MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard
|
|
|
- Shanna Briggs
- 9 years ago
- Views:
Transcription
1 MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard Advances in testing procedures, coupled with greater pressure for better IAQ, leads to a new standard By Ron Wilkinson, P.E. April, 2001 The latest standard addressing facilities indoor air quality (IAQ) ASHRAE Standard represents a quantum leap in the precision and accuracy of air-cleaner ratings. Standard 52.2, the result of more than 10 years of development in the field of filter testing, is aimed at the filter media required for today s modern workplace. Its testing protocol includes the reliable and consistent testing of filter performance on particles of nominal 3-10 microns in diameter. Although the new standard is applicable to the testing of any type of air cleaners, it has been primarily tailored to high-efficiency dry filters used in hospitals, laboratories and clean rooms. Today s challenges The responsibility of today s maintenance and engineering managers to maintain a clean indoor air environment has increased markedly in recent decades. Employees are more concerned about health, they are more aware of allergic conditions, and they are more familiar with and aware of the effects of chemicals in the workplace. Last but not least, workers have better access to legal expertise and are more likely to litigate. As computers have become standard office equipment, they have left the imprint of their own requirements on the building HVAC system. Dust in the workplace eventually will foul the heat sinks found in personal computer (PC) power supplies, causing over-heating and failure. Dust also can cause reading errors on hard drives and digital tape heads.
2 Finally, the fabrication of integrated circuit boards is setting the pace for airfiltration standards found only in exotic aerospace assembly labs a decade ago. Enter a new standard In the works since 1987, ASHRAE Standard 52.2 features two important improvements over previous standards. For more on these standards, see the accompanying sidebar. The first improvement is the substitution of chemically generated potassium chloride (KCl) dust for the test dust used in previous standards. The use of KCl allows the efficient and consistent generation of particles down to an average size of 0.3 microns and less and enables the repeatable testing of filter media performance on very small particles, and testing with even smaller particles as future needs dictate. The second improvement is the de-coupling of filter loading from filter arrestance. The new standard requires the use of standard test dust to load filters, which simulates the normal increases in efficiency and pressure drop that occur as a dry-media filter becomes impacted with fibers and particles. A subject filter is loaded with test dust in six stages, from clean to maximum pressure drop. After each stage of loading, the filter is tested for its ability to arrest KCl particles of microns. This testing provides an accurate and clear description of arrestance at each stage, rather than the average produced by the earlier ASHRAE 52.1 arrestance and dust-spot tests. Standard 52.2 rates filter arrestance differently than the 52.1 protocol, which used either weights or times to generate a ratio, or efficiency. This efficiency was an easy way to describe a filter s performance. Thus, a 50 percent filter would stop a nominal 50 percent of the particles in the air stream as averaged over the test period. Unfortunately, this average over time told a user nothing about performance for a specific particle size at a specific stage in a filter s life. Dry-media filters exhibit an increase in efficiency as they collect material. This increase in efficiency corresponds to a decrease in open area as collected fibers and particles cover the media. The increased efficiency, however, might not be enough to accomplish the required mission in a dust-critical environment, which
3 can t wait for the efficiency to increase to a suitable level. The average is not the issue. As a result of these problems, 52.2 defined the minimum efficiency reporting value (MERV) to describe filter performance. The MERV is based on the worstcase performance of a filter through all six stages of dust loading and all particles microns. Because the rating represents the worst-case performance, specifiers can use it to assure performance in applications where a maximum particle count must be maintained over the filter s entire life. MERV vs. dust spot MERV ratings are not listed in many filter catalogs available today, except for higher-end products. Eventually, the ratings will be a part of all catalog listings, so managers will need to become familiar with them. For managers working with high-efficiency particulate air (HEPA) filters and ultra-low penetration air (ULPA) filters, a working knowledge of 52.2 soon will become vital. The old standard 52.1 is rapidly becoming outdated for describing filter performance at this level. Standard 52.2 lists approximate dust-spot efficiencies and corresponding MERV values. For example: MERV values of 8 and higher correspond to dust-spot efficiencies of more than 30 percent. MERV values of 13 and higher correspond to dust-spot efficiencies more than 80 percent. MERV values of 15 and higher correspond to dust-spot efficiencies more than 95 percent. As a result of these equivalencies, a manager could expect that a facility s current stock of 30 percent pre-filters to eventually be replaced with filters with a MERV rating of 8. Similarly, existing 80 percent filters will have a new rating of MERV 13, and 95 percent filters a new rating of MERV 15. Ratings explained A typical MERV rating tells a specifier the arrestance rating of the filter at three
4 particle sizes of microns at a certain face velocity. For example, a rating of MERV 10 at 0.93 indicates a filter with a MERV 10 arrestance when operated at an airflow of 0.93 cubic meters per second, which is a little less than 500 feet per minute, or 2,000 cubic feet per minute (cfm) for a standard 2-foot-square filter. A rating of MERV 10 corresponds to percent efficiency for particles 1-3 microns and above 85 percent efficiency for particles 3-10 microns. A rating of MERV 13 corresponds to less than 75 percent arrestance efficiency for particles microns, above 90 percent efficiency for particles 1-3 microns, and above 90 percent efficiency for particles 3-10 microns. A rating of MERV 15 corresponds to percent arrestance efficiency for particles microns, above 90 percent efficiency for particles 1-3 microns, and above 90 percent efficiency for particles 3-10 microns. Arrestance efficiencies are based on particle counts taken upstream and downstream of a test filter with an optical, or laser, particle counter. The entire list of MERV ratings based on particle arrestance efficiency is found in Table 12-1 of Standard Although the standard only lists arrestance efficiencies for MERV values to 16, continuously higher ratings can be easily added. In fact, the table lists ratings up to MERV 20. Ratings of MERV 16 to MERV 20 correspond to HEPA and ULPA filters. Standard 52.2 is designed to start a shift away from an arbitrary concept of average efficiency and toward the concept of arrestance based on particle size. Air-filter applications will be based on critical aspects of the process involved, such as circuit dimensions or microbial size, that resolve themselves into target particle sizes. The required MERV rating for filters will follow directly from the maximum allowable particle concentrations in the three bands of microns, microns and microns. Putting the standard to work If Standard 52.2 is going to require more thought in filter selection, the good news is that maintenance and engineering managers will have more control over tailoring the quality of the facility s air supply. They can use the following tips to
5 help transition to the MERV ratings and better indoor air quality: Work with factory representatives to obtain documentation showing the new MERV ratings for their existing products. These ratings will be coming out in the next several years. Look for new MERV ratings that will appear along with the old dust-spot or DOP rating on filters and filter packaging. Use these equivalencies to better understand the new ratings. Create a new strategy for evaluating filters in terms of target particle sizes. MERV ratings encourage filter selection based on particle size requirements. Inspect filter installations for good sealing. No filter can stop particles that bypass the media. Confirm that filters have manometers to indicate the time for change-out, and monitor filters regularly. Managers using these tips and Standard 52.2 are likely to have a better chance of creating and maintaining a healthy and productive indoor work environment in their facilities. Ron Wilkinson is the staff mechanical engineer for the State of Montana Architecture and Engineering Division. The Evolution of Air Filtration Standards ASHRAE Standard 52.2 grew out of ASHRAE Standard , Gravimetric and Dust Spot Procedures for Testing Air Cleaning Devices Used in General Ventilation for Removing Particulate Matter. Standard 52.1, in turn, developed out of Standard , which was the culmination of efforts by the National Institute of Standards and Technology and the Air Filter Institute. Prior to Standard , air filters used in facilities were large mesh furnace filters that kept large fibers from fouling heating and cooling coils. These filters would have had ASHRAE Standard 52.1 dust-spot efficiencies of about 10 percent and arrestance ratings of about 50 percent initially, growing to 80 percent or better as the filter filled with material.
6 Most fine dust passed through these filters directly into the facility. Facilities tolerated this situation because the resulting IAQ was at least as good as the outside air, and the outside air seemed a good de-facto standard of acceptable air quality. But the accelerating use of forced-air HVAC systems in new buildings brought further problems. The fine dust that escaped the single-panel arrestance filters discolored ceilings and other surfaces. Over time, black streaks appeared, radiating out from air supplies. Fine dust also created a cleaning problem on office furnishings. So during the 1970s and 1980s, Standard was developed, including both arrestance and dust-spot tests. The latter test actually simulated the discoloration of a test filter as a basis for rating the product. For both tests, performance was measured with a standard test dust containing a mixture of fine and course materials. But even the finest constituents of test dust were not small enough to match the needs of today s hospitals, laboratories and clean rooms. Ron Wilkinson
A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
3M Purification Inc. 3M Air Management Products for Your Commercial HVAC Needs. Create. Air. Confidence
3M Purification Inc. 3M Air Management s for Your Commercial HVAC Needs Create an Air of Confidence Pursuing Innovation 3M Company has long encouraged employees to pursue ideas and concepts that might,
Commercial Coil Cleaning:
18 Commercial Coil Cleaning: by Barry Harris, PH.D., ASCS 1, Lindell F. Killian, ASCS 2, and Nicolaus P. Neumann, P.E. 3 A Case History Facility managers and HVAC engineering supervisors have limited budgets
Camfil Farr Technical Services Bulletin
Camfil Farr Technical Services Bulletin ASHRAE Testing for HVAC Air Filtration A Review of Standards 52.1-1992 & 52.2-1999 The American Society of Heating, Refrigeration, and Air Conditioning Engineers
G U I D E L CERTIFICATION EDUCATION TRAINING. Procurement Guideline. National Air Filtration Association Recommended Practice
G U National Air Filtration Association Recommended Practice I D E L I N E Procurement Guideline TRAINING EDUCATION CERTIFICATION HVAC Air Filter Purchasing Specification Guideline 1.0 Purpose To provide
Camfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality
Camfil Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality Most non-practitioners notice the HVAC system when it is too hot, or too cold, or in other ways not working
DATA CENTERS. Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS
DATA CENTERS Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS COSTLY FAN ENERGY REDUCED BY CAMFIL PREMIUM PRODUCTS = COST SAVINGS Power Usage Effectiveness (PUE) is an important metric
Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP
Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s
HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.
HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains
EACO DOP / PAO TESTING GUIDELINE 2013
2013 Foreword The guideline promotes industry standards for training, equipment, and methodologies for HEPA filter integrity testing of negative air units, vacuums and any other HEPA filtered equipment
ANSI/ASHRAE 52.2-2007
The Updated Air Filter Standard ANSI/ASHRAE 52.2-2007 Koch Filter Corporation...Durable. Reliable. Versatile. Bulletin No. K-ASH52.2-09 In recent years, the air filter industry has changed important portions
Robert McCabe Director, Health Care Solutions HTS Chicago. Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade
Robert McCabe Director, Health Care Solutions HTS Chicago Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade Biography Robert McCabe has been involved in commercial
IEQ-15 Air Distribution System
AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material Revised November 21, 2013 Application Code of Practice Where asbestos is present or believed to be present in a workplace
How to Choose An Air Filter For Your Boat
How to Choose An Air Filter For Your Boat That Will Reduce Diesel Fumes, Smoke and Odors L-2395 Rev. 1-07-06 Air Filtration Fundamentals Air filters are devices that capture dust and other contaminants
Restoring your Property: How to be prepared for Rapid Response to Flood Damage
Restoring your Property: How to be prepared for Rapid Response to Flood Damage After a flood, the restoration process can be long and complex, particularly for large commercial properties. Failure to apply
There are several types of air cleaning devices available, each designed to remove certain types of pollutants.
Please Note: EPA neither certifies nor recommends particular brands of home air cleaning devices. While some home air cleaning devices may be useful in some circumstances, EPA makes no broad endorsement
Mechanical Systems Proposal revised
Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option
Laminar Flow Cabinets
Laminar Flow Cabinets The World s Most Practical Selection of Benchtop Laminar Flow Cabinets. 24 36 48 Simple, Effective Protection for Samples and Work Processes, Uncompromised Performance, Economical
Certification system of air filter quality (CAF mark)
Certification system of air filter quality (CAF mark) KOREA AIR CLEANING ASSOCIATION 1. Overview What is the certification system of air filter quality (CAF mark)? It is a mark granted by the KACL depending
Trane CleanEffects. Patented technology. Superior performance. READ ONLY
Trane CleanEffects Patented technology. Superior performance. Trane CleanEffects is unlike anything else out there. So is the air it produces. Today s air needs tomorrow s air cleaning system. There may
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?
Trane s Position on UV-C Lights
Trane s Position on UV-C Lights Note: The following Trane corporate position statement was issued on October 6, 2008. Trane monitors technologies that offer the potential to improve indoor air quality
Electrostatic or Electronic: Know the Facts By Robert P. Scaringe, P.E., Ph.D., ---President of Mainstream Engineering
Electrostatic or Electronic: Know the Facts By Robert P. Scaringe, P.E., Ph.D., ---President of Mainstream Engineering HVAC system air filter upgrades are one way contractors can simultaneously increase
HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN
HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN Presented to: ASHRAE YEA Illinois Chapter Specialty Environment Design Conference March 24, 2014 Jean O. Gibbons, PE, LEED AP Senior Vice President Grumman/Butkus
NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS
NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS National Air Duct Cleaners Association 1518 K Street, N.W. Suite 503 Washington, DC 20005 (202)
Specification. Indoor Air Quality Management
GREENGUARD Environmental Institute 2211 Newmarket Parkway, Suite 110 Marietta, GA 30067 1.800.427.9681 Specification Indoor Air Quality Management This Master Specification section is intended for use
Environmental Monitoring
Chapter 10 Environmental Monitoring By the end of this chapter, you will be able to: l List the types of environmental testing l Name three types of checks that are carried out to ensure the isolator is
How to Measure HVAC System Airflow
How to Measure HVAC System Airflow About National Comfort Institute National Comfort Institute is an international training Since our and beginning development in 1994 company we have trained with and
Exhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: [email protected] ADC Part No. 450450 Exhaust
SPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
PREVENTIVE MAINTENANCE OF FIBER OPTIC CABLES AND OPTICS
PREVENTIVE MAINTENANCE OF FIBER OPTIC CABLES AND OPTICS The end of a fiber optic cable and the inner surface of an optical module lens constitute optical surfaces that should be properly cleaned and maintained
HEALTHY CLIMATE HEPA BYPASS AIR FILTRATION SYSTEM READ AND SAVE THESE INSTRUCTIONS! AIR CLEANERS/ FILTERS
AIR CLEANERS/ FILTERS 504,887M 04/2010 HEALTHY CLIMATE HEPA BYPASS AIR FILTRATION SYSTEM HOMEOWNERS MANUAL & DEALER INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE MODELS HEPA-20, HEPA-40, HEPA-60 Rules
ASBESTOS MANAGEMENT PROGRAM
ASBESTOS MANAGEMENT PROGRAM Prepared By: Triumvirate Environmental Program Approval Developed: August 2011 Updated: June 2015 Associate Vice President of Public Safety & Administrative Services Date Associate
Improving Indoor Air Quality on a Tight Budget
Improving Indoor Air Quality on a Tight Budget The HVAC system serving our shelter was outdated, extremely inefficient, and constantly malfunctioning, so it was time for new equipment. I researched information
Basics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
FS209E and ISO Cleanroom Standards
FS209E and ISO Cleanroom Standards Terra Universal is the leading expert in the design and fabrication of critical-environment applications. We offer a complete range of equipment, furnishing and supplies
THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM
1 Application Note AT-102 THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM Lawrence B. Kilham 1 and Randall M. Dodd 2 1 Eco Sensors, Inc. Santa Fe, New Mexico, USA [email protected]
ASHRAE ADDENDA. Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size
ANSI/ASHRAE Addendum b to ANSI/ASHRAE Standard 52.2-2007 ASHRAE ADDENDA 2008 SUPPLEMENT Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size Approved by the
HEPA FILTER DEFECTS ARE COMMON
HEPA FILTER DEFECTS ARE COMMON Kenneth F. Cherry 1 and Kenneth A. Smigielski 2 1 NCEC Inc. 2 First Solar LLC. ABSTRACT HEPA filters (High Efficiency Particulate Air) filters are claimed by vendors to have
What to Know When Considering a Cleanroom. by Simplex Technical Staff
What to Know When Considering a Cleanroom by Simplex Technical Staff What to Know When Considering a Cleanroom by Simplex Technical Staff Does your business plan include the development of an area in your
ROTARY SCREW COMPRESSOR. RMD 30-37 - 45-55 kw
ROTARY SCREW COMPRESSOR RMD - - - 55 kw EN The RMD Coaxial Rotary Compressor high reliability high performance low maintenance is the result of decades of experience in manufacturing design and construction
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling. fantech
Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling 2 Ductless Ventilation & Fresh Air Solutions We can fill your home with healthy, fresh air Indoor Air Pollution is real, and it
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN Umesh Atre Innovative Design Inc 850 W Morgan St Raleigh, NC 27603 [email protected]
Indoor air quality monitoring made easy
Indoor air quality monitoring made easy with the Fluke 985 Particle Counter Application Note Introduction Energy savings is top of facilities owners agenda. HVAC system tends to be the largest contributor
AccuClean. For Air That s As clean READ ONLY
AccuClean For Air That s As clean as it is comfortable. Why is American Standard AccuClean air filtration better than the rest? Cleaner air starts with better airflow. Thanks to the patented technology
Quick wins for energy savings in buildings
Quick wins for energy savings in buildings Choosing low energy air filters for both optimized energy performance and indoor air quality Executive Summary HVAC systems heat, cool and clean the air within
MAC 10. Original & IQ FAMILY OF FAN FILTER UNITS
MAC 10 Original & IQ FAMILY OF FAN FILTER UNITS used in: microelectronics medical device semiconductor disk drive laboratory pharmaceutical markets hospitals clean rooms Table of Contents MAC 10 Original
Essam E. Khalil [email protected]
AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil [email protected] PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract
WATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts
WATER DAMAGE INVESTIGATION Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory
Both health-care facility classification and area classification, as per CSA, determine the design requirements.
HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM (HVAC) Class 1 Facility: General Anesthesia Heating, ventilation and air-conditioning system standards are a primary infection prevention and control strategy
SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING
SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air
www.dataspan.com 800.660.3586 Data Center and Computer Room Services Specialty Services Data Center and Computer Room Products Sub-Floor Cleaning
Data Center Cleaning Services The best way to eliminate downtime? Stop problems before they start. Our specialized anti-static cleaning services will protect your storage media and other important infrastructure
Technical Brief. 3M Commercial HVAC Filters. Commercial HVAC Filter Efficiency Reporting Value. Abstract. Introduction
3M Commercial HVAC Filters Technical Brief Commercial HVAC Filter Efficiency Reporting Value Abstract The effi ciency of fi lters utilized in the HVAC industry is characterized by the Minimum Effi ciency
The Impact of Fouling on the Performance of Filter- Evaporator Combinations
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 The Impact of Fouling on the Performance of Filter- Evaporator Combinations
Building and Grounds Maintenance Checklist
Building and Grounds Maintenance Checklist Name: School: Room or Area: Date Completed: Signature: Instructions 1. Read the IAQ Backgrounder and the Background Information for this checklist. 2. Keep the
SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR. www.sentryair.com 1.800.799.
SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR 1.800.799.4609 www.sentryair.com Pharmaceutical Compounding Safety Solutions Sentry Air Systems
Advantages Of A New And Advanced Nanofiber Coating Technology For Filtration Media Compared to The Electrospinning Process
Advantages Of A New And Advanced Nanofiber Coating Technology For Filtration Media Compared to The Electrospinning Process John Wertz Immo Schnieders Abstract Research and development of nanofibers has
Both health-care facility classification and area classification, as per CSA, determine the design requirements.
HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM (HVAC) Class 3 Facility: Local Anesthesia Heating, ventilation and air-conditioning system standards are a primary infection prevention and control strategy
Construction Drawings and Terminology for the Infection Prevention Professional. Objectives. Disclaimer
Construction Drawings and Terminology for the Infection Prevention Professional APIC Greater St. Louis Chapter 073 October 2012 Objectives Define the terms and descriptions of airborne engineering controls
GUIDE TO. air scrubbing
GUIDE TO air scrubbing 2 WHAT IS AN AIR SCRUBBER? In the simplest terms, an air scrubber is a portable filtration system. It draws in air from the surrounding environment and passes it through a series
Viledon HEPA and ULPA Filters The Patented Solution for Sterile Air and Clean Rooms. Product Overview
Viledon HEPA and ULPA Filters The Patented Solution for Sterile Air and Clean Rooms Product Overview In a class of their own for technology and performance While the performance qualities of air filters
Ventilation Standard For Health Care Facilities
The following article was published in ASHRAE Journal, October 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
Why is my air conditioner dripping on my customers?
De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These
How To Use An Air Scrubber
DRI-EAZ PRODUCTS, INC., 15180 JOSH WILSON RD., BURLINGTON, WA 98233 1-800-932-3030 FAX: (360) 757-7950 www.dri-eaz.com GUIDE TO air scrubbing 2 WHAT IS AN AIR SCRUBBER? In the simplest terms, an air scrubber
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace Our thanks to OK International for allowing us to reprint the following. Why do we need fume extraction? Today s Electronics workplace
SECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
Cartridge Filter Application Notes
Industrial Water Purification (800) CAL-WATER Cal Water 1961 Petra Lane Placentia, CA 92870 FAX: (714) 792-0794 Web Page / Email: www.cal-water.com Cartridge Filter Application Notes Cal Water offers a
KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS
KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS By Jerome E. Spear, CSP, CIH Effective January 1, 2005, consultants who prepare mold management plans for buildings located in Texas must be licensed
Radford University. Indoor Air Quality Management Plan
Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
WATER DAMAGE INVESTIGATION. Massachusetts Gaming Commission 101 Federal Street Boston, Massachusetts
WATER DAMAGE INVESTIGATION Massachusetts Gaming Commission 101 Federal Street Boston, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor Air Quality
Filtration and Air-Cleaning Systems to Protect Building Environments from Airborne Chemical, Biological, or Radiological Attacks
Guidance for Filtration and Air-Cleaning Systems to Protect Building Environments from Airborne Chemical, Biological, or Radiological Attacks Department of Health and Human Services Centers for Disease
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
Coil Cleaning Program
Coil Cleaning Program Procedures and Calculations that Affect your Bottom Line Fact: Did you know that annually cleaning HVAC coils reduces energy consumption in most cases enough to pay for the cleaning
UV100A Ultraviolet Air Treatment System
UV100A Ultraviolet Air Treatment System INSTALLATION INSTRUCTIONS APPLICATION When installed in forced air heating and cooling systems, the UV100A Ultraviolet Air Treatment System kills airborne microorganism
RMF TANDEM 900 OFF-LINE FILTER SYSTEMS
RMF TANDEM 900 OFF-LINE FILTER SYSTEMS RMF Tandem 900 Off-line filter Systems can be applied to every imaginable industrial application where hydraulic or lubrication systems are present. An integrated
Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1
Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1 Background: The past 10 years have seen a dramatic change in the design and function of air handlers, due in
indoor Air quality products Air Filtration Ventilation Purification Humidification
indoor Air quality products Air Filtration Ventilation Purification Humidification how clean is the air in your home? According to the Environmental Protection Agency (EPA), American homeowners spend about
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
Environmental Technology Verification. Test Report of Control of Bioaerosols in HVAC Systems
Environmental Technology Verification Test Report of Control of Bioaerosols in HVAC Systems Columbus Industries SL-3 Ring Panel Prepared by Research Triangle Institute Under a Contract with U.S. Environmental
Technical Cleaning Ó
Technical Cleaning JUSTIFICATION Cleaning of Data Centers and Communications Rooms should be performed by qualified personnel who will use techniques and equipment designed to clean without re-contaminating
Today, healthcare facilities must be prepared to face
Alternate Methods for USING GERMICIDAL UV-C Disinfection Lamps TO SUPPLEMENT HEPA Filtration By Dave Shagott Today, healthcare facilities must be prepared to face potential large-scale threats from chemical,
Guidelines for Mold Remediation (Removal)
Guidelines for Mold Remediation (Removal) Indoor mold growth, water damage, or musty odors should be addressed quickly. Removing mold growth and correcting the underlying cause of water accumulation can
Pulverized Coal Pipe Testing and Balancing
Pulverized Coal Pipe Testing and Balancing By Richard F. (Dick) Storm, PE The first step in optimizing combustion system performance is balancing the air and fuel flowing through each of the plant's coal
Chapter 12 Industrial Ventilation
Chapter 1 Industrial Ventilation Introduction Industrial Ventilation is an important method for reducing employee exposures to airborne contaminants. Ventilation is used to reduce or remove contaminates
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
Owner s Manual Model 5000 Safety, Operating and Maintenance Instructions
Electronic Air Cleaner 90-1147 Owner s Manual Model 5000 Safety, Operating and Maintenance Instructions READ AND SAVE THIS MANUAL WARNING 120 Volts may cause serious injury from electrical shock. Disconnect
March 2007. Get The Mold Out: Mold Clean-Up Guidance for Residences. Introduction
March 2007 Connecticut Department of Public Health Environmental Health Section Environmental & Occupational Health Assessment Program 410 Capitol Avenue MS # 11EOH, PO Box 340308 Hartford, CT 06134-0308
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
Wildfire Smoke and Your Health
PUBLIC HEALTH DIVISION http://public.health.oregon.gov Wildfire Smoke and Your Health When smoke levels are high, even healthy people may have symptoms or health problems. The best thing to do is to limit
Howorth Air Technology. Healthcare Air Management Services
Howorth Air Technology Healthcare Air Management Services Howorth - Pure Protection For more than 150 years, the Howorth name has represented technical creativity and expertise in air engineering and its