Venturi Air Valve or Single-Blade Damper What s Right for You?



Similar documents
Demand Based Static Pressure Reset Control for Laboratories

VAV Laboratory Room Airflow The Lowdown on Turndown

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Powers Controls TH 192 S Single Temperature Room Thermostat

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG March 24, 2010

Chemical Fume Hoods. Environmental Health and Safety

AMD-33 Air Measuring Station with VCD-33 Control Damper

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

Healthcare Solutions Room Pressure Monitors and Controls

SAM HOUSTON STATE UNIVERSITY

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Signature and ISX CM870 Fuel System

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application and Design. Ratings. Features and Control Options.

Accurate Air Flow Measurement in Electronics Cooling

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

Ceriani Replica GP35R forks. Technical description

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

POWERS Controls No. 4 Pneumatic Damper Actuator

PNEUMATIC CONTROLS Selection and Description

The Effect of Forced Air Cooling on Heat Sink Thermal Ratings

Design Information. Designing Your Dust Collection System. Typical dust or fume collection system

Threaded Inline Air Heaters

Cane Creek Double Barrel Instructions

Index Page. Pumping Systems Intensifiers Gas Boosters High Pressure Generators

ENGINEERING DATA. Fan Performance Troubleshooting Guide

Bring the fresh in. Dedicated Outside Air Systems

Fundamentals of Mass Flow Control

Force measurement. Forces VECTORIAL ISSUES ACTION ET RÉACTION ISOSTATISM

Introduction to Accuracy and Repeatability in Linear Motion Systems

ENHANCED LABORATORY HVAC SYSTEM

Chapter 11 SERVO VALVES. Fluid Power Circuits and Controls, John S.Cundiff, 2001

Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace

COUNTERBALANCE VALVES

Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.

Prelab Exercises: Hooke's Law and the Behavior of Springs

MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard

A descriptive definition of valve actuators

FIRE DAMPER APPLICATION GUIDE

General Information... 2

Benefits of Cold Aisle Containment During Cooling Failure

Centrifugal Fans and Pumps are sized to meet the maximum

How To Use A Ds340 (Dsp)

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Exhaust Calculation Booklet

Model 43AP Pneumatic Controller, Style B

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

SELECTION, APPLICATION AND MAINTENANCE

Coal Handling Plant Alignment Standards For Shaft To Shaft Alignment. By Makarand Joshi M.Tech

T U R B I N E G A S M E T E R

Flow Measurement Options for Pipeline and Open Channel Flow

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Why Lead Screws are the Best Fit for Many Linear Motion Applications - and How to Rightly Apply Them

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

Baumann Way Bronze or Stainless Steel Control Valve

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS

MULTIZONE APPLICATION OF SOLUTION UNITS

POWERS CONTROL RC 195 Single Input Receiver-Controller

PRESSURE REDUCING CONTROL VALVE

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

SUMMARY of PRODUCTS. HVAC Systems Control Airflow, Space, & Building Pressurization. Accurate airflow measurement for demanding applications

Chapter 3.5: Fans and Blowers

Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc.

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

PORTER MASS FLOW MEASUREMENT AND CONTROL SYSTEMS

MAXIMIZING THE OUTPUT OF YOUR BRAKES Getting Your Pedal Geometry Right

Chapter 12 Industrial Ventilation

Submersion/Insertion Toroidal Sensor

Application Note 142 August New Linear Regulators Solve Old Problems AN142-1

Recirculating Roof Fans Models ESRMD, ESRMDF and ERD

Basic Hydraulics and Pneumatics

Unit 24: Applications of Pneumatics and Hydraulics

Baumann Flexsleev Sanitary Control Valve

Chemistry 112 Laboratory Experiment 6: The Reaction of Aluminum and Zinc with Hydrochloric Acid

Basic Selection & Proper Application of Overhead Air Distribution Devices

Class II, Type A2 Biological Safety Cabinet HEPA Filter Loading Capacity

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

SELECTION, APPLICATION AND MAINTENANCE

VOLU-probe/SS. Stainless Steel Pitot Airflow Traverse Probes. Accurate airflow measurement for demanding applications

SECTION TESTING, ADJUSTING, AND BALANCING

Industrial Steam System Process Control Schemes

LAB 6: GRAVITATIONAL AND PASSIVE FORCES

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

PIEZOMETER AIRFLOW MEASURING RING

CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB

Unit 24: Applications of Pneumatics and Hydraulics

Welcome to this presentation on LED System Design, part of OSRAM Opto Semiconductors LED 101 series.

DRYER VENTING SPECIFICATIONS DRYER SAFETY

NEW SIX-SEALS CUTTING RING. INTERNATIONAL INDUSTRIAL PATENT Nr of the 10/03/99 FLANKS AND DOES NOT REPLACE THE STANDARD RING CURRENTLY IN USE

A99B Series Temperature Sensors

1 DESCRIPTION OF THE APPLIANCE

DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

Ford F-Series Column Shift Repairs

Technical Guide No High Performance Drives -- speed and torque regulation

FAN PROTECTION AGAINST STALLING PHENOMENON

Transcription:

Technology Report September, 2008 Venturi Air Valve or Single-Blade Damper What s Right for You? This report examines and compares the attributes of a Venturi air valve and a single-blade damper to assist a ventilation system designer. Single-blade dampers have been on the scene for generations and are probably one of the earliest HVAC control devices. They were initially used to manually adjust the chimney draft of wood and coal burning stoves. This made it possible to regulate the stove's heat output. Blade dampers were later coupled with automatic operating mechanisms for various HVAC control applications and continue to be widely used, especially to control ventilation systems. Single-blade dampers function by simple rotation and perhaps provide the least obstruction to airflow when in the maximum open position. Round blade dampers are sometimes called butterfly dampers. This term may be better reserved for dampers that function by a folding and unfolding action (much like a butterfly's wings). VENTURI AIR VALVE The Venturi air valve is a newer airflow control device with a more elaborate mechanical design. Mechanical Operation Figure 1 shows the basic mechanical operation of each device. The single-blade damper consists of a disk mounted on a shaft. As the shaft rotates, the disk blocks more or less of the air path. This rugged arrangement allows gradual adjustment of the flow area from nearly blocked to almost fully open. A Venturi air valve has a curved body that functions as a valve seat, and a cone that moves in and out of the throat of the Venturi to restrict airflow. When used with a suitable airflow controller, either a Venturi air valve or single-blade damper can effectively modulate airflow. SINGLE BLADE DAMPER ACTUATOR SHAFT LEVER ARM ACTUATOR DAMPER SHAFT CRANK ARM ACTUATOR SHAFT ACTUATOR CONE CONE SHAFT VENTURI BODY AREA DUCT HOUSING THE ACTUATOR SHAFT IS CONNECTED TO THE CONE SHAFT BY A LEVER ARM. AS THE ACTUATOR SHAFT EXTENDS OR RETRACTS IT CAUSES THE LEVER ARM TO MOVE THE HORIZINTAL CONE SHAFT. MOVEMENT OF THE CONE SHAFT VARIES THE AREA BETWEEN THE CONE AND THE VENTURI BODY. THE ACTUATOR SHAFT IS CONNECTED TO THE DAMPER SHAFT CRANK ARM. AS THE DAMPER SHAFT EXTENDS OR RETRACTS IT ROTATES THE BLADE DAMPER WHICH VARIES THE AREA BETWEEN THE DAMPER BLADE AND THE DUCT HOUSING. Figure 1. Basic Operation of a Venturi Air Valve and Single-Blade Damper Air Terminal. Siemens Industry, Inc. Page 1 of 8

Mechanical Pressure Independence The brief description of the damper operation skipped over an interesting characteristic of the Venturi air valve. In many valves, the actuator shaft does not directly move the cone. Instead, they are connected by a special spring. This gives the cone some freedom to move along the shaft. The spring exerts a force on the cone, but so does the air that flows through the valve. The cone slides along the shaft to the position where the air pressure balances the spring. Through this mechanical force balancing process, the Venturi air valve can be made pressure independent. That is, as pressures change in the duct system, the cone moves on the shaft, altering the airflow path, counteracting the pressure change, and tending to keep that airflow rate constant. This behavior depends on a careful mechanical design that matches the characteristics of the specially designed, variable-stiffness spring to the shapes of the cone and the Venturi body. REMAINS CONSTANT LOWER STATIC PRESSURE HIGHER STATIC PRESSURE EXPANDED SPRING -- INCREASED AREA COMPRESSED SPRING -- DECREASED AREA Figure 2. Pressure Independence by the Venturi Air Valve Pressure Compensation Spring. Figure 2 illustrates action of the cone and spring. The upper diagram shows, that when a lower static pressure acts on the upstream side of the cone, the spring is only slightly compressed, and the cone sits relatively far out of the throat of the valve. The resulting airflow area between the cone and Venturi body allows the required airflow rate. The lower diagram shows what happens when the duct pressure increases. Pressure on the upstream side of the cone pushes the cone along the shaft (towards the throat) and compresses the spring. This movement of the cone restricts the airflow, countering the effect of the pressure increase. The result is that the airflow rate stays nearly constant. When the system static pressure decreases, the cone spring expands and slides the cone back (away from the throat). This increases the airflow area and maintains the required airflow rate. Clearly, this is a sophisticated mechanical device. Performance depends on carefully selected and maintained mechanical parameters. Pressure independent operation is effective over a range of operating pressures specified for the valve (typically 0.6 in. WC to 3.0 in. WC, 150 Pa to 750 Pa). Stability of this non-linear, spring-mass system depends on the shock absorbing effect of the dash tube (the hollow core of the cone) and the cone bushing (a spacer that supports the small end of the cone on the shaft). As the cone moves along the shaft, it squeezes air through the precise opening between the bushing and the dash tube wall. This shock absorber dissipates energy and keeps the cone from bouncing continually on its spring. Critical mechanical tolerances allow the cone sufficient freedom for motion with sufficient damping. Airflow Control Concepts Closed Loop Control: The most common approach to airflow control in a ventilation system is the closed loop, also called feedback control. By definition, each adjustment by a closed loop controller depends on the measured results of previous movements. 1 As the flow controller adjusts the damper (singleblade, Venturi, or other) it also reads an airflow sensor to measure the flow rate and compare it to the desired value (called the setpoint). If the duct pressure changes, and affects the airflow, the controller measures that change and quickly adjusts the damper opening, continuing to sense airflow until the required rate is restored. This is the usual way to accomplish pressure independent flow control. 1. 2005 ASHRAE Handbook - Fundamentals of Control, Chapter 15, Page 15.1. Page 2 of 8 Siemens Industry, Inc.

Open Loop Control: Another approach uses a Venturi air valve as a simple metering device without measuring airflow. In this scenario, the Venturi operates as an open loop flow controller. This concept is valid as long as the system keeps the valve within the operating range of the spring and cone mechanism. In some installations, the Venturi assembly includes a sensor, which measures position of the actuator shaft. This can be useful. That position signal is sometimes mislabeled as flow feedback, but it s not actually sensitive to airflow. In the open loop design, events in the duct system that change the airflow do not move the actuator, and are not reflected by the position sensor. Operators and designers have mistaken the speed and stability of the position signal as a true indication of airflow, overlooking the dynamic events that occur inside the valve, as the cone and spring continually seek the changing balance point. Most ventilation system designers recognize the value of an airflow measurement. Nearly all specifications call for a flow feedback signal. Position of the actuator should not be construed to satisfy that need. Linearity of Control Components Control engineers characterize components in terms of input/output responses. They consider dynamic characteristics such as speed and overshoot, as well as the steady-state responses. If the steady-state response of a component (for example, airflow versus damper position) can be described with a straight line, the component is called linear. In the days before digital control, linearity was greatly beneficial to engineers piecing systems together from signal processing components. Product developers went to great lengths to linearize responses because it simplified system design. Today, non-linearity in a component is easier to address in software. The physics of airflow is full of non-linearity. For example, the relationship between the position of the cone in the valve, and the corresponding airflow at a particular pressure depends on the complex geometry of the cone and valve body, and is highly non-linear. Similarly, the relationship between the position of the actuator and the resulting position of the cone depends on the non-linear spring in the cone and the pressure forces in the duct. Some manufacturers still linearize their valves by adding a non-linear electronic circuit to distort the relationship between the command voltage and the position of the actuator. These days, that step is usually unnecessary. Airflow Control Accuracy In a closed loop flow control application, accuracy depends mainly on the airflow sensor; the characteristics of the damper (blade or Venturi) have little effect. In such a case, the expression accuracy of the flow control damper doesn t actually mean anything. Sensors are available for a wide range of accuracy requirements. It s important to select sensors appropriate to the application. That means relating the sensing range and accuracy to the ventilation objectives. There is no single accuracy specification that makes sense for all applications. It also means considering the geometry and vulnerability of the components in the air stream. In exhaust systems it s crucial to prevent fouling; a rugged geometry with minimum obstruction of the air path is preferred. A low-profile orifice ring with large pressure taps is very reliable. VENTURI AIR VALVE MEASUREMENT SENSOR SINGLE BLADE DAMPER Figure 3. Venturi Air Valve and Damper Air Terminals with Integrated Airflow Sensors. In an open loop application, (a Venturi air valve without an airflow sensor) flow control depends entirely on the reliability of the flow versus position relationship of the valve. This depends, in turn, on the precisely coordinated mechanical parameters described earlier. Deviations over time in the mechanical parameters degrade open-loop Siemens Industry, Inc. Page 3 of 8

accuracy. The following issues are known to cause mechanical parameters to degrade: 1. With continued use, springs exhibit some departure from their original spring rate curve due to material aging and fatigue. Therefore, mechanical pressure independence is not as precise, nor will it provide the long-term stability that is achieved with closed loop flow control. 2. Reliable pressure independent operation depends on precise mechanical clearance inside the cone, where the dash tube slides back and forth over the cone bushing. Material from the air stream is normally deposited on exposed surfaces in the valve, and over time, can work into this critical area. Figure 4 shows the condition of several air valves removed from service. The center left image shows the cone assembly covered in dust. The bottom left image shows the cone bushing has been damaged by deposited material. Because performance is so sensitive to the condition of these friction surfaces, a clean air stream improves reliability. Figure 4. Venturi Air Valves Fouled During Use. 3. Proper valve orientation (horizontal or vertical) is very important for mechanical pressure independence. In the vertical position, the weight of the cone has an impact on the pressure compensation spring. Thus, the proper spring must be installed in the factory Page 4 of 8 corresponding to the position (horizontal or vertical) in which the valve will be installed. Therefore, it is mandatory that a Venturi air valve is installed in the proper horizontal or vertical position and not in a slanted (angular) position. 4. The air valve is not only susceptible to fouling of the precise friction surfaces. Gross contamination can also upset the open loop relationship of flow versus position. The images in the top and bottom right of Figure 4 illustrate the sort of debris that an air valve can catch in an exhaust system (in this case, large debris). These valves were removed from service after it was observed that the airflow did not seem right. The actuator position signal did not indicate any problem. Flow and Pressure Characteristics The fundamental selection criteria for a flow control device are the range of flow rates, and corresponding pressure drops across the device. These numbers (flow range and pressure range) are a good starting point for a designer selecting a device. It s important to remember that they are not exactly comparable. For the Venturi air valve, these values are the hard limits of the pressure independent operation. Because these values are hard, physical limits, prudent designers leave a cushion, and do not apply the valves right at the limit. For a single-blade damper, the ranges are based on a more flexible set of engineering rating criteria. It s always possible to push more or less air through the damper if the effects on the system are acceptable. Table 1 defines each term and contrasts the meaning between a single-blade damper and a Venturi air valve. Air Capacity Because of the greater airflow area of a single-blade damper type of air terminal, its airflow capacity is significantly more than a Venturi air valve of the same diameter. Since the maximum Venturi air valve size is typically 12 inches in diameter, larger airflows require having multiple units arranged in parallel (ganged together). Figure 5 indicates airflow ranges of Venturi air valves and single-blade air terminals of various sizes. Siemens Industry, Inc.

Table 1. Definition of Sizing Parameters. Sizing Parameter Single-blade Damper Venturi Air Valve definition typical value definition typical value Maximum Airflow A selected rating value. Above this point, system may be considered too loud or lose too much pressure. Often selected between 2,000 and 3,000 fpm. The flow rate approximately maintained by the spring when the actuator is at the end of the stroke. Typically occurs at 1,700 to 1,900 fpm. Minimum Airflow A selected rating value. Below this point, the flow sensor may be inaccurate. Depends on the sensor and the required accuracy. Usually between 0 and 500 fpm. The flow rate approximately maintained by the spring when the actuator is at the other end of the stroke. Typically occurs at 100 to 200 fpm. Maximum Pressure Drop Above this pressure, control may become difficult. Dampers have been applied successfully at 6 in. WC of drop. At this pressure drop, the spring is fully compressed and can no longer regulate airflow. 3 in. WC for all available Venturi air valves. Minimum Pressure Drop Pressure measured across the fully open damper at a rated flow. Usually less than 0.1 in. WC. At this pressure drop, the spring is fully extended and can no longer regulate airflow. Usually 0.6 in. WC or 0.3 in. WC for low pressure valves. LGS_18 AV_312 AV_212 LGS_16 AV_210 LGS_14 LGS_12 AV_112 LGS_10 AV_110 LGS_08 AV_108 LGS_06 AV_106 LGS_04 TYPE FLOW RANGES OF TERMINAL UNITS & VENTURI AIR VALVES The system pressure drop is an important factor in fan energy consumption. Designers motivated by the Green Building movement and sustainability strive to select low-pressure components, so they favor single-blade dampers. 2 3 Like the air capacity, the minimum pressure drop depends on the size of the airflow area. Figure 6 compares of the airflow open area for a Venturi air valve and a single-blade damper. 0 1000 2000 3000 4000 5000 6000 7000 8000 FLOW (CFM) STARTING FROM to FLOW SIGNAL to 1000 FPM TU SHUT-OFF 0.02" (~350FPM) AV CAL MIN Figure 5. Airflow Ranges for Venturi Air Valves and Single-blade Dampers of Various Sizes. Minimum Pressure Drop Minimum pressure drop is an important parameter of an airflow control device. It is the pressure drop across a fully open device at a given airflow rate. The minimum pressure drop (along with the pressure drop of the other system components) determines the static pressure that the supply and exhaust fans must provide to achieve the desired system airflow. 2. U.S. Department of Energy, Low-Pressure-Drop HVAC Design for Laboratories, DOE/GO-102005-2042 (February 2005). 3. Siemens Building Technologies, Inc., Green Lab Facilities: Steps Toward Sustainability Technology Report, 149-488, (April 2008). Siemens Industry, Inc. Page 5 of 8

VENTURI AIR VALVE (END VIEW) AREA SINGLE BLADE DAMPER (END VIEW) AREA Figure 6. Maximum Airflow Areas for the Wide Open Position. Figure 6 shows that a blade damper's fully open airflow area is much greater in comparison to a fully open Venturi air valve of the same diameter. A fully open single-blade damper s airflow area equals the internal duct area less the area occupied by the damper shaft. For a fully open Venturi air valve, the airflow area is limited by the diameter of the cone. The airflow through a Venturi air valve also changes direction as it flows around the cone. For these reasons, a Venturi air valve has a significantly higher minimum (wide open) pressure drop than a singleblade damper air terminal of the same diameter. Typically, a Venturi air valve has a non-recoverable minimum static pressure drop of 0.6 in. WC (150 Pa). Some manufacturers also offer low pressure Venturis with a drop of about 0.3 in. WC (75 Pa) In contrast, the larger airflow area of a fully open single-blade damper results in a non-recoverable minimum static pressure drop of about 0.01 to 0.05 in. WC (2.5 Pa to 12.5 Pa). 4 Cost of Static Pressure Loss The effect of pressure loss on energy consumption can be complicated, but it doesn t have to be. Some lab control publications have confused the issue, perhaps unintentionally. 5 With the right perspective, it can be simple. There are many mathematical ways to express the power that a fan consumes in a ventilation system. For this purpose (calculating the effect of pressure 4. For single duct supply air terminals the pressure drop of the reheat coil must also be considered when selecting and sizing air terminals for a given application. 5. For more information, contact Systems Applications in Buffalo Grove. losses for a given airflow rate) the following equation applies: Airflow Fan Pressure Fan Power Fan Efficiency This means fan power is directly proportional to pressure loss: twice as much pressure consumes twice as much power. If a fan system runs at 5 in. WC of pressure, and we can save 0.5 in. WC by selecting more efficient terminals, that saves 10% of the fan power. If the system is more efficient (for example, 3.0 in. WC) the percentage savings achievable at the terminals is even greater. Some lab control publications mistake the valve pressure drop for the: 1. Static pressure measured at the terminal. If a system runs with 0.5 in. WC (125 Pa) at the terminal, that includes the drop across other components, not just the valve. 2. Signal pressure generated by the airflow sensing element. The sensing pressure is not a loss in the system, and is often many times greater than the drop across the valve. Airflow Sound When airflow through a device causes a pressure drop, that energy is dissipated as heat and sound. The heat component of this energy transformation causes a slight rise in the air temperature flowing through the device, but this is usually small and is disregarded for practical purposes. However, the sound component can be significant and annoying. Therefore, sound ratings are an important consideration when choosing air terminals. A Venturi air valve terminal will typically create somewhat more discharge and radiated sound power for a given airflow than a single-blade damper type of an air terminal due to its greater pressure drop for a given airflow. 6 6. Determining the resulting room sound level caused by HVAC component sound can be a very complex matter. Aside from the air terminal sound, many other factors affect the room's ambient sound level. For additional insight into ventilation related sound, see the Technology Report No. 5 Attaining Acceptable Ventilation Related Sound in Laboratory Rooms (149-979) and to Siemens comprehensive Application Guide Minimizing Excessive Sound in Ventilation System Designs (125-1929). Page 6 of 8 Siemens Industry, Inc.

Airflow Control Loop Performance Performance of an airflow control system can be evaluated without regard to the type of components. Figure 7 displays dynamic airflow data from two chemical fume hoods, one with a Venturi air valve and the other with a single-blade damper. Each plot shows the airflow as a function of time when the fume hood sash is opened. Both hoods exhibit the quick, stable flow control needed for safe laboratory work. 600 600 500 500 400 400 Air Flow Rate (cfm) 300 200 300 200 100 100 0 8 10 12 14 time (seconds) 0 8 10 12 14 time (seconds) Figure 7. Dynamic Airflow Control by a Single-Blade Damper (L) and a Venturi Air Valve (R). Applications for Mechanical Pressure Independence A common application of mechanical pressure independence is in constant air volume (CAV) ventilation systems. Constant airflow can be maintained in critical parts of the CAV system by applying Venturi air valves with pressure independent capability. This eliminates the need for separate airflow controllers and valve actuators and, thus, reduces the overall control system cost. CAV pressure independent applications include CAV fume hood exhaust, biological safety cabinet exhaust, laboratory room specialty equipment exhaust, lab bench exhausts (snorkels), and even the overall room ventilation supply and general exhaust airflow. In pressure independent applications, the Venturi air valve is used without an actuator and with the lever arm in a fixed position. (See Figure 1 for a description of the Venturi air valve components.) To obtain the required airflow, the lever arm must be manually positioned until the required airflow is attained and then the lever arm can be locked into position by a wing nut or a similar means. 7 Conclusion This report explains the issues surrounding use of the Venturi air valve and the single-blade damper as an airflow control device. The Venturi air valve is a more intricate mechanical device compared to the simple damper. Both are successfully applied as components high performance ventilation systems. Table 2 compares the major attributes of a Venturi air valve and a single-blade damper r. The performance achieved in a particular application is primarily a function of the overall airflow control system that includes, and depends on, the controller capability. Performance being equal, owners and engineers should base the decision of Venturi air valve versus single-blade damper on specific application, economical, and safety needs. Regardless of the end device, knowledge of actual airflow is important for informed operation. A thoroughly effective design includes airflow sensors. 7. The airflow through the Venturi air valve must be measured during the setup process in order to establish the proper lever arm position. Siemens Industry, Inc. Page 7 of 8

Table 2. Comparison of Major Air Terminal Characteristics. Attribute Venturi Air Valve Single-Blade Damper Physical Configuration Airflow Capacity More complex physical configuration with more operating components. Higher airflows require multiple ganged units, which takes up more space, increases the unit cost, and requires more duct transitions. Lower maximum airflow due to less airflow area for a given size (diameter) of air terminal. Higher airflow capacities require multiple (parallel ganged) units. Cost Higher cost per unit. Lower cost per unit. Mechanical Pressure Independence Control Curve Yes (within a specific static pressure range) Non-Linear (equal percentage) airflow control action. (Linear control is accomplished by applying a controller with closed loop control capability or the unit must be factory calibrated for use with an open loop controller.) Very simple physical configuration with minimal operating components only two damper shaft pivot points. Duct transitions and the installation are easier especially when higher airflows are required. Higher maximum airflow (70% to 100% greater than the Venturi air valve) for the same size (diameter) air terminal due to the large airflow area. No Non-linear (quick opening) airflow control action. (Linear control output is accomplished by applying a controller with closed loop control capability.) Control Accuracy Nominally +/- 5% as an open loop device Depends on the airflow sensor; which should be selected according to the application Control Turndown Minimum Pressure Drop Sound Generation Materials available to resist corrosion Susceptibility to the effects of chemical or airborne particulate Installation Requirements 8-to-1 with closed loop control. From 10-to-1 through 16-to-1 without closed loop control. 0.30 in. WC (75 Pa) for low pressure model. 0.60 in. WC (750 Pa) for medium pressure model. (This pressure drop is required to enable the mechanical pressure independent function to operate.) Somewhat higher than a round blade damper for the same airflow and pressure drop. Spun aluminum outer shell with Hersite and Teflon protective coatings are available for the shell, cone and shaft. Particulate accumulation on the internal surfaces will degrade the self-contained (non-closed loop) pressure independent function. External closed loop control is required to prevent degraded performance. Each unit must be installed in either the horizontal or vertical orientation in which it was factory calibrated. Higher airflow (ganged) units are cumbersome, heavy, and more difficult to install. Limited by leakage around damper seal. Sometimes reaches 20-to-1. Pressure drop is very low (0.01 to 0.05 in. WC or 2.5 to 12.5 Pa) with the damper wide open. (No minimum pressure drop is required for operation.) Somewhat lower than a Venturi air valve for the same airflow and pressure drop. Multiple materials available for the entire unit: Galvanized steel, Type 316L Stainless Steel and Teflon coating. Particulate accumulation will not degrade the closed loop control action. Units can be installed in any orientation vertical, horizontal, or angular. Higher airflow units are less cumbersome. Maintenance No routine maintenance required.* No routine maintenance required.* * All laboratory ventilation safety standards require periodic (typically on an annual basis) inspections of a laboratory ventilation system's performance. Product or company names mentioned herein may be the trademarks of their respective owners. 2009 Siemens Industry, Inc. Siemens Industry, Inc. Printed in the USA Building Technologies Division 1000 Deerfield Parkway Page 8 of 8 Buffalo Grove, IL 60089-4513 USA