Analysis and Performance Prediction of Data Centre with Different Configurations using CFD



Similar documents
Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

Energy Performance Optimization of Server Room HVAC System

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Effect of Rack Server Population on Temperatures in Data Centers

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.)

Boosting the Energy efficiency of a Server Room: experimental + virtual approach.

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW

Reducing the Annual Cost of a Telecommunications Data Center

Using CFD for optimal thermal management and cooling design in data centers

Benefits of. Air Flow Management. Data Center

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number R1D1. 13 January 2015

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Turbulence Modeling in CFD Simulation of Intake Manifold for a 4 Cylinder Engine

Prompt Engineering applies successfully CFD analysis on large Server Room for a simulation driven Energy saving approach.

Data Center Components Overview

Analysis of the UNH Data Center Using CFD Modeling

How To Improve Energy Efficiency Through Raising Inlet Temperatures

Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data Centers

The New Data Center Cooling Paradigm The Tiered Approach

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET)

The CEETHERM Data Center Laboratory

How To Run A Data Center Efficiently

ME6130 An introduction to CFD 1-1

Ravi Kumar Singh*, K. B. Sahu**, Thakur Debasis Mishra***

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, (2014)

Airflow Simulation Solves Data Centre Cooling Problem

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS

Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013

Green Data Centre Design

CFD Application on Food Industry; Energy Saving on the Bread Oven

INTERNATIONAL JOURNAL OF RESEARCH IN AERONAUTICAL AND MECHANICAL ENGINEERING

Benefits of Cold Aisle Containment During Cooling Failure

Improving Data Center Energy Efficiency Through Environmental Optimization

Rate of Heating Analysis of Data Centers during Power Shutdown

Control Strategies for Plenum Optimization in Raised Floor Data Centers

CFD-Based Operational Thermal Efficiency Improvement of a Production Data Center

3. Prescribe boundary conditions at all boundary Zones:

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Managing Cooling Capacity & Redundancy In Data Centers Today

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

Application of CFD modelling to the Design of Modern Data Centres

Computational Fluid Dynamics (CFD) Modeling Service

Choosing Close-Coupled IT Cooling Solutions

Managing Data Centre Heat Issues

Learning Module 4 - Thermal Fluid Analysis Note: LM4 is still in progress. This version contains only 3 tutorials.

How To Improve Energy Efficiency In A Data Center

Dealing with Thermal Issues in Data Center Universal Aisle Containment

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager

Data center upgrade proposal. (phase one)

APC APPLICATION NOTE #92

Strategies for Deploying Blade Servers in Existing Data Centers

MEASUREMENTS AND PREDICTIONS OF THE FLOW DISTRIBUTION THROUGH PERFORATED TILES IN RAISED-FLOOR DATA CENTERS

Design Best Practices for Data Centers

BRUNS-PAK Presents MARK S. EVANKO, Principal

Keywords: Heat transfer enhancement; staggered arrangement; Triangular Prism, Reynolds Number. 1. Introduction

Thinking Outside the Box Server Design for Data Center Optimization

EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY

AN EFFECT OF GRID QUALITY ON THE RESULTS OF NUMERICAL SIMULATIONS OF THE FLUID FLOW FIELD IN AN AGITATED VESSEL

W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers

COMPUTATIONAL FLUID DYNAMICS (CFD) ANALYSIS OF INTERMEDIATE PRESSURE STEAM TURBINE

GAMBIT Demo Tutorial

11 Top Tips for Energy-Efficient Data Center Design and Operation

Specialty Environment Design Mission Critical Facilities

- White Paper - Data Centre Cooling. Best Practice

Element D Services Heating, Ventilating, and Air Conditioning

Application of CFD Simulation in the Design of a Parabolic Winglet on NACA 2412

TRANSIENT AIR TEMPERATURE MEASUREMENTS IN A DATA CENTER

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Data Center Power Consumption

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015

CFD SIMULATION ENHANCES A DATA CENTER S EXPANSION PROCESS

FLUID FLOW ANALYSIS OF CENTRIFUGAL FAN BY USING FEM

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES

Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics

Tutorial 1. Introduction to Using ANSYS FLUENT in ANSYS Workbench: Fluid Flow and Heat Transfer in a Mixing Elbow

Driving Data Center Efficiency Through the Adoption of Best Practices

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi

Power and Cooling for Ultra-High Density Racks and Blade Servers

Greening Commercial Data Centres

Virtual Data Centre Design A blueprint for success

CFD Application on Food Industry; Energy Saving on the Bread Oven

Energy Efficient Thermal Management for Information Technology Infrastructure Facilities - The Data Center Challenges

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs

Enabling an agile Data Centre in a (Fr)agile market

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

Transcription:

Analysis and Performance Prediction of Data Centre with Different Configurations using CFD Mohammed Faisal K, PG Scholar Department of Mechanical Engineering, M. A College of Engg Kothamangalam,.. Ernakulam (Kerala), India, Abstract-This paper presents computational fluid dynamics (CFD) analysis of airflow, temperature and pressure distribution of the data centre with different configuration. These configurations were under floor supply with ceiling, under floor supply with horizontal, overhead supply with horizontal. The parametric and its optimization were used to determine the best possible layout for cooling strategies. The simulation results predict the high temperature zone within the computer rack in the data centre, and provide a detailed three dimensional analysis of the movement of cold air through the data centre. The position with optimum performance will be taken as the solution. The results of the simulation were discussed using temperature, airflow and pressure contours. Dr. Jeoju M Issac, Professor Department of Mechanical Engg M. A College of Engg., Kothamangalam Ernakulam (Kerala), India, required airflow through the perforated tile(s) located at the inlet of each computer server. Keywords Airflow organization, CFD modeling, Data center cooling, Temperature distribution I. INTRODUCTION Data centers are growing exponentially (in number and size) to accommodate the escalating user and application demands. Likewise, the concerns about the environmental impacts, energy needs, and electricity cost of data centers are also growing. Network infrastructure being the communication backbone of the data center plays a pivotal role in the data center s scalability, performance, energy consumption, and cost. The data centre is a facility used to accommodate computer systems and associated components, such as telecommunications and storage systems. It usually includes redundant or backup power supplies, redundant data communications connections, air conditioning, fire suppression and security devices. Data centers have strictly regulated air parameters; the heat dissipation from the datacom equipment in the canters is high, not uniformly distributed and variable. The increased compactness of the computer equipment, as well as the increased industrial demand for information technology. Most of the data centers use the under-floor plenum below a raised floor to supply cold air to the equipment. The computer room air conditioner (CRAC) units push cold air into the plenum, from where it is flowing into the computer room through opening. Due to the interactive effect of different parameters, the resulting flow distribution is usually not uniform. This means that the computer servers in some areas get too much air, while others get too little. Whenever the cooling-air requirements of any server are not met, its cooling is compromised. The necessary and sufficient condition for good thermal management is supplying the Fig.1 Data Center Model Data center floor layouts are designed using Computational Fluid Dynamics (CFD) modeling offers a more scientific and comprehensive design approach. A typical Data centre model is shown in Fig 1. The cooling infrastructure is an important part of a data centers CFD model used to calculate the threedimensional (3D) velocity, temperature and pressure distributions in the data centre. The local pressure drop across individual CRAC S then determines the corresponding flow rate. The 3D model has been used to predict flow rate distribution in an actual data center, and the results are compared with measurements. Which help to minimize hot spots by predicting the high temperature zone within the computer rack with different configuration in the data centre and to provide a detailed 3D analysis of the movement of cold air through the data centre II. METHODOLOGY A :Data Centre Description CFD consists of three parts-pre-processing, Solver, Postprocessing. Pre-Processing includes geometry creation and Meshing. Here CATIA and ANSYS workbench will be used for Pre-Processing. The geometry will be modeled in CATIA. This software is extensively used in industries and is capable of making the required surfaces with precision. This model will be imported to ANSYS DESIGN MODELLER in STEP form. The domain will be meshed and the mesh quality will be checked.the most appropriate turbulence equation will be used in the solver 570

The solver used will be ANSYS FLUENT. Inside the solver we can give the required materials, give appropriate boundary conditions and select the proper numerical methods to solve the case. CFD POST will be used for Post-Processing. Here we can take the required results like temperature, velocity, pressure contours, streamlines, vectors etc. The data centre was modeled and analyzed using CFD code Fluent to study the effectiveness of cooling within the racks of the data centre. The flow field and temperature distribution in the Rack are reported. Data centre Geometry consists of 36 no of rack, four inlet (CRACK), and three hot air aisle. Fig 1 and 2shows 2D and 3D views of data centre our manuscript electronically for review. Mass flow rate of cold air =1.5605kg/s Total no of servers = 36 Total flow through Racks unit is 2.548m 3 /s Total Rack heat load 16200 watt Required Data centre temperature not below 10 o C and not above 28 o C C:Meshing The grids are generated using FLUENT. The basic principle in meshing is that it should have finer elements to get better accuracy of the result. At the same time, number of grids should not exceed available computational capacity. The geometry imported to ANSYS work bench 14.5 is not necessary to get a converged solution with a particular mesh element or using fine meshes so mesh quality need to be checked. The suitable mesh has been computed using triangular mesh over the surface of the module the mesh should be very fine near the module. Orthogonal Quality ranges from 0 to 1,where values close to 0 correspond to low quality. Fig shows Meshed geometry of under floor supply with ceiling Fig.2. 3D Data centre model B:Data Centre Features The data center is 4 meter long, 3 meter wide and has a height of 3 meter, height from raised floor to ceiling of 2.48 meter. The racks which are holding the server has a length of 2 meter, breadth of 0.2 meter and a height of 2 meter. These racks are six in number. Each rack consist of 36 server. There are four inlet (computer room air conditioner (CRAC) units) openings with a length of 2 meter and breadth of.2 meter. These unit are capable of pushing cold air into the plenum, from where it is flowing into the computer room through opening Description of Data centre and data centre components, air flow through the rack and vent tiles are summarized below. Room dimensions = 4*3*4 m 3 No of CRAC unit = 4 Room Floor Area =12 sq. m Supply plenum height =0.52meter inlet temperature=286.15k Total flow through CRAC units =11m 3 /s Supply Air cooling capacity= 22680watt Total no of Vent tile =4 Average flow through each vent tile =.78m 3 /s CFM per server = 150(.0708m 3 /s) server wattage(power supply per server) = 450Watt heat density in each rack =3409w/m 3 Fig.3. Meshed Geometry Mesh quality and statistics of different configuration: 1. under floor supply with ceiling. Minimum Orthogonal Quality = 5.90306e-01 Maximum Aspect Ratio = 3.90007e+00 Mesh type = triangular mesh No of element: 350309 Nodes :75527 2. under floor supply with horizontal Minimum Orthogonal Quality = 5.70306e-01 Maximum Aspect Ratio = 2.90007e+00 Mesh type = triangular mesh No of element: 282434 Nodes : 69615 3. Over head supply with horizontal Minimum Orthogonal Quality = 4.8.70306e-01 Maximum Aspect Ratio = 3.430007e+00 Mesh type = triangular mesh No of element: 290035 Nodes :71204 571

D:Boundary condition The boundary conditions are: inlet temperature=286.15 K, Total CFM=5400(taken as mass flow inlet).cfm per server is taken as 150(0.078 m 3 /s).the power supply per server is taken as 450 watts. Heat equation is switch on. The servers are taken as porous zones and necessary heat flux is given. As a turbulence model, the realizable k-" function is used. The mass flow rate and the flow direction normal to the boundary are imposed at the inlet. The meshing model then transferring to solver section where the boundary conditions are applied. The standard k-epsilon model was used to calculate the turbulent viscosity this model allows for a more accurate near wall treatment. At the walls of the plenum and at other solid surfaces, stationary walls and the usual no-slip boundary conditions are used III. RESULTS AND DISCUSSIONS The CFD simulation was performed for the model shown in Fig 2.The results of CRAC performance, velocity, temperature and pressure distribution, the room and rack thermal maps, effect on the CRAC return temperatures, are reported. temperature, and pressure distribution for different configuration by considering a plane 2m height from the bottom are shown in the Fig 4 through 8. As discussed earlier, there are 4 CRACs units and the total flow through CRACs is 2.548 m 3 /sec. From these Figures, it can be seen that the mixing of hot air with cold air leads to substantial increment of cold inlet temperatures which cause raising of the racks inlet temperature above the supply air temperature. The flow of air in case of under floor supply with ceiling, is passing through vent to the cold aisle, from where cold air is moved into the server inlets and moved out of the back of the servers into the hot aisle. The hot air is then moved to the sides of the room where it is passed into the CRAC s. Such hot temperature zones cause rise in temperature leading to reliability issues of computer components. Hence proper cooling of data centre is very essential to keep data centre temperature within desired limit.ie required Data centre temperature not below 10 o C and not above 28 o C. From three different configuration of data centre we can seen that the temperature distribution in case under floor supply with horizontal and over head supply with horizontal is above ASHARE recommended limit. Thermal map at a height of 2m from bottom for three different configurations are shown in Fig 4 through Fig 6. Fig.5.Thermal map at 2m height for bottom inlet and horizontal From these figure it is shown that temperature variation in Fig 5and 6 is above 27 0 c.high temperature zone was found along height in which maximum temperature around 50 0 c in a configuration of bottom inlet with horizontal exit, the max temperature in case of top inlet with horizontal was found to be 65 0 c.but max and Min temperature in under floor supply with horizontal exit is varies from 14 to 26 0 c. These temperature limit also meeting ASHARE (American Society of Heating, Refrigerating and Air-Conditioning Engineers) guidelines Fig.6.Thermal map at 2m height for top inlet and horizontal The effectiveness of data centre cooling is measured by its ability to maintain data center equipment from overheating despite of the power density of the room Fig. 7 through 9 reports the pressure distribution in the data centre Fig.7. static pressure map for bottom inlet with ceiling Fig.4.Thermal map at 2m height for bottom inlet and ceiling 572

Fig.8.static pressure map for bottom inlet with horizontal Fig.11. Pressure variation vs length in rack for bottom inlet with ceiling Fig 10 and 11 shows that temperature and pressure variation in the rack when considering the plane along height. from the fig it can be seen that up to certain height(ceiling) temperature and pressure variation in the rack is uniform due to introduction of hot and cold air aisle. Usually, the flow of air is passing from the bottom into to the cold aisle, where the cold air is moved into the server inlets and moved out of the back of the servers into the hot aisle. The hot air is then moved to the sides of the room where it is passed into the CRAC s. In other two configuration that temperature and pressure in the rack are randomly distributed not uniform. Fig.9. static pressure map for top inlet with horizontal Fig 7 shows that pressure in bottom inlet with ceiling. distribution. where pressure is varies from nearly - 3000 Pa to -200 Pa. lower pressure in the data centre room create lower enthalpy ie lower enthalpy is indication of evaporative cooling.in Fig 8 static pressure varies from 0.26pa to 2.631pa.Since the cooling flow is decreases, resulting in an small amount of airflow to the horizontal.. In Fig 9 pressure in uniformly distributed, static pressure is varies from 2.4pa to 2.7pa. this is due there is no need of hot and cold air aisle to convey air from one end to other end. Fig.12.Temperature variation vs length in rack for bottom inlet with horizontal Fig.13.Pressure variation vs length in rack for bottom inlet with horizontal Fig.10.Temperature variation vs length in rack for bottom inlet with ceiling 573

Fig.14.Temperature variation vs length in rack for top inlet with horizontal Fig 18 velocity distribution in top inlet with horizontal Fig 16 through 18 shows that velocity distribution for different configuration. Maximum velocity differences is found to be 1.06m/s and 2.08m/s in the rack in bottom inlet with ceiling exit due to high density difference of air compared to other. Fig.15.Pressure variation vs length in rack for top inlet with horizontal Fig 16 velocity distribution in bottom inlet with ceiling IV. CONCLUSIONS This study establishes a process to determine the optimum supply air temperature ranges that minimizes the total cooling energy of a modular data center with various data centre configuration by considering supply air conditions, server thermal characteristics, cooling system configurations and locations. As a result, the optimum supply air temperature ranges are generally within 14 0 C to 26 0 C even though there are some differences in each the cooling system The high temperature zones were found at computer racks with configuration of under floor supply with horizontal exit and over head supply with horizontal exit. Maximum temperature around 50 0 C and 65 0 C was observed in above two configurations which is above the limit of ASHARE guidelines. But maximum inlet and exit temperature to the rack in under floor supply with horizontal exit were observed as 14 0 C to 26 0 C. This is due to the usage of hot air aisle maintains a steady temperature within the data centre. so the required data center temperature is satisfied in bottom inlet with ceiling. This model could be used for a data centre design to develop a cooling strategy for achieving better thermal performance. This study provides a feasible cooling solution for high heat density data centre with configuration of bottom inlet and ceiling. ACKNOWLEDGMENT The authors would like to thank all the faculties of mechanical engineering department for their valuable support to the research. Fig 17 velocity distribution in bottom inlet with horizontal 574

REFERENCES [1] Sang-Woo Hama, Min-Hwi Kima, Byung-Nam Choib, Jae-Weon Jeonga, Simplified server model to simulate data center coolingenergy consumption, Energy and Buildings 86 (2015) 328 339 [2] Marija S. Todorovica,b, Jeong Tai KimData ce ntre s ener gy efficiency optimization and greening Case studymethodology and R&D needsmarija, Energy and Buildings 85 (2014) 564 578 [3] Baptise Durand Estebe, Cedric Le Bot, Jean Nocolas Mancos, Eric Arquis Data Centre Optimization Using PID Regulation In CFD simulation Energy and Buildings 66 (2013) 154 164 [4] Kyosung Chooa, Renan Manozzo Galanteb, Michael M. Ohadia Energy consumption analysis of a medium-size primary data center inan academic campus Energy and Buildings 76 (2014) 414 421 [5] Hao Tian, Zhiguang He,Zhen Li A Combined Cooling Solution For High Heat Density Data Centre Using Multi Stage Heat Pipe Loops Energy and Buildings 94 (2015) 177 188 [7] Zhihang Song, Brace T, Murray, Bahgat Sammika NUmerical Investigation Of Inter Zonal Boundary condition for Data Centre Thermal Analysis International Journal of Heat and Mass Transfer 68 (2014) 649 658 [8] Reinaldo A. Bergamaschi, Leonardo Piga, Sandro Rigo, Rodolfo Azevedo, Guido Araújo Data center power and performance optimization through global selection of P-states and utilization rates Sustainable Computing: Informatics and Systems 2 (2012) 198 208 [8] Xiaodong Qian, Zhen Li, Zhixin Li, Entransy and exergy analyses of airflow organization in data centers International Journal of Heat and Mass Transfer 81 (2015) 252 259B [9] Yiqun Pan *, Rongxin Yin, Zhizhong Huang Energy Modelling Of two Office Building With Data Centre For Green Building Design Energy and Buildings 40 (2008) 1145 1152 575