SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND



Similar documents
WHITE PAPER Fire & safety performance standards

Errata NFPA 70. Proposed 2014 Edition

800 Communications Circuits

How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

AWG: Cat5e: Cat6: Cat6A:

2012 CATALOG AEROSPACE VVIRE & CABLE INC. aerospacewire.com

UNDERSTANDING. C&M Corporation 51 South Walnut Street, Wauregan, CT Phone: Fax:

2011 National Electrical Code

Specification SFTP CAT6 Network Cable 23AWG CU

Safety & Performance in the Wire and Cable Industry

RoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

AN IN-DEPTH LOOK AT 2011 NEC ARTICLE CABLE TRAY. (The following code explanations are to be used with a copy of the 2011 NEC.

Security & Control Cables

3200 West 22nd Street Erie, PA ph fax

How To Buy Honeywell Genesis Series Fire Alarm Cables

Electrical Code (NEC) Snake Tray Cable Management Solutions

Cable Substitution Chart

Fire Performance Standard

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

Code Compliance for Spring Steel Fasteners Based on the 2005 NEC

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

Fire Life Safety ORC Review Guidelines for PPD Experimental Installations

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager

The most important matter is to select the right product based on the environment in which it will be installed and on its use or application.

Copper Cabling Infrastructure Offering

Excerpts from the Canadian National Building Code (NBC)

MANUFACTURER S CERTIFICATE OF COMPLIANCE

SECTION ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

CABLE TRAY MANUAL Based on the 2011 National Electrical Code

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

Cable Products HONEYWELL SECURITY & CUSTOM ELECTRONICS. Honeywell's Genesis Series provides a full range

Report. Analysis of Cablofil Cable Tray for Power Circuits. Reference: RP10002

The Instrumentation Cable Experts

Outside Telephone Cable

EcoFlex Cable. Smaller. Lighter. Tougher. 100% Recyclable.

Building Cables and Wires

Lifeline Fire Protection Cable Systems. Cables

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

Serial Data Grade Cables

Limited Combustible: The New Standard for Fire Safety

4 Installation Requirements

INTRODUCTION TO CHAPTER 3 WIRING METHODS AND MATERIALS

Requirements for Electrical Installations

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM

STABILOY BRAND FeeDeR SOLuTIONS

STABILOY BRAND FeeDeR SOLuTIONS

WHY CABLE TRAY? BECAUSE A CABLE TRAY WIRING SYSTEM PROVIDES SAFE AND DEPENDABLE WAYS TO SAVE NOW AND LATER

Tremco Fire Protection Systems Group Technical Bulletin

Hook-Up and Lead Wire

Click here to see a video example of cable being burned outside the controlled lab environment. UL-910 Test for Flame-Propagation and Smoke Density

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

rpsa FIRE PROTECTION ENGINEERS

Communication and Control Cable Fire Alarm Cable Coaxial Cable ( CAT V / M ATV & CCTV Cables)

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

West Penn Wire. Access Control Systems and Cables WEST PENN WIRE CABLE WITH CONFIDENCE

100% EMI Emission Containment

A quick product finder for commercial applications JUDD WIRE INC. A member of the Sumitomo Electric Industries group of companies

CCW Continuously Corrugated Welded Cable A RMORED CAB LE FO R HAZAR D O U S LOCATI O N S

KNOW YOUR OPTIONS: 230 KV POWER CABLES

Exane 125 Drilling Rig and Commercial Marine Cable

MHR-2 Cable. MHR-5/6 Cable. MHRHF-5 Cable. M59-3/5/6 Cable. RG59-3MHR-3 Cable. RG6 Cable. MHR-5STP-2 Cable. MHRVGA Cable.

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*

Section kv Power Cables

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

Sound, Alarm & Security Cable 7

SECTION FIRE ALARM AND DETECTION SYSTEMS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Screened cable and data cable segregation

STABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES

Why FOUNDATION Fieldbus?

WIRE & CABLE PRODUCTS

New Cable Tie Type Classifications

Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES

SECTION SIGNAL WIRE AND CABLE

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

B. NICET: National Institute for Certification in Engineering Technologies.

The proof is here!! Ron Goethals, Philadelphia; June 18, 2014

SOUND/SECURITY FIRE ALARM/LIFE SAFETY TEMPERATURE CONTROLS COAXIAL DATACOM HARDWARE FIBER OPTIC SPECIAL APPLICATION C ATALOG, VOL.

with coloured cores and overall copper screen UL/CSA... 17

Heating Cable. Construction

Terms and Definitions In Canada

Tri-Rated Flexible PVC Equipment Wire

INTERNATIONAL STANDARD

Residential Electrical System Aging Research Project. Dave Dini Sr. Research Engineer Underwriters Laboratories

PROFIBUS cable. PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications

APR 2016 Rev M

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Comparative study for cables and busbars

600V Power Cable 600V SOOW SOW

Transcription:

Belden Electronics Division P.O. Box 1980 Richmond, Indiana 47375-1980 2200 U.S. Highway 27 South Richmond, Indiana 47374-7279 Telephone: 765 983 5200 Facsimile: 765 983 5825 SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND BELDEN has put this information together to inform the market of the modifications to the 2002 NEC concerning 300 volt marking on PLTC type cables. Why isn t 300 volts printed on PLTC cable anymore? The 2002 NEC modified the printing requirements that were allowed on the jacket of PLTC type cables. The use of 300 volts or 300 v in the print legend was disallowed because the voltage marking on the cable may be misinterpreted to suggest that the cable may be suitable for Class 1 electric light and power applications. See NEC clause 725.71 (H) Marking below. PLTC type cables will still have the same applications use as before. PLTC cables are still rated 300 volts but cannot be so marked after May 25, 2003. On February 25, 2003 UL issued revisions to UL 13, Standard for Power-Limited Circuit Cables, which governs the listing and marking requirements of PLTC cable. One of those revisions was the removal of the 300 volts or 300 v marking on the cable in accordance with the 2002 NEC. This removal becomes effective May 25, 2003 for all cable manufacturers. Any existing cable that is in stock or anywhere in the industry pipeline which has the 300 volts or 300 v marking will still be an acceptable cable for use. On May 25, 2003 and after cable manufacturers will not be allowed to mark the 300 volts or 300 v marking on PLTC cable or on any label attached to the product. The NEC does allow an exception to allow voltage markings for cables with multiple listings where a voltage marking for one or more listings is required. See NEC clause 725.71 (H) Exception. KEY POINTS The use of 300 volts or 300 v in the print legend of PLTC type cables is disallowed by the NEC for all cable manufacturers. The effective date for the discontinued use of the 300 volts or 300 v in the jacket print legend or on any label attached to the product is May 25, 2003. All cables produced with 300 volts or 300 v markings before May 25, 2003 are acceptable. This covers all inventories in the industry pipeline including manufacturers, distributors, installers, and end users. There is no change in the use application of these cables. A voltage marking exception is permitted on multiple listed cables when required by the other listing. National Electrical Code and NEC are Registered Trademarks of the National Fire Protection Association, Inc., Quincy, MA.

725.71 Listing and Marking of Class 2, Class 3, and Type PLTC Cables. Class 2, Class 3, and Type PLTC cables installed as wiring within buildings shall be listed as being resistant to the spread of fire and other criteria in accordance with 725.71(A) through (G) and shall be marked in accordance with 725.71(H). (A) Types CL2P and CL3P. Types CL2P and CL3P plenum cables shall be listed as being suitable for use in ducts, plenums, and other space used for environmental air and shall also be listed as having adequate fire-resistant and low smoke-producing characteristics. FPN: One method of defining low smoke-producing cable is by establishing an acceptable value of the smoke produced when tested in accordance with NFPA 262-1999, Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces, to a maximum peak optical density of 0.5 and a maximum average optical density of 0.15. Similarly, one method of defining fire-resistant cables is by establishing a maximum allowable flame travel distance of 1.52 m (5 ft) when tested in accordance with the same test. (B) Types CL2R and CL3R. Types CL2R and CL3R riser cables shall be listed as being suitable for use in a vertical run in a shaft or from floor to floor and shall also be listed as having fire-resistant characteristics capable of preventing the carrying of fire from floor to floor. FPN: One method of defining fire-resistant characteristics capable of preventing the carrying of fire from floor to floor is that the cables pass the requirements of ANSI/UL 1666-1997, Test for Flame Propagation Height of Electrical and Optical-Fiber Cable Installed Vertically in Shafts. (C) Types CL2 and CL3. Types CL2 and CL3 cables shall be listed as being suitable for general-purpose use, with the exception of risers, ducts, plenums, and other space used for environmental air and shall also be listed as being resistant to the spread of fire. the CSA vertical flame test for cables in cable trays, as described in CSA

(D) Types CL2X and CL3X. Types CL2X and CL3X limited-use cables shall be listed as being suitable for use in dwellings and for use in raceway and shall also be listed as being resistant to flame spread. FPN: One method of determining that cable is resistant to flame spread is by testing the cable to the VW-1 (vertical-wire) flame test in ANSI/UL 1581-1991, Reference Standard for Electrical Wires, Cables and Flexible Cords. (E) Type PLTC. Type PLTC nonmetallic-sheathed, power-limited tray cable shall be listed as being suitable for cable trays and shall consist of a factory assembly of two or more insulated conductors under a nonmetallic jacket. The insulated conductors shall be 22 AWG through 12 AWG. The conductor material shall be copper (solid or stranded). Insulation on conductors shall be suitable for 300 volts. The cable core shall be either (1) two or more parallel conductors, (2) one or more group assemblies of twisted or parallel conductors, or (3) a combination thereof. A metallic shield or a metallized foil shield with drain wire(s) shall be permitted to be applied either over the cable core, over groups of conductors, or both. The cable shall be listed as being resistant to the spread of fire. The outer jacket shall be a sunlight- and moisture-resistant nonmetallic material. Exception No. 1: Where a smooth metallic sheath, continuous corrugated metallic sheath, or interlocking tape armor is applied over the nonmetallic jacket, an overall nonmetallic jacket shall not be required. On metallicsheathed cable without an overall nonmetallic jacket, the information required in 310.11 shall be located on the nonmetallic jacket under the sheath. Exception No. 2: Conductors in PLTC cables used for Class 2 thermocouple circuits shall be permitted to be any of the materials used for thermocouple extension wire. the CSA vertical flame test for cables in cable trays, as described in CSA

(F) Class 2 and Class 3 Cable Voltage Ratings. Class 2 cables shall have a voltage rating of not less than 150 volts. Class 3 cables shall have a voltage rating of not less than 300 volts. (G) Class 3 Single Conductors. Class 3 single conductors used as other wiring within buildings shall not be smaller than 18 AWG and shall be Type CL3. Conductor types described in 725.27(B) that are also listed as Type CL3 shall be permitted. the CSA vertical flame test for cables in cable trays as described in CSA (H) Marking. Cables shall be marked in accordance with 310.11(A)(2), (3), (4), and (5) and Table 725.71. Voltage ratings shall not be marked on the cables. FPN: Voltage markings on cables may be misinterpreted to suggest that the cables may be suitable for Class 1 electric light and power applications. Exception: Voltage markings shall be permitted where the cable has multiple listings and a voltage marking is required for one or more of the listings. FPN: Class 2 and Class 3 cable types are listed in descending order of fire resistance rating, and Class 3 cables are listed above Class 2 cables, because Class 3 cables can substitute for Class 2 cables. Table 725.71 Cable Markings Cable Marking Type Listing References CL3P Class 3 plenum cable 725.71(A), (F), and (H) CL2P Class 2 plenum cable 725.71(A) and (H) CL3R Class 3 riser cable 725.71(B), (F), and (H) CL2R Class 2 riser cable 725.71(B) and (H) PLTC Power-limited tray cable 725.71(E) and (H) CL3 Class 3 cable 725.71(C), (F), and (H) CL2 Class 2 cable 725.71(C), (F), and (H) CL3X Class 3 cable, limited use 725.71(D), (F), and (H) CL2X Class 2 cable, limited use 725.71(D), (F), and (H)

The following is copied from the UL 13 standard, Second Edition, Copyright 2003, Underwriters Laboratories Inc., 1285 Walt Whitman Road, Melville, NY 11747. This reprinted material is not the complete and official position of the Underwriters Laboratories Inc. on the referenced subject which is represented only by the standard in its entirety. February 25, 2003 Superseded requirements for the Standard for Power-Limited Circuit Cables UL 13, Second Edition The requirements shown are the current requirements that have been superseded by requirements in revisions issued for this Standard. To retain the current requirements, do not discard the following requirements until the future effective dates are reached. 1.2 (1.2) Type PLTC cable is rated for 300 volts and is so marked. Cables for Class 3 circuits are rated for 300 volts but are not so marked. Cables for Class 2 circuits do not have a voltage rating. See 40.1 (h). 1.2 effective until May 25, 2003 ************************************************************************************** Here is the new wording that becomes effective May 25, 2003 1.2 Cables for Class 3 circuits are rated for 300 volts but are not so marked. Cables for Class 2 circuits do not have a voltage rating. See 40.1 (h). Revised 1.2 effective May 25, 2003 Sincerely, Gerald Lee Dorna Gerald Lee Dorna GERALD.DORNA@BELDEN.COM GDORNA@INAME.COM Technical Relations Manager & Product Liability Manager Belden Electronics Division 2200 U. S. Highway 27 South Richmond, IN 47374 PH: 765-983-5534 FAX: 765-983-5825 April 15, 2003