Saeid Rahimi. Effect of Different Parameters on Depressuring Calculation Results. 01-Nov-2010. Introduction. Depressuring parameters



Similar documents
1. Define the System SDV BDV SDV SDV SDV BDV SDV SDV SDV SDV SDV SDV. Process System TO FLARE TO FLARE BDV TO FLARE

Select the Right Relief Valve - Part 1 Saeid Rahimi

No. Name Description Main input Data Main Output Data. cooling duty, process in/out temperature, inlet air temperature

EMERGENCY VESSELS BLOWDOWN SIMULATIONS

Unsteady State Relief Valve Evaluation. External Pool Fire Scenario

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS

Chapter 18 Temperature, Heat, and the First Law of Thermodynamics. Problems: 8, 11, 13, 17, 21, 27, 29, 37, 39, 41, 47, 51, 57

Problem Set MIT Professor Gerbrand Ceder Fall 2003

Jump Start: Storage Tank Protection in Aspen HYSYS and Aspen Plus

Module 5: Combustion Technology. Lecture 34: Calculation of calorific value of fuels

5.2. Vaporizers - Types and Usage

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

RESPONSE TIME INDEX OF SPRINKLERS

FXA Candidates should be able to : Define and apply the concept of specific heat capacity. Select and apply the equation : E = mcδθ

Vapor Chambers. Figure 1: Example of vapor chamber. Benefits of Using Vapor Chambers

How To Design A Refrigeration System

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

Natural Convection. Buoyancy force

Module 1 : Conduction. Lecture 5 : 1D conduction example problems. 2D conduction

Type: Single Date: Homework: READ 12.8, Do CONCEPT Q. # (14) Do PROBLEMS (40, 52, 81) Ch. 12

API Standard Guide for Pressure-Relieving and Depressuring Systems

The Ideal Gas Law. Gas Constant. Applications of the Gas law. P = ρ R T. Lecture 2: Atmospheric Thermodynamics

Heat Pipe Selection Revision 12/04/2001

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

The soot and scale problems

EASIDEW PORTABLE HYGROMETER INSTALLATION, OPERATION AND MAINTENANCE MANUAL

TABLE OF CONTENT

TEACHER BACKGROUND INFORMATION THERMAL ENERGY

Specific Heat Capacity and Latent Heat Questions A2 Physics

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

The Second Law of Thermodynamics

Peltier Application Note

Chemistry 13: States of Matter

HEAT UNIT 1.1 KINETIC THEORY OF GASES Introduction Postulates of Kinetic Theory of Gases

EUROPEAN CHEMCAD SYMPOSIUM 1999

OSHA Tank Venting DEFINITIONS

How does solar air conditioning work?

Engineering Recommendation on: Accumulators Revised Issued January 10, 1979 Page 1 of 7

Answer, Key Homework 6 David McIntyre 1

ORGANIC LABORATORY TECHNIQUES NEVER distill the distillation flask to dryness as there is a risk of explosion and fire.

Vacuum. How It Relates to Refrigeration And Air Conditioning Service

Refrigeration Basics 101. By: Eric Nelson

THE BASICS Q: What is VOC? Q: What are flashing losses/voc emissions from hydrocarbon storage tanks? - 1 -

CHAPTER 12. Gases and the Kinetic-Molecular Theory

Contents and Nomenclature

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

Air Eliminators and Combination Air Eliminators Strainers

Project Renewable Insulation Example Teacher Notes

Gas Laws. The kinetic theory of matter states that particles which make up all types of matter are in constant motion.

TABLE OF CONTENT

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )

Liquid level measurement using hydrostatic pressure and buoyancy

REFRIGERATION (& HEAT PUMPS)

COMBUSTION. In order to operate a heat engine we need a hot source together with a cold sink

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

How To Use A Water Source Heat Pump

Thermodynamics AP Physics B. Multiple Choice Questions

Thermodynamics - Example Problems Problems and Solutions

THE HUMIDITY/MOISTURE HANDBOOK

Liquefied Natural Gas (LNG)

PSAC/SAIT Well Testing Training Program Learning Outcomes/Objectives Level B

COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here.

How To Calculate The Performance Of A Refrigerator And Heat Pump

The Precharge Calculator

In this experiment, we will use three properties to identify a liquid substance: solubility, density and boiling point..

a) Use the following equation from the lecture notes: = ( J K 1 mol 1) ( ) 10 L

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances.

جامعة البلقاء التطبيقية

saving energy in comfort Factsheet Recair Enthalpy

C. starting positive displacement pumps with the discharge valve closed.

Production of R-134a

Molar Mass of Butane

Optimize Pipeline Hydraulics with Multiphase Flow Modeling

Physical Properties of a Pure Substance, Water

This will also provide you with the knowledge to insure long life for your Investment

Boiler efficiency measurement. Department of Energy Engineering

BB-18 Black Body High Vacuum System Technical Description

MATERIAL SAFETY DATA SHEET

Overview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank

Steady Heat Conduction

Chemical Reactions Practice Test

HS-901(A) BASIC STEAM HEATING SYSTEMS

Dry-out Design Considerations and Practices for Cryogenic Gas Plants

Gas Detection for Refining. HA University

Process Control Primer

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

39th International Physics Olympiad - Hanoi - Vietnam Theoretical Problem No. 3

ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS

IDEAL AND NON-IDEAL GASES

The Versatile Differential Pressure Transmitter. By David Gunn Honeywell Process Solutions

Practice Test. 4) The planet Earth loses heat mainly by A) conduction. B) convection. C) radiation. D) all of these Answer: C

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

4 Posiflow Proportional Solenoid Valves

REASONING AND SOLUTION

(Walter Glogowski, Chaz Shapiro & Reid Sherman) INTRODUCTION

EXPERIMENT 15: Ideal Gas Law: Molecular Weight of a Vapor

Engineering Software Enables Designing for the Deep

Rusty Walker, Corporate Trainer Hill PHOENIX

Transcription:

Effect of Different Parameters on Depressuring Calculation Results Introduction Saeid Rahimi 01-Nov-2010 Emergency depressuring facilities are utilized to accomplish at least one of the following objectives: To reduce the risk of catastrophic equipment failure (due to thermal decomposition of unwetted surfaces) and/or BLEVE during fire exposure To reduce the risk of equipment failure during an exothermic runway reaction (out of interest of this note) To reduce the amount of material released if there is a loss of contaminant To rapidly move the system into safe state, in the event of other emergency scenarios like power failure, failure of control system etc. Depressuring valve sized for above cases will be also used to depressurize system for maintence and normal shutdowns. In view of above possibilities and considering different conditions from which depressuring will start, the following categories can be made: 1) Fire depressuring (immediate depressurization of system on fire) 2) Adiabatic depressuring (depressurization of system under emergency scenarios like utility failure or vessel out of fire during fire) 3) Isochoric depressuring (depressurization of system after a prolonged shutdown) Depressuring parameters There are some depressuring parameters which are independent of type of depressuring such as: Vessel dimension Refer to technical note Setting Hysys Depressuring Model Dimensions to Get More Accurate Results for the effect of vessel dimensions on final results and how to set them to get the volume, surface area, wetted area and metal weight of model same as actual system. Valve specifications Since depressuring system is independently sized by vendor using maximum fire depressuring rate and differential pressure given in process datasheet, then any valve type can be used. The only point is that same valve type and CV shall be used for cases other than fire. Valve type may be important when a supercritical mixture is depressurized. Supercritical depressurization sometimes shows a spike in the profile of depressuring flow rate and vessel gas and liquid contents. This is observed when vessel gas content gets suddenly condensed and vaporized again. This error may be resolved if: Type of valve is changed to General Calculate Pressure option is used instead of Calculate CV 1) Fire Case This scenario can be called hot depressuring which is aiming depressuring rate calculation and consequently size of depressuring system (restriction orifice). Initial pressure Different pressures have been recommended as initial pressure in different standards or practices like design pressure, PSV set pressure, high-high pressure switch. Regardless of this variety, higher pressure is more conservative. 1

Final pressure Final pressure has been sometime specified very generic: 6.9 barg or 50% of design pressure whichever is lower within 15 minutes. 6.9 barg within 15 minutes. 50% of design pressure within 15 minutes. Sometimes, it is specified based on type of fire. 6.9 barg within 15 minutes for vessel on jet fire 50% of design pressure within 15 minutes for vessel on pool fire. and sometimes according to vessel content and thickness: 6.9 barg within 15 minutes if vessel contains flammable gas (which may fuel the fire) and vessel thickness is more than 25 mm. 50% of design pressure within 15 minutes if vessel does not contain flammable gas and vessel thickness is more than 25mm. 6.9 barg within 15 minutes minus 3 min. for each 5mm reduction in thickness if vessel contains flammable gas (which may fuel the fire) and vessel thickness is less than 25mm. 50% of design pressure within 15 minutes minus 3 min. for each 5mm reduction in thickness if vessel doe not contains flammable gas and vessel thickness is less than 25mm. 6.9 barg within 8 minutes if vessel containing LPG or light condensate regardless of vessel thickness to avoid BELEVE Shorter time and lower final pressure generates higher depressuring rate and consequently larger depressuring system. See technical note How to Set Depressuring Time for Fire. Depressuring time Refer to above section. Depressuring time can be higher or lower than 15 minutes according to client standard especially for huge vessels such as figure type slug catcher where depressuring rate can exceed flare system design limit. Initial temperature Table 1 Environment factor Maximum operating temperature is normally used as initial temperature for fire depressuring. Initial liquid level The following criteria have been used: High liquid level Normal liquid level High-high liquid level for vessel with on/off level control and Normal liquid level for continuous control Normal liquid level plus 75 mm per tray for trayed columns Normal liquid level plus 30 mm per each 240 mm of internal packing for packed columns Higher level will result in higher depressuring rate. System Description Bare vessel 1.0 Insulated with fire resistant insulation 0.3 25 mm 0.2 37mm 0.15 50mm 0.1 73mm 0.075 100mm and above Mounded 0.03 Underground 0 Heat input model For vessel containing liquid, API- 521 fire equation (q = 43.2 F A 0.82 w ) is appropriate. F shall be defined as per Table 1. No credit is taken for normal insulation, fire fighting and depressuring facilities (F = 1.0). For totally dry systems, Fire equation (q = C 1 + C 2 time + C 3 (C 4 Vessel Temp) +.) is usually used. For this purpose, constant heat input can be defined by setting C 1 = Q A and C 2 = C 3 = C 4 = C 5 = 0 where Q (fire heat flux) range F 2

as advised by API is 80 to 100kW/m 2. Refer to discussion made on fire heat flux in technical note Fire Heat Flux to Un- Wetted Vessel, where the adequacy of this equation is discussed. Heat loss model There are three heat loss models: none, simple, detail. Although specifying the system heat loss in detail model seems more realistic but none model is normally used for fire case. This model assumes that system is totally insulated from surrounding so that total fire heat is absorbed by vessel gas content (not metal) and there is no heat loss to ambient. This is because plate was at fire temperature in API test through which fire heat flux was measured. In other words, fire heat flux given by API (for both wetted and unwetted vessels) is the net heat transmitted to gas which is not taking into account the vessel mass and conductivity. Initial composition It is very hard to generalize the effect of initial composition on depressuring rate and size but it is advised to check high and low molecular weight and density cases. If the system consists of several vessels with different compositions (such as fractionation columns) feed, bottom and top composition can be examined to find the largest required rate. Water as one the major components in any hydrocarbon system needs special attention especially if vessel contains separate water phase (three phase separator). In this case, it is recommended to ignore water and consider vessel containing only hydrocarbon because: 1. Water has very high heat capacity (Cp) and absorbs fire heat input without considerable increase in temperature. Furthermore, system temperature reduction due to joule-thompson effect during depressuring works in opposite way and water (vessel content) does not usually reach boiling point within depressuring time (15 minutes). For example, according to following calculation the temperature raise is only 40 C for 1m 3 of water after 15 minutes exposure to fire where the cool down effect of depressuring can be much more than 40 C. Q = 43.2 F A 0.82 w = 43.2 x 1 x 6 0.82 = 187.7 kj/sec (Maximum wetted area of 1m3 liquid is 6m 2 ) ΔT = Q Time / V C p = (187.7 x 15 x 60) / (1000 x 1 x 4.2) = 40.2 C 2. Water latent heat at boiling point is also 5-10 times of hydrocarbons which results in less depressuring rate. For system containing gas and water/water solution (ideally no hydrocarbon) such as Amine or TEG, water solution can be considered although it may not have much contribution in vapor generation. PV PV of zero may be appropriate for fire case. 2) Adiabatic/Isochoric Case This scenario can be called cold depressuring which is targeting minimum vessel design temperature using orifice size from hot depressuring. Initial pressure Adiabatic blowdown is usually from high-high pressure switch or settle out pressure of compressor loop isochoric blowdown starts from pressure corresponding to system initial temperature Initial temperature Figure 1- System temperature profile with ambient temp. Adiabatic blowdown is usually from normal operating temperature or settle out temperature of compressor loop Isochoric blowdown starts from temperature of system after being exposed to minimum ambient temperature for a long time. As a conservative assumption, minimum ambient temperature is usually used as system initial temperature. This is quite valid assumption for non-insulated small vessels. For large inventory vessels, system temperature will follow ambient temperature changes with some margin and time lag. The margin depends on system heat content and total heat 3

transfer rate. A detail calculation is required to specify minimum system temperature during coldest period of year. In some cases, the margin is so high that system temperature actually flocculates within narrow band as shown in figure 1. Considering the objective of cold depressuring, lower initial temperature is preferred as it will cause lower fluid/metal temperature. Final pressure Final pressure is often atmospheric pressure. Initial liquid level Lower initial liquid level will result in lower fluid/metal temperature therefore LLL of LSLL can be used. PV PV can be specified as per below table. Since higher PV will cause lower fluid/metal temperature, the maximum value of each range is recommended. System Description PV Range (%) Recommended value (%) Liquid filled systems 40-70 70 Initially two phase systems or gas filled with liquid condensation 70-87 87 Gas filled systems 87-98 98 Heat loss model It is obvious that none model will result in lower temperature but it is generally preferred to define the model heat loss features similar to the actual system using detail model. Proper margin can be considered on final temperature results (if required). Below section reviews the effect of detail model parameters on final results. 1) Metal thickness Metal thickness affects heat transfer and heat content. Thicker plate means lower heat transfer and higher mass (heat) content. It seems the effect of metal thickness on heat transfer is negligible because the controlling resistant is not metal conductivity (resistant). Higher mass means that higher amount of heat must be consumed for one degree reduction in system temperature. 2) Insulation thickness Adding insulation will increase the adiabatic behavior of system and result in lower temperature. Insulation specifications shall be entered if actual system is insulated. 3) Ambient temperature Lower ambient temperature will causes lower system temperature. 4) Recycle efficiency Although some people believe that using recycle efficiency of 1% for gas and 100% for liquid as advised by Hysys instruction manual gives different temperature for gas and liquid which is in fundamentally correct but my study shows using recycle efficiency other than 100% will substantially increase the gas temperature. Refer to technical note Validation of Hysys Depressuring Utility where hysys results are in good agreement with experimental data using 100% for both gas and liquid. Valve CV If overdesigned CV from fire case is utilized for cold depressuring, fast depressuring won t allow system to gain some heat from ambient. This will cause lower system temperature. Under-designed CV will have reverse impact. Water If three phases (gas, water and oil) are present, no water to be considered as it has very high heat capacity and doesn t allow system temperature to drop. For system containing gas and water/water solution (ideally no hydrocarbon) such as Amine or 4

TEG, water solution should be considered if ignoring water ends up with exotic material (for very low temperature) which may not be really required for these systems. Case study Fire A two phase vertical flat end vessel without piping and any insulation, 2m ID, 3.18m T/T at initial pressure and temperature of 20 bara and 40 C respectively containing 3m 3 (corresponding to HLL) of liquid with below composition is assumed as a base case. This system is going to be depressurized within 15 minutes during fire through a Fisher valve (100% open, C 1 = 25) and the effect of different parameters on final depressuring results were examined (Table 1). Initial composition: C 1 = 20%mol, C 2 = 20%mol, C 3 = 20%mol, n-c 4 = 20%mol, n-c 5 = 20%mol Adiabatic The same vessel containing 1m 3 of liquid (corresponding to LLL), adiabatically depressurized from 20 bara and minimum ambient temperature of 5 C is considered as a base case for preparation of Table 2 where the effect of different input parameters on depressuring results have been shown. Contact Please feel free to contact S.Rahimi@gmail.com or ContactUs@chemwork.org should you have any comment, question or feedback. 5

Table 1 Effect of different parameters on fire depressurization results Input data Calculation Results Parameter Total Volume (m3) Liquid Volume (m3) Heat input model Time (min) Vessel orientation PV Final pressure (bara) Flow rate (kg/s) Valve CV (gpm/min) Base case 10 3 API 15 Vertical 0% 6.9 1.2 16.25 PV 10 3 API 15 Vertical 50% 6.9 1.189 16.1 Final pressure 10 3 API 15 Vertical 0% 10 0.796 10.8 Liquid volume 10 1 API 15 Vertical 0% 6.9 0.648 8.8 Water 10 2+1(w) API 15 Vertical 0% 6.9 1.042 14.1 Table 2 Effect of different parameters on adiabatic depressurization results Input data Calculation Results Parameter Total Volume (m3) Liquid Volume (m3) Heat loss model Heat loss parameter Amb temp ( C) Ins thick (mm) Metal thick (mm) Vessel orient. PV Final pressure (bara) Valve CV (gpm/ min) Time (m':s'') Flow rate (kg/s) Min fluid temp ( C) Base case 10 1 detail 5 0 10 Vertical 87% 1.2 16.25 21:40 1.199-9.78 CV 10 1 detail 5 0 10 Vertical 87% 1.2 20.00 17:30 1.476-10.30 PV 10 1 detail 5 0 10 Vertical 70% 1.2 16.25 21:45 1.199-8.93 Heat loss model 10 1 none - Vertical 87% 1.2 16.25 20:00 1.199-16.74 Ambient temp 10 1 detail 20 0 10 Vertical 87% 1.2 16.25 21:40 1.199-9.25 Insulation thickness 10 1 detail 5 30 10 Vertical 87% 1.2 16.25 21:40 1.199-9.49 Metal thickness 10 1 detail 5 0 30 Vertical 87% 1.2 16.25 22:50 1.199-4.61 Final pressure 10 1 detail 5 0 10 Vertical 87% 2.5 16.25 14:05 1.199-0.63 Vessel orientation 10 1 detail 5 0 10 Horizontal* 87% 1.2 16.25 21:40 1.199-9.78** Liquid volume 10 2 detail 5 0 10 Vertical 87% 1.2 16.25 33:00 1.199-7.18 Water 10 1(w) detail 5 0 10 Vertical 87% 1.2 16.25 10:06 1.199 0.01 * System dimension has been defined so that horizontal vessel total volume, liquid volume, wetted area and weight is same as base case (vertical vessel) ** Vessel orientation does not have any effect on temperature because Hysys (till version 2006) uses heat transfer model developed for vertical surface for horizontal vessels also. 6