HEAT PUMP FOR DISTRICT COOLING AND HEATING AT OSLO AIRPORT, GARDERMOEN



Similar documents
OPTIMAL POLYGEN COOLING CONCEPT FOR ST. OLAVS HOSPITAL IN TRONDHEIM, NORWAY

UNDERGROUND THERMAL ENERGY STORAGE (UTES) WITH HEAT PUMPS IN NORWAY

How To Use A Water Source Heat Pump

Crowne Plaza Copenhagen Towers The world s greenest hotel

Ground-Source Heat Pump Systems in NORWAY

Thermal Coupling Of Cooling and Heating Systems

The ATES Project at Stockholm Arlanda Airport - Technical Design and Environmental Assessment

Three-years operation experience of a ground source heat pump system in Northern Greece

Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland

Three main techniques are used to exploit the heat available: geothermal aquifers, hot dry rocks and ground-source heat pumps.

Sea Water Heat Pump Project

How Ground/Water Source Heat Pumps Work

Rainwater Harvesting

The Central Solar Heating Plant with Aquifer Thermal Energy Store in Rostock - Results after four years of operation

Norway's Geothermal Energy Situation

Heat Pumps for Swimming Pools

Aquifer Thermal Energy Storage Application in Greenhouse Climatization

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

Norwegian Tax Authority - Oslo Norway

Hybrid system. Energy-efficient and environmentally friendly

Energy consumption and heat recovery of refrigeration system in modern Arena

How To Power A Power Plant With Waste Heat

Renewable Heat Pumps. A guide for the technically minded

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

POLYCITY. Technical measures and experiences at a 6 MW cogeneration plant with wood chip furnace POLYCITY

Contract No.: IEE/08/776/SI

Field test of a novel combined solar thermal and heat pump system with an ice store

Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov to Mar. 15, 2004.

GEOTHERMAL HEATING AND COOLING INTRODUCTION

A Feasibility of Geothermal Cooling in Middle East

Forty-one miles of submerged coils that heat and cool a high school of 2,400 students.

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE

Federation of European Heating, Ventilation and Air-conditioning Associations

LG Electronics AE Company, Commercial Air Conditioning

Facility Operations Physical Safety Guidance Document

Design Considerations for Underfloor Heating Systems. What is Frost Heave Protection?

Gas Absorption Heat Pumps. Future proofing your heating and hot water

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut John F. Sima III P.E.

ENERGY BALANCE OF LOW ENERGY HOUSE WITH GHPS IN HOKKAIDO

Building Energy Systems. - HVAC: Heating, Distribution -

DESIGN AND APPLICATION OF AMMONIA HEAT PUMP SYSTEMS FOR HEATING AND COOLING OF NON-RESIDENTIAL BUILDINGS

Design and Implementation of Geothermal Systems for Heating and Air Conditioning

From today s systems to the future renewable energy systems. Iva Ridjan US-DK summer school AAU Copenhagen 17 August 2015

CHP Plant based on a Hybrid Biomass and Solar System of the Next Generation EU project No. ENER/FP7/249800/"SUNSTORE 4" Dipl.-Ing. Alfred Hammerschmid

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

Geothermal Ice Arenas

Geothermal energy in the built environment. Martijn van Aarssen IF Technology November 29th, 2012

YOUR GUIDE TO HEAT PUMPS & SOLAR THERMAL

Technical data. Danfoss DHP-A

Session 2: Hot Water Supply

Octopus for a sustainable future

Determination of Thermal Conductivity of Coarse and Fine Sand Soils

Yu. F. Vasyuchkov*, M. Yu. Bykova* NEW TECHNOLOGY OF GAS EXTRACTION ON THE BASE OF A COAL TO A HYDROGEN TRANSFER

Each icon on this map represents the physical location of a station.

UNDERGROUND THERMAL ENERGY STORAGE IN THE NETHERLANDS. Loeki Vos, Fugro Ingenieursbureau B.V., Leidschendam, The Netherlands ABSTRACT

Loviisa 3 unique possibility for large scale CHP generation and CO 2 reductions. Nici Bergroth, Fortum Oyj FORS-seminar

Roche Basel/Kaiseraugst

Top Technology for Industry, Agriculture, Business and Communities

SWIMMING POOL HEAT PUMP Owners Manual

Case study on residential building renovation and its impact on the energy use and thermal comfort

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

BOREHOLE SEALING IN A COAXIAL HEAT EXCHANGER BY BENTONITE TREATMENT

AE BIO SOLAR AE BIO SOLAR HYBRID PLANT SOLAR/BIOMASS ADESSO ENERGIA SRL HYBRID PLANT SOLAR/BIOMASS THE BEGINNING OF A NEW ENERGY PRESENTATION

Source: EIA Natural Gas Issues and Trends 1998

Possibilities for Heating and Cooling through Underground Thermal Energy Storage in the Mediterranean area

Drake Landing Solar Community

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS

6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through

District heating and district cooling with large centrifugal chiller - heat pumps

Torino Nord. Cogeneration Plant. The gas turbine. The steam generator. The Torino Nord cogeneration plant produces electricity and heat for district

Stora Enso Fors Ltd Sweden

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

EVALUATION OF UNDERGROUND RAILWAY NETWORKS OPERATING SUSTAINABLE COOLING SYSTEMS. J.A. Thompson*, G.G. Maidment, J.F. Missenden and F.

HEAT TRANSFER ANALYSIS OF COLD STORAGE

Best Practice Guide. Heat Pump Technologies

To find out more about installing a heat pump call or visit energysavingtrust.org.uk

Crawl space heat and moisture behaviour

Typical Cooling Load Profile

Boilers and cogeneration/trigeneration. Abhi Sawant Business Development Manager Simons Green Energy

Energy Efficiency HOSPITALITY.

Range Tribune HE Solar Unvented Direct and Indirect Cylinders

Contents. 1 Introduction systems and applications Types of system Applications Potential benefits 4. 2 General design 6

A NEW CONCEPT OF A HYBRID STORAGE SYSTEM FOR SEASONAL THERMAL ENERGY STORAGE IN SOLAR DISTRICT HEATING

Investigations of a Long-Distance 1000 MW Heat Transport System with APROS Simulation Software

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

10 Nuclear Power Reactors Figure 10.1

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

ARP Food Industry, Portugal

DISTRIBUTED GENERATION AND ENERGY EFFICIENCY FOR ACHIEVING ENERGY SELF-SUSTAINING INDUSTRIAL AREAS

Distributed Energy Systems

Cost Analysis of District Heating Compared to its Competing Technologies

CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS

Glossary of Heating, Ventilation and Air Conditioning Terms

The Water Cycle Now You See It, Now You Don t

Refrigeration Compressed Air Dryer Buran Ultrapulse

8. Heat pumps, heat pipes, cold thermal energy storage

Freezer Floor Heaving and Solution

Transcription:

HEAT PUMP FOR DISTRICT COOLING AND HEATING AT OSLO AIRPORT, GARDERMOEN Geir Eggen 1 and Geir Vangsnes² 1) COWI AS. PB 254 Sentrum, N-7414 Trondheim. 2) Oslo Lufthavn AS, Edvard Munchsvei, 2 Gardermoen. ABSTRACT At Gardermoen, one of the largest groundwater reservoirs in Norway is located. This aquifer is used for both heating and cooling of Gardermoen Airport. In the summer, ground water is pumped from cold wells and used for cooling before it is returned to the warm wells. In winter, this process is turned around, as ground water from the warm wells is used as heat source for the heat pump. The heat pump is mainly designed for cooling, and the design cooling demand is 9 MW. The district cooling water is pre-cooled by the ground water, and post cooled by the combined heat pump/refrigeration plant. The base heat load is covered by the heat pump. Additional heat is supplied from a heat energy central with biofuels as well as oil heated and electrically heated boilers. During the last years, heat production from the heat pump was about 11 GWh/year, and the heat pump also provides about 8 GWh/year of the cooling demand. In addition, approximately 3 GWh/year cold is produced by direct heat exchange with ground water. Compared with a district heating system heated by fossil fuels, and a conventional refrigeration system for district cooling, the pay back period for the aquifer heat pump system is within a couple of years. Key Words: heat pumps, district cooling, district heating, aquifer thermal energy systems (ATES). 1 INTRODUCTION Oslo Airport Gardermoen was opened in 1998. The total building floor area is 18 m 2, and the buildings are equipped with large glass walls. This means large cooling demands in summer as well as large heating demands in winter. The airport is located on one of the largest groundwater reservoirs in Norway. This aquifer is used for both heating and cooling of Gardermoen Airport. This poster gives a short general view of different ground source heat pump systems for heating and cooling, and presents the aquifer thermal energy system (ATES) at Oslo Airport Gardermoen. 2 SURVEY OF GROUND SOURCE HEAT PUMPS FOR HEATING AND COOLING The ground can be used as a cold and heat source in two different ways: Either directly by pumping ground water to be used as cold distribution water or heat source for heat pumps, or indirectly be pumping a brine through tubes in boreholes in rock in a closed loop between the boreholes and the building.

2.1 Borehole Systems Most of the ground source heat pumps are borehole based heat pumps. In most cases, they have been used for heating only purposes. When heat is extracted from the boreholes, the temperature will decrease, and the number and depth of boreholes must be designed so that the brine temperature will not be too low. The brine is, however, suitable for cooling purposes, and the cooling load removed from the building is stored in the rock surrounding the boreholes. When the borehole system is used for both heating and cooling purposes, the size of the borehole system may be decreased considerably. Figure 1 shows how the cold distribution system may be connected to the borehole system. If the cold distribution system is designed for high cooling water temperatures, the borehole system may cover the total cooling demand of the building. If there are small cooling demands in the building, exhaust air past the ventilation air-to-air heat exchanger may also be used to charge the ground with heat. Inlet air Heat recovery heat exchanger Air/air heat recovery system Cooling battery Extraction air Insufflation air Auxiliary boiler Heat Pump Heat distribution Brine pump Boreholes Fig. 1. Ground coupled heat pump with cooling from borehole system. Borehole thermal energy storage systems are easy to construct, simple to operate and need very little maintenance. The borehole system is the most expensive part of the heat pump system, and their payback times are quite long. 2.2 Groundwater Systems If ground water is available in sufficient amounts and with a satisfactory quality, it is a very good cold source, as well as a heat source for heat pumps. Compared with other heat sources, it will give us a good and cheap heat pump solution. 2

Most of the ground water sources in Norway are fluvial deposits with continuous water feed from rivers and lakes etc., and these sources may be used for both cooling only and heating only purposes, as well as for combined cooling and heating purposes. A ground water based heat pump for both cooling and heating is normally built with a closed brine circuit between the ground water system and the heat pump, Fig. 2. A mixture of ethanol or ethylene glycol and water is used as brine for heat pump systems. Auxiliary boiler Cold distribution Brine Heat pump Groundwater circuit Heat exchanger Brine pump - + Heat distribution Infiltrationwell Groundwater well Fig. 2. Ground water based heat pump for both heating and cooling. Aquifers are established as glaciofluvial deposits with a layer of sand and gravel in a hollow tray of clay or rock. The feed water of the aquifer is primarily rainfall, and therefore, in order to gain thermal balance of the system, heat which is stored into the system in summer must be extracted in wintertime. The heat pump system at Oslo Airport Gardermoen is an ATES system (aquifer thermal energy storage system). There are, however, some obstacles in designing and building groundwater based heat pumps and cooling systems, as e.g. iron or calcium in the ground may result in clogging of the heat exchangers which have a detrimental effect for such systems. When the ground water is exposed to the air, formation of iron oxide occurs, acting as a powder which tightens heat exchangers and wells etc. It is therefore important to undertake water analysis before establishing a ground water based cooling and/or heat pump system (Lindblad-Påsse). Groundwater systems need a lot of maintenance, but the investments are normally small compared with borehole systems, and payback times are normally very short. 2.3 Soil Cool A considerable part of the energy consumption in Europe goes to run mechanical cooling systems. In order to reduce the energy consumption and CO 2 emissions related to cooling, the EU Commission and Nordic Energy Research were in 23 24 funding a project on underground cold storage systems Soil Cool. 3

The purpose of the project was the task of sharing, expanding, exploiting and disseminating knowledge within design and optimization of underground cold storages. The project was building on top of experience gathered through several years of IEA work on heat pumps and cold storage. Six countries were participating in the project, with COWI in Denmark as the project manager: Denmark (COWI) Sweden (Lund Tekniske Högskola) Lithauen (Vilnius University) Finland (VTT Building and Transport) Germany (SWT Stuttgart) Norway (COWI and Hjellnes Cowi) As a part of the work, a number of cases of ground source cooling were presented. The ATES system at Oslo Airport, Gardermoen was presented as the Norwegian country case 3 DESCRIPTION OF THE HEAT PUMP SYSTEM AT OSLO AIRPORT, GARDERMOEN At Gardermoen, one of the largest groundwater reservoirs in Norway is located. The area consists of glaciofluvial deposits. The soil structure in the area consists of different layers of clay, sand and gravel. The depth to the ground water is 13-14 m, and the storage is located at approximately 2-45 m below surface level. This aquifer is used for both heating and cooling of Gardermoen Airport. The ground water system consists of 18 wells, 9 warm and 9 cold wells, each with a diameter of 45 mm that were drilled down to 45 m depth. Each well is supplied with its own ground water pump and its own injection tube. The wells are connected to the heat pump/refrigeration system as shown in Fig. 3. District heat Auxiliary heat District cold Heat pump / refrigeration plant Excess heat heat exchanger Heat exchenger Heat exchanger Warm wells Winter operation Summer operation Cold wells Fig. 3. Ground water based heat pump system for both heating and cooling. 4

In the summer, ground water is pumped from cold wells and used for cooling before it is returned to the warm wells. In winter, this process is turned around as ground water from the warm wells is used as heat source for a heat pump before it is drained to the cold wells. The design cooling demand is 9 MW. The district cooling water is pre-cooled by the ground water with a cooling capacity of 3 MW, and post cooled by the combined heat pump/refrigeration plant with a cooling capacity of MW. The design heat demand for space heating is 18 MW (Grønnesby). The base heat load is covered by the heat pump. Additional heat is supplied from a heat energy central with four oil heated boilers and one electrically heated boiler. In addition, the district heating plant of Gardermoen Fjernvarme with biofuels as the primary energy source is connected to the plant. In this way, Gardermoen Airport has got an environmental friendly and flexible energy system. The heat pump is mainly designed for cooling purposes, but it can also cover heating demands up to 5ºC temperature level. Ammonia was chosen as the working fluid for the heat pump because it is a natural fluid and thereby environmental friendly for the global environment, but also because it is an excellent working fluid. However, since ammonia is poisonous, the energy plant was built in a separate building at approximately 1 km distance from the terminal building for safety reasons. The heat and cold from the energy central is transported through insulated district heat and cooling pipelines to the terminal building and to other operational buildings as well as a hotel and a conference centre at Gardermoen Airport. In addition, heat is also used for snow melting at airplane setback areas. The heat is distributed as low temperature heat, e.g. through 4 m 2 floor heating system, and most of the floor heating systems are also used for cooling in summer. 3.1 Design Data District heating: Design heat demand without snow: Design heat demand with snow: Design forward/return temperature district heat: Estimated heat energy consumption: District cooling: Design cooling demand: Design forward/return temperature central plant: Design forward/return temperature local plant: Estimated cold energy consumption: 18 MW 22 MW 7/4ºC 32 5 MWh/year 9 MW 7/17ºC 9/19ºC 5 MWh/year Heat pump: Working fluid: NH 3 Cooling capacity summer: kw winter (part load): 3 9 kw Heating capacity summer: 7 5 kw winter (part load): 4 8 kw Evaporating temp. summer: 5ºC winter: 1ºC Condensing temp. summer: 44ºC winter: 48ºC Ground water wells: Depth: Diameter borehole: Diameter filter tube: 9 warm and 9 cold wells 45 5 m 45 mm 25 mm Warm wells water temperatures in/out in summer: 3/2ºC out in winter: 4.5ºC Cold wells water temperatures out in summer: 4.5ºC in during winter: 4.1ºC Location: Cold wells are located approximately 15 m east of warm wells 5

4 OPERATIONAL EXPERIENCES The groundwater based district heating and cooling plant has been in operation since the airport was opened in 1998. There have been some problems connected to clogging in the groundwater wells. There are no problems connected to pumping the water out of the wells, but in some cases, it has been difficult to press the water back into the infiltration wells. During 24, six of the nine wells were in operation on both the cold and the warm side. Each well was operated with maximum 2 25 m 3 /h ground water capacity, while the design groundwater circulation was 3 m 3 /h. This means approximately 5% reduction of the cooling capacity. Therefore, Gardermoen Airport has to carry out a cleaning process for the ground water wells at a few years interval, and the ground water heat exchangers are cleaned every second year. Figure 4 shows the effect-duration curves for the heating and cooling plants at Oslo Airport, Gardermoen. 2-24 18 1 14 12 Heat demand Measurements 24 Total heat production Heat pump heat production Total cold production -21-18 -15-12 -9 Effect (MW) 1 8 4 2 Ambient temperature Heat pump heat production - -3 3 9 Outdoor temperature ( C) 12 2 4 Cooling demand 15 18 21 24 8 27 5 1 15 2 25 3 35 Duration (days) Fig. 4. Effect-duration curves for heating and cooling demands. 4.1 Economy of ATES System Table 1 shows the heat and cold production as well as the energy consumption for the ATES system at Oslo Airport Gardermoen. The economy for the aquifer heat pump system is also presented in the table.

The maintenance costs of the ATES system is 2% annually of the total investment. The electricity price is on the average 1 c/kwh, and the price for district heat for supplementary heating as well as for alternative heating is set to 9 c/kwh. Table 1. Technical end economical data for ATES at Oslo Airport Gardermoen compared with a traditional heating and cooling system Plant ATES Conventional plant Technical data Heat production from heat pump (MWh/yr) 11 Heat production from heating plant (MWh/yr) 27 38 Direct cooling from ATES (MWh/yr) 3 Cold production from refrigeration plant (MWh/yr) 8 11 Total energy production (MWh/yr) 49 49 Energy consumption Electricity heat pump/refrig. plant (MWh/yr) 4 3 District heat and oil (MWh/yr) 27 38 Total energy consumption (MWh/yr) 31 41 Economical data Investments - Heat pumps / refrigeration systems (USD) - Aquifer system (USD) Total investments (USD) Annual costs Capital costs heat pumps (a =.13) (USD/yr) aquifer syst. (a =.73) (USD/yr) Maintenance (.2 x Tot. investment/yr) (USD/yr) Energy costs electricity (1 c/kwh) (USD/yr) district heat (9 c/kwh) (USD/yr) Total annual costs (USD/yr) Total specific annual cost (c/kwh) Pay-back periode 95 1 7 2 5 97 85 124 1 53 4 2 439 3 14 95.3 2 years 1 3 1 3 133 9 2 3 3 42 3 879 9 7.9 The heat pump cover approximately 7% of the total cooling demand at Gardermoen Airport, and most of it is produced when the heat pump is operating for heat production. The rest is covered by direct cooling from the ground water. The alternative cooling system is to design a mechanical refrigeration system to cover 1% of the cooling demand. A 9 MW air cooled refrigeration system with ammonia as the working fluid would cost approximately 1.3 mill. USD, i.e. the extra costs for the aquifer-based heat pump system is approximately 1.35 mill. USD. REFERENCES Annika Lindblad-Påsse: Järnutfällingsproblemer i grundvattenvärmesystem. Byggforskningsrådet Rapport R 19: 198 Roar Grønnesby: Oslo Lufthavn AS: Orientering om det termiske anlegget (Oslo Airport Gardermoen: Survey of the heating and cooling system) 7