Motor Efficiency and Power Factor ME 416/516



Similar documents
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

UTILITY RATE STRUCTURE

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

Three phase circuits

Power Factor The Basics

Module Title: Electrotechnology for Mech L7

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Power factor correction. An introduction to technology and techniques

3-Phase AC Calculations Revisited

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

SYNCHRONOUS MACHINES

AC Power. by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department

Fig.1 block of PFC using PIC. Index Terms:-power factor, PIC, Hardware

7. Reactive energy compensation

Trigonometry for AC circuits

DIRECT CURRENT GENERATORS

Current Ripple Factor of a Buck Converter

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

VOLTAGE REGULATOR AND PARALLEL OPERATION

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture phase System 4

Line Reactors and AC Drives

Power Factor in Electrical Energy Management

Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

AC Generators. Basic Generator

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Three-phase AC circuits

Current and Temperature Ratings

Transformer circuit calculations

Product Data Bulletin

Inverter technology. bulletin

6/14/02 Chapter 2: Basic Electrical Power Fundamentals 1/6

Variable Frequency Drives and Energy Savings

Diodes have an arrow showing the direction of the flow.

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Application Guide. Power Factor Correction (PFC) Basics

Lecture Notes ELE A6

POWER FACTOR CORRECTION

Direct Current Motors

Properties of electrical signals

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

(3 )Three Phase Alternating Voltage and Current

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Lesson 3 DIRECT AND ALTERNATING CURRENTS. Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks.

PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.

Critical thin-film processes such as deposition and etching take place in a vacuum

Short Circuit Current Calculations

First Year (Electrical & Electronics Engineering)

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research

Inductors in AC Circuits

ANALYTICAL METHODS FOR ENGINEERS

Rectifier circuits & DC power supplies

Electricity Meter in the age of Photovoltaic

Energy Saving systems for Induction motors.

Chapter 11. Inductors ISU EE. C.Y. Lee

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

Section 10. Application Manual for NEMA Motors. Special Applications

The full wave rectifier consists of two diodes and a resister as shown in Figure

Science and Reactor Fundamentals Electrical CNSC Technical Training Group. Table of Contents

The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.

Improvement of Power Factor for Industrial Plant with Automatic Capacitor Bank

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters )

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Lab 8: DC generators: shunt, series, and compounded.

Impedance Matching. Using transformers Using matching networks

UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS

At Load Power Factor Correction Phase 2: Refrigerated Vending Machines

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 3 of 4

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

Guideline for Energy Efficient Electrical systems for building. Presentation by TERI

Chapter 24. Three-Phase Voltage Generation

12. Transformers, Impedance Matching and Maximum Power Transfer

Rectifier filter stage post filtering sense

Chapter 35 Alternating Current Circuits

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

FREQUENCY CONTROLLED AC MOTOR DRIVE

FUNDAMENTALS OF ENGINEERING (FE) EXAMINATION REVIEW

ANADOLU UNIVERSITY DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

Considering the effects of UPS operation with leading power factor loads

Principles of Adjustable Frequency Drives

Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Z +

Reading assignment: All students should read the Appendix about using oscilloscopes.

CONSTRUCTING A VARIABLE POWER SUPPLY UNIT

RLC Resonant Circuits

The Energy Independence and Security Act of The law s requirements for 1 to 500 horsepower AC motors Effective December 19, 2010

Transcription:

Motor Efficiency and Power Factor

Motivation More than half of all electric energy generated goes to power electric motors. Electric motor converts electric power into shaft power. In thermodynamics terms, this is simply converting work from one form to another. The Second Law allows electric motors to have a theoretical efficiency of 100%. In reality, several types of power loss occur from where electricity leaves power plant to the point where shaft power leaves the motor.

Electric Power Losses 1. Transmission and transformer I 2 R and hysteresis losses of real power component. 2. Transmission and transformer losses of imaginary power component. 3. Losses in the motor resulting from winding losses, frictional losses, etc. Loss 1 can be reduced by transmitting power at higher voltage: Power = V I and Loss = I 2 R. Same power can be transmitted by increasing V and reducing I: losses are reduced as 1/V 2.

Electric Power Losses (Cont d) Losses can also be reduced by decreasing R, but this means larger conductors (heavier wire) and copper is expensive. Loss 2 can be reduced by lowering imaginary, reactive part of current, which is accomplished by power factor improvement, discussed next. Loss 3 can be reduced by using more efficient motors, where electric motor efficiency is defined as: η = Shaft Power Out/Electric Power In

Motor Ratings An electric motor s nameplate or rated power is its output power, not its electric input power. Electric power consumption is rated power divided by motor efficiency. Rated power depends on class of motor (which considers intended duty). Industrial grade motors usually are rated for continuous duty. Motor efficiency requirements are set by 1992 Energy Policy Act (EPACT), primarily for larger motors as used in industry and HVAC.

1992 EPACT Selected Full-Load Motor Efficiency Requirements Open Motors Closed Motors hp 2 pole 4 pole 6 pole 2 pole 4 pole 6 pole 1 --- 82.5 80.0 72.5 82.5 80.0 5 85.5 87.5 87.5 87.5 87.5 87.5 10 88.5 89.5 90.2 89.5 89.5 89.5 20 90.2 91.0 91.0 90.2 91.0 90.2 50 92.4 93.0 93.0 92.4 93.0 93.0 100 93.0 94.1 94.1 93.6 94.5 94.1 200 94.5 95.0 94.5 95.0 95.0 95.0

Energy Savings through Electric Motor Efficiency Improvement EPACT was passed in 1992 but motor efficiency provisions took effect in 1997. Commercial, institutional and, particularly, industrial operations use substantial amounts of power for electric motors. Although high or premium efficiencies may have only a few percentage points better efficiencies and may cost thousands of dollars more, they often are good investments.

Example- Elevator Motor An elevator in an Orange Beach condominium lifts an elevator weighing 5500 lbf at a rate of 5 ft/s. The elevator operates 7 hr/day in APCo summer months and 3 hr/day in winter months using an 85% efficient motor installed when the condo was built. Consider a replacement 95% efficient Baldor Super-E motor costing $3500 + $500 installation. Assuming an interest rate of 4%, electricity inflation rate of 4%, overall inflation rate of 2.5%, 40% tax rate, 5-yr depreciation, a 10% tax credit and no salvage value, does it make sense to change motors? The condo is a APCo Rate LPM customer.

Example (Cont d) See Elevator Example Excel Spreadsheet

Power Factor Correction Electrical loss 2 between power plant and useful work output of motor was the transmission and transformer I 2 R and hysteresis losses resulting from the imaginary component of the power. This loss applies whenever an imaginary component is present- not just for motors. Power factor (PF) correction can reduce loss by reducing imaginary component magnitude. PF correction is relatively simple and economical, and often yields large energy and cost savings.

What Is Power Factor? For AC service, total power is the vector sum of the real power and reactive (imaginary) power. The total power in units of kva is given by: kva = Volts * Amps * (N ph ) 1/2 * 10-3 where Volts and Amps are the measured rms voltage and current and N ph is the number of phases (1 or 3). The relation between total power, reactive power and real power is shown in the "power triangle".

Power Factor Triangle Real Power (kw) θ Total Power (kva) Reactive Power (kvar) (kvar)

Notes on Power Triangle Imaginary component of power is due to imaginary impedance elements in the load. Pure resistors have no imaginary component, so current and voltage are "in phase" if impedance consists only of resistance elements. Capacitance causes voltage to lead the current, i.e., V reaches maximum before current (leading). Inductive impedance causes current to lead voltage, i.e., the voltage reaches maximum behind current (lagging).

Power Triangle Notes (Cont d) The cycle angle by which voltage leads or lags behind the current is called the phase angle, θ. By simple trigonometry of the power triangle, the real component of power (in units of kw) is: kw = kva * cos θ Cosine θ is the power factor(pf): PF = cos θ Similarly, reactive power (in units of kvar) is: kvar = kva*sin θ Also by the Theorem of Pythagoras: kva 2 = kw 2 + kvar 2

Why IS PF Less than 1? Many common uses of electricity have inductive components of impedance that produce a lagging power factor: induction motors (AC) power thyristors for DC motor control transformers and voltage regulators electric welding equipment electric arc and induction furnaces neon and fluorescent lights (ballasts)

Why Worry About PF < 1? Because V is fixed, then I is proportional to total power (kva), and kva = kw/pf. The larger phase angle θ between V and I, the smaller PF, the larger kva and, thus, the larger the current the utility must send over its lines. Larger I causes larger I 2 R losses and requires utility to install larger conductors & transformers. Although customer uses same real power, the lower PF costs the utility more to provide it.

Results of Low PF It costs the utility more to deliver the same real power to a customer with low power factor, so utilities charge a higher rate for low PF, either: a direct penalty-higher charge for lower power factors levels (e.g., PF > 95%, no extra charge; 90 < PF < 95%, 5% surcharge; 85 < PF < 90%, 10% surcharge, etc. or charge per kva rather than per kw (APCo). The customer also has to buy larger wiring, switches, transformers, etc., because of higher current and kva.

How Can Low PF Be Improved? Recall that capacitance and inductive elements have the opposite effect on the phase angle between voltage and current. Inductors have negative imaginary impedances, but capacitors have positive imaginary impedances. Capacitors can be added to the power circuitry to increase PF, as described in the power triangle diagram following:

Real Power (kw) Old kva System kvar (New kvar) New kva New θ Old θ kw Cap. kvar

Capacitor Sizing First step is to measure present (old) kva and PF, or get them from the power bill. Calculate kw: kw = PF old * kva old Calculate system kvar sys : Identify a target PF new. Calculate the new kva using target PFnew: kva new = kw/pf new kvar sys = kva 2 old kw 2

Capacitor Sizing (Cont d) Calculate kvar new once target PF new is achieved: kvar new = kva 2 new kw kvar new is the difference between kvar sys and the added capacitor's kvar: kvar new = kvar sys - kvar cap So kvar of the capacitors to be installed is: kvar cap = kvar sys - kvar new 2

Who Is Affected by PF Concerns? Most utilities only assess a penalty for low PF for relatively large power users. For example, to get rate LPL, APCo customers must have a 1200 kva minimum capacity (this corresponds to a $200,000 per year power bill). Consequently, most customers to whom PF correction is most important are industrial or large institutional customers (like UA). Both categories have large portion of load made up by power supplied to large electric motors and to fluorescent and HID lighting.

Location of Capacitors Effective PF correction begins by installing capacitors at largest motors first and then adding capacitors as required at distribution load centers. Capacitors typically are not supplied to motors rated less than 20 hp unless these are the largest motors in service. Capacitors are normally installed on the load side of the motor starter so that they are effective only when the motor is operating.

Location of Capacitors (Cont d) For motors that reverse, jog, etc., or where motor may at times be driven by the load (elevators, cranes), capacitors are connected on supply line side of motor controls with a separate switch. Adding excess capacitance can result in dangerous or damaging capacitor discharge through motor windings after motor is shut off. Capacitance must be controlled to match loads to avoid large discharge through motors and to lower PF from too much leading impedance.

Correcting PF of an Individual Motor One set of following information is needed: Nameplate hp, efficiency, PF Nameplate hp, efficiency, voltage, full load amps (FLA) Nameplate PF, voltage, FLA Measured PF, voltage, FLA

Correcting PF of an Individual Motor (Cont d) Get motor kw and kva using these equations : kw = hp * 0.746/effic. = kva * PF kva = FLA * Voltage * (Nph) 1/2 * 10-3 where N ph is the number of phases (1 or 3). Find the required kvar capacitor as shown before.

Example Given: PF = 0.82 and motor with nameplate info of 100 hp and 94% efficiency. Find: Capacitor kvar needed for Pf new = 0.96. Sol n: Calculate present power requirement: kw = 0.746 kw/hp*100 hp/0.94 = 79.4 kw Calculate present kva kva old = 79.4/0.82 = 96.8 kva Calculate present (system) kvar: kvar sys = (96.8 2-79.4 2 ) 1/2 = 55.4 kvar

Example (Cont d) Calculate new kva if PF = 0.96 is reached: kva new = 79.4 kw/0.96 = 82.7 kva Calculate combined kvar after capacitor added: kvar new = (82.7 2-79.4 2 ) 1/2 = 23.1 kvar Find kvar of the capacitor to be installed: kvar cap = 55.4-23.1 = 32.3 kvar The nearest standard size would be installed, probably 30 kvar. A larger std. capacitor than actually needed would be avoided if PF 1