ASHRAE Std 62.1-2010 Update Where Are We Now?



Similar documents
CHAPTER 4 VENTILATION

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

engineers newsletter live Course Outline

HVAC Checklist - Long Form

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Dedicated Outdoor Air Systems (D.O.A.S.)

CHAPTER 4 VENTILATION AIR SUPPLY

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Radford University. Indoor Air Quality Management Plan

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS

for K-12 School Buildings

Technical Investigation Elizabeth C. Krauss Mechanical Option September 18, 2013

Glossary of HVAC Terms

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Energy Efficiency in Industrial HVAC Systems

Indoor Environmental Quality Checklist Including Background Information in Comment Section

Indoor Air Quality. A Guide to Understanding ASHRAE Standard

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

ENHANCED LABORATORY HVAC SYSTEM

AG-TQS-IAQ-00 March 4, Application Guide. TQS with IAQ Inlet

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Lesson 36 Selection Of Air Conditioning Systems

HVAC Systems: Overview

Dehumidification Frequently Asked Questions

Mechanical and Natural Ventilation

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

1.2 Refrigerant Equipment. General

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

CHAPTER 4 VENTILATION

SECTION HVAC AIR-DISTRIBUTION SYSTEM CLEANING

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

VENTILATION CHAPTER 4

IECC Compliance Guide for Homes in Virginia

Mechanical Technical Assignment One ASHRAE Standard 62.1 and Standard 90.1 Evaluation

Minimizing Indoor Mold Problems through Management of Moisture in Building Systems

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA.

Basics of HVAC Cleaning

Glossary of Heating, Ventilation and Air Conditioning Terms

Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1

ASTACEA4 Inspect complex/central air conditioning systems

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

MULTIZONE APPLICATION OF SOLUTION UNITS

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Molds and mildew are fungi that grow

HVAC Systems in Schools & Commercial Buildings and Radon

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation

DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

Building Energy Codes 101 October 23, Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance

Element D Services Heating, Ventilating, and Air Conditioning

HVAC Characteristics. Test Space HVAC Characteristics

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).

ECHO System for Basements

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Why is my air conditioner dripping on my customers?

Green Built Texas Protocol v3 Project Summary and Checklist, One and Two Family New Construction

HIGH EFFICIENCY RTU. HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

HVAC Simplified Approach Option

Camfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality

Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE

Walkthrough Inspection Checklist

Comparing Energy Savings of Different VAV Systems

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

DOAS UNITS. MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR. Kitchens Hotel Corridors Laboratories. Paint Booths. Capacities Tons MBH

SAM HOUSTON STATE UNIVERSITY

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Chilled Water HVAC Systems

Integrating Kitchen Exhaust Systems with Building HVAC

KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS

Specification. Indoor Air Quality Management

Building Performance Solutions HVAC Design Guide, 2007

Preliminary Final Proposal

Answers to Your Questions from the Webinar

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

bout your HOUSE before you start Renovating Your Basement Moisture Problems

Air Conditioning Clinic

SECTION MORTUARY REFRIGERATORS

bout your house before you start Renovating Your Basement Moisture Problems

Bring the fresh in. Dedicated Outside Air Systems

To provide good indoor air quality

INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

Transcription:

ASHRAE Std 62.1-2010 Update Where Are We Now? October 2012 Dennis A. Stanke Trane La Crosse, WI

ASHRAE Standard 62.1 What Is It? Title: Ventilation for Acceptable Indoor Air Quality Purpose: to specify minimum ventilation rates and indoor air quality that will be acceptable to human occupants and are intended to minimize adverse health effects. Scope: All commercial, institutional, and high-rise residential buildings 2

ASHRAE Standard 62.1 Why Care? Section 6 is the basis for many ventilation codes, include both US model codes (UMC and IMC) Compliance with Std 62.1-2010 (Sections 4 thru 7) is a LEED prerequisite for any credits Compliance with Std 62.1-2010 (Sections 4 thru 8) is required for compliance with: Std 189.1-2011 High Performance Green Buildings ENERGY STAR and beq energy label 4

what does Std 62.1 require? Must Comply With (Sect 4 and 5) Mandatory general requirements To reduce generation of indoor contaminants and introduction of outdoor contaminants (Sect 6) Ventilation requirements Prescribed rates to dilute indoor contaminants Performance rates to limit contaminant concentrations Natural ventilation provisions (Sect 7) Mandatory construction, startup reqmts (Sect 8) Mandatory operation, maintenance reqmts 5

Std 62.1-2010 Section 4 Outdoor Air Quality Project Team 4.1.1 Regional Air Quality. Assess regional outdoor air (OA) quality to determine NAAQS compliance status Check for non-attainment for any EPA criteria contaminants 4.1.2 Local Air Quality. Survey site for unusual local sources Visit the site, look around These assessments inform air cleaning decisions 6

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.1 Ventilation Air Distribution. Design to assure that ventilation air can get to occupied zones Provide means to adjust (balance) airflows Design to assure mixing in RA/OA mixing plenums Document assumptions and air balancing requirements Important in 100% OA systems should really duct OA to zone 7

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.2 Exhaust Duct Location. Prevent leakage of harmful exhaust contaminants into the building Design exhaust ducts to operate at negative pressure Room Duct Fan Outdoors 8

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.3 Ventilation System Controls. Design to assure minimum ventilation Provide controls to enable fan Provide controls to maintain minimum OA flow at any load or dynamic reset condition. VAV systems must include modulating dampers or injection fans 9

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.4 Airstream Surfaces. Reduce space contamination due to air distribution system Use duct materials that resist microbial growth per UL 181 Use duct materials that resist erosion per UL 181 Most matte-face finishes meet these requirements 10

Std 62.1-2010 Section 5 Systems and Equipment architect 5.5 Outdoor Air Intakes. Reduce contamination from outdoors Locate intake a minimum distance from outdoor sources, per Table 5.2. Examples sources/distances: Loading dock Dumpster Surface below intake Cooling tower exhaust 25 ft 15 ft 1 ft 25 ft Design to limit rain water penetration (using hood, proper velocity, etc.) or manage water that penetrates Use bird screens and prevent bird nesting at intake 11

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.6 Local Capture of Contaminants. Reduce recirculation of indoor contaminants Exhaust locally captured contaminants (from printers, for instance) directly to outdoors 5.7 Combustion Air. Reduce pollutants from combustion appliances Provide sufficient combustion air Provide sufficient air for removal of combustion products 12

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.8 Particulate Matter Removal. Reduce rate of dirt accumulation on HVAC devices Use at least a MERV 6 filter upstream of dehumidifying coils and other wet-surface devices (about 20% to 30% Dust Spot) 13

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.9 Dehumidification Systems. Design to reduce dampness in buildings during mechanical cooling By analysis, limit RH to 65% or less at design dew point condition without solar load Design so that intake exceeds exhaust airflow Basic constant volume systems with sensible-only thermostat might not comply with 65% limit 14

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.10 Drain Pans. Assure condensate drainage without flooding or carryover Slope drain pan at least 1/8 per foot Locate drain opening at lowest point of drain pan and size to prevent overflow under normal conditions Use P-trap or other seal to prevent ingestion of air while allowing complete drainage with fan on or off Size drain pan to limit carryover Proper P-trap design helps avoid common water carryover problems 15

Drain Seals Mech Designer total trap height T = D + H where H = air-handler casing pressure + 1 in. wg D = trap depth = ½ H + d d = drain pipe diameter 16

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.11 Finned Tube Coils and Heat Exchangers. Select to reduce water droplet carryover Limit coil pressure drop to 0.75 in.wc.@ 500 fpm Exception: No pressure drop limit when design provides access to both faces for cleaning 5.12 Humidifiers and Water Spray Systems. Reduce water-borne contaminants and design to reduce carryover Use potable water No downstream devices within absorption distance 17

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.13 Access for Inspection, Cleaning and Maintenance. Reduce dirt accumulation in air distribution system Design system with adequate clearance around ventilation equipment Provide access doors/panels for ventilation equipment (air handlers, terminal units) Provide access doors/panels for devices in air distribution system (air plenums, coils, air cleaners, drain pans, fans, humidifiers) 18

Std 62.1-2010 Section 5 Systems and Equipment Architect 5.14 Building Envelope and Interior Surfaces. Reduce intrusion of water and water vapor and uncontrolled condensation Use a weather barrier within the building envelope Use a vapor retarder within the building envelope (typically on the warm side, but it really depends on wall design) Seal all envelope seams, joints and penetrations Insulate pipes, ducts and other cold surfaces 19

Std 62.1-2010 Section 5 Systems and Equipment Architect 5.15 Buildings with Attached Parking Garages. Reduce infiltration of vehicular exhaust Maintain garage pressure below adjacent occupied space Or, use a vestibule Or, otherwise design to minimize air migration from garage to occupied space 20

Std 62.1-2010 Section 5 Systems and Equipment Mech Designer 5.16 Air Classification and Recirculation. Reduce recirculation of dirty air to cleaner spaces Designate air from each space/location (see Table 6.1) Class 1: Low contaminant concentration (office) Class 2: Mild concentration (dining room) Class 3: Significant concentration (daycare sick room) Class 4: Highly objectionable/potentially harmful Design to limit air recirculation as follows: Class 1 to any space or location Class 2 to self, other Class 2 or Class 3 Class 3 to self Class 4 to outdoors only 21

Std 62.1-2010 Section 5 Systems and Equipment Project Team 5.17 Buildings Containing ETS Areas and ETS-Free Areas. Reduce level of ETS in ETS-free areas Classify each area as ETS or ETS-free Pressurize ETS-free areas with respect to ETS areas Separate ETS/ETS-free areas with solid walls, doors, etc (or engineer to assure airflow into ETS areas Maintain transfer airflow paths Don t recirculate from ETS to ETS-free at air handler Exhaust from ETS areas Post sign: This area may contain ETS 22

what does Std 62.1 require? Must Comply With (Sect 4 and 5) Mandatory general requirements To reduce generation of indoor contaminants and introduction of outdoor contaminants (Sect 6) Ventilation requirements Prescribed rates to dilute indoor contaminants Performance rates to limit contaminant concentrations Natural ventilation provisions (Sect 7) Mandatory construction, startup reqmts (Sect 8) Mandatory operation, maintenance reqmts 23

Std 62.1-2010 Section 6.0 Procedures Mech Designer 6.1 General. Find minimum zone and intake OA flow using either the VRP, the IAQP, or the NVP 6.1.1 Ventilation Rate Procedure (VRP). Prescribes procedures and OA rates, assuming typical space contaminant sources and source strengths 6.1.2 IAQ Procedure (IAQP). Requires analysis of contaminants ( performance ) based on sources and target concentrations to find minimum OA rates 6.1.3 Natural Ventilation Procedure (NVP). Prescribes opening areas, and requires mechanical ventilation in most climates (mixed-mode ventilation) 24

Std 62.1-2010 Section 6.2 Ventilation Rate Procedure Mech Designer 6.2 Ventilation Rate Procedure. Find OA intake flow (Vot) using prescribed zone OA rates & system intake calculation procedures in this section 25

Std 62.1-2010 Section 6.2 Ventilation Rate Procedure Mech Designer 6.2.1 Outdoor Air Treatment. If OA is unacceptable per Section 4.1 assessment, must use air cleaning 6.2.1.1 PM10. Where PM10 exceeds the NAAQS (nonattainment areas), use MERV 6 filter 6.2.1.2 PM2.5. Where PM2.5 exceeds the NAAQS (non-attainment areas) use MERV 11 filter 6.2.1.3 Ozone. Where ozone greatly exceeds the NAAQS (very high non-attainment area) use 40% efficient ozone air cleaner NAAQS: the most recent three-year average annual fourthhighest daily maximum eight-hour average ozone concentration exceeds 0.107 ppm (209 μg/m3) 26

Std 62.1-2010 Section 6.2 VRP Zone Calculaitons Mech Designer 6.2.2 Zone Calculations. To assure reasonable breathing-zone dilution for each zone: Use Table 6.1 rates (cfm/per and cfm/sf) and Equation 6-1 to find breathing zone outdoor airflow: Vbz = Rp*Pz + Ra*Az Use Table 6.2 defaults to find zone air distribution effectiveness, Ez (typically 1.0 for cooling) Use Equation 6-2 to find zone outdoor airflow: Voz = Vbz/Ez 30

ventilation rate procedure Minimum Ventilation Rates Mech Designer Table 6-1: Minimum breathing-zone rates for 63 categories Std 62-2001 Std 62.1-2010 Rp Ra Rp Ra Occupancy category cfm/p cfm/ft² cfm/p cfm/ft² Office 20 0.0 5.0 0.06 Classroom (ages 5-8) 15 0.0 10.0 0.12 Lecture classroom 15 0.0 7.5 0.06 Retail sales 0 0.3 7.5 0.12 Auditorium 15 0.0 5.0 0.06 Prescribes both per-person and per-area rates 31

ventilation rate procedure Effective Minimum Rates Mech Designer Comparison of breathing-zone OA flow Std 62-2001 Std 62.1-2010 Occupancy category (default density/1000 ft²) Vbz cfm Effective cfm/p Vbz cfm Effective cfm/p Office (5p) 100 20.0 85 17.0 Classroom (ages 5-8) (25p) 375 15.0 370 15.0 Lecture classroom (65p) 975 15.0 550 8.5 Retail sales (20p) 300 15.0 270 14.0 Auditorium (150p) 2250 15.0 810 5.4 70% of OA rates drop; 30% stay same or rise 32

Std 62.1-2010 Section 6.2 VRP System Calculations Mech Designer 6.2.3 Single-Zone Systems. For ventilation systems with one air handler per zone: Find system-level outdoor air intake flow: Vot = Voz 6.2.4 100% Outdoor Air Systems. For ventilation systems with one air handler supplying only outdoor air to many zones. Find system-level outdoor air intake flow: Vot = S Voz 33

Std 62.1-2010 Section 6.2 VRP System Calculations Mech Designer 6.2.5 Multiple-Zone Recirculating Systems. For ventilation systems with one AHU serving many zones: Find outdoor air intake flow (Vot) using prescribed equations and procedure to account for system ventilation efficiency (Ev): Vot = Vou/Ev outdoor air intake flow Vou = D* S Rp*Pz + S Ra*Az OA used in zones D = Ps/ S Pz population diversity factor Ev = min(evz) system vent efficiency Evz = 1 + Xs Zpz zone vent efficiency Xs = Vou/Vps average OA fraction Zpz = Voz/Vpz zone primary OA fraction 34

Std 62.1-2010 Section 6.2 VRP System Calculations Mech Designer For design, Vpz = Vpz-exp, where Vpz-exp is the lowest expected primary airflow at the design condition. I use the 6.2.5 Multiple-Zone Recirculating Systems. For reheat minimum airflow setting, Vpzm; it s easy but very ventilation systems with one AHU serving many zones: conservative. Find outdoor air intake flow (Vot) using prescribed equations and procedure to account for system ventilation efficiency (Ev): For design, Vps = Vps-exp, where Vps-exp is the highest expected system primary airflow value at the Vot = Vou/Ev outdoor air intake flow design Vou condition. = D* S Rp*Pz I use + fan S Ra*Az block airflow OA used Vps-des: in zones it s easy and usually D = Ps/ worst-case. S Pz population diversity factor Ev = min(evz) system vent efficiency Evz = 1 + Xs Zpz zone vent efficiency Xs = Vou/Vps average OA fraction Zpz = Voz/Vpz zone primary OA fraction 35

Std 62.1-2010 Section 6.2 OA Calculation Example Do we have time for an example? No But, I found total OA intake for a 6-zone school, using different systems and methods: One RTU per zone (six single-zone systems), both in cooling and heating One FC per zone, and a 100% OA system, with both CV and VAV ventilation airflow A reheat VAV (single-path multiple-zone) system using both default Ev and calculated Ev A series fan-powered VAV (dual-path multiple-zone) system using calculated Ev 36

VRP 6-zone school example OA Intake Flow Summary Ventilation System OA Intake (2001 Vot) OA Intake (2010 Vot) % Chg Single-Zone Clg 12,600 8,900-29 Single-Zone Htg 15,800 11,100-30 100% OA CV 12,600 8,900-29 100% OA VAV 8,800 7,000-20 MZS-VAV Default Ev 10,900 10,800-1 MZS-VAV Calc Ev 10,900 8,400-23 MZS-VAV Series FP 10,900 7,800-28 41

Std 62.1-2010 Section 6.2 VRP Dynamic Reset Mech Designer 6.2.7 Dynamic Reset. To assure outdoor airflow meets requirement for ventilation load, without over-ventilating, optional controls may: Reset zone minimum OA flow based on variations in occupancy, i.e., demand controlled ventilation (DCV) Reset OA intake flow based on variations in ventilation efficiency (ventilation reset control) Reset VAV zone minimum airflow based on variations in outdoor air fraction due to free cooling or exhaust-air make-up operation This Section includes operating control options, (rather than design requirements) 43

Std 62.1-2010 Section 6.3 IAQ Procedure Mech Designer 6.3. Indoor Air Quality (IAQ) Procedure Find breathing zone OA flow (Vbz) and system OA intake flow (Vot) based on performance Compliance addresses Contaminant sources Contaminant concentration Perceived indoor air quality Design approach Combined IAQP and VRP Documentation 44

Std 62.1-2010 Section 6.3 IAQ Procedure Mech Designer 6.3.1 Contaminant Sources. Must identify contaminants of concern including mixtures, sources, source strengths 6.3.2 Contaminant Concentration. Must specify target concentration, for each C of C 6.3.3 Perceived IAQ. Must specify target perceived air quality in terms of percent satisfied Requires designer judgment to identify contaminants/mixtures of concern, source and source strength for each, targets concentrations. Judgment = Risk 45

Std 62.1-2010 Section 6.3 IAQ Procedure Mech Designer 6.3.4 Design Approaches. Find highest required zone and system OA flow rates using: Mass balance analysis AND Subjective evaluation, either after construction, OR using OA needed in a substantially similar zone 6.3.5 Combined IAQP and VRP. May use VRP to find minimum OA and IAQP to find additional OA (or air cleaning required) 6.3.6 Documentation. Must document assumptions and calculations. IAQP meets Std 62.1 but does NOT meet Std 189.1 or LEED requirements 46

Std 62.1-2010 Section 6 Natural Ventilation Project Team 6.4 Natural Ventilation Procedure. Use NV with mechanical ventilation in most climates: Perimeter areas must be within defined distance from OA opening with free area at least 4% of floor area Interior areas must be within defined distance from OA opening, and interior-perimeter opening with free area at least 8% of interior floor area, but not less than 25 ft 2 Defined distance depends on window location and ceiling height (2H for single-side, 5H for doubleside) Mixed mode controls must coordinate operation of NV and MV systems 47

Std 62.1-2010 Section 6.5 Exhaust Ventilation Mech Designer 6.2.8 Exhaust Ventilation. To assure minimum removal of local contaminants, some zones require exhaust rates prescribed in Table 6.4. Examples of more than 20 zones listed: Art classroom 0.70 cfm/ft2 Beauty and nail salons 0.60 Kitchenettes 0.30 Locker/dressing rooms 0.25 Copy, printing rooms 0.50 Toilet public 50 (cont.) or 70 (cyc.) cfm/wtr closet 48

what does Std 62.1 require? Must Comply With (Sect 4 and 5) Mandatory general requirements To reduce generation of indoor contaminants and introduction of outdoor contaminants (Sect 6) Ventilation requirements Prescribed rates to dilute indoor contaminants Performance rates to limit contaminant concentrations (Sect 7) Mandatory construction, startup reqmts (Sect 8) Mandatory operation, maintenance reqmts 49

Std 62.1-2010 Section 7 Construction/Start-Up Project Team 7.1 Construction Phase. Must reduce IAQ problems introduced during construction. For example: 7.1.2. Install unit filters before operating fans 7.1.3. Protect materials from rain and moisture. Don t install materials with visible microbial growth 7.1.4. Reduce transfer of construction contaminants into occupied areas 7.1.5. Construct ducts per SMACNA standards 50

Std 62.1-2010 Section 7 Construction/Start-Up Project Team 7.2 System Start-Up. Must reduce potential for IAQ problems prior to occupancy. For example: Balance air flows Test (or certify) drain pan drainage Clean air distribution system before start up Test OA dampers for proper operation Provide ventilation system documentation (HVAC controls information, air balance report, design criteria and assumptions, drawings, etc.) to owner or owner s agent 51

Std 62.1-2010 Section 8 8.0 Operation & Maintenance Project Team 8.2 Operations and Maintenance Manual. Develop a building operations and maintenance manual 8.3 Ventilation System Operation. Operate it whenever spaces are expected to be occupied 8.4 Ventilation System Maintenance. Maintain it in accordance with Manual Compliance with Section 8 is required by Std 189.1-2010 but not by LEED 52

Std 62.1-2010 Summary The 2010 version has a few new requirements It s continually improved (next version in 2013) It s VRP rates and procedures are required by IMC and UMC and by LEED It s required by reference in Std 189.1, which is one of two IgCC project compliance paths We re out of time! 53

Questions? ASHRAE 62.1 update: Where are we now?