SPECIFICATION DIVISION 22 SECTION DESCRIPTION DIVISION 22 PLUMBING SECTION 220519 - THERMOMETERS, PRESSURE GAUGES, AND ACCESSORIES

Similar documents
Many Products...One Source

FLASH TANK ECONOMIZER PRODUCT GUIDE

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

Commercial / HVAC / Plumbing. Specification Guide. For. Pressure & Temperature Instruments & Related Accessories

PLUMBING ROUGH IN INSPECTION

AIR LINE VALVES AND GAUGES

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Purpose:

REGULATORS 175/153 Series

HVAC/R GAS TEST GAUGES SPECIFICATIONS ACCURACY CASE SIZES CASE MATERIAL MOUNTING STYLE HOUSING MATERIAL TUBE & SOCKET MOVEMENT RANGES DIAL STANDARD

MAC-120HE-01 Air-Cooled Chiller

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

1. Conductivity < 15 micro ohms/cm 2. ph of 6.0 to Nonvolatile TOC content < 1.0 ppm

DESIGN STANDARDS SECTION

Element D Services Plumbing

Dew Point Tester. Instruction Manual. CVS Regular Chiller Model A-2. CVS Regular Chiller Model A-2

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Morrison Bros. Co. General Product Specifications

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Engineering Specifications

AABC Specifications for Testing and Balancing HVAC Systems

SAM HOUSTON STATE UNIVERSITY

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

SECTION GENERAL PROVISIONS FOR HVAC WORK

Refrigeration Basics 101. By: Eric Nelson

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing

Rusty Walker, Corporate Trainer Hill PHOENIX

Boilers Compressors Chillers Pipe Systems. HVAC & Refrigeration Applications Pressure and Temperature Measurement

Installation Manual. Thermomax Solar Water Heater ... Installation Procedure for Flatroof and Ground. Revision 8

Medical Air Systems: Scroll

Powers Controls TH 192 S Single Temperature Room Thermostat

Commercial Gas Water Heaters

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

300 Series PA Pump and Cooler Assemblies

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Hose Clamps & Fittings

SECTION MORTUARY REFRIGERATORS

EMERGENCY PLUMBING FIXTURES

SOLFRUNT Pressure Gauges and Other Products for the Process Industries

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

NAVIEN AMERICA INC FITCH AVENUE

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

B. Shop Drawings: Diagram power, signal, and control wiring.

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

INSTALLATION INSTRUCTIONS GEO-BOOSTER TM

MUELLER FALLING FILM CHILLERS

Commercial Semi-Instantaneous Water Heaters

79 GAUGE / THERMOMETER H N O

Lawn Sprinkler Systems Reserve Irrigation Inc. O & M. Version Roseland Drive Macedonia, Ohio

PRESSURE REDUCING CONTROL VALVE

Commercial Gas Cooking Thermostats

ECO-AIR AIR CONDITIONING

Complete Systems & Parts Automatic Oiler & Grease Bank

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Automobile Air Conditioning Primer

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Solar Hot Water Heaters

Element D Services Plumbing

Float and Thermostatic Traps Series H, C and X

PC1130 Electric Air Compressor

ice 3 FLUID TO FLUID HEAT PUMP

NITROUS TRANSFER PUMP INSTRUCTIONS

INSTALLATION AND SERVICE MANUAL

Commercial Storage Tanks

building engineering services association specification for: Domestic Heating

D Youville College July 31, 2008 New Academic Building Cannon Design Project No

FIRING RANGE PHASE 1 DESIGN

PC1131 Electric Air Compressor

Element D Services Heating, Ventilating, and Air Conditioning

Installer s Guide 18-AH39D1-13

FILLING AND PURGING THE SYSTEM

Quik Lining Systems Heater Owners Guide

API Flanged Safety Relief Valves Series 526 CATALOG

Oil and Coolant Circulating Heating System. Model - OCSM

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

Defining Quality. Building Comfort. Heating and Cooling Coils

Steam System Best Practices Condensate System Piping

IDENTIFICATION FOR PIPING AND EQUIPMENT

Facility Operations Physical Safety Guidance Document

Accumulators and Receivers

OUR PRODUCTS TRH-TRS-TRM-TRV. LIQUID RING VACUUM PUMPS AND COMPRESSORS Capacity up to 2100 ACFM Vacuum to 29 Hg. Our Other Products.

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

ASME/ANSI B Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B Malleable Iron Threaded Fittings ASME/ANSI B16.

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Builder Specifications for Solar Ready Homes

Rental Services Temporary Cooling - Flexible Water Hose

Volvo Penta Quality Line Marine Water Heaters. Owners Manual

Fire Pump Plan Review March 2010

WIKA INSTRUMENT CORPORATION

HYDROSTATIC TEST PUMPS

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

Transcription:

ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION DIVISION 22 NUMBER SECTION DESCRIPTION DIVISION 22 PLUMBING SECTION 220519 - THERMOMETERS, PRESSURE GAUGES, AND ACCESSORIES END OF CONTENTS TABLE

DIVISION 22 PLUMBING SECTION 220519 - THERMOMETERS, PRESSURE GAUGES, AND ACCESSORIES REVISIONS: 2013-12-01: ADD MILJOCO, LEAD FREE FOR DOMESTIC, AND OTHER MINOR IMPROVEMENTS. D. KARLE FOR HYDRONICS/STM MTT. 2014-01-06: IMPROVED LEAD FREE REQUIRMENTS TO REFLECT U.S SAFE DRINKING WATER ACT REQUIREMENTS THAT WENT INTO EFFECT JAN. 4, 2014. D.KARLE FOR MTT. PART 1 - GENERAL 1.1 RELATED DOCUMENTS INCLUDE PARAGRAPH 1.1.A AND B IN EVERY SPECIFICATION SECTION. EDIT RELATED SECTIONS 1.1.B TO MAKE IT PROJECT SPECIFIC. A. Drawings and general provisions of the Contract, Standard General and Supplementary General Conditions, Division 1 Specification Sections, and other applicable Specification Sections including the Related Sections listed below, apply to this Section. 1.2 SCOPE OF WORK: A. Thermometers, pressure gauges, and accessories. 1.3 QUALITY ASSURANCE A. Manufacturers and Products: The products and manufacturers specified in this Section establish the standard of quality for the Work. Subject to compliance with all requirements, provide specified products from the manufacturers named in Part 2. B. Reference Standards: Products in this section shall be built, tested, and installed in compliance with the specified quality assurance standards; latest editions, unless noted otherwise. 1. UL Compliance: Comply with applicable UL standards pertaining to meters and gauges. 2. ASME and ISA Compliance: Comply with applicable portions of ASME and Instrument Society of America (ISA) standards pertaining to construction and installation of meters and gauges. 3. ASME/ANSI B40.1, Pressure Gauge Standard. 4. National Sanitation Foundation NSF/ANSI-61 (potable drinking water) and NSF-61 Annex G (listed as 0.25% weighted average lead content)(and/or NSF/ANSI-372)and Annex F. Applies to any item in contact with domestic (potable) water. 5. U.S Safe Drinking Water Act (any item in contact with domestic (potable) water). P00000000 0000 Issued for:bid 220519 - - 1

PART 2 - PRODUCTS 2.1 THERMOMETERS: SPEC EDITOR: "INDUSTRIAL" MERCURY TYPE THERMOMETERS HAVE BEEN REMOVED FROM THE MASTER SPECIFICATIONS BASED ON OSEH REQUIREMENT TO ELIMINATE UNNECESSARY USE OF MERCURY IN CONSTRUCTION. BI-METAL THERMOMETER DELETED PER HYDRONIC TEAM MEETING 10-19- 01 SPEC EDITOR: CHOOSE BETWEEN THE TWO THERMOMETERS LISTED. A. Digital Thermometer: electronic, with LCD display and solar cell, clear plastic window, adjustable angle, separable socket. 1. Range and accuracy: -40 to 300 deg.f, accuracy greater of (+/-) 1 deg.f or 1% of reading. 2. Manufacturers: Weiss Model DVBM25 (vari-angle), Tech Controls, Miljoco Corp. B. Industrial Glass Thermometer: adjustable angle, scale to be 9" long with white aluminum back and black graduation, aluminum casing, blue appearing liquid tube, glass window. Stem for air duct shall be 6" long with protective aluminum slotted bulb guard and mounting flange. Stem for piping shall be 3-1/2" long aluminum, brass or stainless steel, stem to match specified thermometer well. Adjust stem length for insulation extension. 1. Range and accuracy: (+/-) 1 scale div. Except where otherwise noted, select range for maximum precision for system served: 2. Manufacturers: Ashcroft, H. O. Trerice, Marsh, Weksler, Weiss, Miljoco Corp. SPEC EDITOR: VERIFY SPECIFIED RANGE FOR EACH PROJECT Service Range (deg. F) Domestic Cold Water 30-130 or 0-120 Domestic Hot Water 30-180 Chilled Water / Condenser water 30-130 or 0-120 Heating Water 30-240 All other locations shown on drawings C. Thermometer Wells: Brass or stainless steel, with neck extension for insulated piping, with cap and chain fastened to well. 3/4"NPT, 2 1/2" insertion length, and extension length as required to extend well to outside of insulation. Lead free when used for domestic water applications. D. Outdoor thermometers shall be ultraviolet proof and specifically manufactured for outdoor use. 2.2 PRESSURE GAUGES SPEC EDITOR: THIS SPEC IS GEARED TOWARD MAINSTREAM HVAC APPLICATIONS. EDIT FOR CRITICAL APPLICATION. SOME DISCUSSION ON OPTIONS FOLLOW: STAINLESS MOVEMENT IS A BIT MORE EXPENSIVE P00000000 0000 Issued for:bid 220519 - - 2

THAN BRASS, BUT PROBABLY WORTHWHILE FOR ALL APPLICATIONS. BRASS SOCKET IS SUITABLE FOR ALL BUT VERY AGGRESSIVE SYSTEMS. STAINLESS STEEL IS ALSO AVAILABLE. 1/2" SOCKET WORKS WELL WITH 1/2" ISOLATION AND MANIFOLD WE TYPICALLY USE - ALSO LESS PRONE TO PLUGGING THAN 1/4". 2 1/2" AND 4 1/2" ARE MOST COMMONLY USED IN THE INDUSTRY, AND SUITABLE FOR MOST LOCATIONS, EXCEPT WHERE GAUGES ARE DIFFICULT TO GET TO AND READ. ACCURACY (OF FULL RANGE) OF 2%, 1% AND 1/2% ARE AVAILABLE. COST INCREASES SIGNIFICANTLY WITH IMPROVED ACCURACY. 1% IS REASONABLE FOR MOST APPLICATIONS. SPECIFY 1/2% FOR CRITICAL APPLICATIONS ONLY. GLYCERIN FILL HELPS REDUCE VIBRATION AT PUMP, BUT TURNS CLOUDY ABOVE 150 DEG. F, NECESSITATING THE USE OF NEEDLE VALVES TO DAMPEN ABOVE THAT TEMP. DAMPENERS ARE NOT TYPICALLY REQUIRED. THEY PREVENT PRESSURE SURGES WITH A SMALL ORIFICE. DAMPENERS ARE PRONE TO PLUGGING UP AND ARE THEREFORE NOT TYPICALLY SPECIFIED. A. Unless otherwise noted, provide all pressure gauges with clear glass window, cast aluminum, stainless steel or polypropylene case, black on white face, stainless steel wetted parts, brass 1/2" MPT socket, 1% full scale accuracy complying with ASME/ANSI B40-1 Grade 1A. Lead free when used for domestic water applications. B. Water and Compressed Air Services through 2" piping (Utility/Economy): 2 1/2" diameter face, stainless steel case, brass or stainless steel 1/4" MPT socket, 2% full scale accuracy. C. Water and Compressed Air Services over 2" piping: 4 1/2" diameter face, 6" diameter face for location more than 8 feet above floor, sealed glass window, glycerin filled for connections within 10 feet of pumps. For applications exceeding 145 deg. F, provide 316 stainless steel needle valves rated minimum 500 psi, in lieu of glycerin filled. D. Steam Service: 4 1/2" diameter face, 6" diameter face for location more than 8 feet above floor, sealed glass window, brass or stainless steel coil siphon tube with a minimum pressure rating of 1000 psi. SPEC EDITOR: EDIT OR DELETE THE FOLLOWING E. Critical System Pressure Gauges: Stainless steel socket, 1/2% of full range accuracy, 6" diameter face, in accordance with AMSE/ANSI B40-1 Grade 2A. Applicable for the following locations: SPEC EDITOR: LIST APPLICATIONS SPEC EDITOR: EDIT OR DELETE THE FOLLOWING F. Differential Pressure Gauges: 4 1/2" diameter face, 6" diameter face for location more than 8 feet above floor, sealed glass window, glycerin filled for connections within 10 feet of pumps. For applications exceeding 145 deg. F, provide 316 stainless steel needle valves rated minimum 500 psi, in lieu of glycerin filled. Applicable for the following locations: P00000000 0000 Issued for:bid 220519 - - 3

SPEC EDITOR: LIST APPLICATIONS G. Except where noted otherwise, select range for twice normal operating pressure: Service Range Water (CW and HW) 0-100 psig Steam(15#) 30" Hg vac. 30 psig Steam(60#) 30" Hg vac. 100 psig Comp. Air 0-100 psig H. Outdoor gauges shall be ultraviolet proof and specifically manufactured for outdoor use. I. Manufacturers: Ashcroft, H. O. Trerice, Marsh, Weksler, Weiss, Miljoco Corp. 2.3 PRESSURE/TEMPERATURE TEST PLUGS AND KITS: A. Provide 1/4" brass pressure and temperature test plugs where shown on drawings, with two core Nordel rated for 275 degrees and 300 psig. SPEC EDITOR: THE FOLLOWING IS NOT TYPICALLY REQUIRED, BUT CAN BE INCLUDED ON LARGE PROJECTS. B. Provide one readout meter kit including required hoses with a minimum 3-1/2" dial differential pressure gauge. Gauge shall read 0 to 60 psig and have end connections to match both the flow valves and plugs. Included in the case shall be two pocket thermometers (25 to 125 and 0 to 220 degrees), one gauge adapter, and one pocket pressure gauge (0 to 160 psig). Meter shall become property of U of M (hand over to project engineer) after completion of work. C. Manufacturers: 1. Plugs: Petes, Sisco, Schrader, Miljoco Corp. 2. Meter: Auto Flow, Griswold PART 3 - EXECUTION 3.1 THERMOMETERS INSTALLATION A. Install and orient wells and thermometers so thermometer can be read from the floor. Digital thermometers shall be located in areas with adequate light, where possible. B. Thermometer Wells: For piping 2" and below, install in piping tee where thermometers are indicated, in vertical position. For piping below 2 1/2" and above, "weldolets" may be used. Fill well with oil or graphite and secure cap. C. Install in the following locations and elsewhere as indicated: SPEC EDITOR: EDIT LIST BELOW TO SUIT PROJECT REQUIREMENTS. 1. At inlet and outlet of each hydronic zone. 2. At inlet and outlet of each hydronic boiler and chiller. P00000000 0000 Issued for:bid 220519 - - 4

3. At inlet and outlet of each hydronic coil in air-handling units over 5000 cfm. 4. At inlet and outlet of each hydronic heat exchanger. 5. At inlet and outlet of each hydronic heat recovery unit. 6. At inlet and outlet of each thermal storage tank. 7. At outside air intake ductwork. 8. At mixed air plenums. 9. At hot/cold deck plenums. 10. At each zone supply duct of multi-zone systems. 11. At supply duct of single zone systems. 3.2 INSTALLATION OF PRESSURE GAUGES A. Install pressure gauges with 1/2" isolation ball valve. Where needle valves are specified as a substitute for glycerin filled in Part 2, install the needle valve between the ball valve and the gauge. Locate gauges to be readable from the floor preferably at eye level. Mount gauges securely to prevent excessive vibration, adjust needle valve to dampen pulsations. Install syphon tubes for steam pressure gauges, connected after the isolation ball valve. Do not install pressure gauges on bottom of piping. SPEC EDITOR: EDIT LIST BELOW TO SUIT PROJECT REQUIREMENTS. B. Install in the following locations, and elsewhere as indicated on drawings: 1. At suction and discharge of each pump. 2. At inlet and outlet of each pressure-reducing valve. 3. At building water service entrance. 4. At inlet and outlet of hydronic equipment (HW boilers, chillers, heat exchangers, filters). 3.3 INSTALLATION OF TEST PLUGS A. Test Plugs: Install in piping tee where indicated, located on pipe at most readable position. Secure cap. 3.4 ADJUSTING AND CLEANING A. Adjusting: Adjust faces of meters and gauges to proper angle for best visibility. B. Cleaning: Clean meters and gauges. Replace cracked and broken windows. Touch up scratches. END OF SECTION 220519 P00000000 0000 Issued for:bid 220519 - - 5