Rental Services Temporary Cooling - Flexible Water Hose
|
|
|
- Ambrose Floyd
- 10 years ago
- Views:
Transcription
1 Engineering Bulletin Rental Services Temporary Cooling - Flexible Water Hose September 2006 CHS-PRB007-EN
2 Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate intervals throughout this manual. Warnings are provided to alert installing parties of potential hazards that could result in personal injury or death, while cautions are designed to alert personnel to conditions that could result in equipment damage. Your personal safety and the proper operation of the Trane Rental Services temporary chilled water system depend upon the strict observance of these precautions. NOTICE: Warnings and Cautions appear at appropriate sections throughout this literature. Read these carefully. WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. CAUTION: Indicates a situation that may result in equipment or propertydamage only accidents American Standard All rights reserved Rental Services Temporary Cooling - Flexible Water Hose CHS-PRB007-EN
3 Contents Warnings and Cautions Introduction Units Affected Chillers Hose Boxes General Information Weights and Dimensions Contents of Hose Box Component Specification All Hose Sizes For 2.5-in and 4-in Hose Boxes Only Pressure Loss of Flex Hose Installation Instructions Dixon Coupling Proper Hose Installation Guidelines Horizontal Hose Installation Figure 1. Correct Horizontal Hose Installation Figure 2. Incorrect Horizontal Hose Installation Vertical Hose Installation Figure 3. Correct Vertical Hose Installation Figure 4. Incorrect Vertical Hose Installation Horizontal to Vertical Hose Installation Figure 5. Correct Horizontal/Vertical Installation Figure 6. Incorrect Horizontal/Vertical Installation Figure 7. Correct Unsupported Horizontal Installation Material Disposition Exceptions Hard Pipe Installation CHS-PRB007-EN Rental Services Temporary Cooling - Flexible Water Hose 3
4 Introduction This bulletin covers the flexible water hose available to rent for temporary cooling solutions. This includes box contents, technical information on each component, and proper flexible water hose installation. Trane Rental Services offers several sizes of flexible water hose to rent for customers with temporary cooling needs. The hose is proof tested to 150 psig. Trane provides a system of Victaulic couplings, fittings, and various lengths of hose to provide consistent, rapid deployment of water chillers for temporary applications. The flexible water hose is intended for outdoor, horizontal runs connecting the inlet and outlet of the chiller and pump(s) to the building s existing chilled water system. Call Trane Rental Services 24 x 7 at (800) for specific questions. 4 Rental Services Temporary Cooling - Flexible Water Hose CHS-PRB007-EN
5 Units Affected Chillers CSCA0010 CSCA0060 (CGAC/D/E/F) CSCA0080 CSCA0400 (RTAA) CSCA0155 CSCA0500 (RTAC) CSCW0300 CSCW1250 (CVHE/F) Hose Boxes CSCH002xx 2.5 in nominal hose size CSCH004xx 4.0 in nominal hose size CSCH006xx 6.0 in nominal hose size CSCH008xx 8.0 in nominal hose size CSCH010xx 10.0 in nominal hose size Note: Where xx represents the unique inventory number of the hose box. CHS-PRB007-EN Rental Services Temporary Cooling - Flexible Water Hose 5
6 General Information Weights and Dimensions Size Weight of box / Type Length Width Height lb/plastic 4 ft 1 in 3 ft 10 in 2 ft 10 in lb/plastic 4 ft 1 in 3 ft 10 in 2 ft 10 in lb/plastic 4 ft 1 in 3 ft 10 in 2 ft 10 in lb/aluminum 7 ft 5 in 5 ft 3 in 4 ft 4 in lb/aluminum 7 ft 5 in 5 ft 3 in 4 ft 4 in Each box is labeled with a placard or stencil with the unique inventory number. The hose size is indicated in the inventory number. Each box is designed for easy shipping and handling. The boxes are designed to be moved with fork or pallet truck. Occasionally painted steel boxes with a hinged lid may be used instead of the plastic box. The larger aluminum boxes allow unloading of the contents from the front. The contents are displayed on the inside of the box. To avoid potential charges for missing parts when returned, each box should be inspected upon receipt. Please notify Trane Rental Services immediately if any parts are missing. WARNING Heavy Objects! Use a forklift of suitable capacity to move the unit. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage. 6 Rental Services Temporary Cooling - Flexible Water Hose CHS-PRB007-EN
7 General Information Contents of Hose Box 2.5-in Hose Box Components 4-in Hose Box Components 2 90 Degree Elbows 2 90 Degree Elbows 2 45 Degree Elbows 2 45 Degree Elbows 2 Victualic to Flange Adapters 2 Victualic to Flange Adapters 20 Victualic Couplings 20 Victualic Couplings 2 Manifolds with Pressure Gauge 2 Manifolds with Pressure Gauge 2 Temperature Gauge 2 Temperature Gauge 1 Flow Switch 1 Flow Switch 8 5 /8 in x 2¼ in Bolts 16 5 /8 in x 2½ in Bolts 1 10 ft Hose Section 1 10 ft Hose Section 1 15 ft Hose Section 1 15 ft Hose Section 1 25 ft Hose Section 1 25 ft Hose Section 3 50 ft Hose Section 3 50 ft Hose Section 6-in Hose Box Components 8-in Hose Box Components 2 90 Degree Elbows 4 90 Degree Elbows 2 45 Degree Elbows 4 45 Degree Elbows 2 Victualic to Flange Adapters 4 Victualic to Flange Adapters 16 Victualic Couplings 32 Victualic Couplings 16 ¾ in x 3 in Bolts 32 7 /8 in x 3½ in Bolts 1 10 ft Hose Section 2 10 ft Hose Section 1 15 ft Hose Section 2 15 ft Hose Section 1 25 ft Hose Section ft Hose Section 3 50 ft Hose Section 10-in Hose Box Components 2 90 Degree Elbows 2 45 Degree Elbows 2 Victualic to Flange Adapters 16 Victualic Couplings 24 7 / 8 in x 3½ in Bolts 1 10 ft Hose Section 1 15 ft Hose Section 7 25 ft Hose Section CHS-PRB007-EN Rental Services Temporary Cooling - Flexible Water Hose 7
8 Component Specification All Hose Sizes Hose Material: The hose is premium quality, through-the-weave extruded potable water transport hose. Hose is rated NSF61 for transport of potable water. Exterior jacket is polyurethane. Hose is rated for -36 F to 150 F working temperature range. Minimum safe working pressure is 150 psig. Hose is ozone resistant. Hose end fittings: Victaulic type couplings of anodized aluminum. Hose to Victaulic grooved end fittings connection: Factory installed band-on type (Band-It ) connections for excellent coupling integrity. Banded connections are not field repairable or replaceable. Some hose ends may be equipped with Dixon style couplings which feature a bolted clamp to secure the hose end to the hose. The Dixon coupling's bolts are to be torqued to 40ft-lbs prior to charging the hose with water. DO NOT EXCEED 40 ft.-lbs. The torque must be applied evenly between the bolts to ensure a consistent gap on each side of the coupling. Some pinching of the excess hose in the gap area is considered normal and will not create a leak or premature failure. Couplings: Style 78 Snap-Joint Couplings by Victaulic are grooved pipe couplings designed to mate with plastic or steel pipe that has been prepared to Victaulic groove specifications. They also mate with other Victaulic grooved end fittings, valves and related grooved end components. They are not intended for use with plain end pipe and/or fittings. Coupling Gaskets: The proper Victaulic gasket must be used to ensure the integrity of the mating parts. Gaskets must always be lubricated for proper assembly. Silicone based lubricant should be used. Trane Rental Services gaskets are EPDM (material). Hydrocarbon based lubricants should not be used as this will degrade gasket material. Fittings: Each box is equipped with painted Ductile Iron Victaulic to Victaulic fittings in both 90 degree and 45 degree styles. Fittings are compatible with standard HVAC fluids (ethylene and propylene glycol mixtures, calcium chloride and typical scale and corrosion inhibitors). Miscellaneous: Limited quantities of other style fittings, reducers and nonstandard size couplings are available upon request. Contact Trane Rental Services. Vic-Flange Adapters: Each box comes with (2) Victaulic to Flange adapters and gaskets. The adapters are designed to mate to ANSI Class 125 or 150 flange bolt patterns. The gasket provided seals on both the vertical flange face and horizontal pipe surface when installed properly. The gasket profile is a C. Flange Bolts & Nuts: The hex cap bolts and nuts provided are grade 5 zinc plated. 8 Rental Services Temporary Cooling - Flexible Water Hose CHS-PRB007-EN
9 Component Specification For 2.5-in and 4-in Hose Boxes Only Pressure Loss of Flex Hose Manifold: Chiller sizes 60 ton and below may or may not have pressure & temperature gauges and flow proving switch installed, therefore, these parts are provided in the appropriate size hose kits. Victaulic pipe manifolds are provided to allow installation of the pressure and temperature gauges on both the inlet and outlet of the chiller and the installation of flow switch. Pressure Gauge: Gauges are provided to assist with system setup, monitoring and trouble shooting. Temperature Gauge: Gauges are provided to assist with system setup, monitoring and trouble shooting. Flow Switch: The flow switch is used to prevent or stop the compressor operation if the water flow drops off drastically. The flow switch is to be installed and wired per the appropriate chiller IOM, found inside the chiller control panel. The IOM may also be obtained from the e-library or proper product marketing group. Data on the pressure loss in pounds per square inch (psi) per 100 ft of flexible hose is available from Trane Rental Services. To provide the data, it is necessary to know both the flow rate in gallons per minute (GPM) and system pressure. For example at 1000 GPM and at a system pressure of 150 psi, the 6-in hose has pressure loss of 1.8 psi per 100 ft. Chiller nominal, minimum and maximum flow rates are recorded in the Chiller Engineering Bulletin, CHS-PRB006-EN which can be obtained from the e-library or the proper product marketing group. CHS-PRB007-EN Rental Services Temporary Cooling - Flexible Water Hose 9
10 Installation Instructions This section advises Trane Service Companies or contractors acting on the behalf of a Trane Sales Organization as to the proper installation of flexible hose provided as part of a Trane Rental Services rental project. It is critical that this bulletin is followed to minimize premature or catastrophic failure of this hose. Compliance with these instructions will minimize complaints and issues associated with flexible hose installation. Trane disclaims liability for damages and costs resulting from third party failure to follow the instructions in this bulletin. CAUTION Water Damage! Flexible hose should never be used for an indoor installation. Flexible hose can burst. Failure to follow this recommendation could lead to equipment or property-only-damage. CAUTION Hose Damage! Hose must never be pressurized over 150 psi. If higher pressures are required, hard section pipe must be utlized. Failure to do so may lead to hose damage. CAUTION Hose Damage! Hose must always be used in pressurized application. If a negative pressure application is required, hard suction pipe must be utilized. Failure to do so may lead to hose collapse and total system failure. WARNING! Hose Failure! Failure to comply with installation instructions that follow could result in death or serious injury or equipment damage. Hard pipe is recommended for indoor installations. Flexible hose can burst. Failure to follow this could lead to equipment or property damage. Do not support the hose ONLY by its couplings, support over half of the hose s length by ground or other supporting surface otherwise coupling clamps may fail. Do not run hose vertically more than 7 ft; coupling clamps may fail. Do not cut hose to custom fit pieces. This will affect the integrity of the hose. Bleed all air from the system prior to pressurizing hose to avoid couplings separating from the hose. Install elbows for a smooth hose transition on all vertical hose installations, see Figure 3. Never pressurize hose above 150 psig 10 CHS-PRB007-EN Rental Services Temporary Cooling - Flexible Water Hose
11 Installation Instructions Dixon Coupling The Dixon coupling's bolts are to be torqued to 40 ft.-lbs. prior to charging the hose with water. DO NOT EXCEED 40 ft.-lbs. The torque must be applied evenly between the bolts to ensure a consistent gap on each side of the coupling. Some pinching of the excess hose in the gap area is considered normal and will not create a leak or premature failure. Continually monitor and retighten, if necessary, on monthly inspection intervals. Proper Hose Installation Guidelines Horizontal Hose Installation The following figures illustrate the correct and incorrect methods for installing hose in a horizontal hookup application. Figure 1. Correct Horizontal Hose Installation Figure 1 shows a correct hose installation. In this configuration either a 45 or 90 elbow can be installed. This elbow prevents stretching and crimping of the hose at the hose coupling connection. This elbow also directs the hose to the ground at an appropriate angle to minimize the crimping of the hose at the ground or supporting surfaces. CHS-PRB007-EN Rental Services Temporary Cooling - Flexible Water Hose 11
12 Installation Instructions Figure 2. Incorrect Horizontal Hose Installation Vertical Hose Installation Figure 2 shows an incorrect hose installation. Elbows are not installed. This causes the top of the hose to be in tension, which stretches the hose out of the coupling; and the bottom of the hose to be in compression, which causes it to crimp. It also causes the hose to crimp at the ground. The following figures illustrate the correct and incorrect methods for installing hose in a vertical hookup application. Figure 3 shows a correct vertical hose installation. In this configuration, the hose is installed with an elevation less than 7 ft off the ground. A 45 elbow is installed to reduce the stress in the hose coupling connection. This elbow also directs the hose to the ground at an appropriate angle to minimize the crimping of the hose at the ground or supporting surface. Figure 4 shows an incorrect hose installation. In this configuration the hose is installed without an elbow and with an elevation greater than 7 ft off the ground. This creates excessive stress at the hose coupling connection, causing the hose to stretch and separate from the coupling. It also causes the hose to crimp at the ground. Figure 3. Correct Vertical Hose Installation 12 Rental Services Temporary Cooling - Flexible Water Hose CHS-PRB007-EN
13 Installation Instructions Figure 4. Incorrect Vertical Hose Installation Horizontal to Vertical Installation The following figures illustrate the correct and incorrect methods for installing hose in a horizontal and vertical combination. Figure 5 shows a correct vertical/horizontal hose installation. In this configuration, correct installation techniques followed are: Hose is installed with elbows at both connection ends Vertical run of hose is less than 7 ft Hose is adequately supported by more than half its total length on the ground These items minimize the stretching and separation at the hose-coupling interface and also the crimping of the hose at the ground. Figure 6 shows an incorrect vertical/horizontal hose installation. In this configuration, a number of improper installation techniques can be noted: elbows are not installed hose is completely supported by the couplings vertical run of hose is greater than 7 ft hose is not adequately supported by the ground These items cause excessive stress to be generated at the hose-coupling interface, causing the hose to stretch and separate from the coupling. CHS-PRB007-EN Rental Services Temporary Cooling - Flexible Water Hose 13
14 Installation Instructions Figure 5. Correct Horizontal / Vertical Installation Figure 6. Incorrect Horizontal/Vertical Installation 14 Rental Services Temporary Cooling - Flexible Water Hose CHS-PRB007-EN
15 Installation Instructions Figure 7 illustrates a correct horizontal hose installation where there is a section of unsupported hose. The length of unsupported hose should be less than 7 ft. Also, the hose must be adequately supported by having more than half its total length on the ground. Figure 7. Correct Unsupported Horizontal Installation Material Disposition Exceptions Hard Pipe Installation In the event the hose fails or leaks, please call the Trane Rental Services Technical Service Advisor in Charlotte, NC; mark the problem area & obviously tag the hose BAD and place it back in the shipping box. Any exceptions to the guidelines established in this bulletin must be authorized in writing by the Trane Rental Services Technical Service Advisor, Charlotte, NC. Certain installations may require the use of hard pipe (steel or PVC). Hard pipe is typically recommended for (1) Indoor installations, (2) vertical installations greater than 7 feet, (3) installations on the suction side of a pump where negative pressure may result, (4) semi-permanent installations (three months or more) and/or (5) installations with space limitations. When installing hard pipe: Construct and install the piping according to local and national codes. Isolate and support the piping as required to prevent stress on the unit and vibration to building piping. If there are any questions regarding how to install water piping, contact a Trane Rental Services Technical Service Advisor, Charlotte, NC. CHS-PRB007-EN Rental Services Temporary Cooling - Flexible Water Hose 15
16 Trane A business of American Standard Companies For more information, contact your local Trane office or us at [email protected] Literature Order Number CHS-PRB007-EN Date September 2006 Supersedes New Stocking Location Print-on-Demand Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS
Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The
Installation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of
Application Data Important Safety Information
Application Data Important Safety Information Read this page before using any of the information in this catalog. This catalog is designed to be used as a guide in selecting the proper hose for the applications
Installation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK Safety Instructions Installation Warranty IN-LINE SERIES: 2-5 & 7 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON VERTICAL SERIES: 14-20-32-36-52-86-96-119 GALLON KEEP
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
Style 07 Zero Flex Rigid Coupling. Style 75 Flexible Coupling. Style 77 Flexible Coupling 11. Description
Style 07 Zero Flex Rigid Coupling The unique angled pad design adjusts to standard pipe tolerances to positively clamp the pipe to resist flexural and torsional loads. Working pressures are based on standard
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING
60.1 D-O-L FxE expansion couplings are a bolted, split-sleeve design that provides for expansion and contraction at the coupled joint. These couplings are furnished with restraint rings that, when affixed
Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.
1.0 IMPORTANT RECEIVING INSTRUCTIONS Visually inspect all components for shipping damage. Shipping Damage is not covered by warranty. If shipping damage is found, notify carrier at once. The carrier is
2" & 3" Poly Wet Seal Pump Instruction Manual
Always place the pump as close to the liquid to be pumped as possible. Keep the suction line short and with few bends. Keep the pump and engine on a level foundation. A poor foundation and a heavy suction
Select Radiators Installation Guide
Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall
Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
Float and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
ROUGHNECK II Pumpless Drain
SERVICE BULLETIN SB4027 Rev. I 1/11 For Used Oil Only ROUGHNECK II Pumpless Drain Model #4110-022 FOR USED OIL ONLY (Black) For Antifreeze Only Model #4110-023 FOR USED ANTIFREEZE ONLY (Green) Patent #
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
08.08 Vic-Check Valves
The check valves are a product of computer-assisted innovative engineering with quality features including a new hydrodynamically efficient profile. The Vic-Check valve utilizes a spring-assisted, single-disc
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
Installer s Guide 18-AH39D1-13
18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
USE &CARE GUIDE. Remote Faucet Pump System. See Important Safeguards on page 2
Remote Faucet Pump System USE &CARE GUIDE See Important Safeguards on page 2 An exclamation point within an equilateral triangle is intended to alert user to the presence of important operating and maintenance
VERTICAL / FIXED BEAM CLAMP I-BEAM ANCHOR ADJUSTABLE FROM 4-14 Model # HD26249
VERTICAL / FIXED BEAM CLAMP I-BEAM ANCHOR ADJUSTABLE FROM 4-14 Model # HD26249 IMPORTANT!!! ALL PERSONS USING THIS EQUIPMENT MUST READ AND UNDERSTAND ALL INSTRUCTIONS. FAILURE TO DO SO MAY RESULT IN SERIOUS
Service Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007
Service Guide Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines ORDER No: UN-SVG001A-EN DATE: October 9, 2007 Introduction This document defines American Standard and Trane s recommendations
DANGER DANGER. General Information. Safety Is Your Responsibility. Ordering Parts. Contact Information
Safety Safety Is Your Responsibility DANGER To avoid personal injury or death, carefully read and understand all instructions pertaining to the Anthony Liftgates product. Do not attempt to install, operate,
PVC Pipe PVC SCHEDULE 40. Nominal Pipe Size (in.) 1/8. Average I.D. O.D.
CONDENSED CATALOG PVC HPB-0-A Effective 9//97 Revised //99 CLEAR / / / / -/ -/ -/ x/ CLEAR / / / / -/ PVC SDR. PSI (Water @ 7. F.) /.0.9.0.0 PVC SDR -/ -/ -/ 0 0 PVC SCHEDULE 0.0.7.0.00..7.7.00.000.00...
Installation Manual. Solar Pool Heating System. Read the complete manual before beginning the installation
Solar Pool Heating System Installation Manual Read the complete manual before beginning the installation 1. Sizing the System Visit www.techno-solis.com to size the system using the sizing calculator.
Hose Clamps & Fittings
All Stainless Steel Marine or Underground Hose Clamps 5/16 HEX HEAD SCREW 60000 SERIES Highly corrosion resistant Use for marine or underground applications Stainless Steel Band, Housing Plated Steel Screw
NORMAN FILTER COMPANY PRODUCT OVERVIEW
NORMAN FILTER COMPANY PRODUCT OVERVIEW LEADING THE WAY IN QUALITY FILTRATION WWW.NORMANFILTERS.COM FILTER ELEMENT INTERCHANGE Tee-Type Filter 4500, 14500, 34500, and 54500 Series Mini Tee-Type Filter 4100
PRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
This kit may void factory warranty please check with manufacturer.
Mfg Company TM Thank you for purchasing a Sinister Manufacturing Company EGR delete kit. Precision manufactured using aircraft quality 304 stainless steel and billet aluminum; this EGR kit is designed
SELF-STEERING AXLE TABLE OF CONTENTS
SELF-STEERING AXLE TABLE OF CONTENTS Section 1 - Introduction Section 2 - Pre-Installation Check List Section 3 - Ride Height Adjustments Section 4 - Suspension Mount Section 5 - Axle Mount Section 6 -
V47 Series Temperature Actuated Modulating Water Valves
V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate
Installation Instructions For Slider Casement Air Conditioners
Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT
Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer
Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer The user may choose to adopt part or all of this Model Specification; however, the user should ensure that all parts
Finding and Fixing Leaks
Finding and Fixing Leaks Where did all that water go? Could we have splashed all that water out of the tub? These are all common thoughts that can run through your mind when you open up the hot tub cover
08.09. Triple Service Valve Assembly
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS Victaulic Tri-Service valve is an assembly (shipped as individual components) of a standard Victaulic butterfly or Vic-Plug valve and a check valve. This combination
MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS
MASTER Water Conditioning Corp. www.masterwater.com Installation and Operation Manual MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS with the 263/742 Logix Control Valve June 2010 Table of Contents Page No.
HYDRAULIC LIFT TABLE CART 2200-LB.
HYDRAULIC LIFT TABLE CART 2200-LB. OWNER S MANUAL WARNING: Read carefully and understand all MACHINE ADJUSTMENT AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other
Model 1210C Battery Powered Pump Shown. Description
12 Volt DC Rotary Vane Pump Series 1200C Model 1210C Battery Powered Pump Shown Description of Included Models Model Number FR1205C FR1210C FR1211C FR2410C FR2411C Description Basic 12 volt DC pump with
Mueller. Pipe Repair Products. Saddles Tapping Sleeves Pipe Repair Clamps A complete selection for all types of pipe... all from a single source.
Mueller Pipe Repair Products Saddles Tapping Sleeves Pipe Repair Clamps A complete selection for all types of pipe... all from a single source. SERVICE SADDLES Mueller service saddles, available in bronze,
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
RMF Engineering 23 05 23
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal)
Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal) IMPORTANT: It is imperative that the user read these warnings and use of the assembly instructions
Installation Instructions
READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:
INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS
INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS SETTING UP THE PRESS FOR OPERATION For shipping convenience, the gauge, pump handle, hoist crank, screw nose and base angles
Air Eliminators and Combination Air Eliminators Strainers
Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.
SANITARY SEWER SPECIFICATIONS
SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,
OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
Drum Dispensing Stations
Drum Dispensing Stations O Safely Dispense from 55 Gallon Drums over a Spill Compliant Sump. 1-2-and 4 drum models available Drums are securely held on racks by galvanized positioners Sump and frame constructed
Pipe Repair Products A complete selection for all types of pipe
Pipe Repair Products A complete selection for all types of pipe Mueller Service Saddles Manufactured and tested in accordance with ANSI/AWWA C800 & NSF 61 certified. Mueller service saddles, available
SECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
Section 7 Adjustment, Repair and Replacement
Section 7 Adjustment, Repair, and Replacement Page 7-1 Section 7 Adjustment, Repair and Replacement Section Contents Page Overview...7-5 Belts Belt Guard Removal/Installation...7-7 Belt Removal/Installation...7-11
LIST PRICE BOOK MALLEABLE CAST IRON PRESS FITTINGS FOR SCH. 10 40 BLACK & GALVANIZED STEEL PIPE
FASTLOCK fittings are not currently approved for use with gas or fire protection applications. FITTINGS FOR STEEL PIPE LIST PRICE BOOK MALLEABLE CAST IRON FITTINGS FOR SCH. 10 40 BLACK & GALVANIZED STEEL
Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW
Installation, Operating and Maintenance Instructions 90/4.5.5 Rev. 0 Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Table of Contents SECTION I... 2 INSTALLATION...
10 TON HYDRAULIC PRESS
10 TON HYDRAULIC PRESS Model Nos. CSA10F and CSA10B OPERATING & MAINTENANCE INSTRUCTIONS 0200 SPARE PARTS and SERVICING Please contact your nearest dealer, or CLARKE International, on one of the following
ELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
SureSite Magnetic Liquid Level Indicator
SureSite Magnetic Liquid Level Indicator Instruction Bulletin No. 177664-1 (Rev. E) Section 1: Weldments Thank you for purchasing the GEMS SureSite Magnetic Level Indicator. Please read this document prior
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
CEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
HYDRAULIC TABLE CART 500-LB.
HYDRAULIC TABLE CART 500-LB. OWNER S MANUAL WARNING: Read carefully and understand all MACHINE ADJUSTMENT AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic
G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-211 REV. 7 Supersedes Form No. C11-211 Rev. 6 INDOOR COILS RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM
Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.
1.0 IMPORTANT RECEIVING INSTRUCTIONS Visually inspect all components for shipping damage. Shipping Damage is not covered by warranty. If shipping damage is found, notify carrier at once. The carrier is
MUELLER FALLING FILM CHILLERS
MUELLER FALLING FILM CHILLERS MUELLER FALLING FILM CHILLERS ARE DESIGNED TO COOL ANY FLUID TO WITHIN 2 F OF ITS FREEZE POINT. The primary application for Mueller s falling film chiller is to cool food-grade
THE METALITH PERIMETER SECURITY SYSTEM INSTALLATION INSTRUCTIONS. Attention
THE METALITH PERIMETER SECURITY SYSTEM INSTALLATION INSTRUCTIONS Thank you purchasing the Metalith Perimeter Security System. The following document provides the manufacturer s recommendations for successful
FOR ANY QUESTIONS, PLEASE CALL US @ 727.347.9915 M-F 8:00a.m.-8:00p.m. EST. REAR BRAKES 1 AEROSPACE COMPONENTS 727.347.9915
REAR BRAKES 1 AEROSPACE COMPONENTS 727.347.9915 REAR BRAKES Before getting started, remove all stock braking components. Pre-assembly of parts: Clean the bolts and the threads in the hat with acetone.
Water Pump Replacement
1 of 8 2/5/2008 6:36 AM Document ID# 713637 2001 Cadillac Seville Print Water Pump Replacement Tools Required 1. J 38816-A Water Pump Remover & Installer 2. J 38185 Hose Clamp Pliers
Owner s Manual Gantry Cranes
Owner s Manual Gantry Cranes Fixed Height Gantry Crane MODEL NUMBER: SERIAL NUMBER: CAPACITY IN TONS: Telescoping Gantry Crane Bushman AvonTec 262-790-4200, 800338-7810, Fax 262-790-4200 www.bushmanavontec.com
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
General Guidelines for Repairing Buried PE Potable Water Pressure Pipes
515 General Guidelines for Repairing Buried PE Potable Water Pressure Pipes Introduction Traditional piping systems have gasket-sealed bell and spigot joints every 20 feet, which can be a potential maintenance
Installation and Operating Instructions Installation Instructions for SS EPE-316L Series
INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This
MFH-5057 Ford Small-Block V-8 Fresh Water Cooling Kit Instructions
MFH-5057 Ford Small-Block V-8 Fresh Water Cooling Kit Instructions MONITOR PRODUCTS, INC. 15400 Flight Path Dr Brooksville, FL 34604 Tel: 1-800-334-4591 or 352-544-2620 Sales: ext 201 Technical Support:
Cooling system components, removing and installing
Engine BHW Cooling system components, removing and installing Page 1 / 24 19-1 Cooling system components, removing and installing Warning! When doing any repair work, especially in the engine compartment,
TYPE E Main Valve Sizes 3 /8 through 12
SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,
3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: [email protected] Website: www.kellogg-american.com
Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor
Pressure Testing (Hydrostatic / Pneumatic) Safety Guidelines
The INGAA Foundation, Inc. 1.0 ACTIVITY DESCRIPTION 1.1 This document provides basic safety guidelines for the safety of all personnel and the general public during pressure (e.g., hydrostatic, pneumatic)
PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta
PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification Number: 3503-11.2.610 Rev. 2 Rubber Lined Steel Pipe and Fittings Mechanically Coupled Plain End Type System Issued Revised Approved
Stainless Steel Single and Dual Circulation Kits
Instruction Sheet P/N 160780 01 Stainless Steel Single and Dual Circulation Kits Introduction The single and dual high-pressure circulation kits allow you to vary and control the circulation rate of coating
Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.
1.0 IMPPORTANT RECEIVING INSTRUCTIONS Visually inspect all components for shipping damage. Shipping Damage is not covered by warranty. If shipping damage is found, notify carrier at once. The carrier is
James M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-213 REV. 4 Supersedes Form No. C11-213 Rev. 3 INDOOR COILS RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM
Pallet Jack. OWNER S MANUAL Model MH1230. Important Safety Instructions Assembly Instructions Parts and Hardware Identification
OWNER S MANUAL Model MH1230 Important Safety Instructions Assembly Instructions Parts and Hardware Identification Pallet Jack CAUTION: Read, understand and follow ALL instructions before using this product
Power Cube Open Source Ecology Page 1. Power Cube. Version 4
Power Cube Open Source Ecology Page 1 Power Cube Version 4 Power Cube Open Source Ecology Page 2 Contents Table of Contents Power Cube... 1 Contents...2 Introduction... 3 Bill Of Materials...4 Discrete
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
USER MANUAL. 10 GPM Small Single Line Cryogenic Coupling
JC Carter LLC LNG Couplings USER MANUAL 10 GPM Small Single Line Cryogenic Coupling Models 50E722 Nozzle and 50E721 Receptacle User s Manual and Installation Guide! Warning: Read the User s Manual and
3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS
SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS PART 1: GENERAL 1.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of AW facilities. Closely coordinate construction work
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT
OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT INDEX AMERICAN - DARLING 5-1/4 IN. B-84-B-5 FIRE HYDRANT OPERATION AND MAINTENANCE MANUAL OPERATION AND MAINTENANCE REPAIRS Operation and Maintenance...
Copper Meter Resetters
Copper Meter Resetters To Set 5/8", 5/8" x 3/4", 3/4", 1", 1 1 2" & 2" Water Meters 11/12 Table of Contents Page Page Meter Resetters 5/8", 5/8" x 3/4", 3/4", & 1" Horizontal Inlet and Outlet Series 710
INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-211 REV. 3 Supersedes Form No. C11-211 Rev. 2 INDOOR COILS RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller
January 2013 AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller Milliken Valve Company 190 Brodhead Avenue, Suite 100 Bethlehem, PA 18017 Phone: (610) 861-8803 Fax:
Trouble shooting guide
guide DPR/PSR Leak Insuffi ciently tightened, shallow bite Tighten the nut according to correct number of turns, direct assembly only for maintanance/repair, use of recommended pre-assembly machines Mark