Do s and don'ts of connection systems Are there any options when the clearance and creepage distances are not sufficient for UL 1059?

Size: px
Start display at page:

Download "Do s and don'ts of connection systems Are there any options when the clearance and creepage distances are not sufficient for UL 1059?"

Transcription

1 Do s and don'ts of connection systems Are there any options when the clearance and creepage distances are not sufficient for UL 1059? Speaker: Wolfgang Sichmann, Product Manager PCB Plug-In Connectors, Weidmüller Interface GmbH &Co. KG

2 Contents - Introduction - UL device approvals. Listing - UL component approvals, UL UL 1059 application groups for Terminal Blocks and Connectors - UL 1059 case study of clearance and creepage problem - Option to clear the 600 V barrier via UL 508 / UL840 device approval - For connectors soldered on the printed circuit board - Pollution degree / overvoltage category / clearance and creepage distances - for PCB terminals - Pollution degree / overvoltage category / equivalents of clearance and creepage distances - Wire-end ferrules for the American market - Multiple wire connection at one pole POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 2

3 Introduction The trend for increasingly compact and powerful devices is generally met with higher voltages. While maintaining the same power level, current and connection cross-sections are kept within reasonable limits, which impacts positively on the size of the devices. However, higher voltages increase the requirements for clearance and creepage distances. Connection systems are inevitably following the trend for smaller sizes, which poses a challenge in relation to UL 1059 in particular. The UL 1059's strict regulations for field wiring components are absolutely justified, and illustrate the high demands on usage and handling. The aim here is to avoid mistakes in the field, or if mistakes have been made, to minimise the resulting damage. For the part of the connection system that is installed in the device in a secure manufacturing process, there is an option of approval with reduced clearance and creepage distances as part of the device (factory wiring). However, this means that the UL 1059 regulations also have to be observed in full for everything that is wired up or get connected in the field. With regard to the field connection, further differences to European usage and handling must also be taken into account. Topics such as multiple wire connections and wire-end ferrules underline the convergence but it also shows the differences between Europe and the US. POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 3

4 Difference between field and factory wiring Field wiring Plug or terminal with cable or single wires to connect field components Factory wiring Includes, for example, a plug-in connector, which is installed in the device during manufacturing in line with the applicable manufacturing guidelines. Example: By means of fastening and wiring By means on soldering to the PCB Field wiring = UL 1059 / factory wiring = UL 508(C) POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 9

5 UL 1059 application groups for terminals and plug-in connectors Use Group A: service devices Control and operating consoles Control and monitoring systems Use Group B: commercial appliances Cable-connected devices which are not permanently installed Use Group C: Industrial general All devices and systems for industrial applications Use Group D: Industrial limited ratings All devices and systems for industrial applications with limited current data Use Group E: 601 1,000 (1,500) volt Connection systems in the range of 601 to 1,500 volts back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 10

6 UL 1059: clearance and creepage distances Table Limited ratings The spacings specified in item D of Table 8.1 are applicable to a terminal block for use only in or with industrial control equipment where the load on any single circuit of the terminal block does not exceed 15 A at V, 10 A at V, 5 A at V, or the maximum ampere rating, whichever is less. POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 11 back

7 Case 1: selection of a plug-in connector with corresponding requirements Example Component for field wiring Requirement up to 600 V Class C industrial general V UL 1059 rating data 35 A max. Rated voltage (use group B) Rated current (use group B) Rated voltage (use group C) Rated current (use group C) Rated voltage (use group D) Rated current (use group D) 600 V 35 A 600 V 35 A 600 V 5 A ok. Result: The field wiring component meets the requirements of UL Back to UL 1059 back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 12

8 Case 2: Excerpt from catalogue or data sheet UL 1059 rating data Rated voltage (use group B) Rated current (use group B) Rated voltage (use group C) Rated current (use group C) Rated voltage (use group D) Rated current (use group D) To UL 1059 Through air distance 7.62 mm (0.3 inch) 6.9 mm (0.272 inch) 300 V 35 A 300 V 35 A 600 V 5 A? Example: Requirement up to 600 V Class C industrial general V 35 A max. Result: The requirements are not met for UL 1059 at V but are met for UL 1059 at V. Acc. to Table 8.1, UL 1059 for V we need a: Clearance of 9.5 mm Creepage 12.7 mm back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 13

9 But the requirement is between volts?? What now?? Factory wiring The component assembled on the PCB can be jointly approved under device approval 508 (C) if the component fulfils the factory wiring criteria! Field wiring The counter part (field wiring component) must be approved under UL 1059! POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 14

10 Option of device approval via UL 508 / UL 840 for plug-in connectors on the PCB

11 Guide to device approval via UL 508 and UL 840 Component type test - clearance and creepage distance No UL 1059 Terminal Blocks UL 840 exception UL 508 / 508C No Alternative for PCB Components Standard Requirements Industrial Controls / Power Conversion Equipment UL 508A UL 840 exception No Standard Requirements Industrial Control Panels UL 840 exception UL 2011 No Standard Requirements Factory Automation Equipment NEC - National Electrical Code POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 16

12 Step 1: clearance UL V factory wiring (PCB connectors) UL 508 C Table 36.5 clearance distance = UL 1059 Therfore with UL 508 C exception via UL 840 insulation coordination for the clearance distance Pollution degree UL Overvoltage Category UL 840 Table 8.1 UL 840 Table 8.1 min. clearance - UL component type test clearance - connector larger pitch required No Clearance passed according to UL840 POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 17

13 Step 1/1: Finding the clearance distance Weidmüller type test: Lab report, clearance and creepage distance acc. to UL 1059 clearance! to Acc. to UL 1059 (600 V class C) or UL 508 (C) min. clearance = 9.5 mm min. creepage = 12.7 mm UL 1059 POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 18 back

14 Step 1/2: Finding the pollution degree UL Pollution Degree Pollution degrees based on the presence of contaminants and possibility of condensation or moisture at the creepage distance are as follows: Pollution Degree 1: No pollution or only dry, nonconductive pollution. The pollution has no influence. Pollution Degree 2: Normally, only nonconductive pollution. However, a temporary conductivity caused by condensation may be expected. Pollution Degree 3: Conductive pollution, or dry, nonconductive pollution that becomes conductive due to condensation that is expected. Pollution Degree 4: Pollution that generates persistent conductivity through conductive dust or rain and snow. back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 19

15 power supply Overvoltage category Potential isolation Primary Supply Level Distribution Level Load Level Signal Level Overvoltage category IV Primary supply level Overvolt. category III Distribution level Overvolt. category II Load level Overvolt. category I Signal level Take lightning surge into account back Lightning surges do not have to be taken into account Permanent installation Take into account overvoltage caused by switching operations e.g. household devices No overvoltage taken into account Mainly operations with low voltages e.g. small electric devices POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 20

16 Step 1/3: UL 840 Table 8.1 minimum clearance UL 840 Section 8.9 Clearances selected and measured in accordance with the dimensions in Table 8.1 do not require testing. To type test to overvoltage to pollution back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 21

17 Step 2: Creepage UL V factory wiring (PCB connectors) CTI of material (catalogue) Material Group UL840 (catalogue) 600 V Operating Voltage Pollution degree UL Table 9.1 UL840 min. creepage distance - UL component type test creepage distance -connector larger pitch required No Creepage distance according to UL840 POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 22

18 Step 2/1: Finding the creepage distance Weidmüller type test: Lab report, clearance and creepage distance acc. to UL 1059 creepage! min. Acc. to UL 1059 (600 V class C) or UL 508 (C) min. clearance = 9.5 mm creepage = 12.7 mm to UL1059 back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 23

19 Step 2/2: UL 840 Table 9.3 Finding the pollution degree UL 840 section 9.3 Pollution Degree Pollution degrees based on the presence of contaminants and possibility of condensation or moisture at the creepage distance are as follows: Pollution Degree 1: No pollution or only dry, nonconductive pollution. The pollution has no influence. Pollution Degree 2: Normally, only nonconductive pollution. However, a temporary conductivity caused by condensation may be expected. Pollution Degree 3: Conductive pollution, or dry, nonconductive pollution that becomes conductive due to condensation that is expected. Pollution Degree 4: Pollution that generates persistent conductivity through conductive dust or rain and snow. back to creepage table back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 24

20 Step 2/3: UL 840 Table 9.1 minimum creepage Link to pollution degree info 2 3 Material groups Group CTI I >600 II IIIa IIIb CTI of material PBT 200 Wemid 600 LCP 175 Creepage acc. to type test = 9.66 mm Creepage can not be less then over air distance ( 5.5mm) 6.9mm! to type test 1/2 to pollution degree 2/2 back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 25

21 Summary of the solution for the PCB part of the connector using UL 508(C) and UL 840 New clearance distance 5.5 mm acc. to 508(C) & UL 840 Clearance O.K. Clearance distance according to UL840 No UL 508 (C) New Creepage creepage 3.2 distance mm acc.to 508(C) & UL 840 exception UL 840 exception UL 840 No UL 508A No UL 2011 O.K. exception UL 840 NEC National Electrical Code Creepage distance according to UL840 POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 26

22 The demand for increasingly compact connection systems makes this procedure necessary. job done! Factory wiring 600 V via UL 508 & UL 840 PCB part: Approval together with device approval UL 508(C) und UL 840. The component meets the clearance and creepage requirements for 600 Volt! Field wiring 600V UL 1059 class C Field part: No further action possible or necessary. The component meets the requirements of UL 1059 for 600 V! POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 27

23 Option of device approval via UL 508 / UL 840 for PCB terminals

24 Guide to device approval via UL 508 and UL 840 Component type test - clearance and creepage distance No UL 1059 Terminal Blocks UL 840 exception UL 508 / 508C No Alternative for PCB Components Standard Requirements Industrial Controls / Power Conversion Equipment UL 508A UL 840 exception No Standard Requirements Industrial Control Panels UL 840 exception UL 2011 No Standard Requirements Factory Automation Equipment NEC - National Electrical Code POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 29

25 Step 1: Clearance A (equivalency) UL V 9.5 mm clearance distance as per Table 7.1 UL 508 C Table 36.5 clearance = UL 1059 Therefore with UL 508C exception protection against stray strands (splicing) + UL 50 8C exception via UL 840 clearance A (equivalency) Table 7.1 UL 840 Table 7.1 Clearance A (Equivalency) No HV test positive larger pitch required Clearance according to UL840 back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 30

26 Step 1/1: Finding the clearance distance Weidmüller type test: Clearance and creepage distance acc. to UL 1059 clearance! min. Acc. to UL 1059 (600 V class C) or UL 508 (C) min. clearance = 9.5 mm creepage = 12.7 mm back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 31

27 Step 1/2: (replacement test for shorter clearance distances) Finding the test voltage UL Clearance A (Equivalency) 7.1 Other than as noted in 1.6, the requirements of this section may be used to evaluate clearances less than those specified for the end product while maintaining the same overvoltage withstand capability for the equipment. 7.2 A clearance, less than the specified minimum through air spacing, in the product standard, may be suitable if acceptable results are obtained when tested in accordance with Section 14, Dielectric Voltage-Withstand Tests, using a voltage with a value in accordance with Table 7.1 back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 32

28 Step 2: Creepage UL V (PCB terminals) CTI of material (catalogue) Material group UL 840 (catalogue) 600 V Operating voltage Pollution degree UL Table 9.1 UL 840 min. creepage distance - UL component type test creepage distance connector larger pitch required No Creepage distance according to UL 840 POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 33

29 Step 2/1: Finding the creepage distance Weidmüller type test: Clearance and creepage distance acc. to UL 1059 creepage! Back Acc. to UL 1059 (600 V class C) or UL 508 (C) min. clearance = 9.5 mm min. creepage = 12.7 mm to table 9.1 2/4 back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 34

30 Step 2/2: Finding the pollution degree UL Pollution Degree Pollution degrees based on the presence of contaminants and possibility of condensation or moisture at the creepage distance are as follows: Pollution Degree 1: No pollution or only dry, nonconductive pollution. The pollution has no influence. Pollution Degree 2: Normally, only nonconductive pollution. However, a temporary conductivity caused by condensation may be expected. Pollution Degree 3: Conductive pollution, or dry, nonconductive pollution that becomes conductive due to condensation that is expected. Pollution Degree 4: Pollution that generates persistent conductivity through conductive dust or rain and snow. Back to table 9.1 2/4 back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 35

31 Step 2/3: UL 840 Table 9.1 minimum creepage Link to pollution degree info 2 3 Material groups Group CTI I >600 II IIIa IIIb CTI of material PBT 200 Wemid 600 LCP 175 to pollution degr. Creepage acc. to type test = 12,6 mm Creepage can not be less then over air distance (= 8.8mm)! to type test back POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 36

32 Summary: Possible dimensioning of clearance and creepage distances for UL 600 V Product standards UL 1059 requirements clearance / creepage > 9.5 mm for 600 V > 12.7 mm > 6.4 mm for 300 V > 9.5 mm UL 1059 OK for mm from lab. rep. OK for 300 V 9.66 mm from lab. rep. Device standards UL 508 (C) Alternative assessment (insulation coordination) UL 840 Table 9.1 UL 840 Material Group I ( Wemid ) Pollution degree 2 3 Through air 5.5 mm 5.5 mm requ. Creepage (3.2) 5.5mm 8.0 mm requ. OK 600 V OK 600 V Protection against 8.8 mm from lab. rep. > 6.4mm OK for 300 V + + > 9.5 mm 12.6 mm from lab. rep. stray for 300 V POWER FORTONIC FORUM 19 settembre 2013 strands Surge voltage test 10.7 kv no clearance measurement Creepage (3.2) 8.8 mm 8.8 mm requ. OK 600 V Acc. to UL 1059 (600 V Class C) or UL 5.08 (C) min. clearance = 9.5 mm min. creepage = 12.7 mm Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 37

33 Wire-end ferrules for the American market Tools - The ferrules may only be used together with tested tools Twin wire-end ferrules - As they have not been approved, the use of twin wire-end ferrules are not allowed in either control or power circuits Wire-end ferrules for power circuits - All wire-end ferrules must be approved by UL - Can be used in field and factory wiring POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 38

34 Wire-end ferrules for the American market Wire-end ferrules in control circuits - Under factory wiring conditions and < AWG 14, wire-end ferrules may also be used without approval. For UL 508A - There is a UL guideline that permits the usage in control and power circuits under factory wiring conditions UL Usage as in UL 508A is planned UL 508C - No approval is planned for this at the moment POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 39

35 Multiple wire connection at one pole Multiple wire connection - the combination of the used connection system with the used conductors must always to be tested by UL Test - UL will test each combination with the full testing programme Wire cross-section and conductor type - Only conductors with the same cross-section and of the same type may be used Number of conductors per connection - The number of conductors approved by UL is indicated in the designation in brace before the wire cross-section e.g.: (4) AWG 12 str - This really does mean that only four conductors may be used. Two, three or more than four conductors are not permitted. POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 40

36 Any questions? Thank you! POWER FORTONIC FORUM 19 settembre 2013 Wolfgang Sichmann Weidmüller Interface GmbH & Co. KG Slide 41

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials VDE Information General Information The voltage which can be applied to a terminal depends on the relevant regulations, the installation conditions and, of course, the dimensions and insulating materials

More information

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment Scott Aldous, Compliance Engineer What is Insulation Coordination? From IEC 60664-1, Edition 1.2: So what does that mean

More information

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi One of the most common errors uncovered by product safety engineers stems from manufacturers and designers failing to fully

More information

EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH

EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH ENGLISH EMOSAFE EN-100 Product Data Sheet Network Isolators for PCB assembly November 2013 1 GENERAL DESCRIPTION The EMOSAFE EN-100 Network Isolator interrupts all galvanically conducting connections (conductors

More information

RY2 miniature industrial relays

RY2 miniature industrial relays 6 RY2 Relays of general application For plug-in sockets, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting Flat insert connectors - faston x 0,5 mm Recognitions, certifications, directives: RoHS,

More information

picomax The Pluggable Connection System

picomax The Pluggable Connection System picomax The Pluggable Connection System TECHNOLOGY THIS SPECIALIZED CAN T MEET ALL REQUIREMENTS. YES IT CAN. CONTENTS picomax Pin spacing: 3. mm/0.138 in;.0 mm/0.197 in; 7. mm/0.29 in Versatile Pluggable

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

GMKDS 3/ 3-7,62. Extract from the online catalog. Order No.: 1731734

GMKDS 3/ 3-7,62. Extract from the online catalog. Order No.: 1731734 Extract from the online catalog GMKDS 3/ 3-7,62 Order No.: 1731734 The illustration shows a 2-position version PC terminal block, Nominal current: 24 A, Nom. voltage: 500 V, Pitch: 7.62 mm, Number of positions:

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

SMD TERMINAL BLOCKS. Small is Big!

SMD TERMINAL BLOCKS. Small is Big! SMD TERMINAL BLOCKS Small is Big! SMD TERMINAL BLOCKS A compact and low-profile PCB connection is required to achieve the most uniform light distribution, while minimizing shadowing. WAGO s surface-mount

More information

PC 4/ 4-ST-7,62. Extract from the online catalog. Order No.: 1804920

PC 4/ 4-ST-7,62. Extract from the online catalog. Order No.: 1804920 Extract from the online catalog PC 4/ 4-ST-7,62 Order No.: 1804920 The figure shows a 5-pos. version of the product Plug component, nominal current:, rated voltage: 400 V, pitch: 7.62 mm, no. of positions:

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

08. SEK IDC CONNECTORS

08. SEK IDC CONNECTORS . IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these

More information

PC 4/ 2-ST-7,62. Extract from the online catalog. Order No.: 1804904

PC 4/ 2-ST-7,62. Extract from the online catalog. Order No.: 1804904 Extract from the online catalog PC 4/ 2-ST-7,62 Order No.: 1804904 The figure shows a 5-pos. version of the product Plug component, Nominal current: 20 A, Nom. voltage: 400 V, Pitch: 7.62 mm, Number of

More information

Tables Technical data Standards Explanations Increased safety e

Tables Technical data Standards Explanations Increased safety e & DATA Tables Technical data Standards Explanations Increased safety e (printed on devices also as "Ex e") 1411 Contents facts & DATA Contents facts & data Cable glands Pg/metric Tables, technical data

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

SMD Terminal Blocks with Push-Buttons

SMD Terminal Blocks with Push-Buttons SMD Terminal Blocks with Push-Buttons SMD Terminal Blocks Small is Big WAGO s new SMD Terminal Blocks provide push-button termination for conductors 0. 0.75 mm/awg 4 18 (060 Series) and 0.5 1.5 mm/awg

More information

14 PHOENIX CONTACT Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108. info@powermation.com - 800-843-9859 - www.powermation.

14 PHOENIX CONTACT Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108. info@powermation.com - 800-843-9859 - www.powermation. 14 PHOENIX CONTACT PLUSCON circular is a circular connector for use in industrial automation. The range of design sizes available is varied, starting with the design sizes M5 to M8 and M1, for sensor/actuator

More information

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket Technical Datasheet SNK64D00 Catalogue Page SNK64S00 ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket - Ease your test operations with the built-in test sockets, - Screwdriver

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

XG2. Flat Cable Connectors for PCBs. Achieve Total Cost Reduction through High-density Mounting and Reduced Wiring. Terminal Arrangement

XG2. Flat Cable Connectors for PCBs. Achieve Total Cost Reduction through High-density Mounting and Reduced Wiring. Terminal Arrangement Flat Cable Connectors for PCBs XG2 Achieve Total Cost Reduction through High-density Mounting and Reduced Wiring IDC connections allow you to wire all terminals at once without terminating the cable. Can

More information

01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS

01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS . HARTING RJ INDUSTRIAL ETHERNET CONNECTORS Ethernet is is coming up to standard industrial interface. Therefore, automation devices such as controllers, sensors and actuators feature possess on one or

More information

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket Technical Datasheet SNK636D00 Catalogue Page SNK636S00 ZS-SF-T Screw Clamp Terminal Blocks For x 0 and x fuses - with test socket - Protect your circuit with x and x0 fuse terminal blocks (fuse not supplied

More information

Product Information Sheet UH36 Hi Pot Tester

Product Information Sheet UH36 Hi Pot Tester Product Information Sheet UH36 ETL Prüftechnik GmbH Telefon: +49 711 83 99 39-0 E-Mail: info@etl-prueftechnik.de Carl-Peters-Straße 23 D-70825 Korntal-Münchingen Telefax: +49 711 83 99 39-9 Internet: www.etl-prueftechnik.de

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Technicaldata General

Technicaldata General Currenttransformer-operatedoverloadrelay,60-90A,1N/O+1N/C Partno. ZW7-90 Articleno. 002618 CatalogNo. XTOT090C3S Deliveryprogramme Product range ZW7 current transformer-operated overload relays Description

More information

AN583: Safety Considerations and Layout Recommendations for Digital Isolators

AN583: Safety Considerations and Layout Recommendations for Digital Isolators AN583: Safety Considerations and Layout Recommendations for Digital Isolators This application note details the creepage and clearance requirements of an isolator type component, such as a digital isolator,

More information

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade Technical Datasheet SNK646D00 Catalogue Page SNK646S00 ZS6-S Screw Clamp Terminal Blocks Disconnect with blade - Ease your disconnect operations with the disconnect blade operated by hand or with a screwdriver,

More information

Feed-through terminal block - SSK 110 KER-EX - 0502058

Feed-through terminal block - SSK 110 KER-EX - 0502058 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid

More information

J TB/TW Temperature limiter, temperature monitor

J TB/TW Temperature limiter, temperature monitor JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net

More information

Product Information Sheet UH28CS-12kV Hi Pot Tester

Product Information Sheet UH28CS-12kV Hi Pot Tester Product Information Sheet UH28CS-12kV ETL Prüftechnik GmbH Telefon: +49 711 83 99 39-0 E-Mail: info@etl-prueftechnik.de Carl-Peters-Straße 23 D-70825 Korntal-Münchingen Telefax: +49 711 83 99 39-9 Internet:

More information

Spring Cage Feed-Through Terminal Blocks ST

Spring Cage Feed-Through Terminal Blocks ST Spring Cage Feed-Through Terminal Blocks ST The product family ST with the new spring cage system "mini spring" is extremely space-saving. Space is saved thanks to a clearly smaller spring system without

More information

BRÖCKSKES D-VIERSEN PV1-F 4,0 mm BRÖCKSKES D-VIERSEN PV1-F 4,0 mm d d 2 2 C VDE-REG.-Nr. 8292 10/2009

BRÖCKSKES D-VIERSEN PV1-F 4,0 mm BRÖCKSKES D-VIERSEN PV1-F 4,0 mm d d 2 2 C VDE-REG.-Nr. 8292 10/2009 d BRÖCKSKES BRÖCKSKES D-VIERSEN D-VIERSEN PV1-F PV1-F 4,0 mm 4,0 2 mm VDE-REG.-Nr. 2 C 8292 10/2009 s - THE COMPANY DIN EN ISO 9001 More than 60 years of experience in temperature measurement and control

More information

Low Voltage Products. Switches Automatic Transfer Switches

Low Voltage Products. Switches Automatic Transfer Switches Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,

More information

Powermate Range Pitch 7.62

Powermate Range Pitch 7.62 owermate Range itch 7.62 in headers Socket connectors CB connection Solder connection SV 7.62/90 500 V / 43 A SV 7.62/180 500 V / 41 A.2.4 Cable connection Clamping yoke connection Tension clamp connection

More information

ZS25 Screw Clamp Terminal Blocks Feed-through

ZS25 Screw Clamp Terminal Blocks Feed-through Technical Datasheet SNK668D0 Catalogue Page SNK678S0 ZS Screw Clamp Terminal Blocks Feed-through Save space by connecting conductors up to mm² AWG in just mm 0.47 in spacing. SNK68V004 SNK004F0000 D CAD

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

STANDARD MICRO-D CONNECTORS

STANDARD MICRO-D CONNECTORS STANDARD MICRO-D CONNECTORS RECTANGULAR CONNECTORS Pigtail connector - Metal shell.............................. 56 Pigtail connector - Low profile - Metal shell.................... 58 Pigtail connector

More information

Cable Tray Selection-

Cable Tray Selection- Cable Selection- For allowable cable types see the Appendix page A-9. The following guidelines are based on the 2002 National Electrical Code, Article 392. I) Number of Multiconductor Cables rated 2000

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

MKDSN 1,5/ 3-5,08. Extract from the online catalog. Order No.: 1729131

MKDSN 1,5/ 3-5,08. Extract from the online catalog. Order No.: 1729131 Extract from the online catalog MKDSN 1,5/ 3-5,08 Order No.: 1729131 The figure shows a 10-position version of the product PC terminal block, Nominal current: 13.5 A, Nom. voltage: 250 V, Pitch: 5.08 mm,

More information

Jack to Jack adapters Plug to Plug U-Link connectors PCB Right angle plastic PCB Right angle - metal. Ordering Codes

Jack to Jack adapters Plug to Plug U-Link connectors PCB Right angle plastic PCB Right angle - metal. Ordering Codes BNC 75Ω RF CONNECTORS BNC 75Ω RF CONNECTORS To meet the need for higher performance, impedance matched cable interconnections, Amphenol offers a full line of 75 ohm BNC connectors. These connectors can

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

5SV Residual Current Protective Devices

5SV Residual Current Protective Devices s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

TX OPEN RS232/485 module

TX OPEN RS232/485 module s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

PC 4/ 5-STF-7,62. Extract from the online catalog. Order No.: 1828278

PC 4/ 5-STF-7,62. Extract from the online catalog. Order No.: 1828278 Extract from the online catalog PC 4/ 5-STF-7,62 Order No.: 1828278 The figure shows a 5-pos. version of the product Plug component, Nominal current: 20 A, Nom. voltage: 400 V, Pitch: 7.62 mm, Number of

More information

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase

More information

Analog signal converters CC-E I/I Current / current isolators

Analog signal converters CC-E I/I Current / current isolators ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between

More information

IEC Connectors. Introduction

IEC Connectors. Introduction Introduction IEC Connectors A full range of quality mains rated inlets, outlets and connectors conforming to IEC and EN 60320 specifications carrying UL, CSA, VDE and other approvals. With electrical ratings

More information

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02.

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02. Directory chapter 02 - () Types D, E, F, FM, 2F, F9, interface connectors I/U Page Technical characteristics types D and E.............................. 02.10 Type D connectors.................... 02.11

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Cable Solutions for Servo and Variable Frequency Drives (VFD) Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect

More information

1 POLE - 16A 80A Inrush type. (b) Contact configuration A : 1 form A (SPST-NO) C : 1 form C (SPDT) (standard type "K" only)

1 POLE - 16A 80A Inrush type. (b) Contact configuration A : 1 form A (SPST-NO) C : 1 form C (SPDT) (standard type K only) FTR-K1 SERIES POWER RELAY 1 POLE - 16A 80A Inrush type FTR-K1 Series FEATURES Peak 80A inrush current (1 form A type) Low profile (height: 15.7mm) HIGH INSULATION Insulation distance (between coil and

More information

ZIF Connector & Flat Flexible Cable

ZIF Connector & Flat Flexible Cable ZIF Connector & Flat Flexible Cable 09/08-1 ZIF Connector & Flat Flexible Cable As the demand for higher density in electronic equipment increases, the use of Flexible Flat Cable (FFC) or Flexible Printed

More information

THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES

THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES What is Hipot? HIPOT is the short term for high potential (high voltage).

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,

More information

40 Series - Miniature PCB/Plug-in relays 8-10 - 16 A. Features 40.31 40.51 40.52

40 Series - Miniature PCB/Plug-in relays 8-10 - 16 A. Features 40.31 40.51 40.52 Features 40.31 40.51 40.52 1 & 2 Pole relay range 40.31-1 Pole 10 A (3.5 mm pin pitch) 40.51-1 Pole 10 A (5 mm pin pitch) 40.52-2 Pole 8 A (5 mm pin pitch) PCB mount - direct or via PCB socket 35 mm rail

More information

AMPSEAL* Automotive Plug Connector and Header Assembly

AMPSEAL* Automotive Plug Connector and Header Assembly AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

VD4. Vacuum circuit-breaker

VD4. Vacuum circuit-breaker VD4 Vacuum circuit-breaker VD4. The economical solution in power distribution. Applications: Power stations Transformer stations Chemicals industry Steel industry Automotive industry Airport power supply

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data.

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data. Micro Contactors Micro Contactor Relays 0 Micro Contactors Micro Contactors With Solder Pins Coil voltages Micro Reversing Contactor 3 Technical Data 4 Dimensions 8 9 Micro Contactor Relays 4pole C Operated

More information

EDITION 2012 CABLE SYSTEMS

EDITION 2012 CABLE SYSTEMS EDITION 2012 CABLE SYSTEMS Cable fittings for high voltage networks Welcome to the CABLE SYSTEMS Centre of Competence. Our range of cable accessories offers solutions for virtually all applications in

More information

Electronic housing BC for distributor boards

Electronic housing BC for distributor boards Electronic housing BC for distributor boards The requirements of modern building automation grow constantly and change with regard to comfort, control, intelligent linking of systems and their communication

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Features. Applications. Truth Table. Close

Features. Applications. Truth Table. Close ASSR-8, ASSR-9 and ASSR-8 Form A, Solid State Relay (Photo MOSFET) (0V/0.A/0Ω) Data Sheet Description The ASSR-XX Series consists of an AlGaAs infrared light-emitting diode (LED) input stage optically

More information

Medium voltage insulator

Medium voltage insulator Medium voltage insulator Line post insulators type R-ET Commercial designation LPI 24 N ET 1) LPI 24 L ET/5 1)2) LPI 24 L ET/6 1)2) LPI 38 L ET 1) esignation acc. to IEC 720 R 12,5 ET 125 N R 12,5 ET 125

More information

Emergency lighting units EM powerled

Emergency lighting units EM powerled M BASIC 1 W Combined emergency lighting Driver 1 4 W Product description Emergency lighting Driver for manual testing SEV for output voltage < 60 V DC ow-profile casing (21 x 30 mm cross-section) 5-year

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

EGSTON Standard E2xFxWx 12W

EGSTON Standard E2xFxWx 12W General description The family of switchmode power supplies offers an unmatched degree of flexibility and performance fulfilling even the most stringent requirements. Highly flexible electrical configuration

More information

FP2 Relay. The Best Relaytion

FP2 Relay. The Best Relaytion The Best Relaytion 2 pole telecom / signal relay Through Hole Type (THT) Polarized. Relay types: non-latching with1 coil latching with 1 coil latching with 2 coils Features Telecom / signal relay (dry

More information

HARTING Ethernet Cabling 8-poles Overview

HARTING Ethernet Cabling 8-poles Overview Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs

More information

V REG.-Nr. 115719, Z E135149 Technical data 2-pole 4-pole Rated current 12 A 6 A SCHRACK. Accessories Miniature Relay PT. General Purpose Relays

V REG.-Nr. 115719, Z E135149 Technical data 2-pole 4-pole Rated current 12 A 6 A SCHRACK. Accessories Miniature Relay PT. General Purpose Relays Accessories Miniature Relay PT Easy replacement of relays on a densely packed DIN rail No reduction of protection class or creepage/clearance with plastic retainer Plug-in indicator- and protection modules

More information

Tri-Rated Flexible PVC Equipment Wire

Tri-Rated Flexible PVC Equipment Wire Application: High temperature, flame retardant wire designed for use in the switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier

More information

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH Amphenol C 091 A/B/D Circular Connectors Amphenol-Tuchel Electronics GmbH C 091 A Main Features Metal threaded coupling acc. to IEC. Number of contacts are 2 to 8, 12 and 14. Internal metal strain relief

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

EMC Engineering Guidelines For Automation Systems PS 4 PS 416 04/97 AWB 27-1287-GB

EMC Engineering Guidelines For Automation Systems PS 4 PS 416 04/97 AWB 27-1287-GB EMC Engineering Guidelines For Automation Systems PS 4 PS 416 1st edition 04/97 Moeller GmbH, Bonn Author: Werner Albrecht Editors: Klaus Krüger, Thomas Kracht Translator: Chris Baker, Terence Osborn Contents

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

Feed-through terminal blocks for high-current applications

Feed-through terminal blocks for high-current applications 596 PHOENIX CONTACT With the feed-through terminal blocks, you can freely select the connection technology. Choose between traditional screw connection, robust bolt connection, and convenient push-in connection

More information

TEST REPORT. Report nº: 13.08.053.199 LABEL Date: 01-10-2013 Laboratório de Ensaios Eléctricos Page nº: 1/11

TEST REPORT. Report nº: 13.08.053.199 LABEL Date: 01-10-2013 Laboratório de Ensaios Eléctricos Page nº: 1/11 Laboratório de Ensaios Eléctricos Page nº: 1/11 TESTING/ELABORATION: Hugo Santos JOB: Laboratory Technician VERIFICATION: Sónia Valério JOB: Laboratory Technician TECHNICAL APPROVAL: João Costa JOB: Technical

More information

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting Series - Relay interface modules 8-10 - 16 A Features.01.02 1 & 2 pole relay interface modules, screw terminal socket, mm wide. Ideal interface for PL and electronic systems.01-1 Pole 16 A.02-2 Pole 8

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Keystone Network Isolator with ESD- and Lightning Protection

Keystone Network Isolator with ESD- and Lightning Protection Keystone Network Isolator with ESD- and Lightning Protection Introduction The Network Isolator is utilized in copper-based network connections (Ethernet), in order to protect a device linked with the network

More information

Industrial circular connectors

Industrial circular connectors Industrial circular connectors M 16 M 58 010 CONINVERS - M16 to M58 circular connectors for industrial applications CONINVERS GmbH, an independent company, is the specialist for M16 to M58 circular connectors

More information

white paper Ferrules: Your Best Insurance Against Costly Connection Failure Executive Summary

white paper Ferrules: Your Best Insurance Against Costly Connection Failure Executive Summary Ferrules: Your Best Insurance Against Costly Connection Failure white paper Executive Summary Thanks to its superior flexibility, longer flex life*, and resistance to vibration, insulated stranded wire

More information

Automation Solutions. LÜTZE LCOS empty housing for Industrial Automation

Automation Solutions. LÜTZE LCOS empty housing for Industrial Automation Automation Solutions LÜTZE LCOS empty housing for Industrial Automation Open, modular, universal: The new intelligent electronic housing LÜTZE LCOS Flexible: Use of the housing as a standalone solution

More information