SBC Companies Fiber Distribution Frame Interbay Management Panel Cross-Connect Procedures



Similar documents
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER

ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER

SECTION O FIBER OPTICS

Developing the Green Data Center

Intelligent Cable Management Systems

HUBER+SUHNER AG Phil Ward

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

Reduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U

What is a Datacenter?

BIX Termination Blocks

ADC Structured Cabling Solutions

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Terminating 25-Pair Cable and 4-Pair Cross Connects

FiberGuide Fiber Management Systems. 4th Edition

Digital Link Cross Connect (DLx ) System User Manual

InstaPATCH ZERO Solution Guide

DDP-3 Engineering Guide

Developing the Green Data Centre

Cabinet V800 V800 CABINETS

Category 6 Solutions. 4. Category 6 Solutions. 09/ IN TrueNet Structured Cabling. Introduction Cable Patch Panels... 4.

High density Fiber Optic connections in the Data Center. Phil Ward Datacenter Product Market Manager. HUBER+SUHNER AG

T1 Backhaul Connectivity Solution All Products :: Application Note

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

Adtran TA3000 (Rural DSLAM) Notes

Fundamentals of Fiber Cable Management WHITE PAPER

Sewing Methods Chicago Style Stitch

InstaPATCH Cu Cabling Solutions for Data Centers

Telephone Line Distribution Module

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center

The Three Principles of Data Center Infrastructure Design WHITE PAPER

ADC-APC Integrated Cisco Data Center Solutions

Copper Pre-terminated Assemblies

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

Dimensions (HxDxW) Total Cabinet Area 89.96x x 24 in/ 2,285 x 1, x mm 95.47x 48 x 32 in/ 2,425 x 1,219.2 x 812.

Pretium EDGE HD Solutions

Cable Management Solutions for Brocade High Density Port Blades

Interceptor Optical Network Security System. Design Guide. Chapter 4: INTERCEPTOR Optical Network Security System Alarmed Carrier PDS

Next Generation Frame System

Cable Assemblies. Features and Benefits

Design and Construction Criteria C. Utility Coordination

3M Quick Connect System (QCS) 2810 Models 2810A and 2810B

Layer Zero. for the data center

Fundamentals of Fiber Cable Management

Structured and Point to Point Network Cabling for Industrial Automation

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

FRONTIER TELEPHONE COMPANIES TARIFF FCC NO. 6 Original Page 19-1 ACCESS SERVICE INTERCONNECTION BETWEEN COLLOCATED SPACES

Instruction Manual RT-94845SL RR-94845SL Forty-Eight Channel Video Multiplexer With Bi-directional Ethernet Data

Faster Method for Connecting Customers in the Colocation Data Center

Panduit 28 AWG Patch Cords Installation Guideline

FDC Hardware Product Family

FICON to ESCON Converter Planning Specifications. Rev

OCTOBER Layer Zero, the Infrastructure Layer, and High-Performance Data Centers

Data Center Cabling Design Trends

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Patch Cords for Data Center Applications

Lynx Broadband Installation Manual for Residential Packages with a 20 db Amp Quick Start Guide (first two pages)

OVR-3SP Recloser with PCD Control Style Guide 1VAL SG March 30, 2009 Revision B

21 st Century Campus Network Responsibility Matrix 5/26/10

Cable management for rack-mounted systems

Pretium Connector Housings

Module 5. Broadcast Communication Networks. Version 2 CSE IIT, Kharagpur

The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations

PORT INTERFACE CARD QUICK INSTALL GUIDE

Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications

Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure

Corning Cable Systems Optical Cabling Solutions for Brocade

AMP NETCONNECT Data Center Cabling Solutions

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

4RU High Density Shelf Installation Instructions

Statement of Work Server Migration & Cable Management. Installation Services. Table of Contents. 1.0 Executive Summary. 2.0 Features & Benefits

Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center

Top of Rack: An Analysis of a Cabling Architecture in the Data Center

Energy-efficient & scalable data center infrastructure design

Zone Distribution in the Data Center

Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth

Business Customer Demarcation Information

Installation Manual For Support Call or

Network Monitoring - Fibre TAP Modules

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS

Auxiliary equipment for communication with the EuroProt protective devices

DATA CENTER CABLING DESIGN FUNDAMENTALS

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL SG October 13, 2009 Revision F

MINIMUM TOOL REQUIREMENT FOR EPROM UPGRADE

WHITE PAPER. Creating the Green Data Center. Simple Measures to Reduce Energy Consumption

Data Center Topology Guide

ATTACHMENT F 050R CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

Implementing Fast Ethernet

Opticom Fiber Optic Splice Module

TrueAlarm Fire Alarm Systems

Replacement Instructions. Warning: During this procedure, keep small parts away from children.

Fiber-to-the-Home/FTTH

Spec Sheet. Cisco R42610 Rack CISCO SYSTEMS PUBLICATION HISTORY 170 WEST TASMAN DR. SAN JOSE, CA, REV A.6 DECEMBER 9,

Transcription:

Page 1 ADCP -007 PN 7 Rev A 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 1 3 3 3 0 1 2 7 8 2 -A SBC Companies Fiber Distribution Frame Interbay Management Panel Cross-Connect Procedures

I. Introduction Page 3 II. Recommended Jumper lengths Page III. Cross-Connecting Procedures for Lower Route Page IV. Multibay Cross-Connecting Procedures A. Routing jumpers between adjacent bays in a multibay lineup 1. Connecting ports on the outside edges of adjacent bays Page 9 2. Connecting ports on the same sides of adjacent bays Page 3. Connecting ports on the inside edges of adjacent bays Page V. Cross-Connecting Procedures for Upper Route Page VI. Multibay Cross-Connecting Procedures for Upper Route Page 1 VII. Fiber Optic Terminal (FOT) Jumper Routing Page 1 Page 2 ADCP -007 PN 7 Rev A

I. Introduction This routing guide is intended for SBC Companies for the best cable management within bay lineups using ADC FDF with an upper and lower trough. Minimum jumper length in all cases is 2m (approximately ft.) to prevent intermodule noise. Do not use this procedure if upper trough is not present or for non-adc FDF bay configurations. ADC Assistance Technical Assistance 800 3-31 Ext. 37 Center Customer Service 800 3-31 Ext. 00 Returns 800 3-31 Ext. 378 ADCP -007 PN 7 Rev A Page 3

Bay Zoning Map FOT OSP FOT OSP TOP TROUGH 9L 9R 9L 9R 9L 9R 9L 9R BLANK 8L 8R 8L 8R 8L 8R 8L 8R 7L 7R 7L 7R 7L 7R 7L 7R UPPER ZONE L R L R L R L R L R L R L R L R L R L R L R L R 3L 3R 3L 3R 3L 3R 3L 3R LOWER ZONE 2L 2R 2L 2R 2L 2R 2L 2R 1L 1R 1L 1R 1L 1R 1L 1R LOWER TROUGH BAY 1 BAY 2 BAY 3 BAY -B 1. Locate Origination and Destination points on Zone Map. 2. If EITHER Origination OR Destination is in a lower zone (1L, 1R, 2L, 2R, 3L, 3R, L, R, L, R) use procedure on page, Cross-Connecting Procedures for Lower Route. 3. If BOTH Origination AND Destination is in an upper zone (L, R, 7L, 7R, 8L, 8R, 9L, 9R) use procedure on page, Cross-Connecting Procedures for Upper Route. Page ADCP -007 PN 7 Rev A

II. Recommended Jumper Lengths Lower Trough NUMBER OF LOWER TROUGHS REQUIRED PATCHCORD LENGTH (M) 1 2 3 7 8 9 7 8 9 9 13 19-A Upper Trough NUMBER OF UPPER TROUGHS REQUIRED PATCHCORD LENGTH (M) 1 2 3 7 8 9 3 7 8 8 9 -B ADCP -007 PN 7 Rev A Page

1 1 1 1 19 20 21 2 2 2 2 2 2 27 31 32 33 39 3 3 3 3 3 3 3 3 3 3 3 3 0 1 2 0 1 2 0 1 2 0 1 2 7 8 7 8 7 8 7 8 III. Cross-Connect Procedures for Lower Route 1 TERMINATE one end of the patchcord at the appropriate port. 1 193-A 2 ROUTE the patchcord through the vertical cable guides to the lower trough. 2 1-A 3 PLACE the patchcord in the lower trough. 3 Page 0-A ADCP -007 PN 7 Rev A

31 19 2 32 20 2 33 39 21 27 0 3 1 7 1 3 8 2 3 2 1 3 0 3 1 7 3 2 8 2 1 2 3 3 3 0 1 2 III. Cross-Connect Procedures for Lower Route (continued) ROUTE the unterminated end of the patchcord to the second connection port. NOTE: Be sure to leave the extra patchcord slack in the lower trough. 019-A TERMINATE the second end of the patchcord to the appropriate port. 1-A ROUTE the second end of the patchcord through the vertical cable guides to the lower trough. ADCP -007 PN 7 Rev A 1-A Page 7

7 8 7 8 7 8 7 8 III. Cross-Connect Procedures for Lower Route (continued) 7 LOOP the patchcord slack, located in the lower trough, over the appropriate interbay management spool. 7 NOTE: See appropriate application drawing located within this user manual for recommended specific cable routings. CORRECT ROUTING DO NOT WRAP PATCH CORD MULTIPLE TIMES AROUND SAME SPOOL DO NOT WEAVE PATCH CORD AROUND SPOOLS 197-A Page 8 INCORRECT ROUTING ADCP -007 PN 7 Rev A

IV. Multibay Cross-Connecting Procedures for Lower Route Between adjacent bays in a multibay line up Connecting ports on the outside edges of adjacent bays 7-A ADCP -007 PN 7 Rev A Page 9

IV. Multibay Cross-Connecting Procedures for Lower Route (continued) Between adjacent bays in a multibay line up Connecting ports on the same sides of adjacent bays 8-B Page ADCP -007 PN 7 Rev A

IV. Multibay Cross-Connecting Procedures for Lower Route (continued) Between adjacent bays in a multibay line up Connecting ports on the inside edges of adjacent bays 9-B ADCP -007 PN 7 Rev A Page

1 2 3 3 3 0 1 2 7 8 21 1 V. Cross-Connecting Procedures for Upper Route 1 TERMINATE one end of the patchcord at the appropriate port. 1 198-A 2 2 ROUTE the patchcord through the vertical cable guides to the upper trough. 199-A 3 3 PLACE the patchcord in the upper trough. Page 1-A ADCP -007 PN 7 Rev A

21 V. Cross-Connecting Procedures for Upper Route (continued) ROUTE the unterminated end of the patchcord to the second connection port. NOTE: Be sure to leave the extra patchcord slack in the upper trough. 131-A TERMINATE the second end of the patchcord to the appropriate port. 132-A ROUTE the second end of the patchcord through the vertical cable guides to the upper trough. ADCP -007 PN 7 Rev A 133-A Page 13

1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 0 1 2 0 1 2 0 1 2 0 1 2 0 1 2 7 8 7 8 7 8 7 8 7 8 V. Cross-Connecting Procedures for Upper Route (continued) 7 LOOP the patchcord slack, located in the upper trough, under the appropriate interbay management spool. NOTE: See appropriate application drawing located within this user manual for recommended specific cable routings. 7 CORRECT ROUTING DO NOT WRAP PATCH CORD MULTIPLE TIMES AROUND SAME SPOOL DO NOT WEAVE PATCH CORD AROUND SPOOLS 138-A INCORRECT ROUTING Page 1 ADCP -007 PN 7 Rev A

VI. Multibay Cross-Connecting Procedures for Upper Route Between adjacent bays in a multibay line up Connecting ports on the outside edges of adjacent bays 9-A ADCP -007 PN 7 Rev A Page 1

VII. Fiber Optic Terminal (FOT) Jumper Routing TO FOT EQUIPMENT PATCHCORD BUNDLE (ALL TO THE SAME MODULE) FOT OSP PATCHCORD CHANNEL ROUTE BEHIND SPOOLS 133-A BUNDLE TO OTHER MODULE Rear View ROUTE THROUGH FANNING TREE LOOP CORRESPONDING TO ROW POSITION NOTE: Work from the top down. Arrange bundles inside to outside in channel. LEAVE SERVICE LOOP BELOW SPOOL Page 1 ADCP -007 PN 7 Rev A