GroundRod AC Substation Earthing Tutorial



Similar documents
EARTHING AND BONDING AT SECONDARY SUBSTATIONS

Earthing Guidance Notes

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

Substation Grounding Study Specification

Introduction to Data Centre Design

EARTHING SYSTEM CALCULATION

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

Technical Guidance Note 287. Third-party guidance for working near National Grid Electricity Transmission equipment

TABLE OF CONTENT

Fault location on power cables. Fault location on power cables

DESIGN OF EARTHING SYSTEM FOR HV/EHV AC SUBSTATION

Lightning Protection Introduction

Hyperlinks are Inactive

Earth Ground Resistance

Complete Solar Photovoltaics Steven Magee. Health and Safety

12 Appendix 12 Earth Electrodes And Earth Electrode

Strength and Durability for Life CORROSION CONTROL. The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines

Gulf Cable & Electrical Ind. Co.

Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.

SOIL RESISTIVITY MEASUREMENTS

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

1. Franklin Rod Performance 2. LEC/DAS Performance

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

NEW ZEALAND ELECTRICAL CODE OF PRACTICE. for ELECTRICAL SAFE DISTANCES

Comparative study for cables and busbars

environment briefing02

FEASIBILITY OF ELECTRICAL SEPARATION OF PROXIMATE GROUNDING SYSTEMS AS A FUNCTION OF SOIL STRUCTURE

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ScottishPower Distribution Cables & Equipment. Metal Theft

SES Training & Certification Programs Welcome to the SES Grounding, EMI and Lightning Academy

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

Grounding Demystified

Code of Practice Electricity transmission and distribution asset management. February 2009

Screened cable and data cable segregation

High Voltage. Hazards

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

A series of technology briefs spanning Tyco Electronics product portfolio

AS COMPETITION PAPER 2007 SOLUTIONS

Modeling of Transmission Lines

Consultants Handbook

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

FIREFIGHTER SAFETY. Stay safe during substation fires

Advanced Fencing and Security Technologies Ltd

BUILDING OVER OR NEAR WATER & SEWER MAINS POLICY

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

Specifications for Lightning Protection. ASAE Engineering Practice

WORKING IN THE ELECTRIFIED AREA

Work in Substations - General

THE LIGHTNING PROTECTION INTERNATIONAL STANDARD

Section B: Electricity

Unified requirements for systems with voltages above 1 kv up to 15 kv

Cable Size Selection for Energy Efficiency

Current Ratings. TABLE BEC 107. (Continued) Current ratings for 6350/11000 volts grade PILC/SWA/PVC cable to BS6480/69

How Much Voltage Drop Is Acceptable?

Guide to Gate Safety Legislation & the Machinery Directive. In Association with:

EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS

Session 14 Cable Support Systems

High-voltage systems. Identifying high-voltage overhead conductors

FIXED CHARGE: This is a cost that goes towards making the service available, including

CURRENT RATINGS MORE THAN A CABLE

WHITE PAPER Fire & safety performance standards

Regulation IO-6.0: Electrical Safety Regulations

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

Fundamentals of Power

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas

AMSC s Superconductor Cable Technologies for Electric Utilities

Mark Coles BEng (Hons) MIEE

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Arc Flash Energy Mitigation Techniques

GM QUARTERLY GreyMatters Newsletter March 2014

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

Offshore Wind Farm Export Cable Current Rating Optimisation

Understanding Arc Flash

Beware of Simplistic Voltage Drop Calculations. By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards

Grounding & Bonding Why it is done And How to Install Properly

Chapter 9. Bonding and Grounding

Voltage Detection and Indication by Electric Field Measurement

HV Submarine Cable Systems Design, Testing and Installation

Transmission Business Electrical Incident & Safety Performance Reporting Guide

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

Coupling Effect in Substation Ground Measurements

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

Electrical Safety Tips. Help us keep you safe

Handbook 16. Handbook 16. AC electrified lines. GE/RT8000/HB16 Rule Book

Cables, Cable Laying & Accessories Manual

Electrical Resistance Resistance (R)

PRODUCT / APPLICATION INFORMATION

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

INTERNATIONAL STANDARD

Cable Tray Selection-

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

Transcription:

1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities during a fault is not exposed to the possibility of a fatal electric shock. To provide a low impedance path to earth for currents occurring under normal and fault conditions. 2. Earthing standards There are a variety of national and international standards available, which provide empirical formulae for the calculation of earthing design parameters and shock potential safety limits. There is some variation in formulae between the different standards. Three standards, which are widely referred to, are: BS 7354-1990: Code of practice for Design of high-voltage open-terminal stations. IEEE Std 80-2000: IEEE Guide for Safety in AC Substation Grounding. Electricity Association Technical Specification 41-24: Guidelines for the Design, Installation, Testing and Maintenance of Main Earthing Systems in Substations.

2 3. Ground potential rise (GPR) The substation earth grid is used as an electrical connection to earth at zero potential reference. This connection, however, is not ideal due to the resistivity of the soil within which the earth grid is buried. During typical earth fault conditions, the flow of current via the grid to earth will therefore result in the grid rising in potential relative to remote earth to which other system neutrals are also connected. This produces potential gradients within and around the substation ground area as depicted in Figure 1. This is defined as ground potential rise or GPR. The GPR of a substation under earth fault conditions must be limited so that step and touch potential limits are not exceeded, and is controlled by keeping the earthing grid resistance as low as possible. 4. Step, touch, mesh and transferred potentials In order to ensure the safety of people at a substation, it is necessary to ensure that step and touch potentials in and around the yard during earth-fault conditions are kept below set limits. These maximum permitted step and touch potentials are addressed within various national and international standards. An illustration of step, touch, mesh and transferred potentials is provided in Figure 1. 4.1 Step potential The step potential is defined as the potential difference between a person s outstretched feet, normally 1 metre apart, without the person touching any earthed structure. 4.2 Touch potential The touch potential is defined as the potential difference between a person s outstretched hand, touching an earthed structure, and his foot. A person s maximum reach is normally assumed to be 1 metre. 4.3 Mesh potential The mesh potential is defined as the potential difference between the centre of an earthing grid mesh and a structure earthed to the buried grid conductors. This is effectively a worst-case touch potential. For a grid consisting of equal size meshes, it is the meshes at the corner of the grid that will have the highest mesh potential. 4.4 Transferred potential This is a special case of a touch potential in which a voltage is transferred into or out of a substation for some distance by means of an earth referenced metallic conductor. This can be a very high touch potential as, during fault conditions, the resulting potential to ground may equal the full GPR.

3 Figure 1: Basic shock situations 4.5 Maximum permitted step and touch potentials The maximum permitted values of step and touch potentials vary widely between the different standards. The value of maximum permitted touch potential has a dominant role in determining the design of the earthing grid. As a general rule, if an earthing grid design satisfies the requirements for safe touch potentials, it is very unlikely that the maximum permitted step potential will be exceeded. The IEEE 80 standard uses the maximum mesh voltage as the touch voltage, and this usually exists at the corner mesh. UK practice defines the touch voltage differently. In practice the voltage at the surface of the ground is a maximum adjacent to a corner of a grid. UK practice is to define touch voltage as the sum of the step voltage plus the voltage difference between the ground surface adjacent to a corner and the grid beneath. Although the mesh voltage is used as the defining touch voltage in American practice, the maximum permitted touch voltage used is less than that used in British Standards. In practice, compliance with American usage thus also ensures the arrangement will comply with UK requirements. CENELEC have issued a harmonisation document HD 637 S1 containing references to the maximum body impedance and permitted touch voltage. 5. Soil resistivity In order to calculate the GPR, the grid resistance firstly needs to be calculated. To do this, the resistivity of the soil at site needs to be determined. This should ideally be obtained via site measurements but if not possible can be determined from soil resistivity maps or tables available in the standards. The Wenner test method is commonly used for site measurements.

4 The soil resistivity can vary quite widely over a site and it is thus important that the measurements are taken at several points in the site area. The average site value is thus calculated. Due to the difference in resistivity with depth, two or more layer resistivity models are normally determined. 6. Design considerations 6.1 Conductors A substation earthing grid will consist of a system of bonded cross conductors. The earthing conductors, composing the grid and connections to all equipment and structures, must possess sufficient thermal capacity to pass the highest fault current for the required time. Also, the earthing conductors must have sufficient mechanical strength and corrosion resistance. It is normal practice to bury horizontal earthing conductors at a depth of between 0.5m and 1m. This ensures that the conductor has the following properties: Adequate mechanical protection. It is situated below the frost line. The surrounding earth will not dry out. 6.2 Vertically driven rods Where there are low resistivity strata beneath the surface layer then it would be advantageous to drive vertical rods down into this layer. To be effective the vertical rods should be on the periphery of the site. The length of rod is chosen so as to reach the more stable layers of ground below. The rods would stabilise the grid resistance over seasonal resistivity changes at the grid burial depth. 6.3 Substation fences The earthing of metallic fences around a substation is of vital importance because dangerous touch potentials can be involved and the fence is often accessible to the general public. Fence earthing can be accomplished in two different ways: Electrically connecting the fence to the earth grid, locating it within the grid area or alternatively just outside. Independently earthing the fence and locating it outside the grid area at a convenient place where the potential gradient from the grid edge is acceptably low. In America, the common practice is to extend the grid sides to 1 metre beyond the fence line. The common practice in the UK is to erect the fence away from the grid sides, typically 2 metres, and to earth the fence independently. This will, however, present a problem should the fence inadvertently be connected to substation equipment, and hence the earthing grid. 6.4 Other earthing The GPR at a substation is reduced by: Overhead line earth wires which are connected to the substation earthing grid. This diverts part of the earth fault current to the tower footing earthing.

5 Cables entering and leaving the site. The armouring of such cables is usually earthed to the substation earthing grid at both ends. Part of the earth fault current will thus be diverted to a remote earthing grid via the cable armouring. 7. Earthing design calculations Performing earthing design calculations, using one of the standards above, is an involved and time consuming process and there are various subtleties which need to be considered. The GroundRod spreadsheet provides an easy-to-use, fast and accurate means to perform these calculations. The program can perform the calculations in accordance with any of the three above standards. 8. Hot Zone In order to protect telecommunications staff, equipment and users, the International Telecommunication Union (ITU) has provided recommended limits for acceptable GPR in MV and HV networks. These limits have traditionally been used in the electrical industry as 430V for circuits with a fault clearance time of 200ms and 650V for fault clearance times normally less than 200ms (high reliability circuits). In addition, if the GPR exceeds these limits then the 650V or 430V surface potential contour extending into the ground surrounding the grid needs to be specified and is termed the Hot Zone (measured from the edge of the grid). The relevant telecommunications company needs to be notified when these limits are exceeded and what the extent of the Hot Zone is. The GroundRod program provides both these distances and advises that the latter is best practice. For further information on GroundRod please contact: Mr Richard Simmonds Cobham Technical Services ERA Technology Ltd. Cleeve Road Leatherhead Surrey KT22 7SA UK Tel + 44 (0) 1372 367073 richard.simmonds@cobham.com www.cobham.com/technicalservices ERACS Software Cobham Technical Services has also combined world-class electrical engineering experience with leading-edge computer technologies to produce ERACS, the new generation of power systems analysis software. The fully integrated suite features loadflow, fault, harmonics, protection coordination, arc flash and transient stability modules together with an intuitive graphical user interface, universal dynamic modeller and equipment data library. For further information on ERACS please visit www.era.co.uk/eracs