Northern Region. Underground Storage Tank
|
|
- Sharleen Claire Todd
- 8 years ago
- Views:
Transcription
1 California CUPA Northern Region Presents Underground Storage Tank Designated Operators Workshop
2 Workshop Agenda Definitions Tank Construction Corrosion Protection Spill Prevention Overfill Prevention Piping Systems UST Monitoring Testing requirements Unauthorized releases Financial Responsibilities Role of Designated Operator About the Exam
3 Definitions CHSC California Health and Safety Code, Chapter 6.7 CCR California Code of Regulations UST Title 23, Chapter 16 Underground Storage Tank 10% of Tank Capacity is Underground Includes piping
4 SIR Statistical Inventory Reconciliation ATG Automatic Tank Gauging System Cathodic Protection Sacrificial Anode Impressed Current UDC Under Dispenser Containment
5 Single Wall Double Wall Intersititial Space / Annular Space
6 Tank Construction Common Features Riser Spill Bucket Product Piping Overfill Prevention Monitoring
7
8 Corrosion Protection All UST s and Piping Must Have Corrosion Protection, Section 2635 (a)(2) Rust Resistant Material Fiberglass construction Fiberglass coating on steel tank Cathodic Protection, Operating and Maintaining UST Booklet, p34-37 Sacrificial Anodes Anode Attached to the Tank Impressed Current Anode in the Ground Away From the Tank
9 Fiberglass Tank
10 Steel Tank
11 More About Cathodic Protection Sacrificial Anode Requires Cathodic Protection Specialist 6 Months After Installation and Then Every 6 Months After Installation and Then Every 36 Months Thereafter
12 More About Cathodic Protection Impressed Current Maintain -850 mvolts at all Times Maintain an Inspection Log Inspect System Every 60 Days Requires Cathodic Protection Specialist 6 Months After Installation and Every 36 Months Thereafter Retain Records for the Last 2 Cathodic Protection Tests for 61/2 Years
13 Corrosion Protection Interior Tank Lining Inspect 10 Years After Lined Section 2663(h) Then Every 5 Years Thereafter Keep Records for the Life of the Tank
14 Spill Containment 5 Gallon Minimum Spill Bucket, Section 2635(b) Must be Corrosion Resistant Functioning Drain Valve Must be Kept Clean No Product, Water or Debris Must be Tested Annually
15 Spill Bucket
16
17 Overfill Prevention - 3 Types Operating and Maintaining UST Booklet 1. Audible and Visual Alarm Typically connected to ATG Alarm Must be Where Operator and Delivery Driver can See and Hear Alarm 2. Ball Float Valve Restrict Flow to Tank 3. Automatic Shut Off Device A Device in the Fill Pipe Which Shuts Off Flow
18 Ball Float Valve
19 Positive Shut-off Overfill Valve
20
21 Overfill Prevention Requirements Must meet one of the following: Alert Delivery Driver When the Tank is 90% Full by Restricting Flow or Triggering Alarm OR Restricts Delivery Flow 30 Minutes Before Overfill, Must Occur at No More Than 95% Full Must Activate Audio/Visual Alarm at Least 5 Minutes Before Overfill OR Provide Positive Shut Off of Flow to the Tank When at 95% Capacity OR OR Positive Shut Off of Delivery Flow so That None of the Fittings at the Top of the Tank are Exposed to Product
22 Overfill Prevention There are 4 Acceptable combinations to meet this requirement: Ball Float with Sump & Sensor Max 90% Overfill Alarm (ATG) sump & sensor Max 90% Ball Float with Overfill Alarm (ATG) Max 95% Mechanical Flapper Drop Tube Max 95%
23 Overfill Protection What the Operator Must Do: Make Sure You Order the Right Amount Make Sure the Delivery Driver Monitors the Unloading Process Make Sure the Overfill Equipment is Working Properly
24 Piping Systems 3 Types of Piping Systems Pressurized Pushes Fuel to Dispenser Suction Pulls Fuel to Dispenser Gravity Dispenser is Gravity Fed
25 Turbine
26 Fiberglass Piping
27 Flexible Piping
28 Safe Suction vs. Conventional Suction Safe Suction Check Valve is Above Ground Safe because fuel drops back into the tank. No line test required if: Only one check valve per line (directly under dispenser) Piping slopes back to tank System operates under atmospheric pressure Conventional Suction Check Valve is Below Ground Line Tightness Test Every 3 Years Daily Monitor for Presence of Air in Pipeline (Cost/Quantity Wheel Jumps)
29
30
31 Under Dispenser Containment Acts as a Secondary Containment for Transition Piping in Dispenser Contains Releases From Dispenser and Fuel Filter
32
33 Under-Dispenser Containment
34 Sump Sensor Section 2630(d), 2641 (j) Located at the Lowest Point in the Sump Must Be Tested Annually
35 Line Leak Detector Flex Connector Sensor
36 Interstitial Space Monitoring Section 2630(d), 2641 (j) Tank Annular Sensor Dry Float Switch Senses Fuel and / or Water Leak into the Interstitial (Annular) Space Hydrostatic Sensor Interstitial Space Filled With Brine, Float Sensor Detects Change in Volume or Level System Must Be Certified Annually
37 Secondary Containment Piping Penetration (fitting) Reducer (test) Boot Primary Piping
38
39 Required Testing / Record Keeping Monitoring System Certification Title 23, Section 2712(b) Frequency Notify Agency Keep Records Annual 48 Hours 3 Years Line Leak Annual 48 Hours 3 Years Detectors Line Tightness Test Annual (depends on system) 48 Hours 3 Years Secondary Containment Testing 3 Years 48 Hours Corrosion Protection Impressed Current & Sacrificial Anode Corrosion Protection Tank Liner 60 day log for Rectifier Readings System Check Every 3 Years 10 years after installation then every 5 years 48 Hours 6 ½ Years 48 Hours For Life of Tank
40 Unauthorized Releases Recordable Does Not Escape Secondary Containment Does Not Increase Fire Danger Does Not Deteriorate Secondary Containment Rapid Clean Up (within 8 hours) Less Than 25 Gallons
41 Unauthorized Releases Reportable All Spills That Enter a Waterway Regardless of the size of the spill All Spills That Leave a Sheen All Spills That Leave a Sheen on Surface Water
42 Unauthorized Releases Reportable Unusual Operating Conditions Erratic behavior of dispenser Sudden Loss of Product Unexplained Water in the Tank Not required to report if equipment is found to be Not required to report if equipment is found to be defective but not leaking.
43 Unauthorized Releases Reportable Results From Leak Detection Indicate Suspected Release Not required to report if : Monitor Device is found to be defective, and is repaired immediately and further monitoring does not confirm initial suspected release.
44 SIR Section A Trained Professional Conducts a Statistical Analysis of Inventory, Delivery, and Dispensing Data Daily Inventory Reading Daily Readings supplied to SIR Vendor at Least Every 30 Days SIR Method Must be Able to Detect SIR Method Must be Able to Detect Leaks Rates of 0.2 Gallons per Hour
45 Financial Responsibility Dollars and Sense Booklet If Less Than 100 UST s $500,000 per Occurrence $1 Million Aggregate
46 Automatic Tank Gauging System Section 2643 Consists of a Probe Permanently Installed in the Tank, Wired to Monitor Level and Temperature ATG Systems automatically calculate changes in the product volume that can indicate a leak Must Pass 0.2 Gal/Hour leak Test Monthly System Must be Checked Annually
47 Automatic Tank Gauge Port
48 Line Leak Detector Section 2636(f)(2) 2 Types for piping with secondary containment Mechanical Slows the flow of product Electronic Stops the flow of product Must be Able to Detect a 3 gal/hour Leak Must be Tested Annually
49 Pressurized Piping and Monitoring Requirements
50 Line Leak Detector Section 2636(f)(2) Single Walled Piping, without secondary containment Must be Electronic Line Leak Detector Must be Able to Detect 3 gal/hour Leak Must Monitor Monthly for 0.2 gal/hour Leaks, or Annually for 0.1 gal/hour Leaks Must be Tested Annually
51 Role of the Designated Operator Section 2715 Must Pass the ICC Test by January 1, 2005 Owner Must Notify the Local Agency Within 30 Days of Change of Designated Operator Conduct Monthly Facility Inspections By July 1, 2005 (Then Every 12 Months) Train Facility Employees in Emergency Procedures and Operation of the UST System
52 Designated Operator, Monthly Inspections Review Alarm History Check Spill Containers Check UCD Check Sumps (that have had an alarm in the past month) Check that required testing and maintenance Check that required testing and maintenance have been completed
53 About The Exam 60 Multiple Choice Questions Each has one Best Answer All Questions / Answers are from a Required Reference Open Book References are Provided at the Test Center 90 Minute Exam Time $75 Exam Fee
54 About The Exam Computer Based Testing Administered by a Testing Company Test Center Personnel will help familiarize you with the computer and monitor you during the testing. There is time to practice on the computer, before the test, using sample questions. Test Results are Immediately Available
UST RULES CHANGES. Heather Peters, Environmental Specialist
UST RULES CHANGES Heather Peters, Environmental Specialist Today s Topic 2011 Rule package- what s left? Upcoming rule changes Federal Regulation Changes & Testing Protocols How are you doing? 2011 Rule
More informationPetroleum Storage Tank Compliance 101
Petroleum Storage Tank Compliance 101 Palm Beach County Board of County Commissioners Department of Environmental Resources Management Petroleum Storage Tank Compliance Section www.pbcgov.com/erm 561-233-2400
More informationUnderground Storage Tank Operational Compliance Field Guide
Underground Storage Tank Operational Compliance Field Guide Created April 2012, Reaffirmed April 2015 Bureau of Underground Storage Tank Regulations http://www.com.state.oh.us/fire/default.aspx Department
More informationWelcome UST Owners & Operators!!
Welcome UST Owners & Operators!! Underground Storage Tank Owner & Operator Workshop Presented By: Kern County Environmental Health CUPA Kern County Environmental Health Phone: (661) 862-8740 Email: hazmatprogram@co.kern.ca.us
More informationDRAFT REVISED 2015. Musts For USTs DRAFT. Printed on Recycled Paper. Updated June 2015
DRAFT REVISED 2015 Musts For USTs DRAFT Printed on Recycled Paper EPA wrote this booklet for owners and operators of underground storage tanks (USTs). This booklet describes the 2015 revised federal UST
More informationUST Site Inspection Guidance Document
UST Site Inspection Guidance Document September 2004 Publication No. 04-09-089 UST Site Inspection Guidance Document Prepared by: Washington State Department of Ecology Toxics Cleanup Program September
More informationThis page left intentionally blank
1 This page left intentionally blank 2 STATE OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION DIVISION OF UNDERGROUND STORAGE TANKS TECHNICAL CHAPTER 4.2 SPILL AND OVERFILL PREVENTION EFFECTIVE
More informationAlabama Air and Waste Regulatory Update
Alabama Air and Waste Regulatory Update September 24, 2015 RSA Activity Center Montgomery, AL New Federal UST Regulations (Effective Date October 13, 2015) What Does This Mean To Me? The Current ADEM Regulations
More informationUST Regulatory Compliance Inspection Training. State Water Resources Control Board Underground Storage Tank Program September 2004
UST Regulatory Compliance Inspection Training State Water Resources Control Board Underground Storage Tank Program September 2004 Disclaimer The material provided herein is not comprehensive of Chapter
More informationSecondary Containment & Spill Buckets Inspection, Testing, and Repair Solutions. Allen Porter May 28, 2015
Secondary Containment & Spill Buckets Inspection, Testing, and Repair Solutions Allen Porter May 28, 2015 Welcome and overview Introduction Tanknology Proposed Revisions to Federal Regulations Testing
More informationUnderground Storage Tanks
Underground Storage Tanks An Informational and Guidance Document for the University Community. Please contact Yale Environmental Health and Safety for latest Regulatory Requirements. A typical UST installation
More informationBrian Derge Tanknology Inc. February 26, 2015
Secondary Containment & Spill Buckets Inspection, Testing, and Repair Solutions Brian Derge Tanknology Inc. February 26, 2015 Welcome Introduction Tanknology Proposed Revisions to Federal Regulations Testing
More informationApplication for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems
Page 1 of 5 Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems New Hampshire Department of Environmental Services
More informationUST System Inspection Checklist
UST System Inspection Checklist The Petroleum Equipment Institute (PEI) Tank Installation Committee has produced this checklist as a service to owners/operats of underground stage tanks (USTs). Items on
More informationStraight Talk On Tanks Leak Detection Methods For Petroleum Underground Storage Tanks And Piping
Straight Talk On Tanks Leak Detection Methods For Petroleum Underground Storage Tanks And Piping Printed on Recycled Paper Contents Do You Have Questions About Leak Detection?...1 An Overview Of Leak Detection
More informationMAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION
Oxford Hills Bus Garage 36 Brown St, Norway, ME Oil Storage Inspection 2/20/14 CONDITIONS OBSERVED Underground Oil Storage: 12,000 gallon underground oil storage tank (split 10,000 gallon diesel/2,000
More informationDaily Inventory and. Statistical Inventory Analysis. Daily Inventory and Statistical Inventory Analysis (SIA) are inventory control
Introduction: TankSmart Operator Training Class A/B Operators Training Class C Operators Annual UST System Inspections Record Keeping Spills: Cleanup & Reporting Safety Tanks: Double-Walled w/ Continuous
More informationSection A SPCC Plan Implementation Checklist This section of the report addresses compliance with certain requirements of Federal Regulations 40 CFR 112. I. STATUS OF SPCC PLAN (40 CFR 112.3) YES NO A.
More informationSecondary Containment Testing Report Form
Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of this form to report
More informationAUTOMATIC TANK GAUGING SYSTEMS Achieving Compliance. John D. Sieger, Tanknology
AUTOMATIC TANK GAUGING SYSTEMS Achieving Compliance John D. Sieger, Tanknology The Objective: Monitor the Tanks & Piping Systems for leaks TANK GAUGING SYSTEM BRANDS DOUBLE WALL STEEL TANK MONITORING DOUBLE
More information1. Who is your current pollution carrier? Expiration Date: Premium: Retroactive Date:
Named Insured: Business Name (include dba if applicable): Mailing Address: Phone Number: County: In Case of Claim: Contact Name: Phone Number: Type of Business: Corporation Individual Partnership L.L.C.
More informationPMMIC 2013 Inspection Findings. Brian Pottebaum Rounds & Associates/PMMIC
2013 Inspection Findings Brian Pottebaum Rounds & Associates/ 2013 Top Ten Deficiencies Cited 1. Liquid/Debris in Spill Containment 2. Insufficient Secondary Containment (Piping Sump) 3. Insufficient Secondary
More informationALL UST SYSTEMS. MOTOR FUEL, USED OIL, BULK HEATING OIL STORAGE (Federal/State Regulated Systems)
FACTS ABOUT: UST SYSTEMS COMPLIANCE OUTLINE Maryland Department of the Environment In Maryland, certain UST systems must meet various compliance requirements. The following is a summary of the current
More informationMaryland Containment System Testing Protocol. The individual performing the inspection and testing as outlined in this protocol must be either:
MARYLAND DEPARTMENT OF THE ENVIRONMENT Oil Control Program, Suite 620, 1800 Washington Blvd., Baltimore MD 21230-1719 4 410-537-3442 410-537-3092 (fax) 1-800-633-6101 http://www.mde.state.md.us Maryland
More informationMonitoring an Underground Storage Tank Facility
DEVELOPMENT SERVICES DEPARTMENT HAZARDOUS MATERIALS PERMIT APPLICATION / MATERIALS MANAGEMENT PLAN PART I: GENERAL INFORMATION ON UNDERGROUND STORAGE TANK (UST) LOCATION (Please print) UST Location Name:
More informationSpill Control Prevention Plan (SCPP)
Spill Control Prevention Plan (SCPP) FACILITY INFORMATION PLEASE PRINT Facility Name: Mailing Address: Physical address if different: Owner Name: Owner Address: Primary Contact Name: Work Phone Number:
More informationPetroleum Storage Tank Spill and Overfill Prevention
TCEQ REGULATORY GUIDANCE Small Business and Environmental Assistance Division RG-475e Revised April 2011 Introduction Petroleum Storage Tank Spill and Overfill Prevention A guide for owners and operators
More informationLeak Detection and Alternative Fuels 21 st Annual National Tanks Conference Sacramento, CA
Leak Detection and Alternative Fuels 21 st Annual National Tanks Conference Sacramento, CA Greg Bareta, PE Engineering Consultant Wisconsin Department of Commerce Bureau of Petroleum Products and Tanks
More informationTank Environmental Regulations. Aisha Beaty Barr Engineering Company
Federal SPCC vs. State Storage Tank Environmental Regulations Aisha Beaty Barr Engineering Company purpose most industrial facilities utilize storage tanks in some capacity Federal and State regulations
More informationUST Regulations Revision Update
Spring 2009 Number 58 UST Regulations Revision Update Jill Hall The Tank Management Branch (TMB) conducted 3 public workshops in October 2008 to roll out changes to the Delaware Regulations Governing Underground
More informationNDEP Bureau of Corrective Actions Secondary Containment Regulations Guidance Document April 7, 2010 (Revision)
NDEP Bureau of Corrective Actions Secondary Containment Regulations Guidance Document April 7, 2010 (Revision) ADOPTED REGULATION OF THE STATE ENVIRONMENTAL COMMISSION LCB File No. R005-08 (Codified in
More informationCOMPLIANCE MANAGEMENT STRATEGIES. Presented by: Megan Kazmierczak, ECS Eclipse
COMPLIANCE MANAGEMENT STRATEGIES Presented by: Megan Kazmierczak, ECS Eclipse AST vs. UST Compliance requirements Aboveground Storage Tanks (ASTs): Misconception that ASTs are unregulated Most are subject
More informationCompliance and Fuel Management Service. Service Catalog
TM Compliance and Fuel Management Service Service Catalog We Have Received Orders To Comply With The EPA. Over. R o g e r. W i l c o. Introduction By taking on the job of monitoring tanks rather than just
More informationInspections Standard Operating Procedure 5 Aboveground Storage Tanks
Aboveground Storage Tanks Aboveground Storage Tank Inspection This Standard Operating Procedure describes the steps that campus units that manage aboveground oil storage tanks (ASTs) or containers must
More information1) Named Insured: 2) Insured s Street Mailing Address:
NEW BUSINESS: RENEWAL: STORAGE TANK THIRD PARTY LIABILITY CORRECTIVE ACTION AND CLEANUP POLICY APPLICATION NOTICE: PLEASE ANSWER ALL QUESTIONS. ATTACH ADDITIONAL SHEETS OF PAPER IF NECESSARY. THIS POLICY
More informationOREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
More informationSTANDARD FOR SECONDARY CONTAINMENT TESTING OF UNDERGROUND STORAGE TANK SYSTEMS I. INTRODUCTION
SANTA FE SPRINGS DEPARTMENT OF FIRE-RESCUE Environmental Protection Division Certified Unified Program Agency 11300 Greenstone Ave, Santa Fe Springs, CA 90670 Phone (562) 944-9713 Fax (562) 941-1817 STANDARD
More informationSpill Prevention, Control and Countermeasure (SPCC) Rule
Spill Prevention, Control and Countermeasure (SPCC) Rule Code of Federal Regulations Title 40 CFR Part 112 Training Guide for Oil and Fuel handlers on Farms 1 Purpose of SPCC Rule To prevent oil discharges
More informationDIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY. August 2012
DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY August 2012 SECTION 2 The storage requirements in Directive 055 apply to upstream petroleum facilities, well sites, and pipelines
More informationUPDATE ON MAINE'S UNDERGROUND TANK LAWS
MAINE OIL DEALERS ASSOCIATION TECHNICAL BULLETIN #6.5 MAINE UNDERGROUND TANK LAW CHANGES September, 1992 [Replaces Technical Bulletin #6.4, issued January, 1992] UPDATE ON MAINE'S UNDERGROUND TANK LAWS
More informationSpill Containment Device and Containment Sump Testing Protocols. Introduction
Department of Natural Resources and Environmental Control Tank Management Branch 391 Lukens Drive New Castle, DE 19720 (302) 395-2500 (Phone) (302) 395-2555 (Fax) http://www.dnrec.state.de.us/dnrec2000/divisions/awm/ust
More informationThe following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
More informationCITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN Adopted October 5, 2009 Table of Contents Chapter Description Page 1 Facility Descriptions... 3 1.1 Municipal Power Plant, 1001 Park
More informationACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas
ACTIVITY NAME Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas CY 2014 BOTTOM LINE UP FRONT To prevent oil discharges
More informationThe Fuel Storage Tank Regulations 2009
The Fuel Storage Tank Regulations 2009 October 2009 ED/RO1/015 The Fuel Storage Tank Regulations Issued by: The Regulation and Supervision Bureau for the water, wastewater and electricity sector in the
More informationYOUR PETROLEUM STORAGE TANK FACILITY INSPECTION GUIDE
YOUR PETROLEUM STORAGE TANK FACILITY INSPECTION GUIDE HOW WELL DO YOU KNOW YOUR PETROLEUM STORAGE AND DISTRIBUTION SYSTEM? This handbook is provided as a general guide. For specific regulation requirements
More informationInventory Control for Underground Storage Tanks
Inventory Control for Underground Storage Tanks Tanks/Underground #3-20 September 2008 M innesota law requires Underground Storage Tank (UST) systems to have leak detection. Inspections conducted nationwide
More informationNEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM. New Jersey Fuel Dispensing Facilities Compliance Calendar
NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM New Jersey Fuel Dispensing Facilities Compliance Calendar 2016 Welcome The New Jersey Small Business Environmental Assistance Program developed
More informationPOLLUTION LEGAL LIABILITY COVERAGE APPLICATION
AUTOMOTIVE RISK MANAGEMENT & INSURANCE SERVICES, INC. 1919 GRAND CANAL BLVD., SUITE C-7 STOCKTON, CALIFORNIA 95207 PHONE (800) 224-6363 FAX (888) 504-8062 Email: apps@armonline.com CALIFORNIA LICENSE NUMBER.
More informationMorrison Bros. Co. General Product Specifications
Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage
More informationAMERICAN INTERNATIONAL COMPANIES
AMERICAN INTERNATIONAL COMPANIES Commerce and Industry Insurance Company Illinois National Insurance Co. American International South Insurance Company (each of the above being a capital stock company)
More informationA GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS
A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS What is a groundwater protection plan? A groundwater protection plan identifies the activities being conducted that can pollute groundwater and
More informationChemical Feed System Operation and Design Considerations
PNWS AWWA MAY 7, 2014 EUGENE, OREGON Chemical Feed System Operation and Design Considerations Kevin Batridge Lake Oswego Tigard Water Partnership Austin Peters MWH Global Chemical Delivery and Storage
More informationDistrict of Columbia Municipal Regulations UNDERGROUND STORAGE TANKS: GENERAL PROVISIONS 5500 COMPLIANCE WITH OTHER DISTRICT LAWS
CHAPTER 55 UNDERGROUND STORAGE TANKS: GENERAL PROVISIONS Section 5500 Compliance with Other District Laws 5501 Applicability of UST Regulations 5502 Partial Applicability of UST Regulations to Particular
More informationFigure 1 Plugged Dispenser Filter vs. new
FINAL August 16: This document is intended to provide basic information and is not intended to be a complete guidance document. All suggestions may not necessarily be applicable to every station or situation
More informationStorage Tank Guidance for Real Estate Professionals
MARYLAND DEPARTMENT OF THE ENVIRONMENT Land Management Administration Oil Control Program 1800 Washington Boulevard Suite 620 Baltimore Maryland 21230-1719 410-537-3442 800-633-6101 x3442 www.mde.state.md.us
More informationENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS
Facility Name: ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS The following is intended to be used as a guideline for information required to appear on engineered drawings involving petroleum storage
More informationSeptember 2008 AFC 4.6.2.1.(2) Page 1 of 5. Maximum Size and Aggregate Capacities of Aboveground Storage Tank Systems at Fuel Dispensing Stations
FIRE CODE VARIANCE September 2008 AFC 4.6.2.1.(2) Page 1 of 5 ISSUE Maximum Size and Aggregate Capacities of Aboveground Storage Tank Systems at Fuel Dispensing Stations The Alberta Fire Code (AFC) limits
More informationUniversal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal)
Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal) IMPORTANT: It is imperative that the user read these warnings and use of the assembly instructions
More informationNFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
More informationSpill Containment Manholes
Spill Containment Manholes 1-2100 Series OPW and Pomeco Spill Containment Manholes are designed to prevent spilled product from entering the soil near the fill and vapor return riser connections on underground
More informationUnderground Storage Tank Cathodic Protection Checklist
Underground Storage Tank Cathodic Protection Checklist The attached Underground Storage Tank (UST) checklist is required for the activity above. This checklist certifies the Cathodic Protection activities
More informationA cure for water damage in real estate
A cure for water damage in real estate Presented for BC Non-Profit Housing Association by Jeff Shearman, Zurich Services Corporation 2010 Zurich Canada Focused on our customer Reduce overall risk by reducing:
More informationGUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS
Company Name: Address: The City of Attleboro s Rules and Regulations for the use of Wastewater Facilities require each user to provide protection from accidental discharge of prohibited materials and substances
More informationThe following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
More informationOPW EDGE Double-Wall Spill Containers
www.opwglobal.com OPW EDGE Double-Wall Spill Containers Designed in collaboration with contractors and end-users, the OPW EDGE Double- Wall Spill Container installs in the same space as single-wall buckets.
More informationFIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
More informationTLS-300C UST Monitoring and Leak Detection System
TLS-300C UST Monitoring and Leak Detection System Part 1 - General System Requirements 1.1 Description A. These specifications are intended to provide information by which prospective bidders may understand
More informationSafety Manual Title: Spill Prevention & Response Review Date: 6/1/2014
Operation s Purpose The purpose of this plan is to document spill prevention and response requirements. Each Elkhorn Construction, Inc. jobsite will develop a spill prevention and response plan based on
More informationFACILITY ENVIRONMENTAL COMPLIANCE
FACILITY ENVIRONMENTAL COMPLIANCE 2014 TxDOT Environmental Conference 2014 TxDOT Environmental Conference 2014 TxDOT Environmental Conference Table of Contents 1 Introduction 1 2 Facility Environmental
More informationOIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS. Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040
ABSTRACT OIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040 The SPCC regulations entail numerous requirements for the
More informationSPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN XXXX FARM (CITY OR COUNTY), MICHIGAN CONTACT (NAME), OWNER CERTIFICATION: I hereby certify that I have examined the facility, and being familiar with the
More informationEthanol-Water Phase Separation White Paper
Ethanol-Water Phase Separation White Paper Samir Jain Background The use of ethanol as a fuel in the United States has significantly increased over the past decade. Today, greater than 80% of all retail
More informationCATHODIC PROTECTION SYSTEM DESIGN
CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of
More informationGUERNSEY OIL INSTALLATION GUIDELINES
GUERNSEY OIL INSTALLATION GUIDELINES This guidance relates only to liquid oil. For information on the requirements for associated equipment such as the positioning of boilers and flues please refer to
More informationRadioactive Waste Storage Facility and Tank System Design Criteria Standards
UCRL-AR-133355 Rev 1 Radioactive Waste Storage Facility and Tank System Design Criteria Standards John Wood Rich Michalik Karen Doiron May 1999 DISCLAIMER This document was prepared as an account of work
More informationSTORAGE TANK INSPECTION AND COMPLIANCE PHILLIP BENTON CERTIFIED TANK INSPECTOR
STORAGE TANK INSPECTION AND COMPLIANCE PHILLIP BENTON CERTIFIED TANK INSPECTOR HDR EOC PETROLEUM SYSTEMS DIVISION 419 CANYON AVENUE, SUITE 316 FORT COLLINS, COLORADO 80524 INTRODUCTION Various policies,
More informationTECHNICAL ADVISORY BULLETIN
RISK CONTROL AND CLAIM ADVOCACY PRACTICE TECHNICAL ADVISORY BULLETIN November 2014 www.willis.com FIRE PUMP TESTING Fire pumps are a critical part of a fire protection system, especially when they are
More informationFuels Safety Program. Liquid Fuels Handling Code Adoption Document Amendment
Fuels Safety Program Liquid Fuels Handling Code Adoption Document Amendment Ref. No.: FS-207-14 Date: IN THE MATTER OF: Technical Standards and Safety Act 2000, S.O. 2000, c. 16, and Ontario Regulation
More informationSpill Prevention, Control and Countermeasure (SPCC)
Spill Prevention, Control and Countermeasure (SPCC) History Original promulgation 1973, effective 1974 Codified in 40 CFR 112 (EPA Jurisdiction) Proposed rulemaking 1991, 1993 and 1997 Amended July 17,
More informationWaste Oil Collection / Storage
ENVIRONMENTAL & REGULATORY SERVICES Storage Tank Regulation Section P. O. Box 7837 Madison, Wisconsin 53707-7837 TDD #: (608) 264-8777 http://www.commerce.state.wi.us http://www.wisconsin.gov Jim Doyle,
More informationUnderground Storage Tank Flood Guide
Underground Storage Tank Flood Guide Junction, Texas Flood of 1935. Photo courtesy of Texas Escapes Online Magazine and Texas Department of Transportation Printed on Recycled Paper Contents Introduction...
More informationTanks: What's in store?
Tanks: What's in store? Technical and regulatory developments in tank construction prompt changes; operations and maintenance receive greater emphasis. Chemical Processing magazine By Wayne Geyer Tanks
More informationOperation, Maintenance, and Inspection of UST System Release Detection and Prevention Equipment
Operation, Maintenance, and Inspection of UST System Release Detection and Prevention Equipment Objectives Raise awareness of remote monitoring systems capabilities o Methods of connections to ATGs o Difference
More informationList of Frequently Utilized Storage Tank Standards and Practices
List of Frequently Utilized Storage Tank Standards and Practices Below is a list of frequently used storage tank standards and practices from organizations that are referenced in 25 PA Code, Chapter 245.
More informationQuik Lining Systems Heater Owners Guide
Quik Lining Systems Heater Owners Guide Quik Lining Systems, Inc is pleased to present the Quik Heater, an innovative heater used to cure cured in place pipe for sewer laterals. The unit is the most cost
More informationTLS-350R Monitoring Systems. Business Inventory Management.
TLS-350R Monitoring Systems Add value to automated tank gauging with the advanced capabilities of Business Inventory Management. Fuel Dispensing and Control Site and Retail Management Support Services
More informationInspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
More informationALLEGANY WIND POWER PROJECT CONSTRUCTION SPILL PREVENTION PLAN
ALLEGANY WIND POWER PROJECT CONSTRUCTION SPILL PREVENTION PLAN Best Management Practices (BMPs) will be implemented during construction of the Allegany Wind Power Project to prevent and contain spills.
More informationTechnical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil)
Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil) References: Comm 10 2009 EDITION / NFPA 30 2008 EDITION ITEM DESCRIPTION Comm 10 / NFPA General
More informationDoing Inventory Control Right For Underground Storage Tanks
United States Solid Waste And EPA 510-B-93-004 Environmental Protection Emergency Response November 1993 Agency 5403W Doing Inventory Control Right For Underground Storage Tanks CONTENTS Why You Should
More informationUNIVERSITY OF WISCONSIN MADISON
UNIVERSITY OF WISCONSIN MADISON Contractor Spill Contingency Plan (while working on campus) Departments of: Environment, Health & Safety Physical Plant Table of Contents Spill Contingency Plan Most Common
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationFrequent Mishaps and Solutions with Regulated Aboveground Storage Tanks in Pennsylvania
Frequent Mishaps and Solutions with Regulated Aboveground Storage Tanks in Pennsylvania NISTM 4 th Annual Pennsylvania Storage Tank Conference April 25, 2013 Overview Common regulated ASTs missed Performance
More informationMPM. Customer Service Representative Training. Class C Fuel Spill Handling
MPM Customer Service Representative Training Class C Fuel Spill Handling The Class C Operator "Class C operator" means an individual who has daily on-site presence and responsibility to handle emergencies
More informationRecommended Fuel Piping Specification For UPP Piping, UL-971
Recommended Fuel Piping Specification For UPP Piping, UL-971 1.0 General The primary delivery piping system shall be for suction or pressure applications and have semi-rigid coaxial type double wall construction,
More informationTechnical Guide 08/15/14
Technical Guide 08/15/14 1 Table of Contents Contact information.3 Identifying your system..4-8 Model Number Serial number location Parts of your fuel system..9-14 Fuel pump diagram Wire harness schematics
More informationContingency Plan. Facility Name
Contingency Plan Facility Name This plan is reviewed annually and amended whenever changes occur that will significantly affect the ability of this facility to respond to an emergency situation. This includes
More informationCathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants
Cathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants PG&E Office San Francisco January 18, 2007 Craig K. Meier Corrosion Control Incorporated Corrosion process for tanks
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More information