E-STOP relays, safety gate monitors



Similar documents
Contact expansion modules

Contact expander modules

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors

PNOZsigma - Base units

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

PNOZ s3. Safety relays. Operating Manual EN-10

PNOZ s5. Safety relays. Operating Manual EN-09

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Safety technique. Emergency stop module BO 5988 safemaster

RM4TG20 three-phase network control relay RM4-T - range V

mecotron Safety relay ESTOP-2 For emergency stop monitoring

38 Series - Relay interface modules A

Safety automation solutions

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

38 Series - Relay interface modules A

Electronic overload relay EF19 and EF45

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

48 SERIES Relay interface modules 10 A

Electronic overload relay EF65, EF96 and EF146

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Safety Manual BT50(T) Safety relay / Expansion relay

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

49 Series - Relay interface modules A. Features

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

SMS 4 / SMS 5 safety mat Product information

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Quick Connect. quick - simple - efficient.

Redundancy Module QUINT-DIODE/40

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Product and functional description

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Preset Counter signo 721

CONFIGURABLE SAFETY RELAYS

Safety Relays ESM/ESM-F

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

MasterINTERFACE 39 Series - Relay interface modules

RY2 miniature industrial relays

MasterINTERFACE 39 Series - Relay interface modules

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

HERZ-Thermal Actuators

PHOENIX CONTACT Features

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

PROTECT. Safety Relay Modules PROTECT-SRB s Catalogue Protect/04

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

Units PSENmag. PSEN 2.2p Unit features. Function description

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Pluggable interface relays CR-P Pcb relays

Digital input modules

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

Relés e Contatores de Estado Sólido SIRIUS

Emergency lighting units EM powerled

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Preventa Machine Safety Products

AS-i 3.0 PROFIBUS Gateways with integrated Safety Monitor

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/2

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/2x15DC/1

Type: DILM50(230V50HZ,240V60HZ) Article No.:

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

CONFIGURABLE SAFETY RELAYS

225C-024T-05. Continuous control rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER A, SERIES BCF0 AND BCF6

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Thermal-Magnetic Circuit Breaker M1-..

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

Type: DILM32 10(24V50HZ) Article No.:

Type: DILM9 10(24VDC) Article No.:

Power Supplies 3. SDN-P DIN Rail Series

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Three-phase monitoring relay CM-PFE

Switch Actuator, 8-fold, 10 A, MDRC AT/S , GH Q R0111

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Bul. 440R Guardmaster Safety Relays (DI, DIS, SI, CI, GLP, EM, and EMD) Selection Guide

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

40 Series - Miniature PCB/Plug-in relays A. Features

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Technicaldata General

SKR - industry relay

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Transcription:

Unit features Unit description Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of safety contacts from all other circuits 1 semiconductor output Connection options for: E-STOP pushbutton Safety gate limit switch Reset button A connector can be used to connect 1 PNOZsigma contact expander module Operating modes can be set via rotary switch LED indicator for: Supply voltage Input status, channel 1 Input status, channel 2 Switch status, safety contacts Reset circuit Error Plug-in connection terminals (either spring-loaded terminal or screw terminal) Gertemerkmale See order reference for unit types Bestimmung/Gerätebeschreibung NOT-AUS, Schutz_PNOZ The safety relay meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with E-STOP pushbuttons Safety gates Safety features ][Sicherheitseigenschaften Schaltgerät_allgemeiner Teil The relay meets the following safety requirements: The circuit is redundant with built-in self-monitoring. The safety function remains effective in the case of a component failure. The correct opening and closing of the safety function relays is tested automatically in each on-off cycle. Sicherheitseigenschaften Zusatz - Sicherung DC_PNOZ The unit has an electronic fuse. Zulassungen Block diagram Blockschaltbild A2 * 13 23 33 41 = Power = Input Reset/ Start K1 K2 Interface expansion unit Y32 14 24 34 42 * Safe separation in accordance with EN 60947-1, 6 kv

][Zeitdiagram_PNOZs_In_Ub_auto_manu_ueber1_ueber2_aux_Semi E-STOP relays, safety gate monitors Function description ][Funktionen_einkanalig Single-channel operation: no redundancy in the input circuit, earth faults in the reset and input circuit are detected. ][Funktionen_autoStart Automatic start: Unit is active once the input circuit has been closed. ][Funktionen_manuStart Manual reset: Unit is active once the input circuit is closed and then the reset circuit is closed. Timing diagram ][Funktionen_berStart_fall_Flanke Monitored reset with falling edge: Unit is active once the input circuit is closed and then the reset circuit is closed and opened again. the reset circuit is closed and then opened again once the input circuit is closed. ][Funktionen_berStart_steig_Flanke Monitored reset with rising edge: Unit is active once the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details). ][Funktionen_Kontaktvervielfachung_PNOZsigma Increase in the number of available instantaneous safety contacts by connecting contact expander modules or external contactors/relays; A connector can be used to connect 1 PNOZsigma contact expander module. 1 2 a b a 3 b a 4 b Reset/Start POWER/Input Output safe Output aux. Out semi t1 t2 t1 t2 t1 t2 t1 t2 t3 t1 t2 t1 t2 t3 t4 t1 t2 t1 t2 Key Power: Supply voltage Reset/Start: Reset circuit Input: Input circuits -A2 Output safe: Safety contacts 13-14, 23-24, 33-34 Output aux: Auxiliary contacts 41-42 Out semi: Semiconductor outputy32 Wiring ][Verdrahtung_Si_unverz_1Hi_unverz Please note: Information given in the Technical details must be followed. Outputs 13-14, 23-24, 33-34 are safety contacts, output 41-42 is an auxiliary contact (e.g. for display). To prevent contact welding, a fuse should be connected before the output contacts (see technical details). Calculation of the max. cable runs l max in the input circuit: I max = R lmax R l / km R lmax = max. overall cable resistance (see technical details) R l /km = cable resistance/km : Automatic reset : Manual reset : Monitored reset with rising edge : Monitored reset with falling edge a: Input circuit closes before reset circuit b: Reset circuit closes before input circuit Use copper wire that can withstand 60/75 C. Sufficient fuse protection must be provided on all output contacts with capacitive and inductive loads. t 1 : Switch-on delay t 2 : Delay-on de-energisation t 3 : Waiting period t 4 : Waiting period reset circuit was closed -2

Preparing for operation Betriebsbereitschaft herstellen PNOZs Supply voltage Supply voltage AC DC S1 L+ A2 L- Input circuit Input circuit Single-channel Dual-channel E-STOP without detection of shorts across contacts S1 L+ Safety gate without detection of shorts across contacts S1 L+ Reset circuit/feedback loop Reset circuit/feedback loop Reset circuit Feedback circuit Automatic reset 13 (23,33) 14 (24,34) K5 K6 K5 K6 L1 N Manual/monitored reset S3 K5 S3 K6 13 (23,33) 14 (24,34) K5 K6 L1 N Semiconductor output * Y32 PLC Input *Connect together the 0V connections on all the external power supplies

Key S1 S3 E-STOP pushbutton Reset button Gate open Gate closed ][Betriebsbereitschaft_herstellen_Info_Grundgert_DB INFORMATION If a base unit and a contact expansion module from the PNOZsigma range are linked via the connector, no additional wiring is necessary. -4

Terminal configuration Klemenbelegung Installation Dimensions ][Montage_PNOZsigma Install base unit without contact expander module: Ensure that the plug terminator is inserted at the side of the unit. Connect base unit and PNOZsigma contact expander module: Remove the plug terminator at the side of the base unit and at the contact expander module. Connect the base unit and the contact expander module to the supplied connector before mounting the units to the DIN rail. Installation in control cabinet The safety relay should be installed in a control cabinet with a protection type of at least IP54. Use the notch on the rear of the unit to attach it to a DIN rail (35 mm). When installed vertically: Secure the unit by using a fixing element (e.g. retaining brakket or end angle). Push the unit upwards or downwards before lifting it from the DIN rail. Abmessungen *with spring-loaded terminals 98 (3.86") * 100 (3,94") 120 (4.72") 17,5 (0.69")

Notice ][Wichtig_PDB This data sheet is only intended for use during configuration. Please refer to the operating manual for installation and operation. Service life graph Lebensdauerkurve_Relais_Text vor Kurve The service life graphs indicate the number of cycles from which failures due to wear must be expected. The wear is mainly caused by the electrical load; the mechanical load is negligible. Lebensdauerkurve Lebensdauerkurve_Relais_Text nach Kurve_SIF Bsp Example Inductive load: 0,2 A Utilisation category: AC15 Contact service life: 2,000,000 cycles Provided the application requires fewer than 2,000,000 cycles, the PFH value (see technical details) can be used in the calculation. To increase the service life, sufficient spark suppression must be provided on all output contacts. With capacitive loads, any power surges that occur must be noted. With contactors, use freewheel diodes for spark suppression. Technical details PNOZsigma Technical details Electrical data Supply voltage Supply voltage U B DC 24 V Voltage tolerance -15 %/+10 % Power consumption at U B DC 2.0 W Residual ripple DC 20 % Voltage and current at Input circuit DC: 24.0 V 75.0 ma Reset circuit DC: 24.0 V 7.0 ma Feedback loop DC: 24.0 V 7.0 ma Number of output contacts Safety contacts (S) instantaneous: 3 Auxiliary contacts (N/C): 1-6

Electrical data Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V I min : 0.01 A, I max : 6.0 A P max : 1500 VA Safety contacts: DC1 at 24 V I min : 0.01 A, I max : 6.0 A P max : 150 W Auxiliary contacts: AC1 at 240 V I min : 0.01 A, I max : 6.0 A P max : 1500 VA Auxiliary contacts: DC1 at 24 V I min : 0.01 A, I max : 6.0 A P max : 150 W Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V I max : 5.0 A Safety contacts: DC13 at 24 V (6 cycles/min) I max : 5.0 A Auxiliary contacts: AC15 at 230 V I max : 5.0 A Auxiliary contacts: DC13 at 24 V (6 cycles/min) I max : 5.0 A Contact material AgCuNi + 0.2 µm Au External contact fuse protection (I K = 1 ka) to EN 60947-5-1 Blow-out fuse, quick Safety contacts: 10 A Auxiliary contacts: 10 A Blow-out fuse, slow Safety contacts: 6 A Auxiliary contacts: 6 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 6 A Auxiliary contacts: 6 A Semiconductor outputs (short circuit proof) 24.0 V DC, 20 ma Max. overall cable resistance R lmax input circuits, reset circuits single-channel at U B DC 30 Ohm Safety-related characteristic data PL in accordance with EN ISO 13849-1: 2006 PL e (Cat. 4) Category in accordance with EN 954-1 Cat. 4 SIL CL in accordance with EN IEC 62061 SIL CL 3 PFH in accordance with EN IEC 62061 2.50E-09 SIL in accordance with IEC 61511 SIL 3 PFD in accordance with IEC 61511 2.13E-05 T M [year] in accordance with EN ISO 13849-1: 2006 20 Times Switch-on delay with automatic reset typ. 75 ms with automatic reset max. 250 ms with automatic reset after power on typ. 75 ms with automatic reset after power on max. 250 ms with manual reset typ. 75 ms with manual reset max. 250 ms on monitored reset with rising edge typ. 75 ms on monitored reset with rising edge max. 250 ms on monitored reset with falling edge typ. 55 ms on monitored reset with falling edge max. 70 ms Delay-on de-energisation with E-STOP typ. 50 ms with E-STOP max. 70 ms with power failure typ. 50 ms with power failure max. 70 ms Recovery time at max. switching frequency 1/s after E-STOP after power failure

Times Waiting period with a monitored reset with rising edge with falling edge 110 ms Min. start pulse duration with a monitored reset with rising edge with falling edge Supply interruption before de-energisation 10 ms Environmental data EMC EN 60947-5-1, EN 61000-6-2, EN 61000-6-4 Vibration to EN 60068-2-6 Frequency 10-55 Hz Amplitude 0.35 mm Climatic suitability EN 60068-2-78 Airgap creepage in accordance with EN 60947-1 Pollution degree 2 Overvoltage category III Rated insulation voltage 250 V Rated impulse withstand voltage 6.00 kv Ambient temperature -10-55 C Storage temperature -40-85 C Protection type Mounting (e.g. cabinet) IP54 Housing IP40 Terminals IP20 Mechanical data Housing material Housing PC Front PC Cross section of external conductors with screw terminals 1 core flexible 0.25-2.50 mm², 24-12 AWG No. 750102 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve 0.25-1.00 mm², 24-16 AWG No. 750102 without crimp connectors or with TWIN crimp connectors 0.20-1.50 mm², 24-16 AWG No. 750102 Torque setting with screw terminals 0.50 Nm No. 750102 Cross section of external conductors with spring-loaded terminals: 0.20-2.50 mm², 24-12 AWG No. 751102 Flexible with/without crimp connectors Spring-loaded terminals: Terminal points per connection 2 No. 751102 Stripping length 9 mm No. 751102 Dimensions Height 102.0 mm No. 751102 96.0 mm No. 750102 Width 17.5 mm Depth 120.0 mm Weight 170 g Technische Daten_Satz No. No. stands for order number. Si-Kennzahlen_Zusatz_Relais_Lebensdauer_PDB It is essential to consider the relay's service life graphs. The relay outputs' safety-related characteristic data is only valid if the values in the service life graphs are met. The PFH value depends on the switching frequency and the load on the relay output. If the service life graphs are not accessible, the stated PFH value can be used irrespective of the switching frequency and the load, as the PFH value already considers the relay's B10d value as well as the failure rates of the other components. Si_Kennzahlen_Erläuterung_1 All the units used within a safety function must be considered when calculating the safety characteristic data. Si_Kennzahlen_Erläuterung_2-8

INFORMATION A safety function's SIL/PL values are not identical to the SIL/PL values of the units that are used and may be different. We recommend that you use the PAScal software tool to calculate the safety function's SIL/PL values. Technische Daten_Satz Normen The standards current on 2006-04 apply. ][Dauerstrom_DC Conventional thermal current while loading several contacts Number of contacts I th per contact at U B DC 1 6.00 A 2 6.00 A 3 5.00 A Bestelldaten Order reference Type Features Terminals Order no. 24 VDC With screw terminal 750 102 C 24 VDC With spring-loaded terminal 751 102