Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels
|
|
|
- Diana Holmes
- 9 years ago
- Views:
Transcription
1 Fiber Systems Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels 1
2 Introduction Data centers are the central location for data interchange and are found in enterprises, government offices, schools, universities, hospitals, and other networked server farms. The ease of turning nearly any location into an information interchange hub has been enabled by the development of array-based fiber optic cabling systems. Ribbon fiber cables, array-based fiber connectors, and packaged breakout assemblies (i.e., cassettes) provide modular small form factor connectivity and enable fast, reliable interconnection of fiber optic links in high-density data center environments. Once the decision has been made to deploy array-based fiber connectivity, care must be taken to ensure the integrity of connections between the transmitting optical light source and the receiving photo detector. The matching of the transmit signal (Tx) to the receive equipment (Rx) at both ends of the fiber optic link is referred to as polarity. The objective of polarity is simple: provide transmit-to-receive connections across the entire fiber optic system in a consistent, standards-based manner. Ensuring polarity of array-based systems requires careful planning. The end-user is best served by network designs that follow a single method that maintains polarity now over serial fiber channels and can migrate to parallel optics in support of very high data rates ( Gb/s) in the future. This paper describes recently published industry guidelines that address polarity across array-based fiber systems, and discusses the advantages and drawbacks of the three TIA/EIA recommended methods. System Polarity and the Array-Based Fiber Channel In any installation, it is important to ensure that the optical transmitter at one end is connected to the optical receiver at the other. Optical fiber links typically require two fibers to make a complete circuit. Optical transceivers have a transmit side and receive side, and typically employ a duplex fiber connector as the interface. For traditional cabling systems using single fiber connectors, such as LC or SC, maintaining polarity is as simple as ensuring that the A side of one connector pair matches to the B side of the other connector pair in any patch cord or permanent link (Figure 1). This procedure is well documented in the TIA/EIA-568-B.1 Commercial Building Telecommunications Cabling Standard. Note B is the transmit signal and A is the receive signal. Maintaining polarity requires that the B transmit signal connects to the A receive signal. Figure 1. Example of Proper Polarity Over Single-Fiber Connectors 2008 PANDUIT Corp. All rights reserved. 2
3 Responding to the growing adoption of fiber cabling based on array connectivity, TIA/EIA developed and published an addendum to the standards governing cabling systems. TIA/EIA-568-B.1 Addendum 7, Guidelines for Maintaining Polarity Using Array Connectors, outlines three recommended methods for assuring correct transmit-to-receive polarity over serial duplex fiber circuits using ribbon cables and array connectors. Since it is a guideline, the document does not promote one method as being the best. It also states that other methods may be available to establish correct polarity throughout installation and during subsequent maintenance, upgrades, and additions. Ribbon cables and array connectors have introduced new complexities into the fiber installation process. To understand polarity and how to maintain it, the role and function of every part of the array-based fiber channel must be understood (see Figure 2), as each component of the channel has an impact on how polarity is maintained system-wide. Cassettes Array Connectors Ribbon Cable Assembly Patch Cords Array Connectors Figure 2. Example Array-Based Fiber Channel Array Connectors. Special connectors have been developed for ribbon fiber cables that provide multi-fiber capability and high density in a unitary connector design (see Figure 3). These array connectors can house anywhere from 6 to 72 fibers, with 12-fiber arrays being the most common. The connectors have a pin-andsocket design to precisely align mating fibers. Cassettes and hydra cable assemblies are typically manufactured with a male (pinned) connector, and ribbon cable assemblies typically deploy a female (unpinned) connector. Most important for maintaining polarity, array connectors are keyed to ensure that proper endface orientation occurs. The key is a ridge on one surface of the array connector housing to ensure that the connector can only be joined in one orientation against the opposing connector. When looking at the endface of the connector, the key is in the up position and Fiber 1 is the far left fiber on the same side as the white dot on the connector (see Figure 3) PANDUIT Corp. All rights reserved. 3
4 Male Array Connector Pins Key Up Array Adapter No Pins White Dot Female Array Connector White Dot Fiber Position 1 12 Key Up Key Down Pin Location Figure 3. Array Connector Schematic (left) and End View (right) Cassettes. A cassette is a packaged, pre-terminated cabling assembly that transitions from small form factor ribbon-style fiber cables and array connectors to traditional single-fiber connectors (see Figure 4). The primary function of cassettes is to provide quick, scalable plug-in network deployment of up to 12 fiber ports (24 fibers) in a single assembly to support high-density applications. Array adapters at the rear of cassettes are also keyed to ensure proper orientation with keyed array connectors. Patch Cords. Duplex patch cords used to complete serial duplex pair connections are available in two types (see Figure 5), depending on which polarity technique is used. The A-to-B patch cord connects position A on one end of the cord to position B on the other end; this is termed straight-through wiring. The A-to-A patch cord connects position A on one end of the cord to position A on the other end, and is known as crossover wiring. Ribbon Cable Assemblies. Factory-assembled modular fiber cassettes are connected to one another with connectorized ribbon cables. Each 12-fiber ribbon (or trunking ) cable translates into six 2-fiber serial optical circuits that require polarity management. Figure 6 shows the three fiber-and-connector trunk combinations described in TIA/EIA-568-B.1 Addendum 7 for polarity management when using fiber array cables; the chart indicates the transformation of fiber position along each circuit. Figure 4. Fiber Arrangement in Cassette Figure 5. A-to-A and A-to-B Patch Cords 2008 PANDUIT Corp. All rights reserved. 4
5 Understanding Array-Based Polarity The basic strategy for designing polarity into an array-based serial duplex fiber optic system is to think of each ribbon cable as a series of two-fiber optical circuits that require polarity management. At some point along each circuit the fiber in odd-numbered array positions (i.e., the transmit position) must cross its duplex counterpart and end in an even-numbered position (i.e., the receive position) to achieve a Tx/Rx and Rx/Tx circuit rather than a non-functional Tx/Tx and Rx/Rx circuit. This point of crossover is known as a pair-wise flip or, less commonly, as an A-to-B polarity swap. Regardless of the term used, the flip must occur at some point in every serial duplex link. Polarity methods differ, in essence, by the location of the pair-wise flip: Addendum 7 recommends that the flip be built into the duplex patch cords (Method A), array cables (Method C), or through a combination of cassette and trunk fiber transformation (Method B). In array-based channels, the keys on connectors and adapters are used to establish the orientation of the fiber arrays in one connector relative to the array in the mating connector. The fiber numbering within a ribbon cable is also defined with respect to the key: fibers are numbered from left to right with the key facing up, as shown in Figure 6; this figure also indicates in matrix form the numerical alignment of a 12-fiber array under Addendum 7 Methods A, B, and C. The following sections further define TIA/EIA polarity management methods, showing proper orientation of keys and the ribbon cable, cassette, and patch cords transformations necessary for each method. Pair-Wise Flip Figure 6. Array Connector Cables and Input-to-Output Fiber Mapping by Method 2008 PANDUIT Corp. All rights reserved. 5
6 Method A Method A employs Key Up to Key Down Adapters to link straight-through Key Up to Key Down ribbon cables to fiber cassettes (see Figure 7). This method maintains registration of Fiber 1 throughout the permanent link: Fiber 1 in the near-end cassette mates to Fiber 1 in the ribbon cable assembly, which mates to Fiber 1 in the remote cassette. The fiber circuit is completed by utilizing one flipped patch cord, either at the beginning or end of the permanent link, to move Fiber 1 into the Fiber 2 position at the face of the remote cassette to ensure proper Tx-Rx orientation. The method requires two Method A cassettes, a Method A ribbon cable, an A-to-A patch cord at one end of the connection, and an A-to-B patch cord at the other end. PANDUIT recommends that the end user introduce the pair-wise flip consistently at the beginning or end of the channel for easier management. Patch cords with duplexing clips that hold connectors in place may be used rather than permanent molded assemblies. These clips open at the sides to permit installers to easily reverse or swap the order of connectors, so that the A cable becomes B when necessary to maintain polarity. Figure 7. Polarity using Method A (inset shows polarity flip using patch cords with a duplexing clip) 2008 PANDUIT Corp. All rights reserved. 6
7 Method B Method B employs Key Up to Key Up Adapters to link straight-through Key Up to Key Up ribbon cables to fiber cassettes (see Figure 8). Method B cassettes are identical to Method A cassettes except that they use Key Up to Key Up adapters. The fiber channel is completed by flipping the second cassette (i.e., rotating it 180 degrees) and re-numbering it, and then utilizing straight A-to-B patch cords at the beginning and end of the link. This type of mating results in an inversion of the entire numbered fiber array to achieve polarity, meaning that Fiber 1 (Tx) is mated with Fiber 12 (Rx), Fiber 2 (Rx) is mated with Fiber 11 (Tx), and so on. Therefore this particular method requires more in-depth planning than others to properly identify and manage the circuit inversions. Further, Method B does not support singlemode fiber deployments with standards-compliant connector endfaces because the angles of the mating connectors are not complimentary. However, an advantage of this method is that only one type of patch cord is used so patch cords do not need to be flipped. Figure 8. Polarity using Method B 2008 PANDUIT Corp. All rights reserved. 7
8 Method C Method C employs Key Up to Key Down Adapters to link a special Key Up to Key Down ribbon assembly to Method A cassettes (see Figure 9). In this method, polarity is achieved by using a ribbon cable that has the pair-wise flip built in to individual fiber pairs, and the fiber channel is completed by utilizing straight A-to-B patch cords at the beginning and end of the link. In essence, the only difference between this method and Method A is that the pair-wise flip occurs in the array cable itself rather than at the patch cords, so that oddnumbered Tx fibers leaving the near-end cassette are in even-numbered Rx positions when they arrive at the remote cassette. Channels built with this method using one array cable may take the same time to deploy as channels built using other polarity methods. However, in longer channels that connect multiple array cords in sequence, the data center manager must keep close track of the number of array cables used in order to preserve the pair-wise flip, which results in more complex channel designs and longer maintenance times. Figure 9. Polarity using Method C 2008 PANDUIT Corp. All rights reserved. 8
9 Which Method? In complex, high-density fiber installations, the advantages of array connectors can be lost if large-scale confusion and loss of local control result. Also, intermixing the components of these methods may result in incorrect polarity. So, with three guideline-recognized methods from which to choose, how should network stakeholders select the best method for ensuring polarity across their array-based fiber installation? Table 1 summarizes the advantages and disadvantages of the three methods. The most critical consideration is to select one method and stick with it. As stated in TIA/EIA-568-B.1 Addendum 7: The primary consideration faced by data center operators when choosing a method is ensuring that the same method is used throughout all of an operator s installations. Therefore, the method choice should be maintained consistently throughout the installation, and must be clearly communicated to all stakeholders. PANDUIT endorses Method A as the most flexible and reliable method for the following reasons: Customers expect systems based on standards. Standards incorporate best practices and incorporate paths to upgrade as technology advances, so system investments are better protected from risk of obsolescence. Customers need flexibility. Method A provides the most flexible options for current system designs and includes an easy path to migrate to higher data rates via parallel optics. Customers should have the widest choice of installation and component vendors, rather than relying on vendors with proprietary solutions and technologists with specialist skills. Also, proprietary methods not based on TIA/EIA guidelines will neither assure future interoperability, nor availability of future product inventory at a time of greatest need. Table 1. Analysis of TIA/EIA-568-B.1 Addendum 7 Fiber Polarity Methods Method Advantages Disadvantages A One cassette type, easy to produce and purchase Requires pre-configured A-to-A patch Multiple sources for components cords, or field configuration of same Singlemode and multimode Ribbon cables can be linked (need male/female connector) Compatible with many legacy systems Industry standard Standard provides migration path to parallel optics B Single source for components A-to-B patch cord only Industry standard Standard provides migration path to parallel optics C One cassette type, easy to produce and purchase Singlemode and multimode Industry standard A-to-B patch cord only Remote cassette must be flipped and re-labeled Identification and maintenance of cassettes are different on each end Multimode only Not compatible with legacy systems Ribbon cables can only be liked using less available (Key Up to Key Up) adapters (need male/female cord) Fewest vendors Less reliable than Method A Specialized ribbon cable assembly Does not support parallel optics Not compatible with legacy systems Less vendor support than Method A Difficult to extend link 2008 PANDUIT Corp. All rights reserved. 9
10 Conclusion Ensuring fiber polarity over an array-based system requires a significant number of decisions early in the design process. The challenge for the system designer is ensuring that polarity of connections is observed from end to end, particularly in systems that contain many interconnect points. Constant attention is required to ensure that polarity decisions are adhered to by installers and other network stakeholders. TIA/EIA-568-B.1 Addendum 7 provides guidance on three polarity management methods, so it is important to specify one method and implement it consistently in order to manage the risk associated with costly mistakes and re-work over the life of the installation. Method A is endorsed by PANDUIT because it provides the simplest deployment, works for singlemode and multimode fiber channels, supports network extensions, and is easily extendable to emerging parallel optics systems. Array-based fiber optic cabling systems such as the PANDUIT QUICKNET Fiber Optic Cabling System enable faster implementation of scalable, high-density data center cabling deployments. QUICKNET pre-terminated cassettes and cable assemblies improve on the time required for installation of fiber connections by reducing the number of laborious strand-to-strand connections, making deployment of high-speed network-cabled devices in data centers easier, faster, and more cost-effective. When coupled with a consistent policy to ensure polarity across the hundreds or thousands of permanent links in today s data centers, pre-terminated solutions allow quick and scalable deployment. Data center designers can take advantage of array-based fiber optic systems while ensuring the widest choice in installation vendors, component manufacturers, and technology. About PANDUIT PANDUIT is a leading, world-class developer and provider of innovative networking and electrical solutions. For more than 50 years, PANDUIT has engineered and manufactured end-to-end solutions that assist our customers in the deployment of the latest technologies. Our global expertise and strong industry relationships make PANDUIT a valuable and trusted partner dedicated to delivering technology-driven solutions and unmatched service. Through our commitment to innovation, quality and service, PANDUIT creates competitive advantages to earn customer preference. [email protected] PANDUIT Corp. All rights reserved. 10
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems Rudolph A Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand November, 006 Introduction: Optical communication systems provide
TIA Releases Guidelines for Maintaining Polarity Using Array Connectors
Corning Cable Systems TIA Releases Guidelines for Maintaining Polarity Using Array Connectors What is new? ANSI/TIA-568-B.1-7-2006 Commercial Building Telecommunications Cabling Standard, Part 1 General
Upgrading Path to High Speed Fiber Optic Networks
SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations White Paper www.commscope.com Contents Introduction 3 CommScope solution overview 3 InstaPATCH
Migration Strategy for 40G and 100G Ethernet over Multimode Fiber
Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year
MTP Optical Fibre Configurations
MTP Optical Configurations ackground The Excelerator MPO range from Excel utilises the MTP Elite connector manufactured by US Conec. The range is made up of: MTP to MTP Trunk Cables MTP to LC s MTP Patch
AMP NETCONNECT Data Center Cabling Solutions
AMP NETCONNECT Data Center Cabling Solutions Modern business and administrative environments require today more and more sophisticated IT services, what leads to an increasing demand for data provision
How To Make A Data Center More Efficient
Data Center: Technology Drivers Infrastructure Trends 40G / 100G Migration Maurice F. Zetena III Vice President Leviton Technology Data Center Group Leviton Network Solutions Technology Drivers Convergence
Best Practices for Ensuring Fiber Optic System Performance. David Zambrano
Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process
Arista 40G Cabling and Transceivers: Q&A
Arista 40G Cabling and Transceivers: Q&A 40G Cabling Technical Q&A Document 40Gigabit Cables and Transceivers Q. What 40G cables and transceivers are available from Arista? A. Arista supports a full range
Patch Cords for Data Center Applications
Applications General use of patch cords includes the interconnection of the optical fiber cable plant with opto-electronic equipment, and/or the cross-connection between cable plant segments. Pigtails
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G FIBER POLARITY: 10G and 40/100G OPTIONS Why is this significant in the data center? Data centers will be one of the first places where we
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING
Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8
Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,
Infrastructure for the next three generations
Infrastructure for the next three generations Demand for bandwidth and storage is expanding at a breathtaking rate within the data center, which means that the environment is rapidly evolving, making the
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center Doug Coleman, Manager, Technology & Standards, Corning Cable Systems Optical connectivity with OM3/OM4 laser-optimized
HUBER+SUHNER AG Phil Ward
The challenges of building and maintaining Fiber Optic connectivity in the modern Data Center HUBER+SUHNER AG Phil Ward What is our common Global Objective? To connect different types of equipment together
Simplified 40-Gbps Cabling Deployment Solutions with Cisco Nexus 9000 Series Switches
Simplified 40-Gbps Cabling Deployment Solutions with Cisco Nexus 9000 Series Switches Panduit and Cisco Accelerate Implementation of Next-Generation Data Center Network Architecture 2013 Cisco Panduit.
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide
Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com
Design Guide SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution www.commscope.com Contents Introduction 3 How Does a TAP Work? 3 The TAP Ecosystem 4 InstaPATCH 360 TAP Module Family 4 InstaPATCH
Zone Distribution in the Data Center
Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling
PANDUIT is a Technology Developer Partner for Storage Networking Hardware. FIBER OPTIC CABLING SYSTEM SOLUTIONS B EYOND T HE G LASS
PANDUIT is a Technology Developer Partner for Storage Networking Hardware. FIBER OPTIC CABLING SYSTEM SOLUTIONS B EYOND T HE G LASS Bandwidth Requirements Push Fiber Optic Solutions Offices, Operations
The Need for Low-Loss Multifiber Connectivity
WP_LowLoss_D_B 10/13/14 2:08 PM Page 2 The Need for Low-Loss Multifiber Connectivity In Today s Data Center Optical insertion loss budgets are now one of the top concerns among data center managers, especially
Managing Physical Security Risk in Physical Layer Infrastructure Solutions
Managing Physical Security Risk in Physical Layer Infrastructure Solutions Protecting Against Network Intrusion Using Keyed Connectivity Systems www.panduit.com WP-05 November 2008 Introduction Industries
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration Bill Charuk, SR Product Manager, Data Center Solutions Introduction With the advent of data centers in communication infrastructure, various
PHOENIX OPTIX WIRING AND INTERCONNECT SOLUTIONS
PHOENIX OPTIX WIRING AND INTERCONNECT SOLUTIONS Copper or Fiber...Data & Power Solutions Optimized for Low Loss Performance in Commercial and Military Environments PHOENIX OPTIX Wiring Solutions that Meet
Cable Assemblies. Features and Benefits
Features and Benefits Flame-retardant jacket Rugged and durable Superior Performance Testing Every termination is tested to ensure the highest in network performance State-Of-The-Art Manufacturing Processes
The 8-Fiber Solution for Today s Data Center
The 8-Fiber Solution for Today s Data Center Bill Charuk, SR Product Manager, Data Center Solutions Introduction Data center infrastructure is constantly evolving. Fiber optic installations have used the
Secure/Keyed LC System Solutions Overview
Secure/Keyed LC System Solutions Overview Designing performance and efficiency into your secure network Introduction In recent years, physically discrete fiber connection systems have emerged to respond
Data Center Architecture with Panduit, Intel, and Cisco
Data Center Architecture with Panduit, Intel, and Cisco 0GBASE-T Application Note Integrating Panduit Category 6A Interconnects with the Cisco Nexus TM and Intel Ethernet Server Adapter X0-T 0 PANDUIT
Physical Infrastructure Management Solutions
Physical Infrastructure Management Solutions Physical Infrastructure Challenges Require Innovative Solutions The Need for In-Depth Network Intelligence. With increased acceptance of virtualization, cloud
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431. Visit us at www.testequipmentdepot.com
Datasheet: MultiFiber Pro First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media, virtualization and the need for more
Loss & Continuity Testing with MPO/ MTP Connectors
Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular
24 fiber MPOptimate Configuration and Ordering Guide
-Fiber System Overview -FIBER TRUNKING SOLUTIONS Bandwidth and storage demand is expanding at a breathtaking rate. The environment is rapidly evolving. The impact on data center design and management is
Ethernet Patch Cord Wiring
Ethernet Patch Cord Wiring C ONTENTS Ethernet Patch Cords & RJ-45 Connectors... 2 Ethernet Patch Cords and UTP Cabling... 3 What s all the twisting about?... 4 Ethernet Applications... 5 568A & 568B Wiring
The ABC of Direct Attach Cables
The ABC of Direct Attach Cables Thomas Ko, RCDD Product Manager TE Connectivity Network Speed and Technology 10/40/100 Gbps the transition is occurring right now What are Customers Saying about their 10/40/100
Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure
Data Center Optimization: Component Choice and Innovative Design Combine to Allow the Creation of an Enabling Infrastructure Data Center Spaces Data Center Spaces as Defined by the TIA 942 Standard Source:
Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications
3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition
Overcoming OM3 Performance Challenges
White Paper Overcoming OM3 Performance Challenges First Third-Party Test of Pre-terminated OM3 MTP System Demonstrates Flexibility in 10G Network Designs Gary Bernstein, RCDD Director of Product Management
Obsolete Fiber Technology? Not in my Data Center!
Obsolete Fiber Technology? Not in my Data Center! White Paper October 2011 Author: James Young Technical Director, Asia Pacific www.commscope.com Do you remember when people used to say fiber optics are
Copper Patch Cords. Impact On Network Performance and Reliability
Copper Patch Cords Impact On Network Performance and Reliability 1 The Impact of Copper Patch Cords on Network Performance and Reliability As network infrastructures continue to have a higher impact on
Tools for Building a Better Network
Tools for Building a Better Network Key Differentiator NetVanta Cable/SFP Diagnostics Increasing Productivity with Network Diagnostics As businesses continue to make the most out of every available resource,
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
Fiber in the Data Center
Fiber in the Data Center A NetClear White Paper Rudy Montgelas Senior Fiber Product Manager Ortronics/Legrand Lisa Huff Data Center Applications Engineer Berk-Tek, A Nexans Company March 2008 A New Generation
Data Center Design for 40/100G
Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an
Health Care Solutions
Health Care Solutions Increase Service Levels, Meet Expectations A Unified Approach to Health Care Automation Processes Hospitals, clinics, extended care facilities, and physician s offices are facing
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of
High density Fiber Optic connections in the Data Center. Phil Ward Datacenter Product Market Manager. HUBER+SUHNER AG
High density Fiber Optic connections in the Data Center Phil Ward Datacenter Product Market Manager. HUBER+SUHNER AG How to make fast connections. Phill Ward Bicsi National 2 Conference India Projected
Chapter 4 Connecting to the Internet through an ISP
Chapter 4 Connecting to the Internet through an ISP 1. According to Cisco what two things are essential to gaining access to the internet? a. ISPs are essential to gaining access to the Internet. b. No
Implementing Fast Ethernet
Implementing Fast Ethernet R The Next Generation of Ethernet Fast Ethernet (also known as IEEE 802.3u or 100BASE-T) is quickly becoming the successor to Ethernet as the network topology of choice. Fast
InstaPATCH ZERO Solution Guide
SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving
Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices
Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices Robert Reid (Panduit) Frank Yang (CommScope, Inc) 1 The Presenters Robert Reid Sr. Product Development Manager at Panduit Frank Yang Marketing
HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks
HIGHSPEED ETHERNET THE NEED FOR SPEED Jim Duran, Product Manager - Americas WHITE PAPER Molex Premise Networks EXECUTIVE SUMMARY Over the years structured cabling systems have evolved significantly. This
ANSI/TIA/EIA-570. 570-A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD
BICS I CABLING INSTALLATION PROGRAM ANSI/TIA/EIA-570 Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD Copyright BICSI, October 1999 -A Revisited 1.1 Purpose standardize
Data Center Fiber Cabling Topologies and Lengths. Paul Kolesar IEEE 802.3 HSSG, September 2006
Data Center Fiber Cabling Topologies and Lengths Paul Kolesar IEEE 802.3 HSSG, September 2006 Purpose and background Provide channel length distributions within Data Centers as guide for setting distance
www.commscope.com Data Center Topology Guide
www.commscope.com Data Center Topology Guide Data Center Areas 1 Network Operations Center (NOC) The network operations center or NOC is the location where control of all data center networking, server
Polymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
Keyed LC Connector Solution
features and benefits Eight color-coded mechanical key positions Meets TIA/EIA-568-B requirements Keyed connectors and adapters Full solution availability Keyed LC Connectors Photo LAN758 SPECIFICATION
40/100 Gigabit Ethernet: The Foundation of Virtualized Data Center and Campus Networks
40/100 Gigabit Ethernet: The Foundation of Virtualized Data Center and Campus Networks Yinglin (Frank) Yang, CommScope, Inc Gautam Chanda, Cisco Systems White Paper www.commscope.com Contents Contents
The 50G Silicon Photonics Link
The 50G Silicon Photonics Link The world s first silicon-based optical data connection with integrated lasers White Paper Intel Labs July 2010 Executive Summary As information technology continues to advance,
Arista and Leviton Technology in the Data Center
Visit: www.leviton.com/aristanetworks Arista and Leviton Technology in the Data Center Customer Support: 1-408-547-5502 1-866-476-0000 Product Inquiries: 1-408-547-5501 1-866-497-0000 General Inquiries:
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
Data Center Cabling Design Trends
Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:
Modern Data Center needs 10 th of April, 2014. Andrew Sedman, RCDD Head of Training and Technical Service R&M
Modern Data Center needs 10 th of April, 2014 Andrew Sedman, RCDD Head of Training and Technical Service R&M From the Classical Data Center to the Cloud Prior to cloud computing, a physical server handled
Fibre Channel Fiber Cabling
OVERVIEW This paper will discuss the Fibre Channel standards for fiber cables at both 1Gb and 2Gb speeds, and also some discussion of departures from standard. Items discussed will be cable types, plug
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer [email protected] Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards Optical Fiber
Unified Physical Infrastructure (UPI) Strategies for Data Center Networking
Unified Physical Infrastructure (UPI) Strategies for Data Center Networking Physical Infrastructure Considerations for Smart Data Center Consolidation www.panduit.com WP-08 February 2009 Introduction Improving
Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations
From the April, 2014 Issue of Cabling Installation & Maintenance Magazine Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations Pros and cons exist for each configuration,
Plug & Play Gigabit Ethernet Media Conversion Module. Application Note
Plug & Play Gigabit Ethernet Media Conversion Module Application Note The Plug & Play Universal Systems Media Converter Module offers the best of both worlds easy fiber optic scalability and future proofing
Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center
May 2013 Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center Executive Summary There is no single end-all cabling configuration for every data center, and CIOs, data center
DATA CENTER NETWORK INFRASTRUCTURE. Cable and Connectivity for the Most Demanding Networks. BerkTekLevitonTechnologies.com
DATA CENTER NETWORK INFRASTRUCTURE Cable and Connectivity for the Most Demanding Networks Customer-focused, technology-driven, quality-assured for an unparalleled RETURN ON infrastructure investment DATA
INTRODUCTION TO MEDIA CONVERSION
WHITE PAPER INTRODUCTION TO MEDIA CONVERSION Table of Contents Introduction 1 What is a Media Converter? 1 Advantages of Media Conversion Technology 1 Benefits of Fiber Optic Cabling 2 Types of Media Converters
Cable Specifications and Information
APPENDIX A This appendix provides the connector and pinout information you need for making or purchasing cables used with Cisco VG224 voice gateway. To order cables from Cisco, see the Obtaining Technical
How To Properly Maintain A Fiber Optic Infrastructure
How To Properly Maintain A Fiber Optic Infrastructure Best Practices to Minimize Damage and Failures in Fiber Optic Infrastructures White Paper Rodney Casteel, RCDD, NTS, OSP, Technical Manager, CommScope
DATA CENTRES POWERED BY EXCEL
DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,
THE AMP NETCONNECT MT-RJ OPTICAL FIBER SYSTEM
THE AMP NETCONNECT MT-RJ OPTICAL FIBER SYSTEM The Most Significant Development In Fiber Optic Connectivity Is Now The Connectivity Choice For The Networks Of Today And Tomorrow 2 TABLE OF CONTENTS The
HP ProCurve High-Speed Transceivers Installation Guide
HP ProCurve High-Speed Transceivers Installation Guide Introduction The HP ProCurve High-Speed Transceivers can be installed into a number of HP ProCurve networking devices to provide 100 Mbps and 1000
iseries Ethernet cabling and configuration requirements
iseries Ethernet cabling and configuration requirements iseries Ethernet cabling and configuration requirements Copyright International Business Machines Corporation 1999, 2000. All rights reserved. US
FOCONEC. Network Connectivity & Cabling Management. Overview: Features: Brighter Future
CORDS & CABLE ASSEMBLIES Standard Simplex/Duplex Patch Cords Overview: FOCONEC supplies full series of standard simplex, duplex patch cords or pigtails, designed for interconnection or cross connection
Single Port Gigabit Ethernet Media Converter Board (P/N 201350-xxx) User s Manual And Troubleshooting Guide
Single Port Gigabit Ethernet Media Converter Board (P/N 201350-xxx) User s Manual And Troubleshooting Guide August 12, 2009 Rev C Moog Components Group Springfield Operations 750 West Sproul Road Springfield,
Connectors and Cables
APPENDIX B This appendix describes the connectors, cables, and adapters that you use to connect the switch to other devices. Connector Specifications 10/100 Ports The 10/100 Ethernet ports use standard
Fiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable
Fiber Optic Cable Assemblies Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable 1 Cable assemblies used in patch panels (Fiber Distribution Units) are an essential interface
Security & Surveillance Cabling Systems
Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.
Cable Assemblies. Corning Cable Systems
Corning Cable Systems OptiFit Node Assembly Photo CAPSS1721 Description As the industry s leading supplier of single-mode cable assemblies, Corning Cable Systems offers the most complete line of connectors
Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk
Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk Introduction At the IEEE 802.3 Working Group meeting in July of 2012, the Next Generation BASE-T Call for
Choosing a Small Form Factor Connector Advantages of the LC Connector over the MT-RJ
SYSTIMAX Solutions Choosing a Small Form Factor Connector Advantages of the LC Connector over the MT-RJ White Paper May 2004 www.commscope.com Use of Small Form Factor Connectors is Now Widespread With
Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications
Data Sheet Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output
Cable Assemblies. Pretium EDGE Reverse Polarity Uniboots Photo LAN2217-2218. ST Compatible Ultra PC 12-Fiber Cable Assembly Photo LAN2784
Corning offers the most complete line of connectors and factory-terminated cables, from single-fiber jumpers to high-fiber-count assemblies. As the industry s leading supplier of cable assemblies, Corning
Plug & Play Universal Systems
Plug & Play Universal Systems A LANscape Pretium Plug & Play Universal Systems for Data Centers and Storage Area Networks (SANs) Corning Plug & Play universal systems create a fiber optic tip-to-tip solution
Corning Cable Systems Optical Cabling Solutions for Brocade
Corning Cable Systems Optical Cabling Solutions for Brocade Building high-density, high-port-count, structured cabling solutions to scale storage area networks to thousands of ports Contents Executive
SYSTIMAX Solutions. Intelligent Infrastructure (ipatch) Solutions Guide. www.commscope.com. www.commscope.com 1
SYSTIMAX Solutions Intelligent Infrastructure (ipatch) Solutions Guide 1 Vision + Knowledge = Control SYSTIMAX Intelligent Infrastructure Solutions: Add intelligence to copper and fiber structured cabling
Module Connectors and Cable Specifications
Module Connectors, page 1 Cables and Adapters, page 2 Cleaning the Fiber-Optic Connectors, page 6 Module Connectors RJ-45 Connector The RJ-45 connector is used to connect a Category 3, Category 5, Category
Linear Motion and Assembly Technologies Pneumatics Service. Industrial Ethernet: The key advantages of SERCOS III
Electric Drives and Controls Hydraulics Linear Motion and Assembly Technologies Pneumatics Service profile Drive & Control Industrial Ethernet: The key advantages of SERCOS III SERCOS III is the open,
Enterprise Networks EMEA. Core Products FOR DATA CENTRES
Enterprise Networks EMEA Core Products FOR DATA CENTRES EMEA Data Centre Core Products 1 Data Centres GET IT RIGHT, Right Now. Corning Cable Systems offers tens of thousands of fibre optic products for
Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
First Edition. Copyright Optical Connectivity - all rights reserved - 2003 Rev. 2.3 (Doc. # OC0004-2.3)
Optical Connectivity Fiber Optic Systems Guide First Edition Rev. 2.3 (Doc. # OC0004-2.3) Emerson Network Power Your Comprehensive resource for Data Communications & Power. Optical Connectivity Division