DATA SHEET DELOMATIC 4, DM-4

Similar documents
Installation manual. Generator Paralleling Controller GPC multi-line C

A project to optimise quality and energy efficiency must include metering

Quick Connect. quick - simple - efficient.

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

Process Alarm Solutions

Voltage Regulator SPAU 341 C. Product Guide

T Substation Maintenance and Commissioning Test Equipment

Power Meter Series 700

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

Portal Software GSM-PRO Run LED displays module activity Com LED displays activity on the GSM network GSM-PRO

WIND Power Technology: IMD Integrated Motor Drive

Visions become real. Temperature control and cooling systems. The innovative and reliable solution

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Remote Monitoring and REC 501 Control Unit Product Guide

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Rack mounted telephone- and leased line modem for industrial applications

Telephone- and leased line modem for industrial applications TD-36

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Atlas Copco Generators QIX QAS QAC USER MANUAL FOR THE. Qc4001 GENERATOR CONTROLLER

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

OZW30. Central Unit SYNERGYR

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Current and voltage measuring relays

Option field bus: without bus with profibus DP. Design-Index (Subject to change)

Waveguide Access Point WGA631. Product Guide

Fiessler Programmable Safety Center. Flexible Hard- and Software concept. Available with a safe bus system or/and two counter inputs

Technical Specifications: The specifications represent a particular hardware platform. Application-specific software is provided.

Paralleling and Protection Unit Type PPU multi-line E

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Application/Connection Examples

ABB Drives. User s Manual HTL Encoder Interface FEN-31

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

E-STOP relays, safety gate monitors

Capacitor Protection Relay SPAJ 160 C. Product Guide

NEW. EVEN MORE data acquisition and test stand automation

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

Panel Meters and Controllers Modular Panel Meter Type EDM 35

40.3. Control Relays and Timers

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

Eaton s E-Series protective relay family

M2M The measure of efficiency

Technical Specification. Generating Set with Waukesha engine burning natural gas

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

MLC TM Maximum Productivity and Versatility for Control without Compromise!

Everything you need for protection scheme testing

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

Disturbance Recoder SPCR 8C27. Product Guide

THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit , March 2012

Short information Parameters are programmed via front-side membrane keypad

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty Safety notes Policy Warranty.

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications

TRAMS TROLLEY-BUSES SUBWAY

Vibration analysis and monitoring Compact. Powerful. Modern technology.

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

How To Use The Vacon 0 Machinery

FREJA 300 Relay Testing System

Number 1 in efficiency

Annex-A TECHNICAL SPECIFICATION

with Electronic Assistant

EN54-16 Voice Alarm System PRODUCT DATASHEETS

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Safety technique. Emergency stop module BO 5988 safemaster

Temperature & Humidity SMS Alert Controller

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

PCS0100en Persy Control Services B.V. Netherlands

Multifunction devices

Permissible ambient temperature Operation Storage, transport

Modular I/O System Analog and Digital Interface Modules

Safety automation solutions

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

AS-i 3.0 PROFIBUS Gateways with integrated Safety Monitor

Current Monitoring Kit

TX OPEN RS232/485 module

Electronic overload relay EF65, EF96 and EF146

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no

Digital Pressure Measuring Instrument MDR480

Contact expansion modules

Thyristor-controlled power supplies and battery chargers

Applications. diris_826_a_1_gb_cat

Electronic overload relay EF19 and EF45

Contact expander modules

Electronic Control Devices The European Product Catalogue 2007

Why a torque measuring system?

J TB/TW Temperature limiter, temperature monitor

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

Cat Electronic Technician 2015A v1.0 Product Status Report 4/20/2016 2:49 PM

Transcription:

DATA SHEET DELOMATIC 4, DM-4 Gas Gas engine control Integrated speed governor Integrated air/gas mix control Combined heat and power control Generator control and monitoring Mains failure protections integrated Local/remote PC monitoring DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com senborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com 4 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4921240413A SW version:

1. 1.1 General information 1.1.1 Hardware The DM-4 Gas delivery from DEIF consists of: GSM modem (not Deif supply) PI-1 TTL to RS232 interface Internet Modem (not Deif supply) Delomatic-4 GAS 1 2 3 4 5 6 12" touchscreen PC Ignition system (not Deif Supply) Generator 3-phase AC measurement Engine control and monitoring 1.1.2 Application The controller DM-4 Gas is designed as a modular process controller. It covers the special demands of gas driven/renewable energy plants regarding reliability, robustness, flexibility and remote accessibility in an optimal way. Based on an existing generator control system approved for marine applications and used in thousands of ships and land-based power stations over the last 25 years, DM-4 Gas matches the special demands of harsh environments and far-away-locations faced in the off-shore and land-based decentralised energy generation. The control of a gas CHP is designed for unmanned operation. The user interface provides full information to the user and allows an efficient diagnosis and control of the operation locally as well as remotely. 1.1.3 Properties The system DM-4 Gas covers the following functions as a standard: Measurements: Generator voltages three-phase L1, L2, L3, N Mains voltages three-phase L1, L2, L3, N Currents L1, L2, L3 DEIF A/S Page 2 of 10

Active power per phase/total Reactive power per phase/total Active and reactive energy counter Operating hours Circuit breaker operations counter Temperatures and pressures at the engine Measurement values of the plant Protection functions: Mains protection Vector jump df/dt (R.O.C.O.F.) Support of a hardware safety chain with reset function Electrical protections generator over- and undervoltage, over- and underfrequency, current asymmetry, overload, reverse power, minimum power, overcurrent, thermal overcurrent, overexcitation, loss of excitation Overspeed Wire-break proof supervision of the breaker position Supervision of lube oil pressure Supervision of coolant temperature Supervision of pressure and temperature of the gas line Gas leak check Open-time supervision of the gas valves Supervision of the exhaust temperature after turbocharger Exhaust back pressure supervision Emergency stop Water level limiter for coolant, emergency cooler and heating circuit Run time supervision of air flaps Run time supervision of exhaust bypass Tooth-on-tooth supervision of the starter Level supervision in external lube oil tanks (fresh oil min., waste oil max.) Configurable inputs for fault messages (e.g. for digital auxiliary contacts) User interface: Display of all measurements as graphics and in numbers Visualisation of the states of the protections Trending function Logbooks with more than 200 entries with time stamps each Adjustment of parameters Multi-user function with standard hardware as touch screens, laptop computers for direct access (USB, TCP/IP) Remote access (TCP/IP) Living P&I diagrams on the screen shows changes and states of components in graphics Operation of the plant Maintenance calls after operating hours, adjustable Control functions: Fully automated engine start/stop Synchronisation with voltage adjustment and time supervision Heating up control Speed governor with speed ramping function (no external governor needed) Power ramp function for smooth start and stop DEIF A/S Page 3 of 10

Prerun and postrun of auxiliaries Postrun of the engine Load reduction function due to receiver temperature, throttle position, room air temperature and exhaust temperatures Operation of motorised circuit breakers Analogue power setpoint Peak shaving Heat-controlled operation CH4-value-controlled operation Gas level- or gas pressure-controlled operation Voltage adjustment and CosPhi control Control of engine cooling circuit, emergency cooling circuit and heating circuit Control of gas mixture Control of the exhaust bypass flaps Control of the room temperature Control of air flaps Emission control (select between lambda sensor, intake manifold (receiver) pressure/temperature and combustion chamber temperature) Engine preheating Support of a safety chain Demand signal to a compressor Second gas type selectable Typical scope of delivery: DM-4 Gas hardware Touch panel PC if desired Example wiring diagram I/O list List of error messages Commissioning check list P&ID example Handbook 1.2 System components 1.2.1 General description The whole DM-4 Gas system consists of only three hardware modules. Each module contains its own processor, therefore it works independently. All three modules will be delivered in a standard industry rack. Available standard sizes: 24 TE for 2 modules 42 TE for 3 to 4 modules 60 TE for 6 to 8 modules A standard configuration for a 12 cylinder engine covers e.g. the following components in a 42 TE rack: 1 PCM 4.3 1 SCM 4.1 3 IOM 4.2 DEIF A/S Page 4 of 10

1.2.2 PCM 4.3 The PCM 4.3 is power supply and main control module of the DM-4 Gas system with a module width of 8 TE. It is mounted leftmost in the rack. It supplies all other modules in the rack and controls the data exchange on the backplane. Furthermore, it contains the control unit with the application software and the following interfaces: 3 CAN interfaces 125...1000 kbd 1 RS485 interface 9600...38400 Bd 1 ARC-net interface 2.5 MBd 1 USB interface 1 Ethernet 10/100 MBd 1 serial port (9600...38400 Bd TTL) for a GSM modem connection (SMS alarming) In a plant control system, the module behaves as central control. The application software is located in this module; therefore it determines the overall functionality of the plant. 1.2.3 SCM 4.1 The SCM module is used for the measurement of electrical values and execution of fast protections and control functions. It measures voltages up to 690V AC (three-phase) directly (L1 L2 L3 N generator, L1 L2 L3 N mains/busbar). It performs an independent synchrocheck function, can directly trip the circuit breaker and evaluates the breaker feedbacks. Three-phase currents are captured via CTs (1 A or 5 A sec). The SCM module offers a certified measurement of voltage, current, frequency, active power, reactive power and phase angle at class 0.5 between 40 and 70 Hz. The measurements are transferred to the PCM module once per period. Further protection functions are located, trending and logging as a part of the application software. 1.2.4 IOM 4.2 The IOM is a multi-functional I/O module for connection of different sensor types. It also interfaces to other systems by standard analogue and digital signals. The module offers: 6 inputs for Pt100 or Pt1000 sensors in 2-, 3- or 4-wire technique, or 6 thermocouples type K (NiCr- Ni). 4 analogue inputs 0(4)...20 ma with 12 bits resolution. 4 analogue outputs for transducer signals or setpoint signals, burden up to 500 Ohms, output range -20...+20 ma, resolution 10 bits for connection of speed governors, AVRs or frequency converters. 12 digital inputs, 9 36V DC with common potential for sensors switching to plus or minus. 4 individual galvanically separated digital inputs, 9 36 V, for RPM sensor input or pulse signals (1.25 MHz sampling rate). 10 digital outputs with external power supply 9 36V DC, push-pull outputs with a stable operation against GND and against supply voltage up to 200 ma continuously. The outputs are short-circuit protected and furthermore protected against thermal overload. Each board possesses an own galvanic separation between analogue I/O, digital I/O and internal potential. This avoids loops through several boards. DEIF A/S Page 5 of 10

1.3 User interface 1.3.1 User interface description The DM-4 Gas system shows a unique user interface that allows running the operating terminal function on any standard Windows PC like industrial touch-panel PCs and laptop computers. All possibilities for local and remote access wire-less or wire-bound are available using Ethernet or USB connection to the PCM module. If several users are online at the same time, they see the same user interface, each one on his own computer. The remote start can be blocked by a manual switch on the switchboard panel door for safety reasons. This way - during maintenance - the remote access allows for diagnosis and visualisation, but the start can only be performed locally. The user interface uses a browser principle with universal, plant-independent browser software. The information that has to be displayed is therefore defined on application level. Because of this principle, the data is always consistent. The PCM module is the "Server", whereas the different users are "Clients". Buttons on the fully graphical user surface allow easy access to all visualisation pages. The pages are grouped by themes and can be reached fast and easy either using the menu structure or a central navigator. The status field is structured in the same way on all pages. It shows the state of the plant and - if active - the most important error message. Graphical elements like remote position indicators, bar graphs, pointer instruments for electrical values (kw, A, V, CosPhi) give a full overview of the occurrences that take place at engine, generator, mains and plant. The protections are visualised on special diagnostic pages together with the actual states, measurements, limits and running timers. 1.3.2 User interface examples DEIF A/S Page 6 of 10

DEIF A/S Page 7 of 10

Technical information 2. Technical information 2.1 Data, dimensions and disclaimer 2.1.1 Technical data Rack system Operating temp.: Vibration class: Protection class: -25 70 C (-13 158 F) DNV A+C 3 mm: 3.0 13.2 Hz, 2.1 g: 13.2 50 Hz, 0.7 g: 50 100 Hz IP 2x Higher class by application of standard housing for DM-4 racks Climate: Class E according to DIN 40040 Mounting: EMC/CE: Material: Connectors: Weight: Vertical To EN 61000-6-V2/3/4, SS4631503 (PL4) Plastic headers according to UL94-V0, Al housing, steel front plates Phoenix Cage clamp terminals 6/8/20 Arms Screw terminals 20 Arms Depends on configuration PCM 4.3 module Aux. supply: CAN: RS485: 18 30V DC Max. 6 A 3 independent CAN interfaces 125 1000 Mbps Terminals for loop through and termination 1 interface up to 38400 Baud, terminals for loop through and termination SCM 4.1 module Safety: To EN 61010-1 Overvoltage category III 690V AC Pollution degree 2 Meas. range (Un): Up to 690 Vrms directly Other ranges after adaptation by VTs../100 or../110v AC Burden max. 0.5 A per phase Overload max. 2*Un tolerated for 10 s External prefuse max. 2 A time-lag DEIF A/S Page 8 of 10

Technical information Meas. range (In): Galvanic separation: Frequency: Current transformer../-1 Arms or../-5 Arms Burden max. 0.4 VA per phase Continuous overload 10 Aeff, <75 A - 10 s < 300 A - 1 s 2.5 kv isolation between voltage tips and all other potentials 40 70 Hz Accuracy: Class 0.5 according to IEC 60688 Harmonics: Up to 500 Hz are measured IOM 4.2 Digital inputs: Frequency inputs: Accuracy: Class 1.0 Analogue inputs: Accuracy: Pt100 input: Measurement range: Accuracy: Thermocouple input: Measurement range: Accuracy: Analogue outputs: Accuracy: Digital outputs: 9 36V DC, input resistance type. 2.4 kohm, common reference potential + or -, inputs galvanically separated from other potentials (600 V) Same as digital inputs, but with 2 terminals per input Frequency max. 20 khz pulse-pause ratio > 40% Frequency below 10 khz, pulse-pause ratio >20% 0(4) 20 ma, input impedance type 50 Ohm, galvanically coupled to the analogue outputs, Pt100 inputs and thermocouple inputs, galvanically separated from the rest of the system (600 V rms) 16 bit, better than 0.5% of the full range (40 ma) over the entire temperature range 2-, 3- or 4-wire Pt100 or Pt1000, wire break and short-circuit detection -40...+200 C +/- 0.5 K over the full measurement range with 4-wire connection, +/- 1 K with 3- or 2-wire connection, if cable length less than 1 m 2-wire thermocouple type K (NiCr/Ni) 0...1000 K more than cold junction, temperature compensation by measurement of the cold junction with a single Pt100 sensor in the whole system +/- 5 K (@ 500...750 C), +/- 10 K (@ -20...500 C) -20 ma +20 ma, burden up to 500 Ohm 10 bits, better than 0.5% of full range (40 ma) over the entire temperature range Output voltage 8 35V DC with external supply 9 36V DC Output current 0..200 ma (source and sink) Short-circuit protection by current limitation Short-circuit proof. In case of short-circuit or thermal overload, the outputs will be disabled and an error message will appear DEIF A/S Page 9 of 10

Technical information 2.1.2 Unit measurements in mm 60 TE rack 42 TE rack 190.0 PCM 190.0 PCM 266.0 344.7 361.0 180.0 254.3 270.7 24 TE rack 190.0 PCM 164.0 180.4 2.1.3 Disclaimer DEIF A/S reserves the right to change any of the contents of this document without prior notice. DEIF A/S Page 10 of 10