ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

Similar documents
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

Telecommunications Infrastructure Standard for Data Centers Tutorial

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc

Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

TIA-942 Data Centre Standards Overview WHITE PAPER

How To Write An Infrastructural Standard For Data Center Infrastructure

Data Center Design Considerations

TIA-942: Data Center Standards

Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

TIA STANDARD. Telecommunications Infrastructure Standard for Data Centers TIA-942 TELECOMMUNICATIONS INDUSTRY ASSOCIATION

Corning Cable Systems Optical Cabling Solutions for Brocade

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

Data Centre Design ready for your future

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Data Center Topology Guide

BICSI NxtGEN & Global Data Center Standards Update

Network Topologies and Distances

Zone Distribution in the Data Center

Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure

Data Center Cabling Design Trends

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction

Network Design. Yiannos Mylonas

Data Center Design for 40/100G

ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER

Video Systems and Data Center Design Wiring Plant Designation Terminology Infrastructure Deployment

AMP NETCONNECT Data Center Cabling Solutions

Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices

InstaPATCH Cu Cabling Solutions for Data Centers

ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER

The Three Principles of Data Center Infrastructure Design WHITE PAPER

Building a Tier 4 Data Center on a Tier 1 Budget

Corning Cable Systems Optical Cabling Solutions for Brocade

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

CommScope. Enterprise Data Center Design Guide.

DESIGN GUIDELINES. Local Area Network

Data Center Designs and Hospital Operations

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Organizing and Managing Equipment Rooms

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Structured and Point to Point Network Cabling for Industrial Automation

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011

This presentation to be used in conjunction with:

Designing the Data Center

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Building Telecommunications Infrastructure Requirements

What is a Datacenter?

Giganet Copper Cabling Training

This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.

Opportunities in data centers for the ITS professional

Cat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards.

Specifying an IT Cabling System

ADC-APC Integrated Cisco Data Center Solutions

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

DATA CENTER NETWORK INFRASTRUCTURE. Cable and Connectivity for the Most Demanding Networks. BerkTekLevitonTechnologies.com

SECTION TELECOMMUNICATION ROOMS

Standards. 5 ANSI/TIA/EIA-569-A (CSA T530)

** PROPRIETARY ** SAMPLE COUNTY DATA CENTER PROJECT BUDGET ** PROPRIETARY **

How To Determine Data Center Reliability

Data Center Solutions

ATTACHMENT F 050R CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

Data Center Components Overview

Products. Technology. Services. Delivered Globally. DATA CENTER SOLUTIONS

TC Grounding and Bonding for Telecommunications Systems

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

Intelligent Cable Management Systems

Top of Rack: An Analysis of a Cabling Architecture in the Data Center

Engineers Edge, LLC PDH & Professional Training

So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org

SYSTIMAX Solutions Data Center Planning Guide

Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations

Data Center Solutions

Data Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc.

DATA CENTER SOLUTIONS

Cabinets 101: Configuring A Network Or Server Cabinet

Energy-efficient & scalable data center infrastructure design

UT Southwestern Medical Center Information Resources Cable Installation Standard

Obsolete Fiber Technology? Not in my Data Center!

Fabrics SDN and Big Data. What this means to your white space

VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE

Data Center Network Infrastructure The Smart Choice For Your Data Center

Documenting and Managing Infrastructure Connectivity

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

Design Guide. Universal Connectivity Grid. SYSTIMAX Solutions from CommScope

Specifications for Communication Cabling Distribution Systems

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

Designing A Communications Cabling System for the Colocation Data Center Larry Smith President, ABR Consulting Group, Inc.

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)

Telecommunications Systems Narrative Page 1 The Engineering Enterprise

Cabling and Building Infrastructure for Technology

Gigabit Passive Optical Networks

Transcription:

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers standards committee 2005 J&M Consultants, Inc.

Purpose of the Standard Encourage early participation of telecom designers and information technology professionals in the data center design process A data center that is intelligently designed to accommodate the needs of the equipment and technologies it is meant to house need not be more expensive than one that is not, but it will certainly be more usable.

Purpose of the Standard Fill a void by providing nationally recognized standards for the planning of data centers. Provide information for a data center owners to understand data center design tradeoffs and to communicate design requirements to engineers and architects

Purpose of the Standard Define a standard telecommunications infrastructure for data centers Structured cabling system for data centers using standardized architecture and media Accommodates a wide range of applications (LAN, WAN, SAN, channels, consoles) Accommodates current and known future protocols (10 Gigabit Ethernet & 10 Gigabit Fibre Channel) Replaces unstructured point-to to-point cabling that uses different cabling for different applications

Purpose of the Standard Specify data center telecommunications pathways and spaces Establish a standard for data center tiers to replace several proprietary standards. The TIA data center tier standard is: A tool to evaluate existing data centers A tool to communicate design requirements

Who Developed the Standard The standard was developed by the TIA TR-42.1.1 Network Distribution Nodes subcommittee as Project No. 3-00923 (co-chairs chairs Jonathan Jew & Chris DiMinico) Participants included: Architecture & Engineering Firms Consultants End Users Cabling and Equipment Manufacturers Was approved for publication on Feb 3, 2005 Available now www.tiaonline.org

Coordination with Other Data Center Standards Review and Liaison with data center industry organizations The Uptime Institute and 7x24 Exchange ASHRAE Thermal Guidelines for Data Processing Environments (2004) IEEE 1100 Revision 2 Recommended Practice for Powering and Grounding Electronic Equipment (2005) CENELEC EN 50173-5 5 Information Technology Generic Cabling Systems Part 5: Data Centres (2006) ISO/IEC new project (2007?) BICSI Data Center Design and Implementation Best Practices (2006) Jonathan Jew & John Kacperski co-chairs chairs

Relationship of Spaces BUILDING SITE BUILDING SHELL GENERAL OFFICE SPACE TELECOM ROOMS & EQUIPMENT ROOMS for spaces outside data center OFFICE BUILDING SUPPORT SPACE DATA CENTER SUPPORT STAFF OFFICES ENTRANCE ROOM(S) DATA CENTER ELECTRICAL & MECHANICAL ROOMS OPERATIONS CENTER TELECOM ROOM(S) for data center support spaces STORAGE ROOMS & LOADING DOCKS COMPUTER ROOM

Data Center Telecommunications Spaces Offices, Operations Center, Support Rooms Telecom Room (Office & Operations Center LAN switches) Horiz Dist Area (LAN/SAN/KVM Switches ) Zone Dist Area Carriers Entrance Room (Carrier Equip & Demarcation) Main Dist Area (Routers, Backbone LAN/SAN Switches, PBX, M13 Muxes) Horiz Dist Area (LAN/SAN/KVM Switches ) Carriers Computer Room Optional Backbone Cabling Horiz Dist Area (LAN/SAN/KVM Switches ) Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet)

TIA-942 Spaces Entrance Room (ER) - location of interface with campus and carrier entrance facilities Main Distribution Area (MDA) location of main cross-connect connect (MC) Horizontal Distribution Area (HDA) location of horizontal cross-connect connect (HC) Zone Distribution Area (ZDA) location of zone outlet (ZO) or consolidation point (CP) Equipment Distribution Area (EDA) location of equipment cabinets and racks

Unstructured Cabling Systems Carrier Entrance Systems Systems Systems MDF/Core Systems Systems Systems Systems Systems

Collapsed Topology Carriers Carriers Offices, Operations Center, Support Rooms Main Dist Area (Carrier Equip, Demarcation, Routers, Backbone LAN/SAN/ KVM Switches, PBX, M13 Muxes) Computer Room Zone Dist Area Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet)

Distributed Topology with Multiple ERs Offices, Operations Center, Support Rooms Carriers Primary Entrance Room (Carrier Equip & Demarcation) Carriers Carriers Carriers Telecom Room (Office & Operations Center LAN switches) Main Dist Area (Routers, Backbone LAN/SAN Switches, PBX, M13 Muxes) Secondary Entrance Room (Carrier Equip & Demarcation) Horiz Dist Area (LAN/SAN/KVM Switches ) Computer Room Zone Dist Area Horiz Dist Area (LAN/SAN/KVM Switches ) Horiz Dist Area (LAN/SAN/KVM Switches ) Horiz Dist Area (LAN/SAN/KVM Switches ) Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet)

Redundant Topologies Carriers Carriers Carriers Carriers Primary Customer Maintenance Hole (Tier 1 and higher) Secondary Customer Maintenance Hole (Tier 2 and higher) Data Center Tier 1 Tier 3 Tier 2 Tier 3 Primary Entrance Room (Tier 1 and higher) Tier 3 Secondary Entrance Room (Tier 3 and higher) Offices, Operations Center, Support Rooms Tier 1 Tier 4 Tier 3 Tier 4 Telecom Room Main Dist Area (Tier 1 and higher) Tier 4 Secondary Dist Area (Optional for Tier 4) Computer Room Horiz Dist Area Optional Cabling Zone Dist Area Horiz Dist Area Horiz Dist Area Equip Dist Area Equip Dist Area Equip Dist Area

Data Center Cable Types Single-mode fiber (SONET/SDH, MAN, LAN) Multimode fiber (MAN, LAN, SAN) 850-nm laser optimized 50/125 recommended 734-type coax (E-1/E 1/E-3/DS-3) 3) two per circuit 20 AWG solid conductor, 75-ohms Use 75-ohm BNC connectors and panels.

Data Center Cable Types Category 6 or Augmented Category 6 UTP - E-1, T1 & lower speed circuits, voice, MAN, LAN, KVM, console Category 3 UTP low speed circuits Proprietary IBM Parallel Channel & other (outside scope of TIA-942) Mainframe terminals, consoles, ESCON & FICON can be accommodated by structured cabling system but are outside scope of standard TIA 232, V.35, SCSI, other (outside scope of TIA- 942)

Carrier Circuit Lengths in Data Centers Cat 3 instead of Cat 5e or Cat 6 reduces circuit lengths for T-1s T and E-1s E significantly 735 coax (mini-coax) instead of 734 coax reduces circuit lengths for T-3s, T E-1s, E and E-E 3s significantly Circuit length restrictions may : require additional entrance rooms, limit the location of telecom equipment, limit the size of the computer room

Carrier Circuit Lengths in Data Centers Maximum cable lengths for common circuits: E-1 s s over 24 AWG Cat 5/5e/6 UTP: 517 ft (158 m) - 6.4 ft (2 m) per patch panel T-1 s s over 24 AWG Cat 5/5e/6 UTP: 677 ft (206 m) - 6.4 ft (2 m) per patch panel E-3 s s over 734 coax: 574 ft (175m) 17.5 ft (5.3 m) per patch panel T-3 s s over 734 coax: 524 ft (160m) 15.3 ft (4.7 m) per patch panel Distances are from carrier demarcation point to end equipment and assume no customer DSX.

Computer Room Requirements Min clear height of 2.6m/8.5 ft Min door size 1m/3ft wide 2.13/7ft high Min dist floor loading 7.2 kpa/150lbf/ft 2, recommended min 12 kpa/250 lbf/ft 2 20 o C to 25 o C 40% to 55% relative humidity (reduces ESD) Any sprinkler systems must be pre-action system Common bonding network (CBN) equipotential ground reference Bond all cabinets and racks individually to CBN Bond cable trays, conduits, HVAC units, building columns, PDUs, panel boards, raised floor (every 6 th pedestal) to CBN

Entrance Room Demarcation to carriers Telecom Entrance & Campus Conduits Carrier Racks Coordinate power and space requirements with each carrier Provide either AC or DC power to carriers. If ER only has AC power, carriers install DC power from rectifiers to their racks & cabinets Plywood for protectors Not required if no copper entrance cables or if carrier will install protectors on frames or racks

Entrance Room ER may be inside data center but, location outside data center provides best security ER may be consolidated with MDA ER requires the same redundancy for power and cooling as the computer room space Locate ER to avoid exceeding maximum cable lengths for circuits Cabling distances for carrier circuits may dictate multiple ERs in large data centers

Main Distribution Area Location of Main Cross-Connect Connect (MC), the central point of distribution for data center structured cabling system Centrally located to avoid exceeding maximum distance restrictions (typically for E-1s, E-3s, E T-1s T and T-3s) T Install separate racks for Fiber, UTP, and coaxial cable distribution

Horizontal Distribution Area Location of Horizontal Cross-Connect Connect (HC), the distribution point for cabling to equipment distribution area Distribution LAN, SAN, KVM switches and console servers located in HDA MDA may also include an HC for nearby equipment distribution area Number of HDAs depends on the density of cabling and the size of the data center The capacity of the cable tray system and the size of the cross-connect connect limit the size of the HC

Zone Distribution Area Rack, cabinet, or under floor enclosure that houses a zone outlet (ZO) or consolidation point (CP) ZO - structured cabling termination for floor- standing equipment that cannot accept patch panels (e.g. mainframes and large servers) CP - intermediate termination point (e.g. cabling to areas where floor plan is uncertain or dynamic) No active equipment shall be located in the ZDA Maximum of 288 connections in a ZDA Maximum of one ZDA within a horizontal cable run

HOT AND COLD EQUIPMENT AISLES HOT AIR REAR FRONT FRONT REAR HOT AIR REAR FRONT CABINETS COLD CABINETS CABINETS AIR COLD AIR PREFORATED TILES PREFORATED TILES TELECOM CABLE TRAYS POWER CABLES TELECOM CABLE TRAYS POWER CABLES

Equipment Racks & Cabinets Equipment is mounted in racks & cabinets from the front provide adequate clearance for installation of equipment (minimum of 3 feet, 4 feet is recommended). Cabinets and racks should be aligned with one edge along the edge of the floor tile. Arrange cabinets and racks on raised floor to permit tiles along the front and rear of the cabinets and racks to be lifted Floor tile cuts should be no larger than necessary to minimize air pressure loss.

Equipment Cabinets Front rails of cabinets must be recessed to provide adequate room for patch cables and wire managers Adequate space for cable management Arrange switches and patch panels to minimize patching between cabinets & racks Perforated tiles at front of cabinets One edge of cabinets placed at edge of tile

Raised Floor More flexible cooling with raised floor than ducted air Most stand-alone alone computer systems are designed for cabling from below Coordinate under floor cabling with mechanical & electrical engineers Recommend wire basket cable trays in hot aisles for telecom cabling

Example of Wire Basket Cable Trays For Cabling Under Raised Floor 24" RAISED FLOOR TILE 1.375" 9" 4" DIVIDER 18" 5" COPPER FIBER CABLING SUPPORT STRUT 1" 36" 12" 4" 5" FIBER 18" COPPER CABLING SUPPORT STRUT 1" Open Area 13.5" 24" On Center

Under Floor Example Color-coded PDU cables in hot aisles each cabinet fed from 2 PDUs Locking electrical receptacles NEMA L5-20R Signal Reference Grid (SRG) using bare copper conductor Each cabinet bonded to SRG

Overhead Cable Trays Less expensive than raised floor systems Cable trays can be attached to the top of racks and cabinets (if they are uniform in height) Cable trays suspended from the ceiling provide more flexibility for supporting cabinets/racks of various heights and for adding and removing cabinets/racks. Cable trays can be installed with several layers Coordinate location with lighting, ducts, overhead conduits, overhead power distribution

Overhead Cable Tray Example 3 Layer cable tray system: Bottom layer copper Middle layer fiber Top layer power Signal Reference Grid in brackets attached to lower layer of trays Fiber patch cables may be in fiber duct attached to threaded rods

Facilities Specifications & Tiers Informative annex with general architectural, structural, electrical, mechanical, and telecommunications recommendations Annex includes detailed architectural, security, electrical, mechanical, and telecommunications recommendations for each Tier (expands on The Uptime Institute Tiers) Recommended specifications by tier are a uniform way to rate aspects of a data center design and are a starting point for initiating design requirements with qualified architects and engineers.

Future Work Additional revisions to electrical sections for harmonization with IEEE 1100 draft 2 High heat density issues Augmented Category 6 UTP 10 Gigabit Ethernet over UTP (10GBase-T) 10GBase-T T over standard Cat 6 (up to 55 meters) with mitigation: Unbundle and randomize cables in the first 5 to 20 meters Unbundle and randomize patch cords Eliminate intermediate patch panels between horizontal cable patch panels and switches Use non-adjacent Cat 6 UTP ports for 10GBase-T Use Aug Cat 6 or shielded patch cords Longer patch cords Separate long and short cable runs

Conclusion TIA-942 is the first standard that specifically addresses data center infrastructure. Primarily a telecom infrastructure standard, but about half of the content deals with facility requirements. Provides a flexible and manageable structured cabling system using standard media. Guidelines on a wide range of subjects useful to someone designing or managing a data center. An official tiering standard for evaluating data centers. A way to objectively compare one center with another. Standard is available at www.tiaonline.org