OZW30. Central Unit SYNERGYR



Similar documents
Heating Controller. Building Technologies HVAC Products

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RRV934. Multi-controller. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

Digital input modules

PCS0100en Persy Control Services B.V. Netherlands

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

QFP910. Water detector. Building Technologies. CE1N2732en Synco living

OZS Web server. For LPB/BSB plants

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

TX OPEN RS232/485 module

Temperature & Humidity SMS Alert Controller

Drayton Digistat +2RF/+3RF

OZW672...V5.2. Web-Server. For LPB/BSB plants

HMI display Installation Guide

FIREDEX Conventional Fire Panels

Operating Software Service Tool

Adjustable room thermostat for heating only or cooling only systems

IN-OUT Thermometer with Cable Free Sensor and Clock

Voltage Regulator SPAU 341 C. Product Guide

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Disturbance Recoder SPCR 8C27. Product Guide

Duct Humidity Transmitter

Smile. The All-In-One Heating Controller

Product Information Fire alarm panel 8000 C

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

HCR3.2/.. Chipcard reader HOTEL SOLUTION

How To Control A Korean Korean Power Plant

Product Information Sheet UH36 Hi Pot Tester

DC Electronic Loads 8500 series

Quick Connect. quick - simple - efficient.

Rack mounted telephone- and leased line modem for industrial applications

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

Repeaters and Mimics Data Sheet

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

TYXIA. * _Rev.1* Installation and User Guide. Wireless receiver. TYXIA RF channel

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Master & Amplifier For ModuSat Communal Heating

PD 100A. Printing data system

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

Telephone- and leased line modem for industrial applications TD-36

IntesisBox KNX Mitsubishi Heavy Industries AC

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

Permissible ambient temperature Operation Storage, transport

Portal Software GSM-PRO Run LED displays module activity Com LED displays activity on the GSM network GSM-PRO

Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers

Data logger. Installation and operating instructions. Read carefully before installation, commissioning and operation.

Installation & User Instructions

DCS Data and communication server

1. SAFETY INFORMATION

Room Temperature Sensors

Synco Central Communication Unit OZW771 Basic Documentation

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

Product Release LPB Web server V3.0. Infrastructure & Cities

Installation manual. Generator Paralleling Controller GPC multi-line C

OZW V2.0. Web server. Synco TM, Synco TM living

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

ABB Drives. User s Manual HTL Encoder Interface FEN-31

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

AC-115 Compact Networked Single Door Controller. Installation and User Manual

VAV compact controller KNX / PL-Link

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Engineering and service software For KNX and LPB plants

Modular I/O System Analog and Digital Interface Modules

For UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

T0118 T2118 T3118. Instruction Manual

HYDRUS ULTRASONIC METER

KRONOS GA11 WEEKLY-PROGRAMMING DIGITAL CHRONOTHERMOSTAT FOR THE REMOTE CONTROL OF HOT AIR GENERATORS THROUGH BRAHMA INTERFACE BOARD APPLICATION

Remote Monitoring and REC 501 Control Unit Product Guide

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

Electronic Control Devices The European Product Catalogue 2007

DBS720 / FDS221-R / FDS221-W Sounder base, Alarm sounders

HVAC central apartment unit with consumption data acquisition

Panel Meters and Controllers Modular Panel Meter Type EDM 35

3500/93 System Display

NC-12 Modbus Application

Flush-mounted room thermostats

Introduction. In this Self-study Programme we will explain to you the design and function of the CAN data bus. SSP 186/01

Applied Electronics. Commercial Dimming System UPDATE NOTICE

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

ZC-24DO CANopen I/O Module: 24 Digital Outputs

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

LMS The modular management system for condensing boilers. Control Products & Systems OEM. Answers for infrastructure.

GSM ATT Modules Simply effective remote control

ABB i-bus KNX Fan Coil Controller FC/S 1.1

INSTALLING A/C ADAPTER

Power Meter Series 700

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

REMOTE TERMOMETER TE 219 LED USER MANUAL

SLIM LINE FUME HOOD MONITOR

ST Series POWER SUPPLIES USER INSTRUCTIONS

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Transcription:

2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control in the apartments. Has an impact on heat generation depending on the apartments' demand for heat. Acquires operating state signals, actual values and faults. Passes alarms to an operator station. Use The OZW30 central unit is a component of the SYNERGYR control and billing system. The following system functions are only possible when using the central unit: Central readout and storage of the most important consumption data from the individual apartments Fault indication and logging Straightforward readout with the help of the memory card Acting on heat generation For the field of use of the SYNERGYR system, refer to Data Sheets N2800 to N2803 (System Overview). CE1N2841en 04.11.2009 Building Technologies

Functions Collection of consumption data (proportion of thermal energy, DHW, electricity, gas, etc.) acquired in the individual apartments Generation of a consumption data image Delivery of consumption data for external evaluation, via an interface or on a memory card Preselection of minimum and maximum limits of the room temperature setpoints for all apartments Preselection of a 24-hour program for normal and setback temperatures in all apartments Acting on heat generation depending on the actual heat demand from the apartments Acquisition and storage of signals with the possibility of querying from a higher level Interrogation of consumption data of all apartments via the buttons and the display Remote interrogation of consumption data via PC Passing alarms to an operator station Providing support in connection with fault diagnostics by offering the ability to query all important parameters and data of the apartments and the heating group Powering plant via the building bus and a conduit box Type summary Description Central unit Memory card 128 KB Memory card 512 KB Operating set (German) Operating set (English) Operating set (French) Operating set (Dutch) Operating set (Italian) Operating set (Swedish) Operating set (Danish) Type reference OZW30 ALC30.128 ALC30.512 ARG30.DE ARG30.GB ARG30.FR ARG30.NL ARG30.IT ARG30.SV ARG30.DA The operating set is comprised of operating cards and operating manual. Ordering When ordering, please give: Type reference OZW30 for the central unit Type reference of the required operating set If required, type reference ALC30 for the memory card For central unit upgrades, the current software version can be ordered separately: Description Part number Program storage OZW30 ( 16 pairs) 4 340 1047 0 2/9

Equipment combinations The units of the SYNERGYR system allow exchange of data via the building bus. Using version 3 or higher, the central unit can communicate with the following types of ALBATROS heating controllers via LPB: RVL469 of version 3 or higher, RVL47 / RVL470 of version 1.5 or higher, RVL471 of version 1.1 or higher, RVL472 of version 1.0 or higher RVL479, RVL480, RVL481, RVL482 (all of version 1.0 or higher) RVA43.222 of version 2.1 or higher, RVA43.223 / RVA46.531 of version 2.5 or higher, RVA47.320 / RVA63.242 of version 1.1 or higher, RVA63.280 / RVA66.540 of version 1.0 or higher, RVA65.642 of version 1.2 or higher, RVA65.643 of version 2.3 or higher RVD2 of version 1.1 or higher RVP3 of version 1.1 or higher RVP540 of version 1.2 or higher, RVP550 of version 2.3 or higher The LPB is connected directly to the building bus. Using the H-bus, the central unit can communicate with the following types of heating controllers: RVL55 and RVL50 of version 4.0 or higher RVP75.230/237900 and RVP45.500/900 and RVP40.3, RVP97 of series D or higher, version 4.0 Communication with a PC can be established via the RS-232 port in which case the PC requires the ACS30 readout software. Technical design Setting the parameters Interrogation of collected data Evaluation of collected data Parameter setting on the central unit can be accomplished in 2 ways: Via the buttons directly on the central unit; integrated in the central unit is a set of menu cards which describe all parameters that can be set Via the RS-232 port with the help of a PC If there is modem communication, the parameters must always be set via PC. The central unit offers 2 choices of querying consumption data: Directly: Each apartment can be called up via the buttons and the required data can be queried; the data will appear on the display of the central unit Remotely: If the central unit communicates with a PC, the latter can be used to query all apartments and their data In addition, it is possible to call up data such as actual values, etc. (refer to "Diagnostics"). The central unit collects the consumption data acquired and stored in each apartment at regular intervals: Thermal energy, DHW, electricity, gas, etc. For each apartment, the central unit generates an image in which the data are entered. The image is ready configured and continually updated. The image accepts the following values: Current values Set day values Monthly values In addition, the central unit calculates the number of heating degree days. It is capable of acquiring the pulses from a maximum of 192 meters and from 6 "general meters", resulting in the following choices: 3/9

Max. number of apartments Number of WRI80 or WRV per apartment Number of AEW2.1 per apartment Number of AEW2.1 for preacquisition (with addresses) Address plug for WRI80 or WRV and AEW2.1 Configuration 1 Configuration 2 Configuration 3 Configuration 4 32 48 96 32 1 1 1 0 2 1 0 2 3 3 3 3 (121 123) (121 123) (121 123) (121 123) 1 32 1 48 1 96 1 32 Delivery of collected data Acting on room temperature control 24-hour program Setpoint limitations Acting on heat generation Continuous load compensation For evaluation, the data must be loaded to a PC. This can be accomplished as follows: The data are transferred to a memory card, which is inserted in a slot on the central unit; the memory card is then sent to the billing agency which, with the help of a reading device, loads the data to a PC The data are made available at the RS-232 interface; from there, they can be passed on to the external billing agency, either directly or via modem, to be loaded to a PC. The central unit has a jack for powering the modem Room temperature control of the apartments can be influenced via the central unit, in which case all apartments will be affected. It is not possible to address individual apartments. What can be acted upon is the 24-hour program for setback and heating up and setpoint limitations. The central unit offers the function of a 24-hour time switch which is used to enter 1 setback period per 24-hour period. During the setback period, all room units in the apartments are switched to the reduced setpoint and, during the comfort periods, to the normal setpoint. The setting ranges of the room temperature setpoints in the apartments equipped with the QAW20 room unit can be limited. The following settings can be made on the central unit: Maximum limit of the room temperature setpoint; it is used to avoid overheating of apartments; maximum limitation is always active Minimum limit of the room temperature setpoint; it ensures protection against freezing and prevents undesired heat transfer from other normally heated apartments; 2 limit values can be set: 1 for the comfort periods 1 for the setback periods All setpoint limitations can be adjusted in the range 3 30 C. Based on the building's heat demand acquired by the central unit via the apartments, a compensating variable is generated which acts on the flow temperature setpoint of the heating group. This compensating action may be either continuous or switching and is possible with both Siemens controllers and controllers of other manufacture. Continuous load compensation is only possible with controllers communicating with the central unit via LPB or H-bus (refer to "Equipment combinations"). Each apartment may be assigned to a heating group that uses separate flow temperature control. Connections with up to 6 heating groups are possible.based on the heat demand of the individual apartments, the central unit calculates a "common setpoint" for each heating zone, which influences the flow temperature of the heating group. Heat generation is then controlled via the flow temperatures of the various zones. 4/9

Switching load compensation With switching load compensation, the heating group controller is switched from normal temperature to setback temperature, and vice versa. The change to setback operation takes place: When the apartments do not call for heat, e.g. due to solar radiation, or When all apartments are in setback mode The command for changeover can be delivered via: The LPB or H-bus from the bus-capable heating controllers (refer to "Equipment combinations") The load compensation relay of the central unit for controllers with no H-bus or LPB connection facility but with a time switch contact (e.g. RVL46) When there is demand for heat, the relay of the central unit opens its contact, for temperature setback it closes its contact Messages and alarms Status inputs Handling of alarms Diagnostics The central unit has 4 status inputs. They are used to receive and handle signals from plant sections. The signals are delivered by potential-free contacts connected to the status inputs. The contacts are opened and closed by the plant sections. 2 status inputs can be configured either as counting or alarm inputs (connection terminals P1 and P2; can be reconfigured by Siemens service staff) 2 status inputs are ready configured as alarm inputs (connection terminals P3 and P4) Counting inputs are used for acquiring operating times such as burner running times. Counted is the time during which the contact delivering the signal is closed. Alarm inputs acquire and register signals from any plant sections. An alarm is triggered when the contact closes. The alarms have the following origin: Various signals, received at the status inputs Unit faults (hardware or software), received via the building bus Operating voltage faults, received via the building bus Faults in communication, received via the building bus Measuring errors, received via the building bus Interventions from outside, received via the building bus Heating plant malfunctions, received via the LPB or H-bus If required, alarm handling can be reconfigured by Siemens service staff. With all alarms, it is possible to configure if and with what priority they are to be delivered. There are 3 priorities. For the configuration of alarm handling, the central unit offers the following choices: Energizing an alarm relay; the contact is closed when there is an alarm Indication on the central unit Passing on to an operator station Registration on the memory card Each alarm must be acknowledged on the central unit. For diagnostics, service and alarms, the central unit monitors the entire plant. Faults can be configured as alarms (see above). The diagnostics function provides the following information: Control and heat meter interface WRI80: Flow rate of the connected heat meter, flow and return temperatures, operating mode Control and heating cost allocation valve WRV : Flow rate, pressure differential, flow and return temperatures, operating mode Room units QAW : Actual value and room temperature setpoint Communication: Number of building bus users, LPB, H-bus, RS-232 interface currently active or not.. 5/9

Mechanical design The central unit consists of a base, with the power supply section and the connection terminals, and hinged operating section. Base Operating section Operation Display and buttons The base is made of plastic and can be mounted in 2 ways: On a wall; the base has fixing holes In a panel cutout; to facilitate fixing, each corner has a catch For cable entry, the base has a total of 12 knockout holes. The printed circuit board carries 2 bases which accommodate the connection terminal blocks, all relays and some of the electronic components. Wiring is simplified by removing the terminal blocks from their bases. The hinged operating section also serves as a cover. Its front carries the display, the buttons and the operating cards. All operating elements are located beneath a hinged transparent cover. It can be locked with a key while the operating section is secured to the base by means of a lead-sealable screw. The operating cards are joined together and can simply be inserted. The RS-232 port, the jack for powering the modem and the slot for the memory card are located on the underside of the operating section. The connection between the printed circuit board in the housing and that of the operating section is established with a ribbon cable. The electronic circuits of the operating section feature a clock which, via the building bus, also serves as a reference clock for all other units installed in the plant. The display comprises: The address and designation of the information; the numbers are selected with 3 buttons; this part of the display is subdivided as follows: Application, that is, consumption, control, diagnostics, and commissioning Numbers of the apartments and of the unit Number of the parameter, actual value or function; the designations assigned to the numbers are shown on the operating cards 1 2 3 4 5 6 7 2841Z25 1 Buttons on the left 2 Display 3 Buttons on the right 4 Button for storing the consumption values on the memory card 5 Operating cards 6 Lock 7 Hole for the sealable fixing screw 8 9 10 8 Jack for modem power supply 9 RS-232 interface 10 Memory card ALC30 6/9

The information; it is assigned to the selected address and the designation; parameters are changed via 3 buttons The unit (kwh, l/h, C, etc.) 4 text symbols: DATA: Loading data CARD: Memory card inserted and accepted ERROR: Fault status message BAT: Battery exhausted (reserve and memory card) Another button is used to store consumption data on the memory card. During operation, the display shows the time of day or if present alarms. Data protection Operating cards Tampering on the central unit (changing parameters, etc.) is prevented by a leadsealed fixing screw. The transparent cover of the operating section can only be opened with a key. Also, interrogation of apartment-specific data such as room temperatures, etc., can be prevented by setting a shorting plug. A set of operating cards is integrated in the front of the unit. They serve for setting the parameters on the central unit, as a setting aid, and for data interrogation. They tell which functions, parameters, indications, etc., are assigned to which numbers. The makeup of the operating cards is matched to the display. Each operating card comprises: 1 application (consumption, control, diagnostics, and commissioning) and the assigned number in the display The parameters, actual values and inputs relating to the application and the numbers assigned to these variables in the display Also, the set of operating cards contains brief instructions for operating the buttons and interpreting the display. Engineering notes The local regulations for heat metering and electrical installations must be observed. The operating voltage of AC 24 V is supplied by an isolating transformer which powers the whole SYNERGYR system and which must be installed near the central unit. When sizing the transformer, the power consumption of all units must be taken into consideration. The secondary side of the transformer must not be earthed. Mounting notes When choosing the mounting location, the environmental conditions must be observed. The central unit is suitable for mounting On a flat surface such as a wall, inside a control panel, etc. In a front panel cutout Commissioning notes The parameters of the central unit will be set by Siemens staff. Communication parameters can only be entered with a PC. When setting the parameters is completed, the central unit must be lead-sealed. The central unit is supplied with a detailed Operating manual. 7/9

Technical data General unit data Building bus Operating voltage SELV / PELV AC 24 V ±20 % Rated voltage AC 24 V Frequency 50 Hz Power consumption 10 VA Permissible ambient temperature Transport and storage Operation Weight (incl. battery) 25 +65 C 0 50 C 1.1 kg Baud rate 4,800 Baud Open-circuit voltage 15.5 V ±10 % Voltage under load 13.8 V at 150 ma Short-circuit current 300 ma ±10 % Modem supply Continuous load Voltage under load max. 120 ma min. 8.5 V Safety data Standards Degree of protection (with cover closed) IP40 to EN 60529 Safety class III to EN 60730 Electromagnetic compatibility Immunity (for use in domestic environment) EN 61000-6-1 Emissions (for use in domestic environment) EN 61000-6-3 conformity to EMC directive 2004/108/EC Connection terminals MB G1, G2 Operating voltage AC 24 V DB Data building bus MB Ground building bus H11, H12 Alarm relay S13, S14 Switching contacts for load compensation J1, J2 RS-485 interface (with no function) M Ground for H-bus D Data H-bus P1, P2 Inputs for acquiring the hours run or for receiving fault status messages from external devices (with potential-free contact) P3, P4 Inputs for receiving fault status messages from external devices (with potential-free contact) 8/9

R185 2841M01 138 + 1 0 111 147 138 108 Connection diagram P1 P2 P3 P4 X1 AC 24 V H1 Alarm device (AC 24 V) N1 Central unit OZW30 N2 ALBATROS heating group controller (e.g. RVL470) N3 H-bus capable heating group controller (e.g. RVL55), as an alternative to controller N2 N4 Any type of controller with a time switch contact (e.g. controller of other manufacture), as an alternative to controller N2 P1, P2 Devices with a potential-free contact for hours run or fault status messages P3, P4 Devices with a potential-free contact for fault status messages X1 Conduit box ALW30 or ALW84 Dimensions 1,5...6 175 60,5 50,5 5,6 234 + 1,2 0 Minimum clearance 90 mm for memory card Dimensions in mm 1995-2009 Siemens Switzerland Ltd Subject to alteration 9/9