Fire detection equipment



Similar documents
Analogue addressable devices

conventional system operation

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19

MINERVA MX MX Virtual Multi-Sensor Detectors

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

AlarmSense 2-wire detection and alarm system. Product Guide

Advanced Intelligent Modules. Overview. Description

HART HSSD High Sensitivity Smoke Detection

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

Fire Detection Systems

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

welcome to our world fire alarm systems - series 600

Fire Detection Product Range

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

FIREDEX Conventional Fire Panels

Triple Waveband Infra-Red Flame Detection

D287/D288/D292/D293A/D293E

The supplier and installer of the system should be approved by the local civil defence authority.

Fire. The Fire Installers Mate. A guide to fire alarm systems design

XP95 ENGINEERING PRODUCT GUIDE

SECTION FIRE ALARM AND DETECTION SYSTEMS

CB Zone Conventional Control Panel

25 Years of Manufacturing Excellence. Premier Quatro Addressable Fire Alarm System. Assessed to ISO 9001: 2008

Module 5. Fire and Emergency Alarm System Part I- Basics

THE OPTIMUM IN FIRE DETECTION

Smoke Detectors Ordering Information DS230 DS230 Series Heat Detectors DS230F DS233F Peripheral Accessories EOL200 TP280 Bases Features

Discovery 1-4 Loop Analogue Addressable Control Panel Application Guide

25 Years of Manufacturing Excellence INFINITY. The Intelligent 2 Wire Fire Detection System for Professionals

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems

Fire Alarm system Installation Guide

BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEM EURO ALARM WIRELESS BURGLAR ALARM SYSTEM OASIS

SERIES 65 ENGINEERING PRODUCT GUIDE

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

Premier M Plus & Infinity 8

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

Fire & Security DETECTORS

Carbon Monoxide (CO) Detection PRODUCTS. Accessories Conventional Detectors

Using your LED Plus keypad

Consultant s Guide for Fire Detection & Alarm Systems for Buildings

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Conventional Fire Detection and Extinguishant Control System Specification

FIRE DETECTION AND ALARM SYSTEMS

C E R T I F I C AT I O N LPCB B O A R D P R E V E N T L O S S. Cooper Fire Systems

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings

SECTION DETECTION AND ALARM

PowerCode Wireless. Fully supervised wireless system. Features

Application Guide HMOs

VEGA Analogue Addressable Control Panels

FSD Circular Letter No. 7/95 Automatic Fire Detection System - Design and Maintenance Considerations

SMART SENSOR COLLECTION

E-PDD Duct Smoke Detector Installation Sheet

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

PLAN REVIEW GUIDE FOR FIRE ALARM

FIRE ALARM SYSTEM. reliable fire detection and alarm signalling system

BS5839 Part 1:2002 Overview

(68.52) X. June 2000 Supercedes February xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we business differently

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE

NJP-400A NJP-401A. Safely into a new day. Advanced modular FIRE ALARM CONTROL PANEL with additional functionality. I m on FIRE (Bruce Springsteen)

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

OPAL TM Detector range

DBS720 / FDS221-R / FDS221-W Sounder base, Alarm sounders

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

Overview of Fire Alarm Systems and Maintenance

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

FAST, INTELLIGENT FIRE ALARM SYSTEMS THAT DELIVER IT ALL

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

Fire alarm system EBL512 G3

Overview. Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products

VR8. User Guide Intruder Alarm System

HERNANDO COUNTY FIRE ALARM GUIDELINES

Solution Ultima ICP-CC488 Home security you can rely on

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

nr 28 nr 68 nr 4 nr 1

EVALUATION OF THE PERFORMANCE OF FIRE DETECTION SYSTEM IN AN INSTITUTIONAL BUILDING

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

Global System Technology(UK) PLC The Intelligent Solution

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Quantec Wiring Instructions

SECTION ZONED (DC LOOP) FIREALARM SYSTEM

wireless alarm system reliable protection for small-size buildings

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

Consultant s Guide for Designing Fire Detection & Alarm Systems

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

Solution Ultima ICP-CC488 Home security you can rely on

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

SECURIT 800L+ CONTROL PANEL

Bold items are particular to the City of Euless

FIRE ALARM SYSTEM RECORD OF COMPLETION

Beam Detection Systems Application Guide

P/N Rev D

EQUIPMENT SPECIFICATIONS

SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS

LIFT CONTROL SYSTEMS CATALOGUE 2007

Transcription:

PRODUCT CATALOG Fire detection equipment www.apollo-fire.com

Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980, Apollo has been supplying fire detection products to system providers in the USA since 1980. Apollo detectors are installed in such landmark buildings as the Statue of Liberty and the Staples Center in Los Angeles. Apollo has established a research and development facility in Louisville, Kentucky in order to support the development of products that comply with the requirements of and with current best practice in the US. Apollo detectors and modules are available through fire detection system providers. For more information call us on 502 964 6565. Apollo has developed ranges of detectors for the American market and those markets which require classification. Apollo has carefully researched and developed the ranges to ensure that they meet not only the and other standards but also the demands of today s high technology environments. Coming in 2010 Loop-powered Sounders 115V Mains Switching Input/Output Unit Addressable Pull Station Information in this catalogue is given in good faith, but Apollo Fire Detectors cannot be held responsible for any omissions or errors. The company reserves the right to change specifications of products at any time without prior notice.

XP95A 3 The XP95A range of analog addressable fire detectors is advanced in design and performance and offers unique features that benefit both the installer and the end user. XP95A The range is based on Apollo s XP95 range. XP95A has a central intelligence system where all the decisions are made by the control panel. Each detector is addressed using Apollo s patented XPERT card, supplied with the mounting bases. The XP95A range includes an ionization detector, a photo-electric detector, a heat detector, a multisensor, an isolator and a series of modules. Key features of XP95A include: XPERT card addressing Analog value report Address confirmation Alarm flag Unobtrusive design Error check

4 XP95A XP95A Ionization Smoke Detector The XP95A Ionization Detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm. Responds well to fast-burning, flaming fires Designed to operate in a variety of environments Minimal effects from temperature, humidity, atmospheric pressure XP95A Ionization Smoke Detector 55000-550 XP95A Ionization Smoke Detector (C) 55000-555 xp95a Photo-Electric Smoke Detector The XP95A Photo-Electric Smoke Detector works on the light-scatter principle and is ideal for applications where slow-burning or smouldering fires are likely. Responds well to slow-burning, smouldering fires Well suited for bedrooms and escape routes Unaffected by atmospheric pressure xp95a Photo-Electric Smoke Detector 55000-650 xp95a heat Detector The XP95A Heat Detector monitors temperature by using a single thermistor network which provides a voltage output proportional to the external air temperature. It is classified as an Ordinary detector by. Ideal environments that are dirty or smoky under normal conditions Well suited for warehouses, loading bays and car parks Unaffected by wind or atmospheric pressure xp95a heat Detector 55000-450 xp95a multisensor The XP95A Multisensor contains a photo-electric smoke sensor and a thermistor (temperature sensor) whose outputs are combined to give the final analog value. Sensitive to a wide range of fires Well suited for environments such as hotel bedrooms or warehouse loading bays Unaffected by wind or atmospheric pressure xp95a Multisensor 55000-886 Does not have C approval

XP95A 5 XP95A Loop Powered Beam Detector The XP95A Beam Detector is made up of three main parts: the transmitter, which projects a beam of infra-red light, the receiver, which registers the light and produces an electric signal, and the interface, which processes the signal and generates alarm or fault signals. XP95A Loop Powered Beam Detector 55000-266 Loop-powered Four selectable alarm levels Drift Compensation Remote interface Simple wiring and alignment Designed to protect large open spaces such as museums, churches and warehouses XP95A Low Power Relay Base The XP95A Low Power Relay Base incorporates a low power relay to control field equipment such as automatic door closers. Gives a set of voltage free contacts controlled by the remote output of a detector Draws negligible current XP95A Low Power Relay Base 4 45681-242 For information on XPERT cards, please see page 23. XP95A Mounting Base All detectors in the XP95A range fit the XP95A Mounting Base which is a low insertion force base with stainless steel contacts for the detector terminals. XPERT cards are supplied with all bases. XPERT addressing One way fit Locking feature to prevent unauthorised removal XP95A Mounting Base 4 XP95A Mounting Base 6 45681-210USA 45681-225USA E-Z Fit Base The E-Z fit base is a low profile 6 mounting base for XP95A detectors. High degree of protection against unauthorized removal E-Z Fit Base 45681-250

6 XP95A XP95A Isolating Base The XP95A Isolating Base senses and detects short circuit faults on XP95A loops and spurs. XP95A Isolating Base 45681-321USA Up to 20 devices may be installed between isolating bases XPERT addressing xp95a Isolator The XP95A Isolator is placed at intervals on the loop and ensures that, in the case of a short circuit, only the section between the isolators will be affected. When the short circuit is removed, the isolators automatically restore power and data to the isolated section. Detects wiring short-circuits using patented technology Minimises disruption from short-circuits Automatic de-isolation on short-circuit removal Up to 20 devices may be installed between isolators xp95a Isolator 55000-750 XP95A Isolator Base The XP95A Isolator Base is unique and designed to only accept the XP95A Isolator. Only accepts isolators XP95A isolator Base 45681-211USA XP95A Mini Priority Switch Monitor Module The XP95A Mini Priority Switch Monitor is designed to monitor the state of one or more single pole, volt free contacts and to report the status to Apollo compatible analog control equipment. It can also place a signal on the loop to provide early warning if a device such as a pull station is operated. Three input states - normal, fault and alarm Visible LED with remote LED connection option Loop powered Designed to fit into equipment with limited space Easy to install Monitors equipment where a fast response is required Interrupt facility XP95A Mini Priority Switch 55000-830 Monitor Module

XP95A 7 XP95A Mini Switch Monitor Module The XP95A Mini Switch Monitor Module is designed to monitor the state of one or more single pole, volt free contacts and to report the status to Apollo compatible analog control equipment. Three input states - normal, fault, and alarm Visible LED with remote LED connection option Loop powered Designed to fit into equipment with limited space Easy to install XP95A Mini Switch Monitor Module 55000-831 Mini Monitor Module The Mini Monitor Module is an interface within an entirely new housing. This allows the unit to be fitted onto a standard 35mm DIN-rail (using a twist-click motion) or mounted within an enclosure, for example a manual call point. It is designed to monitor the state of one or more single pole, volt free contacts connected on a single pair of cables and to report the status to Apollo compatible analogue control equipment. Designed for use where space is limited Interrupt/non interrupt in one unit Pre-alarm status available Three, colored LEDs, giving clearer status indication Mini Monitor Module 55000-765 xp95a Switch Monitor Module The XP95A Switch Monitor Module is designed to monitor the state of one or more single pole, volt free contacts connected and to report the status to Apollo compatible analog control equipment. Three input states - normal, fault, and alarm Visible LED Loop powered XP95A Switch Monitor Module 55000-805 xp95a Priority Switch Monitor Module The XP95A Priority Switch Monitor Module is designed to monitor the state of one or more single pole, volt free contacts and to report the status to Apollo compatible analog control equipment. It can also place a signal on the loop to provide early warning if a device such as a pull station is operated. Three input states - normal, fault, and alarm Two visible LEDs Loop powered Fast response time Interrupt facility XP95A Priority Switch Monitor 55000-806 Module

8 XP95A Dual Priority Switch Monitor Module The XP95A Dual Priority Switch Monitor Module contains two priority switch monitor modules (55000-806) on a single plate. Loop powered Fast response time Interrupt facility XP95A Dual Priority Switch Monitor 55000-790 Module xp95a Switch Monitor Input/Output Module The XP95A Switch Monitor Input/Output Module provides a voltage free, single pole, change-over relay output, a single, monitored switch input and unmonitored, non-polarized opto-coupled input. It can report fault, switch open and switch closed levels Visible LED Loop powered xp95a switch Monitor 55000-820 Input/Output Module xp95a sounder Control Module The XP95A Sounder Control Module monitors and controls the operation of a zone of conventional sounders and reports their status to the control panel. xp95a sounder Control Module 55000-825 Allows sounders to be operated continuously or be pulsed, 1 second on, 1 second off May be synchronized when in pulsed operation Can also be used for public address speakers XP95a relay Output Module The XP95A Relay Output Module provides a single 2-pole changeover relay. Loop powered Can be placed anywhere on loop XP95a relay Output Module 55000-863 All XP95 modules can be installed in both XP95A and Discovery systems.

9 Series 65A is a range of conventional fire detectors available in three versions: Standard Flashing LED Flashing LED and magnet operated test switch Series 65A

10 Series 65A Series 65A Ionization Smoke Detector The Series 65A Ionization Smoke Detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm. Series 65A Ionization Smoke Detector - Standard 55000-227 Series 65A Ionization Smoke Detector 55000-226 with flashing LED Series 65A Ionization Smoke Detector 55000-225 with flashing LED and magnetic test switch Responds well to fast burning, flaming fires Designed to operate in a variety of environments Wide operating voltage Flashing LED option Flashing LED and magnet operated test switch option Series 65A Photo-Electric Smoke Detector The Series 65A Photo-Electric Smoke Detector incorporates a pulsing LED located within the housing of the detector. The detector housing is identical to that of the Ionization Detector but has an indicator LED which is clear in quiescent state but produces red light in alarm. Series 65A Photo-Electric Detector - Standard 55000-327 Series 65A Photo-Electric Detector 55000-326 with flashing LED Series 65A Photo-Electric Detector 55000-325 with flashing LED and magnetic test switch Responds well to slow-burning, smouldering fires Well suited for bedrooms and escape routes Unaffected by wind or atmospheric pressure Wide operating voltage Flashing LED option Flashing LED and magnet operated test switch option Series 65A Heat Detector The Series 65A Heat Detector monitors temperature by using a dual thermistor network which provides a voltage output proportional to the external air temperature.there are nine heat detectors in the Series 65A range designed to suit a wide variety of operating conditions. Series 65A Heat Detector 135 F - Standard 55000-140 135 F - flashing LED 55000-139 135 F - flashing LED and magnetic 55000-138 test switch 170 F - Standard 55000-143 170 F - flashing LED 55000-142 170 F - flashing LED and magnetic 55000-141 test switch 200 F - Standard 55000-146 200 F - flashing LED 55000-145 200 F - flashing LED and magnetic 55000-144 test switch Can be used for applications where smoke detectors are unsuitable Ideal environments that are dirty or smoky under normal conditions Wide operating voltage Flashing LED option Flashing LED and magnet operated test switch option

Series 65A 11 Series 65A Standard Base The Series 65A Base has been designed to enable detectors to be fitted without the need of force particularly useful when fitting to suspended ceilings. All Series 65A bases have a one way only fit. Detector locking mechanism One way fit Easy to wire Contains a ground wire terminal Contains no electrical parts Series 65A Base 4 Series 65A Base 6 45681-200USA 48681-220USA Series 65A Standard Relay Base 4 The Standard Series 65A Relay Base provides one set of volt-free, changeover (form C) contacts that change state when the detector signals an alarm. Series 65A Standard Relay Base 4 45681-255 Detector locking mechanism One way fit Easy to wire Contains a ground wire terminal Series 65A Auxiliary Relay Base 4 The Series 65A Auxiliary Relay Base provides two sets of volt-free changeover contacts to facilitate the switching of a remote LED or other auxiliary device. Detector locking mechanism One way fit Easy to wire Contains a ground wire terminal Series 65A Auxiliary Relay Base 4 45681-256 Series 65A End-of-Line Relay Base The Series 65A End-of-Line (EOL) Relay Base is intended for use with 4-wire circuits and feature two sets of changeover contacts and a power supervision relay. Detector locking mechanism One way fit Easy to wire Contains a ground wire terminal Series 65A 12V End-of-Line Relay Base 4 45681-257 Series 65A 24V End-of-Line Relay Base 4 45681-258

12 SERIES 65A Series 65A Low Profile Base 6 A low profile mounting base for Series 65A detectors. Detector locking mechanism One way fit Easy to wire Contains a ground wire terminal Series 65A Low Profile Base 6 45681-232 Series 65A E-Z Fit Base 6 A low profile mounting base for Series 65A detectors. High degree of protection against unauthorized removal Series 65A E-Z Fit Base 6 45681-251

SERIES 65A 13 Discovery is a range of highspecification, intelligent fire detectors developed to meet the requirements of sophisticated systems while providing engineers with an additional dimension in fire protection capability. Discovery has a distributed intelligence system where decisions are made in the detector head as well as at the control panel. Drift compensation is also incorporated into the detector, allowing it to adapt to dirty or dusty environments, which reduces false alarms. Discovery Each detector in the Discovery range can operate in one of five response modes, which can be selected from the control panel. The response characteristics have been carefully set so that the detectors comply with the requirements of the relevant part of in all response modes. Mode One will give a higher sensitivity to fire than Mode five. Discovery gives you total reassurance in installations where adaptability to changing conditions and protection against unwanted alarms are paramount. Key features of Discovery include: Rejection of transient signals Flashing LED option Five response modes for ease of optimization to changing environments Drift compensation to ensure constant sensitivity Four bytes of non-volatile memory for user data Alarm flag for fast alarm reporting Conventional alarm facility during control panel processor fault 360 visibility in alarm Compatible with XP95A systems

14 DISCOVERY Discovery Ionization Smoke Detector The Ionization detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm. Responds well to fast-burning, flaming fires Designed to operate in a variety of environments Remote test feature Discovery Ionization Smoke 58000-550 Detector Discovery Photo-Electric Smoke Detector The Discovery Photo-Electric Smoke Detector works using the light scatter principle and is ideal for applications where slow-burning or smouldering fires are likely. Discovery Photo-Electric 58000-650 Smoke Detector Responds well to slow-burning, smouldering fires Well suited for bedrooms and escape routes Unaffected by wind or atmospheric pressure Remote test feature Discovery Heat Detector The Discovery Heat Detector, distinguishable by the low airflow resistant case, uses a single thermistor to sense the air temperature around the detector. Discovery Heat Detector 58000-450 Ideal environments that are dirty or smoky under normal conditions Well suited for warehouses, loading bays and car parks Unaffected by wind or atmospheric pressure Remote test feature Discovery Multisensor Detector The Discovery Multisensor Detector comprises optical smoke and thermistor temperature sensors whose outputs are combined to give the final analog value. As a result, the Multisensor is useful over a wide range of applications and is highly immune to false alarms. Ideal for wide range of applications Highly immune to false alarms Well suited for sensitive environments Unaffected by wind or atmospheric pressure Remote test feature Discovery Multisensor Detector 58000-750

DISCOVERY 15 XP95A Mounting Base All detectors in the Discovery range fit the XP95A Mounting Base. The Mounting Base is a low insertion force base with stainless steel contacts for the detector terminals. XPERT cards are supplied with all bases. XPERT addressing One way fit Locking feature to prevent unauthorised removal XP95A Mounting Base 4 XP95A Mounting Base 6 45681-210USA 45681-225USA E-Z Fit Base The E-Z Fit Base is a low profile 6 mounting base for Discovery detectors. High degree of protection against unauthorised removal E-Z Fit Base 45681-250 XP95A Isolating Base The XP95A Isolating Base senses and detects short circuit faults on Discovery loops and spurs. Up to 20 devices may be installed between isolating bases XP95A Isolating Base 45681-321USA xp95a Isolator The XP95A Isolator can be used on a Discovery loop and is placed at intervals on the loop and ensures that, in the case of a short circuit, only the section between the isolators will be affected. When the short circuit is removed, the isolators automatically restore power and data to the isolated section. Detects wiring short circuits using patented technology Minimises disruption from short-circuits Automatic de-isolation on short-circuit removal Up to 20 devices may be installed between isolators xp95a isolator 55000-750 xp95a Isolator Base The XP95A Isolator Base is unique and designed to only accept the XP95A isolator. However, both can be used with a Discovery system. Only accepts the XP95A Isolator xp95a isolator Base 45681-211USA

Apollo Fire Detectors Ltd 2007-2009 PP2390-A/2009/Issue 1