Copper Patch Cords. Impact On Network Performance and Reliability



Similar documents
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges

Innovative Connectivity Solution for Maximum Performance and Security

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

Enhanced Category 5 Cabling System Engineering for Performance

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)

Panduit 28 AWG Patch Cords Installation Guideline

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER

Network Engineers Everywhere:

PANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security

Total Solutions Verification

Category 8 Cabling Standards Update

Position Cat5e (EMT) Modular Plug Connectors. Application Specification

Polymer Coated Fiber Cable (PCF)

Category 6 Solutions. 4. Category 6 Solutions. 09/ IN TrueNet Structured Cabling. Introduction Cable Patch Panels... 4.

How to Choose the Right Cable Category

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8

Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer

Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek

Category-6 / Class-E Cabling

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

SYSTIMAX Copper Solutions Designed for the Digital Generation

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

CABLE TERMINATION BEST PRACTICES A guide to improved cable performance through proper termination and installation.

The Effect of Network Cabling on Bit Error Rate Performance. By Paul Kish NORDX/CDT

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8

The High Cost of a Low-Cost Cable Certification Tester

Accelerating Light. Copper Cabling Solutions. Category 6A

Structured and Point to Point Network Cabling for Industrial Automation

Copper Cabling Troubleshooting Handbook

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk

Patch Cords / Cable / Cable Assemblies. Patch. Cords/Cable/ Premise Connectivity Systems. Cable Assemblies

Upgrading Path to High Speed Fiber Optic Networks

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

Patch Cords for Data Center Applications

Managing Physical Security Risk in Physical Layer Infrastructure Solutions

Ethernet Patch Cord Wiring

PANDUIT is a Technology Developer Partner for Storage Networking Hardware. FIBER OPTIC CABLING SYSTEM SOLUTIONS B EYOND T HE G LASS

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT

Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka

Power over Ethernet with Panduit Copper Cabling

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems

Impedance Matching. Throughput SOLUTIONS NETWORK PERFORMANCE. Only the TrueNet Impedance-matched System Protects Network Performance

White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION STRUCTURE CABLING TESTING

White Paper. Power over Ethernet Plus Update and Cabling Considerations

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

Data Communications Competence Center

Simpler all over. Simpler all round. 500 MHz. 10 GB ether. fully shielded. Poe+ Cat.6 A. Data Voice. MFP8 Cat.6 A Field assembly RJ45 plug

Physical Infrastructure Management PanView iq (PViQ ) System Hardware

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

AMP CO Plus Insert for Cat. 6 A Applications

Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand

Installation & Weatherproofing Guide for ENCOM Broadband Radios

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Abstract: This document examines the alien NEXT performance of various bundled cables and measures the impact upon various networks performance.

ATT-TP Ethernet Copper Cable & Ethernet Copper Assembly Specification

GigaSPEED X10D Solution How

Network Design. Yiannos Mylonas

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems

Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels

Intelligent Data Center Solutions

Data Center Architecture with Panduit, Intel, and Cisco

Transmission of High-Speed Serial Signals Over Common Cable Media

Case Study. Molex PDS Delivers Voice and Data Streams around Shanghai Unicom Tower

SIEMON Data Center Solutions.

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS

Open System Architecture

SYSTIMAX Solutions. GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions.

Data Centre & Enterprise Solutions. RapidNet

CCNA Discovery Chapter Four

INTELLIGENT INFRASTRUCTURE MANAGEMENT

Standards Affecting a Premise T-1 Installation

Terminating 25-Pair Cable and 4-Pair Cross Connects

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Lynx Broadband Installation Manual for Residential Packages with a 20 db Amp Quick Start Guide (first two pages)

Model CFA-24 Transparent Cable Farm Automation Switch

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

CommScope Intelligent Building Infrastructure Solutions (IBIS)

SMARTen 24 STP Patch Panels

Safety & Performance in the Wire and Cable Industry

IT Cabling Solutions

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

MPO. Fast Fibre Solution for Data Centres

SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS

TIA Releases Guidelines for Maintaining Polarity Using Array Connectors

Nathan Dayton ADNET. ADNET SYSTEMS, Inc. Slide Number 1

Open Office Cabling Architecture SYSTIMAX. Structured Cabling System Opens Office Cabling to New Possibilities

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

Cat7/Class F New Installation Concept New infrastructure. Handbook

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions

Transcription:

Copper Patch Cords Impact On Network Performance and Reliability 1

The Impact of Copper Patch Cords on Network Performance and Reliability As network infrastructures continue to have a higher impact on an organization s productivity and competitive position, it becomes increasingly important to select a reliable end-to-end structured cabling system that will allow for future network growth. To maximize usable network bandwidth, it is critical that patch cords properly support the performance, quality, and dependability of the entire structured cabling system. The performance of the link between the switch and computer is most impacted by noise generated in the area of the channel closest to the active equipment. This is where the patch cords are located and where quality should never be compromised by using off-brand patch cords. It is vital that patch cords have the following design features: Mated performance with connecting hardware to maximize cancellation of near-end-crosstalk Robust construction to ensure long-term reliability of the network under day-to-day moves, adds and change conditions Certified component performance to ensure maximum network availability Investing in high quality patch cords ensures the channel components work together as an end-to-end solution to maximize performance and reliability. Various testing scenarios, as outlined below, provide quantifiable results to support the importance of high quality patch cords. Importance of Mated Connecting Performance One of the key factors to achieve high-end channel bandwidth is the optimum mated performance of the patch cord plug and the jack connector. Fundamentally, connectors and plugs are designed to have equal but opposite component pair coupling effects. A properly tuned jack compensates for the noise generated by the patch cord plug. Thus, mated performance is achieved when the crosstalk within the patch cord plug is cancelled by the compensation in the connector. The TIA/EIA 568-B.2 Category 6 standard addresses the issue of mated performance by establishing a de-embedding procedure to test the electrical performance of modular plugs. De-embedding is a process that uses a reference jack connector with known values to obtain the NEXT loss values for plugs. The mated performance of a typical Category 6 connector has a bell shape performance curve across the de-embedded patch cord plug range. If a jack connector is designed correctly, the optimal mated performance is at the center of the Category 6 de-embedded test plug range. Graph 1 2006 PANDUIT Corp. All rights reserved. www.panduit.com 2

Conversely, the connector must also meet the mated connecting hardware pair-to-pair NEXT loss specification across the allowable Category 6 de-embedded test plug NEXT loss range. In the case of pair combination 3,6-4,5, the optimum performance is with a centered deembedded plug of 37.0 at 100 MHz (shown in Graph 1) but the connector must also pass the mated connecting hardware pair-to-pair NEXT loss specification with test plugs ranging from 36.4 to 37.6. When a plug is outside of this range, mated performance declines and is no longer compatible to the connecting hardware. A jack connector that performs well when mated to a patch cord plug with high or low de-embedded NEXT may not provide the same performance when mated with a patch cord plug that is centered in the de-embedded range. In some cases, that connector may even fail the Category 6 connecting hardware requirements when using a patch cord plug at the other end of the de-embedded range. In other words, when a connector is not optimized with a centered plug, it minimizes backward compatibility and interoperability with other channel components. This can limit network performance. Conversely, the PANDUIT MINI-COM TX6 PLUS Jack Module and DP6 Patch Panels are designed with complementary technology to meet the connecting hardware pair-to-pair NEXT specification with the de-embedded NEXT loss ranges. However, if one of these connectors is mated with an off-brand patch cord that is not tightly centered to the de-embedded range, the channel performance could be significantly degraded. To deliver superior reliability, the PANDUIT TX6 PLUS Category 6 Patch Cords are manufactured with plugs that are tightly centered in the Category 6 de-embedded plug NEXT loss ranges for maximum performance when mated with the PANDUIT MINI-COM TX6 PLUS Jack Module or DP6 Patch Panels. The PANDUIT TX6000 Copper Cabling System delivers usable bandwidth beyond 300 MHz (shown in Graph 2), over 50% higher than specified by the TIA/EIA Category 6 standard! Graph 2 NEXT Standard PANDUIT NEXT Insertion Loss Standard PANDUIT Attenuation Affects of Besides having properly mated patch cords and connectors to ensure maximum performance during initial installation, patch cords also have to be designed to easily handle frequent moves, adds, and changes. Due to the handling that patch cords receive, TIA/EIA 2006 PANDUIT Corp. All rights reserved. www.panduit.com 3

568-B.2 requires mechanical stress testing of patch cords to ensure they continue to operate under real-world conditions. Per the TIA/EIA 568-B.2 requirements, patch cords are mechanically tested for performance after bending in various configurations: Patch Cord put into a 6-inch diameter cable loop, up to 10 loops total Patch Cord compressed into a 2.5-inch coil to form an ellipse Patch Cord rotated on one end on the coil ellipse by 180 0 to form a figure eight 2006 PANDUIT Corp. All rights reserved. www.panduit.com 4

Testing of off-brand patch cords by PANDUIT Laboratories has shown consistent deterioration of electrical performance to levels below the TIA/EIA 568-B.2 specifications resulting in non-compliant patch cords and degraded channel performance. TIA/EIA 568-B.2 Mechanical Stress Test of Off-Brand Patch Cords NEXT BEFORE NEXT AFTER 100.00 NEXT 100.00 NEXT 90.00 90.00 80.00 80.00 70.00 70.00 60.00 60.00 SPEC 45-36 45-12 45-78 36-12 36-78 '12-78 SPEC 45-36 45-12 45-78 36-12 36-78 '12-78 Return Loss BEFORE Return Loss AFTER RETURN LOSS RETURN LOSS 45.00 45.00 35.00 35.00 25.00 25.00 20.00 20.00 15.00 15.00 10.00 SPEC PAIR 45 PAIR 12 PAIR 36 PAIR 78 10.00 SPEC PAIR 45 PAIR 12 PAIR 36 PAIR 78 2006 PANDUIT Corp. All rights reserved. www.panduit.com 5

TIA/EIA 568-B.2 mechanical stress test of high quality patch cords, such as the PANDUIT TX6 Patch Cords shows electrical performance that exceeds the TIA/EIA 568-B.2 specifications resulting in superior long-term channel performance and increased network reliability. TIA/EIA 568-B.2 Mechanical Stress Test of PANDUIT Patch Cords NEXT BEFORE NEXT AFTER 100.00 NEXT 100.00 NEXT 90.00 90.00 80.00 80.00 70.00 70.00 60.00 60.00 0 50 100 150 200 250 SPEC 45-36 45-12 45-78 36-12 36-78 '12-78 0 50 100 150 200 250 SPEC 45-36 45-12 45-78 36-12 36-78 '12-78 Return Loss BEFORE Return Loss AFTER RETURN LOSS RETURN LOSS 45.00 45.00 35.00 35.00 25.00 25.00 20.00 20.00 15.00 15.00 10.00 SPEC PAIR 45 PAIR 12 PAIR 36 PAIR 78 10.00 SPEC PAIR 45 PAIR 12 PAIR 36 PAIR 78 2006 PANDUIT Corp. All rights reserved. www.panduit.com 6

To ensure PANDUIT patch cords withstand the stress of actual installations, PANDUIT has incorporated the following innovative features in its design for maximum channel performance, reliability and usability: Patented tangle free latch prevents snags and provides easy release, which saves time on frequent moves, adds and changes Slender strain relief boot provides easy access in highdensity applications and mechanical reliability for longterm consistent performance of your channel Contacts plated with 50 micro inches of gold for robust and reliable connection to support sensitive PoE applications Plug uses an integral pair manager to optimize performance and consistency by reducing untwisting of conductors within the plug and effectively reducing cord-to-cord variability Tight conductor twist rates and cable construction for advanced performance and long term mechanical reliability Plug compliance with all applicable FCC part 68 Subpart F requirements and exceed IEC 6060J-7 specifications 100% Component Testing Beyond mated performance and mechanical testing, an additional measure to ensure patch cord performance is to test each patch cord to the TIA/EIA-568-B.2 component requirement. PANDUIT implements a strict ISO 9001 quality procedure that 100% tests every PANDUIT patch cord to the electrical transmission requirements per TIA/EIA-568-B.2. Every patch cord assembly produced is tested for Wire Map, NEXT, and Return Loss using a Fluke * Digital Cable Analyzer. Each patch cord is then shipped with a quality control label, which is referenced to actual test data verifying high performance. *Fluke is a registered trademark of Fluke Corporation. 2006 PANDUIT Corp. All rights reserved. www.panduit.com 7

Conclusion Patch cords are an integral component impacting the performance of the entire structured cabling system. Investment should be made in patch cords that utilize advanced features to deliver maximum reliability and usability of the network. Off-brand patch cords jeopardize network performance due to: High degree of plug variability which leads to degradation of channel performance Inferior design features which do not perform over time due to the mechanical stresses of real-world conditions Untested, low quality patch cords which may not meet electrical requirements In addition, patch cords must be properly mated and tuned to connecting hardware (jacks, panels, and horizontal cable) to keep the network running at peak performance. This directly minimizes the impact of costly network downtime. The proven performance of high quality PANDUIT Copper Patch Cords, tested to exceed TIA/EIA 568-B.2 specifications as a key component of the complete end-to-end solution, helps ensure maximum network bandwidth. Specifying and installing these patch cords can support the critical network demands for today and tomorrow. Additional References: 1. The Weakest Link in High-Performance Cabling Systems, Fluke Networks, 5/2005 2062074 A-US-N rev B 2. Testing Proves Most Cords Fail TIA Requirements (Buyers are not getting what they paid for), Quabbin Wire & Cable Co., Inc., 4/03 2006 PANDUIT Corp. All rights reserved. www.panduit.com 8