit Ethernet (1000Base-T) Ethernet was developed by the Xerox Corporation in the early 1970 s and has emerged as the dominant networking
MapIT G2 Infrastructure Management
MapIT G2 Infrastructure Management Introducing MapIT G2, a complete upgrade of Siemon s popular MapIT intelligent infrastructure management (IIM) solution. MapIT G2 integrates a powerful combination of
Quick Reference Guide High Speed Input/Output Solutions
Quick Reference Guide The pluggable I/O interface offers significant advantages as a high speed I/O interconnect. With a standard equipment I/O interface and the flexibility of pluggable modules come the
Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc [email protected]
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc [email protected] J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
Ethernet over VDSL2 PoE PD Converter
Ethernet over VDSL2 PoE PD Converter UVE7312-MSPD User Manual Ver 1.02 Copyright EUSSO Technologies, Inc. All rights reserve 1 Table of Content 1. Introductions... 2 2. Application Notes... 2 3. Features...
Product Specifications
Cisco Model EPR2320 EuroDOCSIS 2.0 Residential Gateway with Wireless Access Point The Cisco Model EPR2320 EuroDOCSIS 2.0 Residential Gateway (EPR2320) combines a cable modem, router, and wireless access
ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL
Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL User s Guide Version 1.0 07/01/2009 Michael Stevens & Partners Ltd. has made
Laying the groundwork for a new level of wireless access performance. White Paper
Laying the groundwork for a new level of wireless access performance White Paper Contents Wireless capabilities move closer to the core 3 Opportunities and challenges of evolving enterprise wireless access