2B.1 Chilled-Water Return (and Supply) Temperature...119. 2B.3 Cooling-Water Supply Temperature / Flow... 124



Similar documents
2A.1 Features of Chiller Control Components A.3 Chilled-Water Supply Temperature Control A.4 Cooling-Water Supply Control...

Chapter 3.4: HVAC & Refrigeration System

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

New absorption chillers for high efficient solar cooling systems

How To Clean Water From An Ammonia Refrigeration System

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

Absorption. LG HVAC Solution.

The final numerical answer given is correct but the math shown does not give that answer.

ADVANCED EXCEL FOR ENERGY EFFICIENCY PROFESSIONALS

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

Energy Matters Heat. Changes of State

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

Maintenance for Energy Efficiency

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

3/29/2012 INTRODUCTION HVAC BASICS

GLOBACON 05 HVAC Systems for Cogen

UNIT 2 REFRIGERATION CYCLE

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

Appendix C. Minimum Equipment Efficiency Standards

How To Save Energy With High Pressure Control

AdSORPTION CHILLER NAK

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes.

Research on the Air Conditioning Water Heater System

The Second Law of Thermodynamics

SOLAR-POWERED COOLING, DEHUMIDIFICATION AND AIR CONDITIONING

An Overview of Solar Assisted Air-Conditioning System Application in Small Office Buildings in Malaysia

Modelling and Simulation of the Freezing Systems and Heat Pumps Using Unisim Design

COST AND PERFORMANCE ANALYSIS OF A SOLAR THERMAL COOLING PROJECT

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

HVAC Efficiency Definitions

Boilers and cogeneration/trigeneration. Abhi Sawant Business Development Manager Simons Green Energy

Glossary of Heating, Ventilation and Air Conditioning Terms

Rusty Walker, Corporate Trainer Hill PHOENIX

WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS

Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling

CRAC Precision climate control units for data centres

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping

VACUUM REFRIGERATION SYSTEMS

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

Model-Based Performance Monitoring: Review of Diagnostic Methods and Chiller Case Study

Refrigeration Basics 101. By: Eric Nelson

Secondary Loop Chilled Water In Super High-Rise

AIR CONDITIONING TECHNOLOGY

Model-Based Approach for Optimizing a Data Center Centralized Cooling System

Commercial Hot Water. Make a difference...

SOLAR COOLING WITH ICE STORAGE

Testing methods applicable to refrigeration components and systems

HVAC Systems: Overview

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process.

Dharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014

Type: Single Date: Homework: READ 12.8, Do CONCEPT Q. # (14) Do PROBLEMS (40, 52, 81) Ch. 12

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Impact of Control System Technologies on Industrial Energy Savings

Small-Scale Solar Heating and Cooling Systems

How To Understand Evaporator

Silicagel-water adsorption cooling prototype system for mobile air conditioning

Refrigeration and Air Conditioning with Psychrometry

Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger

Energy savings in commercial refrigeration. Low pressure control

Solar Cooling. Methods and Applications. Sargon Ishaya, PE, LEED AP

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Mohan Chandrasekharan #1

Modeling Guide for Daikin VRV in EnergyPro 6

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

News in Data Center Cooling

What are the Carrier ChillerVu Energy Dashboards?

Improving Data Center Energy Efficiency Through Environmental Optimization

1 Overview of applications and system configurations

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Simulation of a small size solar assisted adsorption air conditioning system for residential applications

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

How To Know If A Refrigeration System Is Efficient

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Creating Efficient HVAC Systems

SustainE(Sustainable Energy)

6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through

ME 201 Thermodynamics

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances.

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Energy consumption and heat recovery of refrigeration system in modern Arena

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

Hines Property Management, NYC

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

8. Heat pumps, heat pipes, cold thermal energy storage

Dew Point Tester. Instruction Manual. CVS Regular Chiller Model A-2. CVS Regular Chiller Model A-2

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX

Transcription:

Appendix 2B: Chiller Test Results...119 2B.1 Chilled-Water Return (and Supply) Temperature...119 2B.2 Chilled-Water Flow... 122 2B.3 Cooling-Water Supply Temperature / Flow... 124 2B.4 Pressure/Temperature... 127 Figure 2B - 1: COP variation with change of chilled-water temperature...121 Figure 2B - 2: Cooling load variation with change of chilled-water temperature...121 Figure 2B - 3: COP variation with change of chilled-water...123 Figure 2B - 4: Cooling load variation with change of chilled-water...123 Figure 2B - 5: COP variation with change of cooling-water temperature...125 Figure 2B - 6: Cooling load variation with change of cooling-water temperature...125 Figure 2B - 7: COP variation with change of cooling-water...126 Figure 2B - 8: Cooling load variation with change of cooling-water...127 Figure 2B - 9: COP variation with change of steam pressure...128 Figure 2B - 10: Cooling load variation with change of steam pressure...129 Table 2B - 1: Primary inputs of the test program... 119 Table 2B - 2: Primary inputs and outputs of tests varying chilled-water temperature...120 Table 2B - 3: Primary inputs and outputs of the tests by varying chilled-water...122 Table 2B - 4: Primary inputs and outputs of the tests by varying cooling-water temperature...124 Table 2B - 5: Primary inputs and outputs of the tests by varying cooling-water...126 Table 2B - 6: Primary inputs and outputs of the tests by varying steam pressure...128 118

Appendix 2B: Chiller Test Results The effects of cooling load variations on the chiller performance (chilled-water temperature) have been summarized in sunsections 2.3.1 and 2.3.2. In the testing program, the effects of the following five operating conditions on chiller performance were tested using the same test approach: chilled-water (and ) temperature chilled-water cooling-water temperature / steam pressure Each of the five operating conditions identified above was varied one at a time over a range of their design values, as indicated in Table 2B-1. Table 2B-1 listed the variable adjusting ranges for each of the five operating parameters. Within its range each operating condition was tested at six to twelve values, and each test obtained 30 to 300 data sets at 2-minute intervals during steady-state operation of the chiller. A total of 51 tests were conducted over an estimated 220 hours of chiller operation. Table 2B - 1: Primary inputs of the test program Chilled-water Chilled - water m 3 /h Primary operation parameters Cooling-water Cooling-water pressure kg/s kpa 7 2 30 1.55 600 Chilled water 10.93 22.02 Design Design Design Design Chilled water Design 1.2 3.62 Design Design Design Cooling water T Design Design 24.8 36 Design Design Cooling water Design Design Design 0.78 1.55 Design pressure Design Design Design Design 175 645 Number of tests 11 10 12 6 12 The results of these tests in terms of the chiller load and the coefficient of performance are reported and discussed in subsection 2B.1 to 2B.4. 2B.1 Chilled-Water Return (and Supply) Temperature There were a total of 11 individual tests of different chilled-water temperatures. The primary inputs and outputs of the chiller are listed in Table 2B-2. In these tests, the chilled-water temperature was set at 7, but when the chilled-water temperature was varied from 10.9 to 22, the chilled- 119

water temperature increased from 5.1 to 13.5. The chiller coefficient of performance and the cooling load are plotted in Figure 2B-1 and 2B-2, respectively. In Figure 2B-1, as the chilled-water temperature increases gradually from 5.14 to 13.53, the COP increases from 1.0 to 1.14. In Figure 2B-2, the solid curve represents the measured cooling load, and the dashed curve represents the cooling load provided by the manufacturer for a natural-gas-driven chiller with the same cooling capacity and similar structure. The two curves check closely. The primary reason for the cooling load and the COP increase with the increase of chilled-water and temperature is that the heat transfer in the evaporator is facilitated by increasing the chilledwater and temperature. The heat transfer capacity is a function of chilled-water and temperature, and rate. The component and comprehensive computational models will be used in chapter 3 to analyze the quantity effects of the chilled-water and temperature. In the operation of this absorption chiller, increasing the chilled-water and temperatures is one of the effective strategies to save thermal energy consumption. Both the COP and the cooling load are increased by increasing the chilled-water and temperatures. Table 2B - 2: Primary inputs and outputs of tests varying chilled-water temperature Measurement values for chiller inputs Coolingwater Chilled Cooling- water water Measurement values for chiller outputs Condensate Cooling load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s 1 2.03 1.43 10.93 30.49 165.30 99.14 17.53 5.14 13.66 0.88 2 2.07 1.44 11.11 30.40 165.32 98.99 18.35 5.37 13.86 0.91 3 2.06 1.43 12.22 30.57 165.25 99.16 20.10 6.01 14.87 0.94 4 2.08 1.43 12.22 30.43 165.30 98.92 18.65 6.16 14.66 0.95 5 2.04 1.43 13.52 30.46 165.20 99.13 19.78 6.91 15.65 1.01 6 2.08 1.43 14.44 30.59 165.14 99.11 20.88 7.70 16.33 0.99 7 2.07 1.43 15.56 30.68 165.13 99.12 22.90 8.35 17.35 1.02 8 2.07 1.43 16.67 30.66 165.05 99.14 23.28 9.20 17.95 1.07 9 2.10 1.43 17.77 30.61 164.94 99.15 24.03 9.90 19.21 1.09 10 2.10 1.43 18.88 30.53 164.74 99.15 25.47 10.69 19.98 1.11 11 2.13 1.43 22.02 30.50 164.66 99.14 25.85 13.53 21.03 1.14 kg/h kw 120

Figure 2B - 1: COP variation with change of chilled-water temperature 1.4 Coefficient of Performance (COP). 1.3 1.2 1.1 1.0 0.9 0.8 0.7 Thermal COP Overall COP 0.6 3 5 7 9 11 13 15 Chilled Water Supply Thermal COP Overall COP Temperature, T32 ( ) Figure 2B - 2: Cooling load variation with change of chilled-water temperature 24 Actual cooling load (kw). 22 20 18 16 14 12 Measured data Manufacturer's rated performance data 10 3.0 5.0 7.0 9.0 11.0 13.0 15.0 Cooling load Rated performance data Chilled water temperature ( ) 121

2B.2 Chilled-Water Flow To investigate how the chilled-water affects the chiller performance and other internal properties of the chiller, the chilled-water was varied from 1.2 m 3 /h to 3.6 m 3 /h in a series of 10 tests. The chilledwater temperature is maintained at 7 by decreasing and varying the chilled water temperature from 17 to 10.6. The cooling-water temperature is set at 30, but the chiller actually maintains the cooling-water around 31 for all tests. The steam pressure is fixed at 620 kpa, the steam changed on the basis of the cooling loads. The test conditions and primary results are summarized in Table 2B-3. The bold line in the table refers to the design condition. Figure 2B-1 shows that the thermal COP increased from 0.96 to 1.06 as the chilled-water was increased from 1.2 m 3 /h to 3.6 m 3 /h. Figure 2B-2 shows the cooling load changes with the variations of chilled-water for the ten tests. The test results indicate that the chiller can be operated within a broad range of chilled-water from 2 m 3 /h to 3.3 m 3 /h without degrading chiller performance. The cooling load is affected slightly by the chilled-water because of its effect on the heat transfer in the evaporator, but the does not affect the COP and cooling load as much as the chilled-water and temperature. The quantitative analysis of chilled-water on the chiller performance will be discussed on the basis of chiller model in chapter 3. These data show that the best operational, most efficient strategy for chiller operation is to satisfy the cooling load to the extent possible with high chilled-water s and with high (and ) temperature. Table 2B - 3: Primary inputs and outputs of the tests by varying chilled-water Measurement values for chiller inputs Coolingwatewater Chilled- Cooling- water Measurement values for chiller outputs Condensate Cooling load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s 1 1.20 1.43 17.05 31.07 165.26 99.21 19.20 7.00 13.99 0.91 2 1.50 1.43 15.34 31.19 165.24 99.24 19.73 7.05 14.43 0.95 3 1.67 1.44 14.54 31.25 165.27 99.27 18.65 7.02 14.63 0.98 4 2.04 1.45 13.89 31.13 164.89 99.35 22.05 6.69 17.09 1.01 5 2.23 1.44 13.06 31.25 165.25 99.36 19.73 7.00 15.76 1.00 6 2.52 1.45 12.77 31.06 165.16 99.40 22.64 6.97 17.02 0.99 7 2.67 1.45 12.23 31.00 165.13 99.40 21.72 6.91 16.52 1.00 8 2.96 1.45 11.67 30.95 165.09 99.36 22.31 6.91 16.44 1.00 9 3.32 1.44 11.10 30.96 165.16 99.36 23.01 6.81 16.57 0.98 10 3.62 1.44 10.56 31.01 165.11 99.40 21.87 6.92 15.31 0.92 kg/h kw 122

Figure 2B - 3: COP variation with change of chilled-water 1.30 Coefficient of Performance (COP). 1.20 1.10 1.00 0.90 0.80 0.70 0.60 0.50 Overall COP Thermal COP 0.40 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 Thermal COP Overall COP Chilled Water Supply Flow Rate (kg/s) Figure 2B - 4: Cooling load variation with change of chilled-water 20 Measured cooling load (kw). 18 16 14 12 10 Cooling load 8 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Chilled Water Supply Cooling load Flow Rate (kg/s) 123

2B.3 Cooling-Water Supply Temperature / Flow Cooling-water removes heat from the absorber and the condenser. The heat transfer in these two components is a function of cooling-water and temperature. These conditions directly affect both the sorbent and the refrigerant temperature. Lower cooling-water temperature and higher rate effectively remove the heat generated in the absorber and the condenser, so the COP and cooling capacity are high, but if the cooling-water temperature is too low, the chiller is in danger of freezing the evaporator tubes and crystallizing the sorbent in the LTHX. Both situations are harmful to the chiller. The purpose of these tests is to investigate the effects of the cooling water temperature and rate on the chiller performance and other internal properties of the chiller. In these tests, the cooling-water temperature is decreased from 36.09 to 24.82 in a total of 12 steady state tests. The test results are plotted in Table 2B-4, Figures 2B-5, and 2B-6. Table 2B - 4: Primary inputs and outputs of the tests by varying cooling-water temperature Measurement values for chiller inputs Cooling- Chilled- Coolingwater water water Measurement values for chiller outputs Condensate Chilled- Cooling water load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s 1 2.50 1.58 13.92 24.82 163.11 99.17 27.91 5.83 23.51 1.24 2 2.44 1.54 13.87 26.48 163.76 99.37 25.16 5.77 22.99 1.19 3 2.19 1.58 13.88 27.57 163.50 99.39 24.58 6.08 19.88 1.11 4 2.09 1.57 13.93 28.88 163.60 99.40 26.12 6.31 18.49 1.03 5 2.02 1.53 13.90 29.57 163.73 99.41 24.20 6.65 17.02 1.05 6 2.12 1.45 13.89 29.54 165.17 98.44 21.37 6.86 17.32 1.04 7 2.12 1.43 13.89 30.52 165.12 99.00 22.57 6.65 17.85 1.06 8 2.12 1.43 13.87 31.62 165.28 98.97 21.17 7.23 16.23 1.00 9 2.12 1.43 13.89 32.02 165.34 98.92 19.20 7.45 15.91 0.99 10 2.40 1.56 13.89 33.10 163.75 99.33 21.27 8.01 16.43 0.98 11 2.13 1.43 13.88 33.25 165.34 98.97 18.82 7.94 14.68 0.97 12 2.46 1.41 13.88 36.09 164.12 99.23 17.25 9.27 13.21 0.89 The cooling-water rate was decreased from 1.55 kg/s to 0.78 kg/s in a total of six steady-state tests. The cooling load for this experiment is lower than the design capacity because the cooling-water temperature is set at 32 instead of 30. The test results are summarized in Table 2B-5, Figures 2B-7 and 2B-8. In the experiments, the chilled-water temperature was set at 14 ; the chilled-water temperature set point was 7, and the steam pressure was fixed at 640 kpa. kg/h kw 124

The test results indicate that decreasing the cooling-water temperature is one of the most effective ways for improving the total performance of the absorption chiller. The increase of cooling-water rate can improve the COP and the cooling load of the chiller; but the improvement is less effective than the decrease of cooling-water temperature. Figure 2B - 5: COP variation with change of cooling-water temperature 1.3 Coefficient of Performance (COP). 1.2 1.1 1.0 0.9 0.8 Overall COP Thermal COP (model) Thermal COP 0.7 24 26 28 30 32 34 36 38 40 Thermal COP Overall COP Cooling Water Supply Temperature ( ) Figure 2B - 6: Cooling load variation with change of cooling-water temperature 26 24 Measured cooling load (kw). 22 20 18 16 14 12 Cooling load 10 24 26 28 30 32 34 36 38 40 Cooling Water Supply Cooling load Temperature ( ) 125

Table 2B - 5: Primary inputs and outputs of the tests by varying cooling-water Measurement values for chiller inputs Coolingwater Coolingwater Measurement values for chiller outputs Chilled- Condensate water Cooling load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s 1 2.05 0.78 13.91 32.75 164.33 99.34 18.86 9.00 11.71 0.76 2 2.05 0.83 13.87 32.26 164.15 99.34 19.08 8.68 12.34 0.79 3 2.05 0.98 13.91 32.55 163.92 99.33 20.80 8.37 13.22 0.82 4 2.05 1.22 13.90 32.55 163.74 99.32 20.08 7.87 14.37 0.90 5 2.04 1.46 13.90 32.46 163.87 99.36 21.64 7.65 14.85 0.96 6 2.03 1.55 13.89 32.09 163.84 99.43 19.78 7.62 14.82 1.00 kg/h kw Figure 2B - 7: COP variation with change of cooling-water 1.2 Coefficient of Performance (COP). 1.1 1.0 0.9 0.8 0.7 0.6 Thermal COP Overall COP 0.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 Thermal COP Overall COP Cooling Water Flow (kg/s) 126

Figure 2B - 8: Cooling load variation with change of cooling-water 18 Measured cooling load (kw). 16 14 12 10 Cooling load 8 0.2 0.4 0.6 0.8 1 1.2 1.4 Cooling load Cooling Water Flow (kg/s) 2B.4 Pressure/Temperature The chiller requires steam input to the HTRG to heat the sorbent solution and produce the refrigerant at a pressure/temperature that allows for additional heat transfer to the sorbent and refrigerant production in the LTRG. The pressure of the steam should be appropriate to optimize the chiller performance in terms of the COP and cooling load. If the steam pressure/temperature to the HTRG is too low, it cannot transfer sufficient heat to the sorbent solution, and produce sufficient refrigerant; therefore, both the cooling load and COP are decreased. If the steam pressure is too high, too much refrigerant is generated, consequently the evaporation pressure/temperature may be too low and ice may formed in the evaporator. Excess refrigerant may spill from the refrigerant tray into the sorbent pool in the absorber, loosing its evaporation cooling capacity. If the steam pressure and the solution temperature are too high, corrosion will occur more rapidly in the HTRG and the noncondensable gases will degrade chiller performance. In practice, the sorbent solution temperature should not exceed 160. The chiller control system automatically adjusts the steam valve to avoid excess steam pressure/temperature. Figure 2B-9 shows that a COP increase from 0.61 to 0.99 results from increasing steam temperature from 176 kpa to 644 kpa. It is notable that a steam higher than 300 kpa or 145, changes the COP very little. Figure 2B-10 shows that the cooling loads increase almost linearly with the improvement of steam pressure. The effect of steam pressure/ temperature on chiller 127

performance will be further investigated on the basis of a computational performance model developed in chapter 3. Table 2B - 6: Primary inputs and outputs of the tests by varying steam pressure Measurement values for chiller inputs Coolingwater Coolingwater Measurement values for chiller outputs Chilled- Condensate water Cooling load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s 1 2.00 1.50 13.86 30.48 166.12 99.04 25.53 6.28 17.65 0.99 2 2.00 1.50 13.90 30.12 163.06 98.96 24.92 6.70 16.82 0.96 3 2.01 1.50 13.93 29.94 161.66 98.71 25.71 6.89 16.44 1.01 4 2.01 1.50 13.89 29.72 158.77 91.77 21.55 7.47 15.03 0.98 5 2.01 1.50 13.89 30.18 156.77 87.31 21.65 7.76 14.37 1.00 6 2.02 1.50 13.89 29.74 154.06 81.93 20.15 8.24 13.26 0.99 7 2.02 1.50 13.90 29.60 150.53 74.67 19.65 8.58 12.48 0.95 8 2.02 1.50 13.88 30.31 146.88 69.91 17.08 9.18 11.05 0.99 9 2.02 1.50 13.90 30.83 143.59 79.00 14.99 9.72 9.84 0.93 10 2.02 1.50 13.89 30.27 139.89 98.87 15.76 10.43 8.11 0.80 11 2.02 1.50 13.89 30.31 134.51 98.80 12.05 11.34 5.99 0.70 12 2.03 1.50 13.89 29.73 129.18 96.59 9.17 12.12 4.19 0.61 kg/h kw Figure 2B - 9: COP variation with change of steam pressure 1.2 Coefficient of Performance (COP). 1.0 0.8 0.6 0.4 Thermal COP Overall COP 0.2 125 135 145 155 165 175 Supply Thermal COP Overall COP Temperature ( ) 128

Figure 2B - 10: Cooling load variation with change of steam pressure 20 Measured cooling load (kw). 16 12 8 4 Cooling load 0 125 135 145 155 165 175 Supply Cooling load Temperature ( ) 129