DeviceNet Motor Control



Similar documents
DeviceNet Bus Software Help for Programming an Allen Bradley Control System

Application about Communication

User Manual. DeviceNet Network Configuration

Configuring the SST DeviceNet OPC Server

QuickPanel Control DeviceNet Master Communications Card (IC754DVNM01) Quick Start Guide. Thursday September 20, 2007

L5354 ControlNet Communications Interface

DeviceNet Communication Card

DeviceNet Configurator User Guide

RSNetWorx RSNETWORX FOR DEVICENET GETTING RESULTS GUIDE. PUBLICATION DNET-GR001H-EN-E October 2015 Supersedes Publication DNET-GR001G-EN-E

DeviceNet Communications handbook

Install the DeviceNet Module using the following procedure:

Ethernet Interface Manual Thermal / Label Printer. Rev Metapace T-1. Metapace T-2 Metapace L-1 Metapace L-2

8903/CN ControlNet Communications Interface

Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP. 1 Application Description Objective Goals...

GlobalProtect Agent User Guide for Windows

CMC-DN01 DeviceNet Slave Communication Card Operation Manual

NVMS User Manual

for both the Verbatim Gateway and Catalyst Autodialer EtherNet Options

Work with Arduino Hardware

How do I configure the wireless printer using a USB or Ethernet cable and install the printer driver in Windows?

Legal Notes. Regarding Trademarks KYOCERA Document Solutions Inc.

ControlLogix Remote I/O Communication Module

Colorfly Tablet Upgrade Guide

1 Application Description Objective Goals... 3

DeviceNet Communication Manual

Print Server Application Guide. This guide applies to the following models.

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

IPRS-7 IP/GPRS PC Receiver Software Quick Start V1.2

C441 series communication modules Accessories for electronic overload relays and soft starters. Monitoring and control made simple

Charter Business Desktop Security Administrator's Guide

CMC-PD01 PROFIBUS DP Slave Communication Card Operation Manual

User Manual. Thermo Scientific Orion

ScanShell.Net Install Guide

Termination Resistors:

DeviceNet Scanner Module

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: Rev 6

How To Use Mview On A Powerline 2.2 (Powerline) On A Pc Or Macbook 2 (Powerplst) On An Iphone Or Ipa 2 (Aldo) On Your Iphon 2 (

Cart Interface Installation & Control Board Manual for M38 XP and RX Carts and Legacy M39 Carts

Installation and Operation Manual Portable Device Manager, Windows version

How to read this guide

About This Guide SolarEdge Configuration Tool Software Guide. About This Guide

Module 1 Overview ControlLogix5000

Troubleshooting and Diagnostics

Using the AnyBus -X Gateway to Communicate between a DVT camera and a Profibus Master

Centurion PLUS CPC4 Download Guide

RKAT Audit Trail Module RK-LINK TM Software For the Radio Key 600 Series

Introduction: Implementation of the MVI56-MCM module for modbus communications:

Print Server Application Guide

1769-SDN DeviceNet Scanner Module. Catalog Numbers 1769-SDN User Manual

CTERA Agent for Mac OS-X

TL-PS310U Single USB 2.0 Port MFP and Storage Server

Learn how to create web enabled (browser) forms in InfoPath 2013 and publish them in SharePoint InfoPath 2013 Web Enabled (Browser) forms

Global Common Controls Software Design (GCCS-2) Course (Version 6.0)


DEPLOYING A VISUAL BASIC.NET APPLICATION

1/4/12 Installing and Configuring WebDAV on IIS 7 : WebDAV for IIS 7.0 : Publishing Content to Web Sites : T

RSLinx Classic Getting Results Guide

WINDOWS PROCESSES AND SERVICES

Bluetooth to Serial Adapter

WSDOT ProjectWise V8i Training 101

Modbus RTU (RS-485) TCP/IP (Ethernet)

Mobility with Eye-Fi Scanning Guide

Software localisation: Working with PASSOLO

DCS DCS 6000 Digital Conference System Firmware Upgrade & Feature License Key Manual. Upgrade Manual. Digital Conference System

Installing S500 Power Monitor Software and LabVIEW Run-time Engine

Test Center Enterprise. ios Device Onboarding Guide

Emonitor INSTALLATION MANUAL INSTALLING EMONITOR SOFTWARE WITH A GUPTA SINGLE USER DATABASE

QUANTIFY INSTALLATION GUIDE

Before you start, you should prepare the following items

Configuration Manager

IDDERO HCx-KNX TOUCH PANELS. Quick start guide

Using IDENT M System T with Modbus/TCP

ELM Server Exchange Edition Virtual Archive Mailbox version 5.5

32 Transferring Projects and Data

13 Managing Devices. Your computer is an assembly of many components from different manufacturers. LESSON OBJECTIVES

NVMS USER MANUAL. Version 2.1.0

Application Note Profinet Modules

PaperStream Connect. Setup Guide. Version Copyright Fujitsu

Virtual COM Port Driver Installation Manual

Virtual COM Port Driver Installation Manual

Contents. Hardware Configuration Uninstalling Shortcuts Black...29

BECKHOFF. Application Notes. BC9000: Getting Started Guide. For additional documentation, please visit.

Using Ladder Logic Instructions to Communicate with an Ethernet IP Nexus Unit

Application/Connection Examples

Viewing and Troubleshooting Perfmon Logs

How To Use An Apple Macbook With A Dock On Itunes Macbook V.Xo (Mac) And The Powerbar On A Pc Or Macbook (Apple) With A Powerbar (Apple Mac) On A Macbook

Online Backup Client User Manual Mac OS

Online Backup Client User Manual Mac OS

DeviceAnywhere Enterprise. ios Device Onboarding Guide

Server Manager Performance Monitor. Server Manager Diagnostics Page. . Information. . Audit Success. . Audit Failure

IP Link Device Interface Communication Sheet

Network Detective Client Connector

5 Setting up a Contact Center

16-PORT POWER OVER ETHERNET WEB SMART SWITCH

NETWORK PRINT MONITOR User Guide

Pharos Control User Guide

Micro800 Programmable Controllers: Getting Started with CIP Client Messaging

SECURE MOBILE ACCESS MODULE USER GUIDE EFT 2013

Tutorial: Configuring GOOSE in MiCOM S1 Studio 1. Requirements

isppac-powr1220at8 I 2 C Hardware Verification Utility User s Guide

Transcription:

Quick-Start Guide for the DN65 DeviceNet I/O Module using Rockwell RSNetWorx version 2.22 or later This Quick-Start Guide provides instructions for configuring a Cutler-Hammer Freedom full voltage, non-reversing (FVNR) or full voltage, reversing (FVR) starter with a DN65 DeviceNet I/O Module. Firmware Version Notes: Firmware version 1.01 (or later) of DN65 is supported. EDS Files: Electronic Data Sheets (EDS) files are available from the Cutler-Hammer Motor Control Center Intranet site location at http://www.ch.etn.com/mcc_2/products/devicenet_mcc_techinfo_eds_files.html Due to changes in ODVA specifications and enhancements to DeviceNet configuration software tools, it is recommended that Cutler-Hammer Technical Support (1-800-809-2772) be contacted for information about the latest EDS files. When inquiring about EDS files, have the following information ready:! Which Cutler-Hammer motor starters are being used?! What DeviceNet interface is installed?! Are reversing starters being used?! Are reduced voltage (across-the-line) starters being used?! Are Advantage Control Modules (ACM s) used on non-reversing starters?! The Firmware # or Rev. code letter for the DeviceNet I/O Module.! NetView or RSNetWorx software revision number. Product Information: A Technical Data Publication for the DN65 DeviceNet I/O Module is available from local Cutler-Hammer Sales Offices. Specify publication TD.09.01.T.E. This information is also available from the Cutler-Hammer Internet and MCC Intranet. Page 1 of 8

Equipment Setup: 1. Connect the DeviceNet Trunk cable to the DeviceNet scanner interface being used. 2. Connect the DN65 DeviceNet I/O Module to the network using the DeviceNet terminals located on the top of the unit. Note that the DeviceNet cable Shield is not terminated at the DN65. 3. Check that the 24Vdc Power Supply disconnect switch is ON and that 24Vdc is present on the DeviceNet network cable (V+ & V- at any location). Network Setup: 1. Have functional RSNetWorx software and interface hardware as needed. 2. Install the Cutler-Hammer supplied EDS file using the EDS Wizard. 3. Once you have determined that you have the correct EDS file, click on Tools, EDS Wizard, Next choose Register an EDS File(s), Next, Choose File to identify the location of the EDS file, locate the EDS file and double-click on it. Then, click Next. A next to the EDS file path indicates that the EDS is valid. Click Next. A new Vendor device listing under General Purpose I/O called DN65 Discrete I/O Device will be displayed. Click Next, then Finish. Page 2 of 8

Connecting to the DN65 I/O Module: Once the EDS file is installed, the Hardware listing (left side of RSNetWorx window) will include a new device as shown: 1. To see if the starter is found correctly click on Network, Online. RSNetWorx will browse all possible Macid s for the network. The DN65 icon should show up in the Network View window. Page 3 of 8

Troubleshooting Note: If it does not show up in the top right window, and instead shows up in the bottom as not being registered on this computer then you probably have the wrong EDS file loaded for the particular version of DN65. To check the version, right click on the Globe icon for the node that isn t being recognize and select properties. You should then see a window with the revision number for the device. Make a note of the revision number. To compare the hardware version to the EDS file version, go to the Hardware listing tree and select the Cutler-Hammer DN65 Discrete I/O Device. Right click to view the properties of the EDS file and compare that revision number with the installed hardware. If they do not match, download the correct EDS file from the Cutler-Hammer Internet site. Once you get the DN65 to show up in the network window you can modify the appropriate parameters in your Freedom Starter DeviceNet interface. Setting Properties: MAC ID and possibly Baud Rate are the only two parameters that typically need to be modified. 1. Double-click on the DN65 icon to open the Properties Window. Upload the parameters. Select Device Parameters. As shown in the window to the right, all of the configuration parameters will be listed. Some will be locked (read-only). Others allow you to modify the parameter as needed. Typical parameters that need to be configured are " MACid " Baud Rate Page 4 of 8

Note: The MAC ID, or node address, must be a unique number between 0 and 63. It is recommended that address 63 be reserved for new (or replacement) devices being added to the network. Also, a good practice for motor control center applications is to leave a few network addresses available for expansion. The host control platform network scanner also consumes one MAC ID address. 2. Use the following steps to configure the DN65 DeviceNet I/O Module for operation. a) Macid: With the Parameters window displayed as shown above, click on the MACid field under the Current Value column. Right click and select Edit. Enter in the new network address number. Click on Apply and then Download to Device. In the Network window, delete the DN65 node referencing the old MAC ID. Perform a Single Pass Browse to locate the new MAC ID. b) Baud Rate: The factory default is 125Kb/s. This is suitable for most applications. Increasing the Baud Rate will limit the overall distance allowed for the network Trunk cable. If the network is to operate at a higher Baud Rate, click on the Baud Rate field under the Current Value column. Right click and select Edit. Select the new Baud Rate (250 or 500). Click on Apply and then Download to Device. The Network configuration master being used must also be changed to match the new Baud Rate. Page 5 of 8

3. Map the DN65 DeviceNet I/O Module I/O Data to the Host Scanner Module A DeviceNet scanner is a device that manages input and output data for the processor. The scanner receives input data from I/O devices, organizes the information into scanner data tables, and sends the input data to the processor when the processor requests it. In addition, it sends output data, which it receives from the processor, to the I/O devices. a) Open the Scanner module s Properties window by right-clicking on the Scanner icon. Select the Scanlist Tab to view the available slave devices on the network. Suggestion: Remove the Automap on Add feature to allow changes to the mapping location. b) Click on the DN65 device and add it to the Scanlist by clicking on the > arrow. c) Next, choose Edit I/O Parameters to tell RSNetWorx how many bytes of data to expect. Select Polled, and Rx Size to be 1 bytes and Tx size to be 1 byte. These are the default settings. Page 6 of 8

d) Next, select the Input Tab. Choose the Memory location and Start Word for the Input data. Click on the desired DN65 Node and select AutoMap. e) Repeat the process for the Output data by selecting the Output Tab, then specifying the Memory location and the Start Word. f) Click on Apply to save the your configuration. Note: ControlLogix and SLC/PLC5 have different memory options. This example is based on the 1756-DNB memory location. Now the Input data (information transmitted from the starter) and Output data (commands from logic to the starter) are mapped to the Scanner s I/O table. Page 7 of 8

In this example (based on the 1756-DNB scanner), input data will be located as follows: 1:I.Data[1] Bit 0 State of Input 1 1:I.Data[1] Bit 1 State of Input 2 1:I.Data[1] Bit 2 State of Input 3 1:I.Data[1] Bit 3 State of Input 4 1:I.Data[1] Bit 4 unused 1:I.Data[1] Bit 5 unused 1:I.Data[1] Bit 6 unused 1:I.Data[1] Bit 7 unused Output data will be located as follows: 1:O.Data[1] Bit 0 Control of Output 1 1:O.Data[1] Bit 1 Control of Output 2 1:O.Data[1] Bit 2 unused 1:O.Data[1] Bit 3 unused 1:O.Data[1] Bit 4 unused 1:O.Data[1] Bit 5 unused 1:O.Data[1] Bit 6 unused 1:O.Data[1] Bit 7 unused You have now successfully commissioned a DN65 DeviceNet I/O Module. Depending on the PLC/PC platform you are using for control, you may need to create ladder logic elements to move the DeviceNet data from the scanner to the PLC/PC memory. For any questions regarding the hardware, software or procedures mentioned in this document please contact Cutler-Hammer Technical Support at 1 (800) 809-2772. Page 8 of 8