Box and Conduit Fill Calculations



Similar documents
Department of Labor and Industry Electrical Licensing

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Electrical Code Regulation

Residential Electrical Inspection. Checklist

Residential Electrical Inspection. Checklist

STREETLIGHT SYSTEM GROUNDING AND BONDING

BRANCH CIRCUIT AND FEEDER REQUIREMENTS

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

INSPECTION GUDELINES

Entrances to and from Electrical Equipment Rooms

Residential Electrical Inspection Checklist

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

Cable Tray Selection-

Electrical Grounding. Appendix C

The Service Entrance. Technical Terms Drip loop Insulator Meter Meter enclosure

Electrical Wiring Guide

Major Types of Electical Boxes

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

Generator DoCKInG StatIonS

Grounding & Bonding Why it is done And How to Install Properly

The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022.

Raceway and Boxes for Electrical Systems Page 1 of 7

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

Line Loss WSDOT Winter 2008 BZA

POWER DISTRIBUTION. Power and Undercarpet Products POWER AND UNDERCARPET PRODUCTS. Chapter Summary

HomeOwner Wiring. Please remember you are required to contact your inspector for inspections

Washer, Electrical Equipment Bond WEEB

MANUFACTURER S CERTIFICATE OF COMPLIANCE

2012 Electrical Code Changes Module 2 Sections 6-16

BASIC NEC CODE RULES AND DESIGN PRACTICE

Recommended Practices for Designing and Installing Copper Building Wire Systems

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009)

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.

David Brender Copper Development Association Inc. Miramar, March 8, 2013

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

UNDERSTANDING. C&M Corporation 51 South Walnut Street, Wauregan, CT Phone: Fax:

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT

WISCONSIN DEPARTMENT OF SAFETY & PROFESSIONAL SERVICES

Report. Analysis of Cablofil Cable Tray for Power Circuits. Reference: RP10002

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

Code Compliance for Spring Steel Fasteners Based on the 2005 NEC

Electrical Code (NEC) Snake Tray Cable Management Solutions

Electrical Installations A homeowner guide to the Winnipeg Electrical By-law requirements for a Single Family Dwelling, Detached Garage or Shed.

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Short Circuit Current Calculations

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines

GENERAL ELECTRICAL REQUIREMENTS

Massoud Sadeghi: (425) Brett Portwood: (562) Transport Airplane Directorate; ANM-117

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations

The Adventures of Conduit Phil

Washer, Electrical Equipment Bond. WEEB Patent Pending INSTALLATION INSTRUCTIONS. For Kinetic Solar K-Rack only

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

Services. Three Phase Service

CHAPTER 2 EXAMPLES AND TABLES

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

Carlon Zip Box Blue Switch and Outlet Boxes

AC Module Installation Guide Content

Do s and don'ts of connection systems Are there any options when the clearance and creepage distances are not sufficient for UL 1059?

Installation Guide Content for P250xV-240 microinverters

NEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps

NEC CODE QUESTIONS. Western Section IAEI 101 st Annual Meeting September 19-21, 2005

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

XL PREMIUM OIL COOLER KIT

SPECIAL GUIDELINES FOR ELECTRICAL INSTALLATION

HMI display Installation Guide

CMP-8 Raceways, Wireways, Busways, Gutters, Cable Tray, Etc. (per NEC Chapter 3) And Tables 1-4 of Annex C (Conduit & Tubing)

FLEXIBLE COPPER & ALUMINIUM CONNECTIONS. Product Range 1 VGL - ALLIED CONNECTORS

TC Grounding and Bonding for Telecommunications Systems

2011 National Electrical Code Changes

Residential Wiring Guide 12th Edition

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

Mobile Home Pre-Inspection Checklist


Electrical Drawings - Table of Contents

Minimum Standards for Data/Voice Infrastructure in New Building Construction

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4

800 Communications Circuits

IRRIGATION PUMPING Table of Contents - Section 900

Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.

Construction Electrical Terminology. Electricians

BELL WEATHERPROOF BOXES, COVERS AND LIGHTING

Chapter 9. Bonding and Grounding

Conductor Sizing and the National Electrical Code

ELECTRICAL INSPECTION BULLETIN (Effective )

GENERAL WIRING RULES FOR HOUSES

Description. Lesson Outcomes. Assumptions. Terminology. Electrician

Dock Electrical Systems

Transcription:

Box and Conduit Fill Calculations

Volume required per conductor

Conduit fill - Box sizing Table 314.16(a) : Number of conductors in box 600v, nominal or less CONDUCTORS: 1. Conductors originating outside box, terminating in box count as 1 conductor 2. Conductors originating outside box, spliced in box counts as 1 conductor 3. A conductor entering a box, spliced to a conductor leaving box counts as 2 conductors 4. Conductors passing through box without splices or terminations count as 1 conductor 5. A conductor of which no part leaves the box shall not be counted

Conduit fill - Box sizing 2005 NEC Change Looped conductors now count as 2 conductors

EQUIPMENT GROUNDING CONDUCTOR: 1. One, two or more bare, insulated or covered system grounding conductors all count the same size, count as 1 conductor 2. One, two or more bare, insulated or covered system grounding conductors of various sizes, count as one conductor based upon largest equipment grounding conductor 3. A separate ISOLATED equipment grounding conductor counts as 1 conductor in addition to system grounding conductor. Count as size of ISOLATED grounding conductor or largest if various sizes.

CLAMPS: 1. Clamps installed inside box by factory count as 1 conductor 2. Clamps installed in box in the field count as 1 conductor (Conductor size based on largest conductor in box) SUPPORT FITTINGS: 1. Fixture studs count as 1 conductor 2. Fixture hickeys count as 1 conductor (Conductor size based on largest conductor in box)

DEVICE(S) IN BOX: 1. Yoke or strap with switch, counts as 2 conductors 2. Yoke or strap with duplex receptacle counts as 2 conductors 3. Yoke or strap with triplex receptacle counts as 2 conductors 4. Yoke or strap with switch & light on same yoke or strap counts as 2 conductors 5. Yoke with any combination of three devices on same yoke or strap counts as 2 conductors (Conductor size based on LARGEST conductor connected to device or equipment)

Yoke or Strap

Conductor Counts for other than wire Cable Clamps NM 12-2 W/GRD Hickey Fixture Stud Fixture Stud = 1 Conductor Hickey = 1 Conductor Cable Clamps (2) = 1 Conductor Total Conductor Count = 3 Conductors

1 Yoke 1 Device 1 Conductor Counting Devices 1 Yoke 3 Devices 1 Conductor 1 Yoke 1 Device 1 Conductor 1 Yoke 2 Devices 1 Conductor

Through Box Terminate in Box Through Box 2 Terminate in Box 4 Total Count = 6 All Conductors Terminate in Box Count 6 total conductors

Factory installed clamps 8-12 s s & 1 clamp = 9 Box & conduit Fill Calculations Factory or Field Installed Clamps #12 AWG #12 AWG

EGC = Equipment Grounding Conductor IEGC = Insolated Equipment Grounding Conductor BJ = Bonding Jumper Box & conduit Fill Calculations BJ EGC = 1 IEGC = 2 BJ = 0 Total = 2 EGC IEGC To Receptacle

Octagonal / 4/0 Box 2 - #8 AWG 2 - #12 AWG 2 - #12 AWG 2 - #8 @3.00 Cu = 6 Cu in Fix Stud @3.00 Cu in = 3 Cu in 4 - #12 @2.25 Cu in = 9 Cu in Total = 18 Cu in

#14 Bare EGC #8 AWG #12 AWG #18 AWG fixture wire #10 AWG #18 = 1.5 cu in x 2 = 3.00 cu in #14 = 2.0 cu in x 1 = 2.00 cu in #12 = 2.25 cu in x 4 = 9.00 cu in #10 = 2.50 cu in x 2 = 5.00 cu in #8 = 3.00 cu in x 2 = 6.00 cu in Fix Stud = #8 = 3.00 cu in = 3.00 cu in Total Box volume required = 28,00 cu in

Bad Planning

314.16(b)(1) Exception Canopy Cover Box & conduit Fill Calculations 4 - Smaller than #14 Fixture wires EGC Terminations in Canopy Cover Dome Canopy To Fan To Fixture Do not count for Box Fill Calculations

Counting with a device Box & conduit Fill Calculations 2 - #8 AWG 2 - #12 AWG Largest conductor allowed = #10 NEC 110.14(A) 2 - #12 AWG 2 - #8 @3.00 cu in = 6 cu in 4 - #12 @2.25 cu in = 9 cu in Yoke @2.25 cu in = 4.5 cu in Total Volume Required = 19.5 cu in

Conduit Fill Calculations

Major Fraction Change Box & conduit Fill Calculations

What size EMT is needed for 3-2/0 AWG THW Cu conductors and 4-4/0 AWG THHN Cu conductors?

What size EMT is needed for 3-2/0 AWG THW Cu conductors and 4-4/0 AWG THHN Cu conductors? Table 5 Cross-Sectional Area of Individual Conductors 2/0 AWG THW Cu =.2624 X 3 =.7872 4/0 AWG THHN Cu =.3237 X 4 = 1.2984 Total Square Inches for Conductors = 2.0820 Table 4 40% fill column for Over 2 wires. 2.0820 Sq.In. Requires a 2 ½ inch EMT Conduit 40% fill for 2 ½ inch EMT = 2.343 Sq. In. Answer = 2 ½ Inch EMT

What size IMC is required for 6-12 AWG RHH Cu conductors without outer covering and 4-14 AWG RHH Cu Conductors with outer covering?

What size IMC is required for 6-12 AWG RHH Cu conductors without outer covering and 4-14 AWG RHH Cu Conductors with outer covering? Table 5 Cross-Sectional Area of Individual Conductors 14 AWG RHH Cu With Outer Covering =.0293 X 4 =.1172 12 AWG RHH Cu Without Outer Covering =.0260 X 6 =.1560 Total Square Inches for Conductors =.2732 Table 4 40% fill column for Over 2 wires..2732 Sq.In. Requires a 1 inch IMC Conduit 40% fill for 1 inch IMC =.384 Sq. In. Answer = 1 Inch IMC

Box & Conduit Fill Exam 10 Questions 30 Minutes

Box fill Answers Box & conduit Fill Calculations 1. (b) 10.75 cu in 314.16(b) 3 - #12 s @ 2.25 cu in = 6.75 cu in 2. (b) 2 conductors 314.16 (b) 3. (b) 4 Table 314.16(a) 2 - #14 s @ 2.00 cu in = 4.00 cu in 4. (d) 17.5 cu in Table 314.16(b) #10 = 2.5 cu in 7 - #10 s x 2.5 cu in = 17.5 cu in 10.75 cu in 5. (a) 0.0181 in 2 Table 5 (note * notations by insulations) * ONLY APPLIES TO RHH,RHW,RHW-2

Box fill Answers Box & conduit Fill Calculations 6. (d) 39.75 cu in Table 314.16(b) #8 = 3.00 cu in #12 = 2.25 cu in Clamps - #8 = 3.00 cu in 7 - #8 @ 3.00 cu in = 21.00 cu in 1 - #8 @ 3.00 cu in = 3.00 cu in 7 - #12 @ 2.25 cu in = 15.75 cu in 39.75 cu in

3 - #8 ungrounded conductors count as 3 {314.16(b)(1)} 3 - #8 grounded conductors count as 3 {314.16(b)(1)} 3 - #8 grounding conductors count as 1 {314.16(b)(5)} 4 - clamps count as 1 {314.16(b)(2)} 3 - #12 ungrounded conductors count as 3 {314.16(b)(1)} 3 - #12 grounded conductors count as 3 {314.16(b)(1)} 3 - #12 grounding conductors count as 1 {314.16(b)(5)} #8 conductors 7 - #8 @ 3.00 cu in = 21.00 cu in Clamps 1 - #8 @ 3.00 cu in = 3.00 cu in #12 conductors 7 - #12 @ 2.25 cu in = 15.75 cu in 39.75 cu in

7. (b) 2.2831 in² T.5 8. (b) 1 1/4 IMC T.4 9. (a).384in² T.4 10. (C).2637in² T.5