STANDARD FOR SECONDARY CONTAINMENT TESTING OF UNDERGROUND STORAGE TANK SYSTEMS I. INTRODUCTION



Similar documents
Spill Containment Device and Containment Sump Testing Protocols. Introduction

UST RULES CHANGES. Heather Peters, Environmental Specialist

Welcome UST Owners & Operators!!

Maryland Containment System Testing Protocol. The individual performing the inspection and testing as outlined in this protocol must be either:

Underground Storage Tank Operational Compliance Field Guide

Secondary Containment Testing Report Form

Recommended Fuel Piping Specification For UPP Piping, UL-971

Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems

Northern Region. Underground Storage Tank

September 2008 AFC (2) Page 1 of 5. Maximum Size and Aggregate Capacities of Aboveground Storage Tank Systems at Fuel Dispensing Stations

ALL UST SYSTEMS. MOTOR FUEL, USED OIL, BULK HEATING OIL STORAGE (Federal/State Regulated Systems)

Petroleum Storage Tank Compliance 101

DRAFT REVISED Musts For USTs DRAFT. Printed on Recycled Paper. Updated June 2015

Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil)

Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal)

PMMIC 2013 Inspection Findings. Brian Pottebaum Rounds & Associates/PMMIC

Secondary Containment & Spill Buckets Inspection, Testing, and Repair Solutions. Allen Porter May 28, 2015

The following definitions apply with regard to requirements specified in this document:

This page left intentionally blank

Healy Enhanced Vapor Recovery Troubleshooting Guide

UST Regulatory Compliance Inspection Training. State Water Resources Control Board Underground Storage Tank Program September 2004

MAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION

UST System Inspection Checklist

Brian Derge Tanknology Inc. February 26, 2015

District of Columbia Municipal Regulations UNDERGROUND STORAGE TANKS: GENERAL PROVISIONS 5500 COMPLIANCE WITH OTHER DISTRICT LAWS

NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM. New Jersey Fuel Dispensing Facilities Compliance Calendar

The following definitions apply with regard to requirements specified in this document:

Safety Manual Title: Spill Prevention & Response Review Date: 6/1/2014

Straight Talk On Tanks Leak Detection Methods For Petroleum Underground Storage Tanks And Piping

A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS

Waste Oil Collection / Storage

UPDATE ON MAINE'S UNDERGROUND TANK LAWS

ACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas

BODY OF KNOWLEDGE API TES TANK ENTRY SUPERVISOR

ABOVE-GROUND STORAGE TANKS

UST Site Inspection Guidance Document

Underground Storage Tanks

UDOT SPILL PREVENTION and RESPONSE PLAN for CONSTRUCTION SITES

Tanks: What's in store?

NOTIFICATION OF PERFORMANCE TESTING FOR GASOLINE DISPENSING FACILITIES (GDFs) NESHAP 40 CFR, Part 63, Subpart CCCCCC (Sections

Powered Industrial Truck Safety Program

SPILL PREVENTION AND RESPONSE PLAN TEMPLATE FOR BUSINESSES IN DAYTON S SOURCE WATER PROTECTION AREA

Secondary Containment Options for Aboveground and Underground Tanks. Wayne Geyer Steel Tank Institute

WORKING IN CONFINED SPACES GUIDELINES

FUELING AND FUEL STORAGE

Spill Control Prevention Plan (SCPP)

Spill Prevention, Control and Countermeasure Plan (SPCC) Program

Daily Inventory and. Statistical Inventory Analysis. Daily Inventory and Statistical Inventory Analysis (SIA) are inventory control

CHECKLIST FOR INSTALLING OR CONVERTING EQUIPMENT TO DISPENSE E15, E30 E85 AND OTHER BLENDS OF ETHANOL General Information:

Used Oil Guidance. Tank and Secondary Containment Requirements For Used Oil Processors

VEHICLE SERVICE FACILITIES. Best Management Practices

Spill Prevention, Control & Cleanup SC-11

PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT

CHAPTER PETROLEUM CONTACT WATER

SECTION IV - TESTS AND INSPECTIONS PART 1 - GENERAL Testing - General

ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS

Sample Hazard Communications Program for Spray Polyurethane Foam Applications

OIL POLLUTION PREVENTION REGULATIONS

Notes. Material 1. Appropriate Flammable Liquids

OIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS. Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040

4.7 HAZARDS AND HAZARDOUS MATERIALS

SAMPLE FRACTION MITIGATION CONTINGENCY PLAN FOR DIRECTIONAL DRILLING

BP WIND ENERGY POLICIES AND PROCEDURES

MPM. Customer Service Representative Training. Class C Fuel Spill Handling

AUTOMATIC TANK GAUGING SYSTEMS Achieving Compliance. John D. Sieger, Tanknology

Storage Tank Systems for Petroleum products and allied petroleum products regulations

CONFINED SPACE POLICY

APPENDIX O. Spill Prevention and Emergency Response Plan. G3 Terminal Vancouver Port Metro Vancouver Project Permit Application APPENDIX O

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

HAZARDOUS WASTE SATELLITE ACCUMULATION MANAGER RESPONSIBILITIES

1. Who is your current pollution carrier? Expiration Date: Premium: Retroactive Date:

History of the SPCC Rule

Morrison Bros. Co. General Product Specifications

Source Sampling Manual Volume II

The Fuel Storage Tank Regulations 2009

APPLICATION FOR DRY CLEANERS PROGRAM (THIS APPLICATION IS FOR A CLAIMS MADE POLICY)

Universal Installation and Maintenance Instructions 71CD-1212 Spill Containment Bucket

Grade Level Spill Containment Manholes

Recharge Procedure for Telemark TVP-2000 and TVP-3500

LNG Fuel Tank System LNG Tank overview

Steel Tank Institute AST Inspections. Dana Schmidt, PE STI/SPFA

Standards and best practice guidelines for vapour recovery at petrol service stations. Department of Environment, Climate Change and Water NSW

Leak free means a system where no gasoline is leaked while the system is

Extraction Oil and Gas, LLC. Diamond Valley Central Oil Terminal Waste Management Plan

Spill Clean-up. Flammable Liquids Liquids with flash points below 100 degrees Fahrenheit.

Figure 1 Plugged Dispenser Filter vs. new

Clean Water: Supply side potable water, not wastewater. Gray Water/Sewage: Wastewater originating from a drain (sink, toilet, urinal).

ABC CIRCUITS 10 Circuit Drive Circuit Town, IN SLUG CONTROL PLAN

STANDARD OPERATING PROCEDURE EMERGENCY EYEWASH AND SHOWER EQUIPMENT

Good Housekeeping Practices for DPW/Fleet Maintenance Facilities

Revised April (May) 2015

Fuel Storage Who to ask: tank farm owners/operators

Transcription:

SANTA FE SPRINGS DEPARTMENT OF FIRE-RESCUE Environmental Protection Division Certified Unified Program Agency 11300 Greenstone Ave, Santa Fe Springs, CA 90670 Phone (562) 944-9713 Fax (562) 941-1817 STANDARD FOR SECONDARY CONTAINMENT TESTING OF UNDERGROUND STORAGE TANK SYSTEMS I. INTRODUCTION A. Purpose: The purpose of this standard is to establish a consistent regulatory guide for secondary containment testing of underground storage tank systems containing hazardous substances. B. Scope: This standard applies to the testing of secondary containment for all underground tank systems containing hazardous substances. The testing shall be conducted using a test procedure that demonstrates that the system performs at least as well as it did upon installation. For example, if the secondary containment system was tested upon installation by using a test method that applied a pressure of 5 psig, then the periodic test pressure must be conducted using a method that tests the system at an equivalent pressure. These tests shall be performed in accordance with these standards. If there are no applicable manufacturer s guidelines, industry codes, or engineering standards, a test method approved by a state registered professional engineer shall be used. Any deviations from the this standard must be approved by the Santa Fe Springs Department of Fire Rescue (SFSFR). This standard is intended to consolidate different industry testing protocols into one standard. Code References: Section 2637 California Code of Standards, Title 23, Division 3, Chapter 16. C. Authority: California Health and Safety Code, Chapter 6.7, Section 25299.2 II. RESPONSIBILITY A. Individuals, Companies and Corporations with underground tanks regulated by the SFSFR shall be responsible for compliance with this standard. B. Plan approval must be obtained prior to testing the secondary containment of an underground storage tank system. The SFSFR will issue an approval letter once the plan is reviewed and approved. C. Notification to the SFSFR of secondary containment testing is required 48 hours in advance. D. The California Health and Safety Code require that such tanks, which are installed, must have the secondary containment system and spill container tested six months after installation (for tank systems installed after January 1, 2001), then every three years thereafter. Tanks installed before January 1, 2001 must be tested by December 31, 2002 on April 3, 2002 and modified by the Santa Fe Springs Fire Department on July 29, 2009 1

and every three years thereafter. Spill containers must be tested annually for all UST systems. III. POLICY Before the secondary containment for an underground storage tank system, as defined in California Health and Safety Code, Chapter 6.7 can be tested, the party responsible for the tank must submit a testing protocol for approval. A site safety plan must be prepared and available on site. The party must demonstrate how the regulated tank and appurtenances will be tested in compliance with the Uniform Fire Code, California Health and Safety Code, Chapter 6.7, California Code of Standards (CCR) Title 23, and this standard. An approval letter will be sent once the plan is approved. IV. PROCEDURES A. It is the responsibility of the tank owner to provide the test procedure to the SFSFR and to have a specific site safety plan on site. The secondary containment test plan must be approved prior to testing notification. Once the secondary containment testing plan is approved, the testing company will be allowed to perform secondary containment testing anywhere in the City of Santa Fe Springs jurisdiction. Notification must be provided to the SFSFR a minimum of 48 hours prior to performing secondary containment testing. B. The following information must be provided when submitting the secondary containment test procedure and specific site plan: 1. Proof of one or more of the following: a. Primary tester is manufacturer trained and has current certification for the monitoring equipment on site, and b. Primary tester possesses a valid ICC Service Technician s certification, or c. Primary tester possesses a valid California Tank Tester License, or d. State Contractors License (A General, C-10, C-34, C-36, C-61, or D-40), 2. Copies of the manufacturer s secondary containment testing protocols if manufacturer specifications will be used in lieu of this standard. Please note, no changes in pressure or vacuum will be permitted, unless a request for a variance is submitted and approved by the Fire Chief. 3. Information on the proposed testing equipment. The following information must be provided: a. Pressure/Vacuum gauges or measuring devices (1) Manufacturer on April 3, 2002 and modified by the Santa Fe Springs Fire Department on July 29, 2009 2

(2) Accuracy range (a) (b) (c) (d) (e) (f) (g) Dial gauges must have a minimum accuracy of 0.5% of dial span. Dial gauges must have a minimum dial size of 4 inches. Pressure dial gauges must be liquid filled and have a range of 0 to a maximum of 15 psig. Vacuum dial gauges must be glycerin filled and have a range of 0 to a maximum of 30 in Hg. Combination gauges are not acceptable. Digital gauges must have a minimum accuracy of 0.5% of scale. Digital gauges must read pressure to 0.01 psig. All gauges must be certified at least annually, with a certification sticker attached to each gauge. (3) Last certification date. b. Pressure/vacuum pumps/vacuums (1) Manufacturer (2) Power Source (if electric, proof of Class I, Division I, Group C/D hazard) 4. Method of disposal for all cleaning, rinse and testing water. 5. Manufacturer's information on all repair material expected to be used at the site. The material must be compatible with the underground storage tank system components, and compatible with the hazardous substance stored in the tank system. C. The following testing procedures should be used: 1. Tank a. The tank interstitial space shall be tested through placing a vacuum. The vacuum shall be set at 10 inches of mercury, and hold for a minimum of 60 minutes. The vacuum must not decrease in the hour to achieve a pass. on April 3, 2002 and modified by the Santa Fe Springs Fire Department on July 29, 2009 3

2. Piping System (1) For tanks 20,000 gallons or more, a 120 minute test shall be performed. Please indicate the sizes if the capacity of any tank to be tested is equal to or greater than 20,000 gallons. (2) If the tank does not maintain the vacuum, the contractor can re-test the interstitial space. If after the second test, the tank did not pass, the secondary containment must be considered not liquid tight. Repairs shall be made by the tank manufacturer or authorized representative under permit. a. Secondary containment piping shall be tested in the following manner: (1) An inert gas shall be used (examples are commercial grade nitrogen, argon or helium). (2) The secondary containment shall be made airtight with either the rubber test boot or fiberglass test fitting installed at time of installation (if the test boot is missing or damaged, an approved replacement test boot or fiberglass test fitting can be installed). (3) The piping shall be pressured to 5 psig, allowed to balance for 10 minutes, then tested for 60 minutes. (4) To pass the test, the piping must be at 5 psig after the 60 minute test interval. The gauge dial or readout must not decrease from the initial setting. If the piping does not pass, the contractor can verify all clamps are tight, and re-test the piping. If after the second test, the piping did not pass, the secondary containment must be considered not liquid tight. The piping must be repaired using the piping manufacturers repair procedures under permit. 3. Turbine/piping and dispenser containment sumps a. The turbine/piping and dispenser containment sumps shall be tested in the following manner: (1) The sump must be free of dirt, petroleum products and debris. Rinse water must be properly handled and disposed in accordance with State and local requirements. (2) Place test fluid in the sump and spill container, a minimum of 2 inches above the highest piping penetration. (a) Piping includes all pipes which could contain the underground storage tank product, including primary/secondary product piping, vent piping, vapor recovery piping and siphon piping. on April 3, 2002 and modified by the Santa Fe Springs Fire Department on July 29, 2009 4

(b) It is strongly recommended to fill the sump to a minimum of 2 inches above all penetrations, including all electrical penetrations. 4. Spill Containers (3) After the test fluid has settled for 30 minutes, measure the test fluid level using test equipment with an accuracy of ± 0.002 inches. (4) The test must demonstrate no observable change at the end of 2 (two) 15 minute test intervals. If the sump does not pass the test, the contractor may reinspect the sump penetrations, tighten clamps and repair possible minor leaks (see Repairs), and retest. If after the second series of tests, the sump did not pass, the secondary containment must be considered not liquid tight. The sump must be repaired using the sump manufacturers repair procedures under permit. Spill containers shall be tested in accordance with the document titled Underground Storage Tank Annual Spill Container Testing. 5. Confined Space Entry You must indicate if confined space entry will be performed and identify who will be designated as the confined space rescue team. D. Site Safety and Inspection Preparation 1. Site activities shall be in accordance with the Site Safety Plan. The Site Safety must be maintained on site. Some appropriate components to include in the plan are: a. Site manager for the testing contractor, including contact telephone number. b. Site Safety Officer. The Site Safety Officer must remain on-site for the duration of any work related to the secondary containment testing or repair. c. Emergency response agencies, including address and contact telephone numbers. d. Nearest hospital, including address, contact telephone numbers and map providing directions to the hospital from the site. e. Confined space training certifications for employees performing confined space entry work. on April 3, 2002 and modified by the Santa Fe Springs Fire Department on July 29, 2009 5

f. Confined space entry procedures and permit. g. Hazards anticipated on the sites, including mechanical, physical, and chemical. h. Emergency procedures for injury, fire, or entrapment. 2. If in the determination of the inspector, or the contractor, vehicle traffic at the site presents an unsafe area, the site shall be closed for the testing. 3. At a minimum, the area involved with the testing shall be barricaded off from vehicle and pedestrian traffic. 4. If necessary, the monitoring system can be de-activated to allow for testing. Technicians authorized to work on the monitoring equipment shall only perform the deactivation. Whenever possible, the monitoring system should remain in service, with sensors placed above liquid levels. E. Repairs F. Report 1. All repairs, except for tightening or connecting and installing test boots, are classified as system modifications, including minor "fixes" and must be approved by the SFSFR. 2. A qualified person(s) must perform repairs as soon as possible. Some repairs will require a permit to be obtained from this or other agencies. Consult with the inspector of record for advice on repairs or permits. The SFSFR shall issue final approval of all repairs. 3. All repairs shall be conducted in accordance with the manufacturers recommendations for long-term repairs. Methods for all repairs should consider the expected lifetime of the system. Repair records must be maintained for the life of the tank system. 4. All material uses shall be compatible with the product being stored. 5. All repairs identified as requiring a permit shall have a permit issued before initiation of repair work. 1. A report documenting the secondary containment testing must be submitted within thirty (30) days upon completing the test. 2. The "Secondary Containment Testing Report Form" developed by the State Water Resources Control Board shall be used. on April 3, 2002 and modified by the Santa Fe Springs Fire Department on July 29, 2009 6