AC Coupling of Inverters for Grid Tied PV Systems



Similar documents
Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters

Application Note: String sizing Conext CL Series

Xantrex Solar Monitor Widget. User Guide

FLOW DIAGRAM OF FIVE DIFFERENT TYPES OF INVERTER SYSTEMS

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

AC Coupling Grid Tie Inverters With OutBack Battery Based Inverters

Cooling Fan Replacement September Rev A1 Page 1 of 6

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

Manual. Solar Fountain Mobile Phone Charger

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

YSmart Technology Co.,Ltd

User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1

PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where

Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation

Photovoltaic Incentive Program

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Inverter / Charger Installation General Operations and AC and DC Connections

Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter System

Temperature Compensated Charging of Lead Acid Batteries

Off-grid solar and backup power installations

User s Manual Before using the inverter, you need to read and save the safety instructions.

Conext Grid Tie Solar Inverter Conext TX 2800 NA Conext TX 3300 NA Conext TX 3800 NA Conext TX 5000 NA

Xantrex XW Hybrid Inverter/Charger

AC COUPLED HYBRID SYSTEMS AND MINI GRIDS

12 Volt 30 Amp Digital Solar Charge Controller

How to connect your Victron to a computer with VE Bus Quick Configure

AC Coupling in Renewable Energy Systems

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva

Anti-blackout system for grid connected solar installations (Solsafe concept)

Installation and Operation Back-UPS 1250, 1300, 1500

Re-defining the utility-scale inverter

egate INVOLAR Grid-Connected Photovoltaic Power Interface Model Number PIU4KA-230-UK User Operating Manual (Version_eGate(UK)G83_PIU4KA_1.

Understand Hybrid Generator Battery Systems

2.06. Version. Kinglong New Energy Technology Co.Ltd. Sunteams 1500 Sunteams Sunteams 4000 Sunteams 5000

Technical Requirements for Renewable Energy Systems Connected to the Low Voltage (LV) Network via Inverters

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Freedom SW Sine Wave Inverter/Chargers

Application Information Improving Efficiency in Smart Grid Applications With Fully Integrated Current Sensing ICs

Batteries and inverters

OWNER S MANUAL 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada

Xantrex GT , Xantrex GT PG, Xantrex GT & Xantrex GT PG 500 kw Grid-Tied Photovoltaic Inverters

Batteries and Solar Power:

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Electrical safety requirements in DC distribution systems

MidNite Solar E-Panels Explained

Optimal solar backup. Minimal configuration. General description. Features & advantages. Application Schematic. All Xtender Series

HOW A DC UTILITY METER CAN TRANSFORM THE U.S. SOLAR INDUSTRY

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems

PowerLogic Sub Meter Display (SMD and SMDOPN)

Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger

Engineering innovation

BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES

MIDNITE SOLAR AND SOLAR WASHINGTON

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

Instructions & Safety Information Models A220-20D and A220-20L Version 2

A relay capable of the generator s starter amps with a coil that draws no more than 12V.

FW-X240 AUTO TRANSFORMER Installation Manual

ABB central inverters PVS to 1000 kw

Liebert NXL Power-Tie Controls

Xantrex GT630 E GI 1K. Grid-Tied Photovoltaic Inverters

User Manual WatchPower

Connecting your Victron product to a computer with VE Configure

Battery Backup for Grid-Tied PV Systems

Nokia Bluetooth Headset BH-102. Issue 1

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

NEWTECH PRO KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw

CENTRAL ELECTRIC COOPERATIVE, INC. NET METERING AGREEMENT

Nokia Bluetooth Headset BH-101. Issue 1

System Status: Float Charging RC7 RC7GS. Installation and Operator s Manual. Xantrex RV Series Remote Controls

Hybrid and Off grid Systems Princeton Power Systems Inverter Technology Ken McCauley and Alan Cohen Princeton Power Systems

Solar Energy Conversion using MIAC. by Tharowat Mohamed Ali, May 2011

DANGER! HIGH VOLTAGE HAZARD

Additional Solar System Information and Resources

2016 Santee Cooper Solar Home & Solar Share Home Program Manual

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

Application Technique. Safety Function: Magnetic Door Switch Monitoring

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Nokia Bluetooth Headset BH-109

Adding the battery back-up power option to existing grid-tied PV/solar systems

SRS2025. Home & small Business. Energy Storage Solution

TROUBLESHOOTING GUIDE

Configure Inverter output for two utility settings, (1)120V/60Hz, (2)220V/50Hz

Achat 115MA full-range speaker. user manual

SNMP Web Management. User s Manual For SNMP Web Card/Box

BB800 Off-Grid Solar System

SA Power Networks Planning for Solar PV? Customer information guide to network connected solar PV inverter systems

/ The personal storage solution for 24H Sun. / Dynamic Peak Manager. / Smart Grid Ready THREE-PHASE

Battery Power Inverters

OWNER'S MANUAL. Model CUL AC Power Inverter/Charger System OM/A96283 REV. A

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

Energy savings and sustainability

ABR Brake Rectifier Instruction Manual

XW-MPPT Owner s Manual. XW Solar Charge Controller

Transcription:

AC Coupling of Inverters for Grid Tied PV Systems AC Coupling with Conext s, Xantrex GT Inverters, and Conext TX Inverters Application Note 976-0240-01-01 Rev B DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH This Application Note is in addition to, and incorporates by reference, the relevant product manuals for each product in the Schneider Electric Conext XW series of inverter/chargers, Xantrex GT series of single-phase inverters, and Conext TX series of single-phase inverters. Before reviewing this Application Note you must read the relevant product manuals. Unless specified, information on safety, specifications, installation, and operation is as shown in the primary documentation received with the product. Ensure you are familiar with that information before proceeding. Failure to follow these instructions will result in death or serious injury. This Application Note outlines how Conext XW inverter/chargers, Xantrex GT single-phase inverters, and Conext TX single-phase inverters (Conext XW, Xantrex GT, and Conext TX inverters) can be interconnected or 'AC coupled' to form an AC grid while in stand-alone mode. This Application Note contains the following sections: Scope on page 2 Audience on page 2 Introduction on page 2 Operation While Grid Connected on page 4 Operation While Not Grid-connected on page 5 Limitations on page 6 Conext XW AC Coupling Firmware on page 6 Installation in Single-Phase System on page 8 Installation with a Generator on page 8 Installation in a Renewable Feed-In-Tariff (FIT) System on page 9

Scope This Application Note provides safety guidelines as well as planning and setup information. It provides procedures for forming an AC grid. For information on particular brands of photovoltaic (PV) panels, consult your PV manufacturer. Audience This Application Note is intended for qualified installers. To design and install a system that will operate correctly, qualified installers must have training and experience in solar power systems to safely and correctly follow these instructions and the applicable electrical and building codes. Qualified installers must have an awareness of the hazards involved in performing electrical installation work and how to reduce those hazards. DANGER HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, OR ARC FLASH Conext XW inverter/chargers and Xantrex GT/Conext TX inverters contain no user-serviceable parts. Attempting to service the inverters yourself may result in a risk of electrical shock or fire and may void your warranty. Internal capacitors remain charged after all power is disconnected. Only qualified personnel should perform the instructions contained in this Application Note. To reduce the risk of electrical shock, qualified installers must disconnect both AC and DC power from Conext XW inverter/chargers and Xantrex GT/ Conext TX inverters before attempting any maintenance or cleaning or working on any circuits connected to them. Putting the inverter in Standby mode does not reduce the risk of electric shock. Failure to follow these instructions will result in death or serious injury. Introduction An AC-centric, or AC-coupled system, is one where all the energy sources and loads are connected directly to the AC bus. The benefits of an AC-centric system over a DC-centric (DC-coupled) system are: Low voltage high current DC connections are kept to a minimum by using AC power coupling. Thus, installation is easier and less expensive, due to the reduced number of large DC wired connections. 2 976-0240-01-01 Rev B

Improved array-to-grid efficiency due to the removal of a conversion step. In an AC-centric system, the array is connected to the grid through a grid-tie inverter: DC (array) -->Inverter -->AC (grid). In a DC-coupled system, the array is connected to the battery bank through a charge controller, which is then connected to the grid through an inverter/charger: DC (array) --> Charge Controller --> DC (battery) -->Inverter --> AC (grid). Improved array-to-load efficiency if demand occurs at the same time as solar production. The weaknesses of an AC-coupled system over a DC-coupled system are: Lower array-to-load efficiency if demand does not occur at the same time as solar production necessitating that energy is stored in the battery for later use. When using energy which was first stored in the battery the conversion steps are: array --> charge controller --> energy stored in battery --> energy taken out of battery --> inverter --> AC loads. Grid-tie string inverters are generally more expensive than solar charge controllers. Figure 1 AC coupled diagram Solar Charger Controller Figure 2 DC coupled diagram 976-0240-01-01 Rev B 3

Operation While Grid Connected On each of its two bi-directional AC input ports, the Conext XW is equipped with a relay that closes only when the AC source is qualified (within the useradjustable range). Closing the relay connects the AC source directly to the AC output terminals of the Conext XW. In this pass-through mode, the Conext XW stays in charge mode and charges the battery bank. If the grid voltage and frequency are within limits, then-after a five minute delay-the Xantrex GT/Conext TX PV string inverter will harvest the solar energy from the array. This energy will be consumed by the AC loads and used by the Conext XW to charge the battery, following the normal three-stage charging process. Any excess energy will be exported to the grid (either through the Conext XW or through a separate transfer switch and Feed-in meter connection, depending on the applicable regulations within the jurisdiction where the system is installed). The Conext XW continuously monitors the AC input voltage and frequency. If the voltage or frequency move beyond the acceptable ranges-for example, during a power surge or outage-the Conext XW opens its relay, disconnecting both the Conext XW inverter/charger and the Xantrex GT/Conext TX inverter from the grid and forcing them to stop exporting energy to the utility grid. As soon as the relay opens, the Conext XW transfers from charge mode to invert mode to provide backup power to the critical loads. The Xantrex GT/Conext TX may detect the temporary loss of AC during this transfer and stop harvesting until it detects a stable AC voltage for a minimum of five minutes. NOTE: Before enabling the "SELL" feature on the Conext XW or on the Xantrex GT/Conext TX, consult with the electric utility company or electrical inspector for the jurisdiction to obtain a written authorization. During utility outages or instability, the system meets all anti-islanding requirements and becomes a stand-alone system by detaching from the grid. Figure 3 Power flow while grid-connected 4 976-0240-01-01 Rev B

Operation While Not Grid-connected When the utility grid is not present and the Conext XW is inverting, it acts as an AC voltage source, forming a local stand-alone AC grid by providing tightly controlled voltage and frequency. The Xantrex GT/Conext TX and AC loads are 'coupled' to this AC voltage through the installed sub-panel. The Xantrex GT/ Conext TX will qualify and connect to the AC voltage provided by the Conext XW just like it would the utility grid. When the Conext XW is in invert mode, AC electrical current is free to flow in either direction. This means if the Xantrex GT/Conext TX is providing more power on the AC bus than the loads can consume, current will flow back in through the Conext XW invert output connection and charge the battery bank. Unlike its normal three-stage behavior when charging from utility grid, the Conext XW does not tightly regulate charging in a three-stage process when power is back fed through AC inverter output connection to the battery. In this mode charging is a single-stage process, and the absorption charge and float stage are not supported. Charging is terminated when the battery voltage reaches the bulk voltage settings, which prevents overcharging of the batteries. Repeated charging of lead acid batteries in this way is not ideal and could shorten their useful lifetime. Figure 4 Power flow while not grid-connected 976-0240-01-01 Rev B 5

Limitations The Conext XW is only recommended for use with grid-tie AC-coupled systems. The rated power of Xantrex GT/Conext TX inverter should not exceed the rated power of the Conext XW inverter/charger, and it must match the phase configuration. If the Xantrex GT/Conext TX does exceed the rated power of the Conext XW the Conext XW may repeatedly shut down due to overload or phase configuration issue and each shut down will require a manual restart of both the Xantrex GT/Conext TX and Conext XW. The Conext XW is not recommended for, nor can we provide advice for, ACcoupling in completely off-grid installations, due to its reduced ability to charge batteries (see Operation While Not Grid-connected on page 5). Additionally, battery suppliers may not fully warranty their batteries which have repeatedly been charged in this manner. The power metering on the Conext XW may not work properly when the inverter/ charger is acting as the grid forming voltage source and power is flowing back into the batteries. Conext XW AC Coupling Firmware NOTICE HAZARD OF BATTERY OVERCHARGING AND DAMAGE Use the Conext XW only with firmware which has the AC coupling feature implemented. Use the firmware version (or higher) listed in Table 1 for your model. Failure to follow these instructions may cause equipment damage. AC coupling with earlier firmware versions is not supported. For firmware upgrade instructions, see the Conext XW Config User's Guide (document part number: 975-0365-01-01) available on the Schneider Electric website. Table 1 Firmware versions and part numbers Model Firmware Version Firmware Part Number a XW6048 120/240 60 1.05 150-0175-01-05 XW4548 120/240 60 1.04 150-0176-01-04 XW4024 120/240 60 1.07 150-0177-01-07 XW6048 230 50 1.07 150-0218-01-07 XW4548 230 50 1.07 150-0219-01-07 XW4024 230 50 1.07 150-0220-01-07 a.the last two fields are the same as the firmware revision, Make sure your firmware s part number matches or is higher than what is listed in the table (based on the last two fields). 6 976-0240-01-01 Rev B

The firmware with the AC coupling feature is a power control program that varies the Conext XW output line frequency causing the grid-tie inverters to cease producing power, thereby protecting the battery from being overcharged and also preventing the over supply of power to the local stand-alone grid. While the Conext XW and Xantrex GT/Conext TX are AC coupled, the Conext XW changes the frequency only when the battery voltage reaches the Bulk Voltage setting. Note: The Bulk Voltage setting is user-adjustable in Custom battery set up menu. The internal maximum frequency adjustment range when the Bulk Voltage setting is exceeded is: North American models: fline=[60-55]hz European models: fline=[50-45]hz Figure 5 shows the effect of the frequency generation function when the Conext XW changes the grid frequency with a rate of change of 0.4Hz/s. 5tr Figure 5 Results in stand-alone mode a a.the Conext XW decreases the grid frequency at a rate of 0.4 Hz/s when the DC exceeds the Vbulk setpoint limit. The change in frequency will quickly take the Xantrex GT/Conext TX off-line ceasing AC current generation. This will cause battery charging to stop. b) fo is the nominal line frequency at 60 Hz or 50 Hz. c) If fo is 60 Hz: fmax = 5 Hz. d) If fo is 50 Hz: fmax = 5 Hz. e) Vbulk setpoint = [50...64]V. 976-0240-01-01 Rev B 7

Installation in Single-Phase System Each Xantrex GT/Conext TX requires its own AC breaker in the critical load subpanel that is connected to the AC load (output) of the Conext XW. Although there is room to add breakers for the Xantrex GT/Conext TX inverters directly into the Conext XW Power Distribution Panel (XW PDP), it is easier to install the Xantrex GT/Conext TX breakers in the AC sub-panel. These breakers must be installed according to the installation guide for the Conext XW inverters. This sub-panel may also contain load breakers. (See Figure 1 for reference). Install one or more Conext XW inverters according to the procedures outlined in the Conext XW Power System Installation Guide (document part number 975-0239-01-01). Key Settings for Conext XW Installation Search Grid Sell Grid Support Disabled Enabled Enabled For all other settings, see the Conext XW Power System Installation Guide (document part number: 975-0239-01-01) and the Conext XW Series Hybrid Inverter/Charger Operation Guide (document part number: 975-0240-01-01). Installation with a Generator To prevent the generator from being back fed power from the Xantrex GT/Conext TX inverter an 'either-or' interlocked switch can be installed between the generator output and the AC2 (gen) input. Either/or Interlocked AC Switch Generator AC Input 2 Figure 6 Installation of AC-coupled system with a generator 8 976-0240-01-01 Rev B

Installation in a Renewable Feed-In-Tariff (FIT) System Application Note If a Xantrex GT/Conext TX system is connected to the grid according to a FIT program, then it can be converted to an AC backup system by using a Conext XW and an AC transfer switch. The output from the Xantrex GT/Conext TX is connected to the common point on the AC transfer switch. The normally closed contacts are wired to the sub panel of the Conext XW. The normally open contacts are wired to the utility grid supply. Use an AC transfer switch with an AC coil type energized from utility grid lineto-neutral voltage. AC Transfer Switch Normally Open AC Transfer Switch Energy Coil Activation Line Normally Closed FIT Meter Purchase Meter Figure 7 Installation in a renewable feed-in tariff system Copyright 2012 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Exclusion for Documentation UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; (B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK; AND (C) REMINDS YOU THAT IF THIS DOCUMENTATION IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT www.schneider-electric.com. Date: September 2012 Revision: Rev B Document Number: 976-0240-01-01 Contact Information: www.schneider-electric.com For other country details please contact your local Schneider Electric Sales Representative or visit the Schneider Electric website at: http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page 976-0240-01-01 Rev B 9