I D F GB E NL GS3 551T GS3 551T1

ONE STAGE LIGHT OIL AND KEROSENE BURNERS

Kerosene and Gas oil burner

Installation, use and maintenance instructions. Gas oil burner. One stage operation CODE MODEL TYPE G20S 482T50

Kerosene burners. One stage operation KEROSENE BURNER KEROSENE AND GAS OIL BURNER. Installation, use and maintenance instructions

OPERATING AND MAINTENANCE INSTRUCTIONS LIGHT OIL BURNERS

OIL BURNERS LOW PRESSURE, DESIGNED FOR COMBUSTION OF LIGHT FUEL OIL, MEDIUM FUEL OIL-1P, WASTE OILS.

TWO STAGE GAS BURNERS RIELLO 40 GSD SERIES GS10D 29/ kw GS20D 58/ kw

ONE STAGE GAS BURNERS RIELLO 40 FS SERIES FS kw FS kw FS kw FS kw FS kw

Trouble Shooting. Pump

Volkswagen Jetta, Golf, GTI 1999, Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

POSEIDON 2-29, 2-25 & 2-22 POSEIDON 2-29, 2-25 & 2-22 XT

820 NOVA mv THERMOPILE POWER SUPPLY THERMOELECTRIC SAFETY DEVICE SERVO-CONTROLLED PRESSURE REGULATOR SHUT-OFF SOLENOID VALVE.

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)

MODULATING LIGHT OIL BURNERS RL/M SERIES

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS

M A N U A L

DKG 972 Gas Burner Safety Control

OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

TWO STAGE GAS BURNERS

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

Munchkin Heat Exchanger Maintenance

Elektromotoren und Gerätebau Barleben GmbH

FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES

! WARNING. Before using product, read and understand instructions.

Volkswagen Jetta, Golf, GTI 1999, 2000 Brake System 47 Brakes - Hydraulic Components (Page GR-47)


1 DESCRIPTION OF THE APPLIANCE

SERVICE SERVICE COMPACT MANUAL. Mod X Mod X Mod X. Part 2

DIAMOND Retractable Rodding Robot Model SPRAYROD-R

TOBY DVR5 OIL CONTROL & SAFETY VALVE

Oil and Coolant Circulating Heating System. Model - OCSM

- mark gas burners Cuenotherm NC.4 - NC.6 - NC kW.

Rexroth Hydraulic Pump A10VO Series User Manual


Operating instructions

Cooling system components, removing and installing

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00

Fuel Injection Pump, Rotary ( )

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

SunMaxx Solar Filling Station Operating Instructions

Boiler and Burner Cleaning and Servicing Specifications


Overheating limit control

Table of Contents. Overview 1. Pump Disassembly 2. Control Disassembly / Reassembly 7. Pump Reassembly 13. Adjustment Procedures DR Control 19

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 12/6/10

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Thermo Top - Troubleshooting Tree

Fossil fuel heating equipment

Rapide Inline Ceiling Extractor Fan, White Fascia Rapide Inline Ceiling Extractor Fan, Chrome Fascia

Chapter 7 Hydraulic System Troubleshooting

Oil, Gas and Dual Fuel Burners

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:

BOWIE PUMPS OPERATION - MAINTENANCE

T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

Operating instructions

Weishaupt gas burners type G Gas/oil dual fuel burners types GL and RGL Sizes 1 and 3 1/2000 GB

Hydraulic Trouble Shooting

Servicing manual. Gas wall hung boiler condensing 600 Series - 11S / 19S / 24S / 24C /2006 GB(EN) For trade use

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

IOM SERIES 820-E/P Electro-Pneumatic Positioner

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

Evaluate, Clean, and Tune Guidance

SWIMMING POOL HEAT PUMP Owners Manual

HERZ-Thermal Actuators

BLACK TIE. Instructions Manual

Universal Adjustable Fuel Pressure Regulator

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

RL Series. Technical Data Leaflet. Two Stage Light Oil Burners. Light Oil TS0035UK03

LCD Readout Digital Pressure Switch

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

Maintenance and Operating Instructions SIS 120P/SISF

Vacuum Gate Valve DN 100 and DN 150

GREISINGER electronic GmbH

Mikrofill Ethos Condensing combination boiler

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R EN - Edition 01-26/10/2009

OPL BASIC. Dosing System for Professional Laundry machines. Contents

EC DECLARATION OF CONFORMITY FOR MACHINES

PTU Series Ultrahigh-Purity Pressure Transducers

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual

The cylinder head bolts tightening stages have been updated as listed in Table 1.

AGA GAS MARK 2 BURNER (CONVERSION) FITTING INSTRUCTIONS

Cable Plug acc. to DIN EN , Form A

Please also see 10 golden rules for correct Saniflo installation on

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Elektromotoren und Gerätebau Barleben GmbH

Duct Humidity Transmitter

Drayton Digistat +2RF/+3RF

INSTRUCTION MANUAL HYDRAULIC GATE TRANSMISSION SYSTEM ECO240-ECO360

Action Plan Template HVAC Page 1

Technical Information

Transcription:

Montage und Bedienungsanleitung Manuel d entretien Installation, use and maintenance instructions Installatie-, gebruiks- en onderhoudsvoorschriften Oδηγίες εγκατάστασης, χρήσης και συντήρησης D F GB NL GR Öl-Gebläsebrenner Brûleur fioul Light oil burner Stookoliebrander Καυστήρας Πετρελαίου Einstufiger Betrieb Fonctionnement à allure One stage operation Eentrapsbranders Μονοβάθμιοι CODE - Κ ΙΚΟΣ MODELL - MODELE MODEL - ΜΟΝΤΕΛΟ TYP - TYPE ΤΥΠΟΣ 3739950 RG5S 399 T 290 (2)

INDEX. BURNER DESCRIPTION............. Burner equipment................. 2. TECNICAL DATA................ 2 2. Technical data.................... 2 2.2 Overall dimensions................. 2 2.3 Working field..................... 2 4. WORKING....................... 6 4. Combustion adjustment.............. 6 4.2 Recommended nozzles.............. 6 4.3 Combustion head setting............. 7 4.4 Electrodes adjustment............... 7 4.5 Pump pressure and air output......... 7 4.6 Burner start-up cycle................ 8 3. INSTALLATION................... 3 3. Boiler fixing...................... 3 3.2 Fuel supply...................... 3 3.3 ydraulic systems................. 4 3.4 Electrical wiring................... 5 5. MAINTENANCE................... 8 6. FAULTS / SOLUTIONS.............. 9. BURNER DESCRIPTION One stage light oil burner. CE Certification No.: 0036 030/0 as 92/42/EEC. The burner meets protection level of IP 40, EN 60529. Burner with CE marking in conformity with EEC directives: EMC 89/336/EEC, Low Voltage 73/23/EEC, Machines 98/37/EEC and Efficiency 92/42/EEC. Fig. Oil pump 2 Control-box 3 Reset button with lock-out lamp 4 Flange with insulating gasket 5 Air damper adjustment assembly 6 Nozzle holder assembly 7 Photoresistance 8 ydraulic jack 9 Start delaying device SW006. BURNER EQUIPMENT Flange with insulating gasket....no. Screw and nuts for flange to be fixed to boiler. No. 4 Screw and nuts for flange......no. Flexible oil pipes with nipples.............. No. 2 7 pin plug...................no. GB

2. TECNICAL DATA 2. TECNICAL DATA TYPE 399T Output - Thermal power 3.5 26. kg/h - 60 309.5 kw 4 Fuel Light oil, viscosity 4 6 mm 2 /s at 20 C Electrical supply Single phase, ~50z 230V ± 0% Motor Run current 2.A 2730 rpm 286 rad/s Capacitor 8 µf Ignition transformer Secondary 8 kv 6 ma Pump Pressure: 8 5 bar Absorbed electrical power 0.47 kw 2.2 OVERALL DIMENSIONS 247 55 300 23 27 285 345 99 ø 25 45 99 45 2,5 60 D5390 36 90 2.3 WORKING FIELD (as EN 267) 4 Pressure in combustion chamber mbar 3 2 0 2 4 6 8 20 22 24 26 Fuel output kg/h D6230 50 70 90 20 230 250 270 290 30 Thermal power kw 2 GB

3. INSTALLATION TE BURNER MUST BE INSTALLED IN CONFORMITY WIT LEGISLATION AND LOCAL STANDARDS. 3. BOILER FIXING Put on the flange () the screw and two nuts, (see fig. 3). Widen, if necessary, the insulating gasket holes (4), (see fig. 4). Fix the flange () to the boiler door (3) using screws (5) and (if necessary) the nuts (2) interposing the insulating gasket (4), (see fig. 2). After installation ensure that burner is lightly inclined as in fig. 5. Fig. 2 D502 Fig. 4 Fig. 3 S707 Fig. 5 D5025 3.2 FUEL SUPPLY The burner is designed to allow entry of the oil supply pipes on either side. Depending on the oil supply pipes position (to the right or to the left hand side of the burner) the fixing plate () and closing plate (2) should be reversed, (see fig. 6). Fig. 6 2 D407 3 GB

3.3 YDRAULIC SYSTEMS WARNING: The pump is designed to allow working with two pipes. In order to obtain one pipe working it is necessary to unscrew the pin (2), remove the by-pass screw (3) and then screw again the pin (2), (see fig. 7). It is necessary to install a filter on the fuel supply line. Before starting the burner make sure that the return pipe-line is not clogged. An excessive back pressure would cause the damage of the pump seal. Fig. 7 4 7 6 5 SYSTEM NOT PERMITTED IN GERMANY meters L meters I. D. 8 mm I. D. 0 mm 4 max. 4 m Fig. 8 0.5.5 2 0 20 40 60 20 40 80 00 3 2 D408 D5745 - Suction line 2 - Return line 3 - By-pass screw 4 - Gauge connection 5 - Pressure adjuster 6 - Suction gauge connection 7 - Valve PRIMING PUMP: On the system in fig. 8 it is sufficient to loosen the suction gauge connection (6, fig. 7) and wait until oil flows out. On the systems in fig. 9 and 0 start the burner and wait for the priming. Should lock-out occur prior to the arrival of the fuel, await at least 20 seconds before repeating the operation. The pump suction should not exceed a maximum of 0.4 bar (30 cm g). Beyond this limit gas is released from the oil. Oil pipes must be completely tight. In the vacuum systems (fig. 0) the return line should terminate within the oil tank at the same level as the suction line. In this case a non-return valve is not required. Should however the return line arrive over the fuel level, a nonreturn valve is required. This solution however is less safe than previous one, due to the possibility of leakage of the valve. meters 0 0.5.5 2 3 3.5 I. D. 8 mm 35 30 25 20 5 8 6 L meters I. D. 0 mm 00 00 00 90 70 30 20 Fig. 9 Fig. 0 max. 4 m max. 4 m D5744 = difference of level; L = max. length of the suction line; I. D. = internal diameter of the oil pipes. 4 GB

3.4 ELECTRICAL WIRING WARNING DO NOT EXCANGE NEUTRAL WIT PASE ~ 50z 230V PE L N Main switch T6A NOTES: Wires of min. mm 2 section. (Unless requested otherwise by local standards and legislation). The electrical wiring carried out by the installer must be in compliance with the rules in force in the Country. TESTING Check the shut-down of the burner by opening the thermostats and the lock-out by darkening the photoresistance. our counter (230V - 0.A max.) Safety thermostat Limit thermostat Remote lock-out signal (230V - 0.5A max.) 7 pin plug 7 pole socket Photoresistance CARRIED-OUT ESEGUITO IN TE IN FACTORY FABBRICA CONTROL BOX 552SE Brown Blue Black White Blue Oil valve Capacitor D93 Motor Ignition electrodes Burner-earth Fig. CONTROL BOX (see fig. ) To remove the control-box from the burner, loosen screw (A) and pull to the arrow direction, after removing all components, the 7 pin plug and earth wire. In case of disassembly of the control box, retighten the screw (A) with a torque wrench setting of.2 Nm. S7072 A 5 GB

4. WORKING 4. COMBUSTION ADJUSTMENT In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and testing must be carried out observing the instruction manual of the boiler, including verification of the CO and CO 2 concentration in the flue gases, their temperatures and the average temperature of the water in the boiler. To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the setting of the combustion head, and the air damper opening in accordance with the following schedule. The values shown in the table are measured on a CEN boiler (as per EN 267). They refer to 2.5% CO 2 at sea level and with light oil and room temperature of 20 C. Nozzle Start delaying Pump Combustion device pressure pressure Burner Air damper adjustment head output Low-flame igh-flame adjustment Low-flame igh-flame GP Angle bar bar kg/h ± 4% Set-point Set-point Set-point 3.00 60 9 5 3.5 0 0.4.3 3.50 60 9 5 5.7 0 0.5 2.0 4.00 60 9 5 8.0 2 0.7 2.5 4.50 60 9 5 20.2 4 0.8 3.0 5.00 60 9 5 22.4 6 0.9 3.7 5.50 60 9 5 24.7 8. 5.8 6.00 60 9 4 26.0 0.3 6.0 4.2 RECOMMENDED NOZZLES: Monarch type R Delavan type W (up to 3,00 GP) Delavan type B (over 3,00 GP) Steinen type S; Danfoss type S. Fig. 2 TO FIT NOZZLE CARRY OUT TE FOLLOW- ING ACTIONS, (see fig. 2) Remove nozzle-holder assembly () after loosing screws (2) and nut (3), remove the small cables (4) from the control box and the photoresistance (5). Withdraw the small cables (4) from the electrodes, remove the diffuser disc-holder assembly (8) from the nozzle-holder assembly () after loosing screw (3, fig. 3, page 7). Screw the nozzle (9) correctly and tighten it as shown in fig. 2. Attention During the reassembly of the nozzle-holder assembly screw the nut (3) as shown in the figure below. TIGTEN WITOUT MOVING BACKWARDS TO TE END 3 D5684 SW007 6 GB

4.3 COMBUSTION EAD SETTING, (see fig. 2, page 6) It depends on the output of the burner and is carried out by rotating clockwise or counterclockwise the setting screw (6) until the set-point marked on the regulating rod (7) is level with the outside plane of the nozzle-holder assembly (). In the sketch the combustion head is set for an output of 4.00 GP at 5 bar. The set-point 2 of the regulating rod (7) is at the same level with the outside plane of the nozzle-holder assembly () as shown in the schedule. 4.4 ELECTRODES ADJUSTMENTS, (see fig. 3) WARNING: MEASURES MUST BE RESPECTED. Fig. 3 0 4.5 0.5 mm 5 4 6 7 mm Lean the diffuser disc-holder assembly () on the nozzle-holder (2) and lock it by screw (3). For prospective adjustments loosen screw (4) and move the electrodes assembly (5). To have access to the electrodes carry out operation as described in chapter 4.2 RECOMMENDED NOZZLES (page 6). 3 2 D409 4.5 PUMP PRESSURE AND AIR OUTPUT The burner, in order to guarantee good smooth starts, irrespective of the type of boiler, is fitted with a hydraulic device which, independently of the control-box, reduces the fuel- and air-flow. At ignition, the pressure at the nozzle is 9 bar. After 3-9 seconds, it automatically increases to 5 bar. The air-flow, initially adjusted to the low setting, is, at the change-over of pressure, automatically brought to the air-flow required for the big flame. Fig. 4 SETTING FOR TE LOW IGNITION-FLAME (See fig. 4) ADJUSTMENT OF AIR SUTTER Unloosen the screw (8), by approximately one full turn; in this way, the burner remains permanently on low flame. Unloosen the nut (5), turn the screw (4) until the indicator (6) reaches the position desired. Then lock the nut (5) and tighten the screw (8). ADJUSTMENT START DELAYING DEVICE This is set at 9 bar at the factory. The pressure gauge must be mounted in place of plug (4, fig. 7, page 4). Should it be necessary to S76 re-set or alter such pressure, this can be done, by adjusting screw (7), always after having loosened screw (8). For the adjustment, follow what indicated in the table at page 6. Anyway, it is advised to adjust the content of CO 2 at values not lower than 2%. 7 GB

IG-FLAME SETTING, (see fig. 4, page 7) AIR-DAMPER ADJUSTMENT Loosen the nut (3), turn the screw (), until the indicator (2) is in the required position. Then, lock the nut (3). PUMP-ADJUSTMENT This is set at 5 bar at the factory. The pressure gauge must be mounted in place of plug (4, fig. 7, page 4). Should it be necessary to re-set or alter such pressure, this can be done, by adjusting screw (5, fig. 7, page 4). When burner shuts down the air damper automatically closes till a max. chimney depressure of 0.5 mbar. 4.6 BURNER START-UP CYCLE Thermostat Motor Ignition transformer Valve Low-flame igh-flame Lock-out lamp Normal Lock-out due to failure to light B ~ 2s 3 9s ~ 2s 5s D5544 B Lock out is indicated by a lamp on the control box (3, fig., page ). 5. MAINTENANCE The burner requires periodic maintenance carried out by a qualified and authorised technician in conformity with legislation and local standards. Maintenance is essential for the reliability of the burner, avoiding the excessive consumption of fuel and consequent pollution. Before carrying out any cleaning or control always first switch off the electrical supply to the burner acting on the main switch of the system. TE BASI CECK ARE: Check that there are not obstructions or dents in the supply or return oil pipes. Clean the filter in the oil suction line and in the pump. Clean the photoresistance, (7, fig., page ). Check for correct fuel consumption. Replace the nozzle (fig. 2, page 6) and check the correct position of electrodes (fig. 3, page 7). Clean the combustion head in the fuel exit area, on the diffuser disc. Leave the burner working without interruptions for 0 min. and set rightly all the components stated in this manual. Then carry out a combustion check verifying: Smoke temperature at the chimney; Content of CO2 (%); Content of CO (ppm); Smoke value according to opacity smokes index according to Bacharach scale. 8 GB

6. FAULTS / SOLUTIONS ere below you can find some causes and the possible solutions for some problems that could cause a failure to start or a bad working of the burner. A fault usually makes the lock-out lamp light which is situated inside the reset button of the control box (3, fig., page ). When lock out lamp lights the burner will attempt to light only after pushing the reset button. After this if the burner functions correctly, the lock-out can be attributed to a temporary fault. If however the lock out continues the cause must be determined and the solution found. FAULTS POSSIBLE CAUSES SOLUTION Check presence of voltage in the L - N clamps of the 7 pin plug. The burner doesn t start when the limit thermostat closes. Burner runs normally in the prepurge and ignition cycle and locks out after 5 seconds ca. Burner starts with an ignition delay. Lack of electrical supply. The photoresistance sees false light. Start thermostats are faulty. The connections in the control box are wrongly inserted. The photoresistance is dirty. The photoresistance is defective. Flame moves away or fails. The ignition electrodes are wrongly positioned. Air output is too high. Nozzle dirty or worn. Check the conditions of the fuses. Check that safety thermostat is not lock out. Eliminate the light. Replace them. Check and connect completely all the plugs. Clear it. Change it. Check pressure and output of the fuel. Check air output. Change nozzle. Check the coil of solenoid valve. Adjust them according to the instructions of this manual. Set the air output according to the instructions of this manual. Replace it. WARNING The manufacturer cannot accept responsibility for any damage to persons, animals or property due to error in installation or in the burner adjustment, or due to improper or unreasonable use or non observance of the technical instruction enclosed with the burner, or due to the intervention of unqualified personnel. 9 GB